Sei sulla pagina 1di 9

International Journal of Refrigeration 25 (2002) 1093–1101

www.elsevier.com/locate/ijrefrig

Experiment and simulation on the performance of


an autocascade refrigeration system
using carbon dioxide as a refrigerant
S.G. Kim, M.S. Kim*
School of Mechanical and Aerospace Engineering, Seoul National University, Seoul 151-742, South Korea

Received 7 August 2001; received in revised form 15 November 2001; accepted 30 November 2001

Abstract
The main purpose of this study is to investigate the performance of an autocascade refrigeration system using zeo-
tropic refrigerant mixtures of R744/134a and R744/290. One of the advantages of this system is the possibility of
keeping the highest pressure of the system within a limit by selecting the composition of a refrigerant mixture as com-
pared to that in the vapor compression system using pure carbon dioxide. Performance test and simulation have been
carried out for an autocascade refrigeration system by varying secondary fluid temperatures at evaporator and con-
denser inlets. Variations of mass flow rate of refrigerant, compressor power, refrigeration capacity, and coefficient of
performance (COP) with respect to the mass fraction of R744 in R744/134a and R744/290 mixtures are presented at
different operating conditions. Experimental results show similar trends with those from the simulation. As the com-
position of R744 in the refrigerant mixture increases, cooling capacity is enhanced, but COP tends to decrease while the
system pressure rises. # 2002 Elsevier Science Ltd and IIR. All rights reserved.
Keywords: Refrigeration system; Compression system; Refrigerant; Carbon dioxide; R134a; Propane; Mixture; Refrigerating circuit;
Cascade system; Design; Performance; Measurement; Modelling

Etude expérimentale et simulation de la performance d’un


système frigorifique à cascade utilisant le dioxyde de carbone
comme frigorigène

Mots cle´s : Système frigorifique ; Système à compression ; Frigorigéne ; Dioxyde de carbone ; R134a ; Propane ; Mélange ; Circuit
frigorifique ; Systéme en cascade ; Conception ; Performance ; Mesure ; modélisation

* Corresponding author. Tel.: +82-2-880-8362; fax: +82-2-


883-0179.
E-mail address: minskim@snu.ac.kr (M.S. Kim).

0140-7007/02/$20.00 # 2002 Elsevier Science Ltd and IIR. All rights reserved.
PII: S0140-7007(01)00110-4
1094 S.G. Kim, M.S. Kim / International Journal of Refrigeration 25 (2002) 1093–1101

Nomenclature Subscripts
1 Inlet of compressor
DP Differential pressure (kPa) 2 Outlet of compressor
h Enthalpy (kWkg1) 2nd Secondary heat transfer fluid
m Clearance volume ratio c Condenser
:
mr Mass flow rate of refrigerant (kgs1) dew Dew point
P: Pressure (kPa) e Evaporator
Q Heat capacity (kW) i Inlet
DT Logarithmic mean temperature difference o Outlet
( C) sup Superheated region
v: Specific volume (m3 kg1) tp Two phase region
V: comp Compressor displacement rate
W Compressor power (kW)

Greek letters
v Volumetric efficiency

1. Introduction better performance while keeping the gas cooling pres-


sure in the order of 10 MPa. Nekså et al. [2] sought simi-
Carbon dioxide had been used as a refrigerant in the lar applications of CO2 in heat pump water heater with
1930s and 1940s in ships’ refrigerators and other sta- highest pressures up to 11 MPa. Many other studies
tionary systems. However, after an introduction of CFC have compared transcritical cycles using carbon dioxide
(chlorofluorocarbon) and HCFC (hydrochlorofluoro- with conventional vapor compression cycles that use
carbon) refrigerants, which became major refrigerants in halocarbon refrigerants and mentioned that the adop-
vapor compression refrigeration system afterwards, car- tion of carbon dioxide shows quite similar, sometimes
bon dioxide faded away from the market and was sel- worse, sometimes better performance [3–8]. Extensive
dom used as a refrigerant. However, the ozone depletion reviews on these subjects are well summarized by Kruse
and global warming caused by CFC and HCFC et al. [9].
refrigerants became one of the universal concerns, and However, it is a possible disadvantage that the oper-
resulted in several international agreements to restrict ating pressure of the transcritical refrigeration system
the production and use of these refrigerants. using pure carbon dioxide is too high. One way to
Many researchers have tried to find out new overcome this high pressure disadvantage may be a
alternative refrigerants that are ideal for the refrig- choice of cascade refrigeration system, where carbon
eration systems, and HFC (hydrofluorocarbon) dioxide refrigeration system is precooled by other
refrigerants or their mixtures are now being sug- refrigeration system. Hesse and Kruse [10] proposed a
gested for a drop-in or mid-term replacement which cascade refrigeration system using CO2 with ammonia
have zero ODP (ozone depletion potential). However, where ammonia is used in the higher stage and CO2 in
there is an argument that these refrigerants are harmful the lower stage so that the operating pressure is similar
to the environment because of its rather high GWP to that in conventional refrigeration system, not
(global warming potential). Therefore, it must be a bet- exceeding the pressure limit of about 2.5 MPa. It should
ter solution to use naturally existing and environmen- be remembered, however, two or more compressors are
tally harmless substances as alternative refrigerants in required in a cascade system depending on the number
refrigeration systems. As Lorentzen suggested [1], car- of refrigerants used.
bon dioxide (CO2) is a good refrigerant which is envir- One other solution to avoid high operating pressure is
onmentally friendly, nonflammable, nontoxic, easily a choice of autocascade refrigeration system where CO2
available, and has excellent thermophysical properties, is used as a main working fluid and other refrigerant
even among the naturally existing refrigerants, although with lower vapor pressure is being used to cool the main
the absolutely ideal refrigerant in every respect does not working fluid through internal heat exchange. This sys-
exist. tem was well described by Stoecker [11]. Even though
Lorentzen [1] summarized several possible tran- the system efficiency is lowered, some of the advantages
scritical cycles with carbon dioxide covering car air are to use only one compressor in the system, to main-
conditioners, large heat pumps, and commercial refrig- tain lower pressure ratio, and either to obtain low
eration systems. He described several cycles to pursue temperature or to avoid high pressure risk.
S.G. Kim, M.S. Kim / International Journal of Refrigeration 25 (2002) 1093–1101 1095

Fig. 1. Schematic diagram of an autocascade refrigeration system.

This paper investigates the performance variations of in Fig. 2. Point 1 represents the inlet of the compressor
an autocascade refrigeration system using refrigerant and the P-h diagram with the point 1 is for the mixture’s
mixtures of R744 (carbon dioxide) with R134a or R290 composition of initial charge. After compression to
(propane). The choice of R134a seems not purely ‘nat- point 2, the refrigerant mixture is cooled down in the
ural’, but it is aimed at finding a possible solution for condenser, but only partially condensed to point 3 by
the transient period of probable reduction in production the heat sink whose temperature is near the ambient
of HFCs in the future before shifting to natural working temperature, as the bubble point of the mixture is much
fluid systems. So far, little work except one of the lower than the ambient temperature. In the phase
authors’ previous work [12] has been performed for an separator, liquid phase at point 4 will have a different
autocascade refrigeration system using CO2. In this composition from the vapor phase at point 7, and each
work, as a continuation of our study, experiment and phase will flow through different passages. The mass
simulation have been carried out to provide perfor- flow rate of each passage is strongly dependent on the
mance characteristics of an autocascade refrigeration quality in the phase separator, which means that low
system for various mass fractions of R744 in the R744/ quality refrigerant at the exit of condenser will force a
134a and R744/290 mixtures and for several operating greater mass flow rate of liquid phase in the evaporative
conditions. condenser. Therefore, the quality at the condenser outlet
should be well determined to maintain a proper heat
balance in the evaporative condenser. In addition to
2. Operation of the autocascade refrigeration system this, the temperature difference should be moderate to
transfer the necessary heat to condense the vapor phase
The autocascade refrigeration system is shown in by evaporating the low temperature refrigerant in the
Fig. 1 and the pressure-enthalpy (P-h) diagram is shown evaporative condenser. Since the vapor phase and liquid
1096 S.G. Kim, M.S. Kim / International Journal of Refrigeration 25 (2002) 1093–1101

Fig. 2. Pressure-enthalpy diagram of autocascade refrigeration system.

phase refrigerants have different compositions, two dif- The exit pressures of evaporative condenser and the
ferent P-h diagrams which correspond to the overall evaporator should be equalized very quickly, however, the
composition of each phase describe each heat transfer temperature of two streams will not always be the same.
process. Liquid phase has lower mass fraction of carbon
dioxide, therefore the front P-h diagram shown in Fig. 2
is applied, while the rear P-h diagram is applied to the 3. Experiments
flow of the vapor phase from the phase separator. The
liquid phase is then expanded from point 4 to a lower 3.1. Description of experimental setup
temperature at point 5 entering the evaporative con-
denser to cool the vapor phase in the phase separator. Experimental setup for the performance test of an
This stream flows through one side of the evaporative autocascade refrigeration system consisted of a com-
condenser, vaporizing and leaving slightly superheated pressor, a condenser, two expansion valves, an eva-
at point 6. The vapor phase is condensed from point 7 porator, an evaporative condenser, a phase separator,
to point 8 in the internal heat exchanger. Then, the two and a vapor line to suction line heat exchanger (internal
phase of carbon dioxide rich mixture condenses on the heat exchanger) as shown in Fig. 1. The compressor in
other side of the evaporative condenser, leaving as this study was of an open, reciprocating type with two
saturated liquid or as slightly subcooled liquid at point cylinders each of which had the diameter of 32 mm and
9. This fraction of the refrigerant mixture is then the stroke of 28 mm. Refrigeration oil used for the
expanded to a state with lower pressure and temperature compressor was mineral oil of ISOVG32. The condenser
(point 10). It becomes a superheated vapor (point 11) in and the evaporator were counterflow-type heat
the evaporator by absorbing heat from the secondary exchangers with concentric dual tubes. Metering valves,
fluid and is mixed with the refrigerant coming from eva- which could finely regulate the flow rate, were used as
porative condenser (point 6). Eventually, the state is expansion valves. The rotating speed of the compressor
indicated by point 12 after mixing. The temperature of was also kept constant, and torque transducer was
the mixed refrigerant rises to point 1 through a heat installed between the driving motor and the compressor.
exchange with the vapor refrigerant coming from the Water was used as a secondary fluid in the condenser,
separator. The compressor receives the low pressure and ethylene glycol and water mixture (40:60 by mass)
refrigerant from the internal heat exchanger, and it was used in the evaporator as a secondary heat transfer
forms a complete cycle. fluid.
S.G. Kim, M.S. Kim / International Journal of Refrigeration 25 (2002) 1093–1101 1097

3.2. Test conditions and test method tained near 0.5 by controlling the flow rate of the second-
ary fluid while keeping the inlet temperature and the
The performance test during cooling conditions was overall temperature difference of the secondary fluid in the
carried out for the refrigerant mixtures of R744/134a condenser. Table 1 shows the inlet and outlet temperatures
and R744/290. As for composition of the refrigerant and pressures of the refrigerant mixture at the condenser
mixtures, the mass fraction of R744 was selected 0.21– and evaporator together with the calculated dew point
0.36 for R744/134a and 0.13–0.31 for R744/290, so that temperatures, which are estimated from the measured
the maximum operating pressure was below 3 MPa. pressures at the inlet of the condenser and evaporator.
The temperature differences of the secondary heat The cooling capacity was measured by the heat loss or
transfer fluids between the inlet and outlet at condenser gain of the secondary heat transfer fluid in the eva-
and evaporator were set to 8 and 7  C, respectively. In porator and condenser, and the work input to the com-
order to cover the operating ranges for outdoor tem- pressor was calculated from the torque and rotating
perature change during room cooling, the condenser speed measurement. Rotating speed of the compressor
inlet temperature of the secondary heat transfer fluid was kept 1500 rpm.
was varied from 27.8 to 40.0  C for the designated sec- When the variation of temperature measurement was
ondary fluid inlet temperature at the evaporator of within 0.3  C, that of the pressure measurement
26.7  C. The quality at the condenser outlet was main- within 5 kPa, and the change of the mass flow rate of

Table 1
The inlet and outlet temperature levels, pressures and the estimated dew point temperatures at the condenser and evaporator

R744/134a

xCO2 T2nd,ci ( C) Pci (kPa) Pei (kPa) Tci ( C) Tco ( C) Tei ( C) Teo ( C) Tdew,c ( C) Tdew,e ( C)

0.21 27.8 1560.6 519.9 76.4 28.6 23.8 26.9 37.9 3.4
0.21 31.0 1745.1 541.9 85.1 31.8 23.0 26.9 42.0 2.9
0.21 35.0 1954.6 544.6 91.9 35.7 20.8 27.2 46.2 2.9
0.21 40.0 2193.8 543.8 99.8 40.7 17.1 27.1 50.5 2.3
0.26 27.8 1813.7 536.6 79.1 28.5 29.8 26.7 39.4 6.7
0.26 31.0 2012.4 553.2 89.3 31.4 29.1 26.7 43.2 6.5
0.26 35.0 2267.3 543.8 97.2 35.5 27.1 26.6 47.6 7.0
0.26 40.0 2502.8 531.3 103.9 40.5 25.2 26.7 51.3 6.6
0.30 27.8 2000.9 632.9 84.3 28.3 27.2 26.8 40.2 5.1
0.30 31.0 2198.3 636.8 91.4 31.6 26.1 26.8 43.6 4.9
0.30 35.0 2409.3 623.6 98.2 35.5 24.5 26.8 46.9 5.0
0.30 40.0 2671.8 596.9 106.7 40.5 21.5 26.7 50.8 5.2
0.36 27.8 2363.2 760.9 86.7 28.2 27.7 26.8 41.4 4.8
0.36 31.0 2574.5 767.0 97.1 31.4 26.8 26.7 44.5 4.5
0.36 35.0 2831.6 762.2 103.9 35.5 24.8 26.9 47.9 4.0
0.36 40.0 3131.4 723.6 113.1 40.4 22.0 26.8 51.6 4.4

R744/290

xCO2 T2nd,ci ( C) Pci (kPa) Pei (kPa) Tci ( C) Tco ( C) Tei ( C) Teo ( C) Tdew,c ( C) Tdew,e ( C)

0.13 27.8 1534.9 714.5 69.1 29.7 10.3 26.9 36.9 3.6
0.13 31.0 1648.4 638.6 77.1 32.9 10.4 26.7 39.9 0.0
0.13 35.0 1794.3 635.7 82.6 36.5 8.5 26.9 43.4 0.1
0.13 40.0 2009.4 633.3 89.5 41.5 5.5 26.9 48.3 0.0
0.22 27.8 1821.3 785.4 71.5 29.1 14.6 26.6 38.8 0.9
0.22 31.0 1955.9 754.8 79.6 32.2 13.9 26.7 41.7 0.3
0.22 35.0 2235.7 719.3 88.7 35.9 14.1 26.6 47.3 3.0
0.22 40.0 2418.7 702.6 95.4 40.9 12.6 26.9 50.7 2.5
0.31 27.8 2365.2 976.3 78.7 28.3 17.2 26.6 43.2 0.9
0.31 31.0 2519.2 968.9 83.9 31.5 16.1 26.6 45.8 0.5
0.31 35.0 2727.1 911.8 92.0 35.8 12.8 26.7 49.0 1.5
0.31 40.0 2937.2 912.7 98.2 40.5 10.2 26.5 52.1 0.1
1098 S.G. Kim, M.S. Kim / International Journal of Refrigeration 25 (2002) 1093–1101

refrigerant was within 0.2 g/s, the system was assumed It is assumed that pressure drop and heat loss in heat
steady and data were collected. exchangers are negligible.
Combined standard uncertainty in measuring the Evaporative condenser is used to condense the vapor
heat capacity in condenser and evaporator is  3.4% of phase of refrigerant in the phase separator that has
the measured heat transfer rate, and that in calculating higher fraction of carbon dioxide by the evaporating
COP (coefficient of performance) is  3.5%. The repeat- refrigerant of low temperature which has relatively
ability of the measurement is within the range of  3.0%. higher fraction of R134a or R290. Evaporative con-
denser is also a counterflow heat exchanger that is
assumed to have negligible pressure drop and heat loss.
4. Autocascade cycle simulation It is idealized to have heat exchanger effectiveness of 1.
Expansion device is modeled to be isenthalpic.
4.1. Modeling of autocascade cycle The refrigerant from the condenser outlet should pass
through the phase separator. In the phase separator, the
Compression process is described by a simple way refrigerant mixture’s vapor and liquid phases are coex-
using the concept of a constant isentropic efficiency. The isting and its composition of liquid phase is different
mass flow rate of refrigerant is calculated considering from that of vapor phase for zeotropic mixtures in this
the compressor displacement rate, volumetric efficiency, study. In this case the mass fraction of carbon dioxide
and specific volume of gas entering the compressor as (R744) is higher in vapor phase, and the liquid phase is
shown in Eqs. (1) and (2). richer in R134a or R290. Even though the phase
separation is not perfect in this flowing situation com-
1
v ¼ 1  mð  1Þ ð1Þ pared with the case of phase equilibrium, it is quite a
2 unique way to assume the liquid and vapor phase have
: the compositions that can be obtained for the phase
: Vcomp 
mr ¼ ð2Þ equilibrium state. Once the compositions are determined
1 from the equilibrium relation, it is idealized that the
liquid and vapor phases are flowing independently in
Here, m represents a clearance volume ratio to have the separate passages.
value of 0.04.
Both the evaporator and condenser are modeled as 4.2. Simulation conditions
counterflow heat exchangers as shown in the experi-
ment. Even though the local heat transfer coefficients In the autocascade refrigeration system, evaporating
vary as a function of refrigerant flow rate, heat flux, temperature, condensing temperature, the ratio of mass
mass quality, etc., average temperature difference flow rate at each branch circuit, and the mass fraction of
between the refrigerant and the secondary heat transfer the charged refrigerant are important variables. In order
fluid is designated in the simulation, which is taken as to investigate the effects of the variation of these vari-
an average of test data sets obtained from the experi- ables on the system performance, quality at condenser
ment. The average temperature difference between two outlet, degree of superheat and isentropic efficiency are
fluids is defined as in Eqs. (3) and (4), which is propor- held constant.
tional to the heat transfer rate of each phase of refrig- In order to compare the experimental results with the
erant in the heat exchanger considering the logarithmic simulation results, simulation conditions are made
mean temperature difference of each subsection [13]. The similar to experimental conditions. The selection of the
separation of two phase flow region and the superheated composition of the mixture is limited by the capability
region of refrigerant mixture is necessary, and this is of the thermodynamic property calculation using
quite straightforward since we know pressure and tem- REFPROP [14] near the critical point of the mixture.
perature at each point of heat exchangers. Correspond-
ing secondary fluid temperatures and transferred heat
can be easily obtained from the energy balance based on 5. Results and discussion
mass flow rate of refrigerant and the enthalpies at each
point of heat exchangers. 5.1. Performance at cooling conditions
: :
1 Qsup;c Qtp;c The variations of cooling capacities with respect to
¼ : þ : ð3Þ
Tc Qc Tsup;c Qc Ttp;c the mass fraction of R744 are displayed in Fig. 3.
Cooling capacity is calculated by multiplying three fac-
: : tors of mass flow rate of secondary heat transfer fluid,
1 Qtp;e Qsup;e
¼ : þ : ð4Þ specific heat, and the temperature difference between the
Te Qe Ttp;e Qe Tsup;e
inlet and outlet including the heat gain from the ambient
S.G. Kim, M.S. Kim / International Journal of Refrigeration 25 (2002) 1093–1101 1099

air. As the mass fraction of R744 increases, refrigerant the pressure ratio of the compressor increases, which
mass flow rate increases owing to the smaller vapor results in the increase in the compressor power. The
specific volume of R744 than that of R134a and R290 compressor power of R744/290 is greater than that of
for the same temperature and pressure conditions. Since R744/134a at the same composition of R744, which is
cooling capacities are very much dependent on the mass because the saturation pressure of R290 is greater than
flow rate of refrigerant, increased mass flow rate of that of R134a.
refrigerant under constant compressor speed condition The coefficient of performance (COP) is defined as
is expected. The cooling capacity of R744/290 is about the refrigeration capacity divided by the work per unit
twice greater than that of R744/134a, because the time required by the compressor. The variation of COP
refrigeration effect of R290 is greater than that of R134a. with the change of the mass fraction of R744 and the
When the inlet temperature of the secondary heat trans- secondary fluid temperature at the condenser inlet are
fer fluid to the condenser increases, the cooling capacity represented in Fig. 5. As the mass fraction of R744 in
decreases mainly because mass flow rate of refrigerant the mixture increases, COP decreases. Fig. 5 also pre-
decreases due to the increased compressor discharge sents COP variation for several condenser temperature
pressure. Since the specific volume of refrigerant is levels, which indicates it decreases with an increase in
reduced at the discharge line of compressor with ele- the condensing temperature.
vated discharge pressure, compressor volumetric effi- The variations of condensing pressure with respect to
ciency will decrease, and accordingly the mass flow rate mass fraction of R744 are shown in Fig. 6. As the tem-
of refrigerant decreases, as indicated in Eqs. (1) and (2). perature of secondary heat transfer fluid at condenser
Fig. 4 presents the trend of compressor power inlet is elevated and the mass fraction of R744 in the
requirement which is measured by the torque transducer mixture increases, condenser pressure increases. This
and tachometer. The figure shows the compressor power figure shows the limit of the mass fraction of R744 in
increases when the mass fraction of R744 increases, the mixture which should be kept in order for the max-
which is due to the increased mass flow rate and the imum pressure not to exceed a certain limit. For exam-
higher pressure of refrigerant mixture. The specific ple, if the condenser maximum pressure should be kept
volume at the compressor suction remains constant and not to exceed 3 MPa when the condenser inlet tempera-
the specific volume at the compressor discharge decrea- ture of the secondary fluid is 40 C, the mass fraction of
ses as the condensing temperature increases, so that the R744 in R744/290 mixture should be less than about
volumetric efficiency of the compressor decreases. Hence 0.31. Therefore, this figure presents the condenser pres-
sure of the system that can be kept within a certain

Fig. 3. Variations of cooling capacity with respect to mass Fig. 4. Variations of compressor power with respect to mass
fraction of R744 at cooling condition. fraction of R744 at cooling condition.
1100 S.G. Kim, M.S. Kim / International Journal of Refrigeration 25 (2002) 1093–1101

range similar to that for conventional refrigeration sys-


tem by selecting a composition of R744/134a and R744/
290 according to the secondary fluid temperature at the
condenser inlet. The simulation shows a good agreement
with the experiment.

5.2. Effects of condenser exit quality on the performance

Simulation model was used to investigate the varia-


tion of the performance of the autocascade refrigeration
cycle using R744/290 (30:70 wt.%) and R744/134a
(30:70 wt.%) when the quality at the condenser exit
changes. This supports the selection of condenser exit
quality in this study. Just like the degree of subcooling
in the standard vapor compression cycle, the choice of
condenser exit quality is dependent on the temperature
level and the flow rate of the secondary fluid. Calcu-
lated refrigeration capacity, compressor power, and
COP are presented in Fig. 7 for the quality changes
at the condenser outlet when the secondary fluid
temperature at condenser inlet is kept as 20  C and
that at evaporator inlet as 0  C. In order to make
the quality at the condenser outlet decrease, the con-
Fig. 5. Variations of COP with respect to mass fraction of densing pressure should increase when the log mean
R744 at cooling condition. temperature difference in the condenser is kept con-
stant, which results in greater requirement of the
compressor power. In refrigeration capacity point of
view, the unbalance in the mass flow rate through the
evaporative condenser is a great concern, where the
mass flow rate of vapor to be condensed in the eva-
porative condenser is quite reduced for higher quality
at the condenser outlet, while that of liquid to be eva-
porated in the evaporative condenser is quite reduced

Fig. 6. Variations of inlet pressure of condenser with respect to Fig. 7. Performance with respect to condenser exit quality for
mass fraction of R744 at cooling condition. R744/290 and R744/134a mixture.
S.G. Kim, M.S. Kim / International Journal of Refrigeration 25 (2002) 1093–1101 1101

for lower quality. Therefore, the maximum COP was [2] Nekså P, Rekstad H, Zakeri GR, Schiefloe PA. CO2-heat
obtained for the quality of about 0.4 for R744/134a pump water heater: characteristics, system design and
(30/70 wt.%) and 0.5 for R744/290 (30/70 wt.%), experimental results. Int J Refrig 1998;21(3):172–9.
respectively. [3] Halozan H, Rieberer R. CO2 as refrigerant—possible
applications. Proceedings of the 4th IIR-Gustav Lor-
entzen Conference on Natural Working Fluids at Purdue,
2000 July 25–28; West Lafayette, USA. 2000, p. 43–50.
6. Concluding remarks [4] Pettersen J, Aarlien R, Nekså P, Skaugen G, Aflekt K. A
comparative evaluation of CO2 and HCFC-22 room air
The performance of an autocascade refrigeration sys- conditioners. In: Proceeding of IEA-IIR Workshop-CO2
tem using zeotropic refrigerant mixtures of R744/134a Technology in Refrigeration, Heat Pump and Air Con-
and R744/290 has been investigated. It is aimed that the ditioning Systems, 13–14 May 1997; Trondheim, Norway.
system using carbon dioxide is devised while keeping the 1997, p. 177–91.
highest pressure of the system close to that of conven- [5] Brown JS, Yanna Motta S, Domanski P. A. Analysis of
tional vapor compression systems. The performance was an automotive air conditioning system operating with CO2
evaluated by both experiments and computer simula- and R134a. Int J Refrig [in press].
[6] Aarlien R, Frivik PE. 1998, Comparison of practical per-
tions for various mass fractions of R744 and several
formance between CO2 and R-22 reversible heat pumps
operating conditions. for residential use. In: Natural Working Fluids 98, Pro-
The performance test and simulation showed that as ceeings of the IIR-Gustav Lorentzen Conference, 2–5 June
inlet temperature of the secondary heat transfer fluid to 1998; Oslo, Norway 1998. p. 341–50.
condenser increased, the refrigeration capacity and COP [7] Aarlien R, Pettersen J, Skaugen G, Nekså P. Residential
decreased while the compressor power increased. Fur- air conditioning with CO2-preliminary results. In: Pro-
thermore, as the mass fraction of R744 increased, cool- ceeding of IIR Conference-Applications for Natural
ing capacity and compressor power increased, but COP Refrigerants, 3–6 September 1996; Aarhus, Denmark
decreased. 1996. p. 659–66.
In this study, it is found that the autocascade refrig- [8] Hwang Y, Radermacher R. Experimental evaluation of
CO2 water heater. In: Natural Working Fluids 98, Pro-
eration cycle has a merit of low operating pressure as
ceeings of the IIR-Gustav Lorentzen Conference, 2–5 June
low as that in a conventional vapor compression refrig- 1998; Oslo, Norway, 1998. p. 321–8.
eration cycle. Natural refrigerants or HFC refrigerants [9] Kruse H, Heidelck R, Süss J. The application of CO2 as a
with relatively small amount of charge can be used as a refrigerant, IIR Bulletin, No. 1, Paris: International Insti-
refrigerant in the autocascade refrigeration system. tute of Refrigeration, 1999.
However, lower COP of autocascade refrigeration cycle [10] Hesse U, Kruse H. Alternatives for CFCs and HCFC 22
is a disadvantage, and the way to improve it should be based on CO2. Proceeding of IIR Conference-Energy Eef-
sought in the future. ficiency in Refrigeration and Global Warming Impact,
Ghent, Belgium, 1993. p. 317–25.
[11] Stoecker WF. Industrial refrigeration, Vol. II. Business
News Publishing Company, 1995. p. 319–25.
Acknowledgements
[12] Park SN, Kim MS. Performance of autocascade refrig-
eration system using carbon dioxide and R134a, In: Nat-
This study is supported by Korea Science and Engine- ural Working Fluids’98, Proceeings of the IIR-Gustav
ering Foundation (Grant No. 1999-1-304–006–3) and by Lorentzen Conference, 2–5 June 1998; Oslo, Norway.
the BK21 project of the Ministry of Education. 1998. p. 311–20.
[13] Domanski P, McLinden M. A simplified cycle simulation
model for the performance rating of refrigerants and
References refrigerant mixtures. Int J Refrig. 1992;15(2);81–8.
[14] McLinden M, Klein S, Lemmon E, Peskin A. NIST thermo-
[1] Lorentzen G. Revival of carbon dioxide as a refrigerant. dynamic and transport properties of refrigerants and refrig-
Int J Refrig 1994;17(5):292–301. erant mixtures, Ver. 6.0. Gaithersburg, USA, 1998.

Potrebbero piacerti anche