Sei sulla pagina 1di 32

Totally Integrated Power

Intelligent Transformer Substations


for Future-Proof Power Distribution
The Modular Concept Based on 8DJH Medium-Voltage Switchgear

www.siemens.com/transformersubstations
Why smart grids?

The requirements on power distribution and therefore on medium-


and low-voltage grids are increasing continuously.
Changing directions of power flow, load and voltage fluctuations,
which are caused especially by the strongly growing number of
power supplies from volatile power sources, e.g. photovoltaic/
biogas plants and wind farms, make the distribution grids of today
go to their capacity limits.

2
Always well supplied – Active distribution grid with intelligent Benefits of intelligent
no chance for blackouts transformer substations for a smooth transformer substations
Many of today‘s transformer substations, infeed of renewable energies
originally designed for a merely unidirec- While the additional load capacity required • Monitoring and assurance of
tional energy flow and equipped with due to the expansion of renewable energies power quality
conventional transformers, are no longer can be provided by means of grid expan- • Controlling of overload
capable of coping with the effects of vol- sion, the effects resulting from the alter- situations
atile power sources. The consequences nating direction of power flow, load fluc- • Minimization of loss of
are more and more frequent supply tuations, and voltage range limitation can power grid revenue by notably
breakdowns in the classical distribution only be handled with ­intelligent solutions. reduced interruption times
grid, with ever increasing downtimes. The answer is an active distribution grid • Optimization of grid expansion
In order to reduce such downtimes nota- with intelligent transformer substations as
• Object monitoring of the
bly and to limit the associated blackout key components. These contribute to an transformer substation
costs, quick adjustments to the changed active load management in the distribu-
load conditions must be possible. tion grid and enable an automatic and fast
fault clearance in case of blackouts.
In this way, you are always well supplied.
3
Conventional grid with unidirectional power flow

Hydroelectric
power station

Hydroelectric
Industry power station

110 kV* Industry Private households


Large power station

20 kV*
110 kV* Building infrastructure Private households
Large power station 0.4 kV* Industry
20 kV*
Building infrastructure

0.4 kV* Industry


Active distribution grid with intelligent transformer substations

Large power
station
Wind power station

Large power
station
Wind power station

110 kV*

110 kV*
Hydroelectric Building infrastructure
power station
20 kV*
Industry

Hydroelectric Building infrastructure


Solar power station
power station
20 kV* Biomass
Industry
power station
0.4 kV*
Solar power station
Legend
Communication Biomass
Power flow to: power station
Private households • High-voltage grid
0.4 kV* • Medium-voltage grid
• Low-voltage
Legend grid
E-car Communication
Primary Power flow to:
Battery
Private households transformer • High-voltage grid
Fuel cell substation • Medium-voltage grid
Building infrastructure • Low-voltage grid
Secondary
E-car transformer
substation Primary
Battery
transformer
* The given voltage values
Fuel cell substation
are exemplary
Building infrastructure
Secondary
transformer
substation
* The given voltage values
are exemplary

4
A consistent concept:
The suitable component
for every task

Distribution grids must meet the require- Modular design


ments resulting from the increasing inte- The centerpiece of a substation is the
gration of decentralized power sources. associated medium-voltage switchgear.
Counterbalancing the effects caused by The switchgear can be integrated modu-
changing directions of power flow as larly into a smart grid together with the
well as load and voltage fluctuations following components:
becomes the key task in the distribution • Remote terminal units
grid. SICAM MIC / EMIC / CMIC
• Uninterruptible power supplies SITOP
Siemens offers distribution grid opera- • Communication solutions with TCP-IP,
tors a consistent concept for intelligent GPRS, GSM, WiMAX, BPL, UMTS, etc.
transformer substations and the suitable • Short-circuit / ground fault direction
component for every task. The concept ­i­ndicators SICAM FCM
includes compact medium-voltage • Current and voltage sensors
switchgear with communication capabil- • Regulated distribution transformers
ity, regulated distribution transformers, FITformer® REG
as well as integrated telecontrol and • Power quality recorder
automation solutions which monitor and SICAM P850 / 855
control the medium- and low-voltage • Medium-voltage switchgear from the
grid. In this way, overloads of opera- 8DJH family
tional equipment are detected earlier • D ecentralized energy management
and voltage stability is ensured, e.g. by DEMS
stipulation of setpoint values for the • Control center system for utility
decentralized generators. ­companies SICAM 230
• Switchgear visualization SICAM SCC
A stable grid without extension of the • Connection to: Network control system
grid capacity SINAUT PowerCC
The benefits of this concept are that, in • Substation automation SICAM PAS / AK
many cases, decentralized power sources • Electronic meters AMIS.
can easily be integrated into the existing
distribution grid without expensive Solutions out of one hand make the
investments in grid expansion. Thus, a ­distribution grids ready for the challenges
stable grid offering reduced downtimes created by the growing integration of
is guaranteed. renewable energies. In addition, they
allow utilities a more efficient operation
of their infrastructure, thus offering
important competitive advantages.
5
4 1 2 3

Conceptual design of an
intelligent transformer substation
The above illustration shows the concep-
Typical room planning
tual design of an intelligent transformer of a transformer substation
substation

1 Medium-voltage switchgear 3 Low voltage


with motor operating mechanisms to Acquisition of load conditions,
Telecontrol room
actuate the switch-disconnectors or cir- power quality measurement,
cuit-breakers from external switching ­p osition indicators
points (e.g. network control center),
MV switchgear

­sensors to measure currents and voltages,


and intelligent short-circuit / ground fault
direction indicators 4 Telecontrol unit
RTU*, modem, uninterruptible
2 Transformer power supply
Standard transformer or regulated
LV distribution

Transformer

­distribution transformer

* Remote Terminal Unit

6
The key components in the grid

Planning, design and maintenance of a Intelligent transformer substations


smart distribution grid are complex allow for:
tasks for municipalities and distribution • Management of the low-voltage dis-
grid operators. The ability to seamlessly tribution grid with handling of meter
integrate sensors, actuators, communi- data, compensation of reactive power
cation and IT systems into the existing and harmonics, regulation of the
infrastructure significantly reduces ­distribution transformer, as well as
these challenges. Intelligent trans- the coordination of supply and load
former substations – with switchgear, • Supervision and control of the trans-
transformers, protection devices, as former substation on the medium-
well as telecontrol and automation voltage side regarding fault location
solutions – allow applications for higher and automatic recovery of supply.
reliability of supply. • Provision and transmission of
­measured values and indications from
Intelligent transformer substations the medium- and low-voltage system.
as key components of the modern
­distribution grid
In the future, transformer substations
will become a key component in the
distribution grid.

7
A smart grid communicates

A basic precondition for the operation of The following telecommunication


Your benefits
smart grids is the monitoring and control ­t­echnologies can usually be selected:
of as many grid components as possible. • Fiber optic or copper cables
• Comprehensive customer-­
specific communication solution
The basis for this is a reliable telecommu- • Broadband/high-speed powerline
optimized for the conditions nication infrastructure. ­s ystems
on site • Private wireless networks (e.g. WiMAX)
• Profit from our outstanding This telecommunication infrastructure • Public wireless networks.
expertise both in the energy on the medium- and low-voltage level
and the telecommunication is usually heterogeneous. The most Essential prerequisites for successful
fields
­suitable technologies for this are sub- operation are both the contractual
stantially determined by the local struc- ­assurance of a stable communication,
ture (big city, rural region, distances), also in case of blackouts, and perma-
the regulatory marginal conditions nently attractive data tariffs for
(transmission power, availability of f­re- machine-to-­machine-connections
quency bands and associated licenses), (M2M).
as well as the applications used.
They must therefore be adjusted individ- Siemens offers solutions for all men-
ually to every customer and every case of tioned telecommunication technologies,
application. including especially hardened, standard-
compliant routers and switches, in order
to enable your grid to communicate
­intelligently.

8
SICAM CMIC

Universal automation and


remote terminal unit SICAM CMIC
Universal remote terminal unit Versatility of SICAM CMIC:
SICAM CMIC: Portrait
SICAM CMIC is a universal automation and • Nodal functionality for use as sub­
remote terminal unit. With a temperature ordinate remote terminal unit with
Communication interfaces
range from –40 °C to +70 °C, a high EMC serial and Ethernet connection and protocols
resistance and the small, compact dimen- • Coupling of additional devices over • Ethernet: IEC 61850,
sions, SICAM CMIC can be used in a rough Modbus RTU IEC 60870-5-104, DNP(i)
• Serial: IEC 60870-5-101/-103,
environment also under smallest space • Freely programmable user programs Modbus RTU
conditions. With its technical and mechani- for local control, interlocking or regula-
Operation and display
cal benefits, SICAM CMIC is suitable for tion tasks, according to IEC 61131-3 • Display (128 x 96 pixels) incl.
electrical distribution substations, gas • Remote maintenance, remote diagnos- operation via 4 function keys
­distribution stations, hydropower plants, tics, and remote parameterizing • LEDs for status indications and
status of the communication
pipelines, railway power supplies, object • Configuration, diagnostics and test interfaces
protection, or as an alarm device. through a web browser, alternatively • Integrated web server for
via SICAM TOOLBOX II. configuration and diagnostics
Inputs / outputs
Intelligence of SICAM CMIC: • 12 digital inputs (24-60 V DC)
• 8 digital outputs
If all possibilities offered by SICAM CMIC
• Extension modules from the
are retrieved, the unit can be integrated TM series
into an intelligent transformer substation Auxiliary voltage
in three steps: • 18-72 V DC
1. Supervision/monitoring Temperature range
2. Telecontrol • From –40 °C to +70 °C
3. Automation and load flow control. Safety
• Security requests from
­tomorrow (BDEW white paper
conformity and integrated
crypto chip)

9
SITOP

Reliable 24 V DC – also in case of power failure


SITOP power supply unit
A reliable, constant power supply is DC-UPS for 24 volts nonstop
SITOP: Portrait
imperative for safe system operation. In case of a power failure, guaranteed
Depending on the requirements, the ­uninterrupted operation of protection
• Reliable power supply units
for almost all system voltages,
SITOP power supply units can be and control units is decisive. The motor
ratings and demands on individually upgraded with extension operating mechanism of the switch-­
regulated 24 V DC, as well as modules as well as with uninterruptible disconnector or circuit-breaker must also
on other output voltages power supply units. still operate safely in case of a power
• SITOP power supply unit ­failure. To ensure this, the SITOP power
PSU200M 24 V DC / 5 A and 10 The SITOP product range offers high- supply units can be upgraded to an unin-
A with ultra wide-range input
quality power supply units for almost terruptible 24 V DC power supply system.
85-264 / 176-550 V AC and
high overload capacity every requirement. The technology Depending on the energy demand,
­product line SITOP modular includes the ­maintenance-free battery modules with
• Additional modules to increase
the availability, e.g. for single-phase power supply units SITOP lead-gel batteries enable further opera-
­uninterruptible 24 V DC power PSU200M for maximum demands. tion in the range of hours. The intelligent
supply, for further operation Thanks to their ultra wide-range input battery management of the DC-UPS
on hour level (UPS1600) or
they guarantee constantly regulated module SITOP UPS1600 monitors all
minute level (UPS500)
24 V DC even in case of large voltage ­relevant operating data.
• DC-UPS SITOP UPS1600 fluctuations, and are as well suitable for
24 V DC / 10 A and 20 A with
digital inputs / outputs,
two-phase operation. The power boost Extremely communicative
­optionally with USB or two ­delivers up to three times the rated The grid and battery status can even be
Ethernet / PROFINET interfaces ­current for a short time in order to transmitted to PC or PLC systems via
• Remote monitoring with switch high loads also without problems. ­Ethernet / PROFINET. The integrated web
integrated web server server also enables remote diagnostics.
(UPS1600)

10
SCALANCE M874 coupled with SICAM CMIC

Mobile communication router


SCALANCE M874
The SCALANCE M874 are mobile commu- Applications:
SCALANCE M874: Portrait
nication routers for the cost-effective The SCALANCE M874 routers are univer-
and safe connection of Ethernet-based sally applicable. Due to their design and
• Robust plastic enclosure
subnetworks and automation devices via electrical properties, the routers are
the mobile communication network. especially suitable for industrial applica- • Automatic dial-up and holding
of the IP-based online connec-
SCALANCE M874-3 uses mobile commu- tions:
tion to the Internet
nications of the 3rd generation (UMTS)
• World-wide flexible system access for • Integrated IPsec
and supports HSPA+ (High Speed Packet
maintenance and diagnostics purposes
Access). In this way it allows high trans- • VPN tunnel encryption
mission rates of up to 14.4 Mbit/s • Connection of static and mobile partici- • Management and configuration
­downlink, and up to 5.76 Mbit/s uplink pants for control and monitoring of e.g. via comfortable WBM
(depending on the infrastructure of the – Sewage and water treatment plants
• Diagnostics via SNMP
mobile communication provider). – Oil and gas supply
SCALANCE M874-2 uses the mobile – District heating networks • Comprehensive logging infor-
mation available via SysLog
­communication network of the 2nd – Power distribution
­generation (GSM) and supports GPRS – Pumping stations • Extended event management
via e-mail, SMS and digital
(­General Packet Radio Service) and – Traffic engineering input
EDGE (Enhanced Data Rates for GSM
• Applicable world-wide* by • Fast mobile diagnostics with
Evolution). Access and communication
– UMTS (penta-band technology) smartphone/tablet thanks to
security is guaranteed by the safety func- WebApp
– GSM (quad-band technology).
tions of the integrated firewall, and by
the VPN tunnel (end-to-end encryption
of the communication connection by the
establishment of IPsec tunnels).

* Note: Country-specific approvals must be observed!

11
SICAM FCM

Digital SC indicator with measuring function


SICAM FCM feeder condition monitor
On the pulse of your distribution grid Benefits at a glance:
SICAM FCM: Portrait
SICAM FCM is a short-circuit and ground • The first short-circuit indicator to
fault indicator with direction indication, employ sensors conforming to the
Communication
• Interface RS485 Modbus RTU
operating with protection algorithms standard IEC 60044-7/ -8
Operation and display and the latest low-power sensor • High-precision measurement without
• 4 function keys, 3 LEDs and ­technology according to IEC 60044. calibration and adjustment to the
display This provides best results, especially in ­primary values
Inputs / outputs isolated or compensated distribution • Usable in all grid types
• 3 inputs for alternating voltage
100 V/√3 or low-power sensors
grids. For workload monitoring of distri- • Precise and fast fault localization
3.25 V/√3 bution grid components, SICAM FCM for minimum expenses regarding
• 3 inputs for alternating offers comprehensive measured values. ­p ersonnel and traveling costs
current low-power sensors The evaluation of this data can be used • Selective fault information with
225 mV@300 A
• Alternative current input L2 for for a specific network planning regard- ­direction indication as a basis for
low-power sensor 225 mV@60 A ing grid expansion and the application of “self-healing” applications
for sensitive ground fault investment funds. Through a Modbus • Resupply times possible in the range
detection RTU interface, SICAM FCM delivers all of minutes or seconds ­(depending on
Auxiliary voltage
relevant information, thus allowing to the primary equipment)
• 24-60 V DC, 230 V AC
• Battery for 2,000 hours, evaluate and display the status of the • Minimum loss of power grid and end
service life approx. 20 years distribution grid correctly and precisely. customer revenue
Temperature range • Reliable measured values for opera-
• From –30 °C to +70 °C tional management and planning.
Measurands
• TRMS (True RMS) measured
values
• Phase voltage and currents;
ground current; power
­frequency and cosφ; active,
reactive and apparent power

12
Low-power sensors

Intelligent current and


voltage sensors
Low-power sensors In this context, the three-phase version
Low-power sensors: Portrait
Our low-power sensors conform to the can also be equipped with two phase
standards IEC 60044-7 and -8. current sensors and a zero-sequence
• Current and voltage sensors
They offer measured values for current ­current sensor for sensitive ground fault according to the international
and voltage which are e.g. acquired and detection. instrument transformer
processed in SICAM FCM. This enables ­standards IEC 60044-7 or -8
high-precision measurements without Voltage sensors • Accuracy class 0.5, 1 or 3
calibration or adjustment to the primary The voltage sensors are resistor dividers
• No calibration or adjustment
values. which provide an output signal of to the primary values
3.25 V / √3 at the rated primary voltage.
• Small size for retrofitting and
Current sensors The voltage sensors are available as cast-
for new systems
The current sensors are inductive current resin plugs, which are inserted into the
transformers whose secondary winding cable T-plugs instead of the blind plugs. • Tested for severe ambient
conditions (temperature /
delivers a voltage signal through a preci- Here, the cone conforms to the type C condensation / EMC)
sion shunt. At the rated primary current, standardized in EN 50180 / 50181.
• Installation Switchgear
this is 225 mV. The current sensors are ­minimally interfered with
available in two versions: Divisible cable- during installation
type current transformers – used espe-
cially for retrofitting existing switchgear,
and closed ring cores – mounted on the
outside-cone bushing of the 8DJH
switchgear in a single- or three-phase
version.

13
FITformer® REG

Regulated distribution transformer


FITformer® REG
As one of the main components in distri- Their application helps to decouple the
FITformer® REG: Portrait bution stations, transformers fulfill an medium- and low-voltage grid as regards
important task: They are responsible for voltage stability. Thus, ranges of +/- 10%
• Power range up to 630 kVA, the final customers being supplied with are available in both grids for regulation
max. operating voltage: 36 kV the correct voltage. Grid operators must purposes.
• Low-voltage load regulation therefore guarantee a low voltage supply
within the allowed voltage band for Regulated distribution transformers have
range in three steps
every household. However, the rising established themselves as an integral
• Operating properties and component of smart grids, as real-time
dimensions correspond to infeed of renewable energies overstrain
those of common distribution many transformer substations. Consider- monitoring and control of the low-voltage
transformers able voltage fluctuations are the conse- grid is absolutely necessary for a stable
quence and can even lead to an power supply as the proportion of
• Design example
21 kV / 420 V infringement of the permissible voltage ­renewable energies increases.
Example for possible load band.
regulation range: FITformer® REG – the adaptable
+/- 3.57% @ 400 kVA Increasing trend towards regulated distribution transformer
distribution transformers The ratio of the regulated distribution
+/- 4.34% @ 630 kVA
In case of non-compliance with the vol- transformer FITformer® REG can be
• Additional setting range on the tage quality criteria due to the decentra- changed under load. These adjustments
high-voltage side for optimum
operation:
lized supply from renewable energies, are possible due to the three-step
+/- 2.5% and +/- 5% grid operators are forced to a costly low-voltage load regulation range of the
(adjustable in de-energized expansion of the distribution grid. transformer. With this transformer,
condition) In this context, regulated distribution energy suppliers can guarantee the sup-
transformers, such as FITformer® REG, ply voltage within the tolerance limits,
represent a cost-efficient alternative. and comply with the standard EN 50160.

14
SICAM P850 / 855

Power meter and power quality recorder


SICAM P850 / 855
Device description Benefits at a glance:
SICAM P850 / 855: Portrait
The multifunction measuring device • Universal for single-phase, three- and
SICAM P85x serves for acquisition, visual- four-wire grids (with neutral conductor)
Communication interfaces
ization, and transmission of measured • Large current measuring range and protocols
electrical values such as alternating (up to 10 A max.) • Ethernet: MODBUS TCP,
­current, alternating voltage, frequency, • High accuracy due to small measuring IEC 61850 Edition 2
power, harmonics, etc. Acquisition and error • Serial: Modbus RTU,
IEC 60870-5-103
processing of measurands and events • Easy parameterizing by integrated
Operation and display
are performed according to the power web server • Full graphic display incl.
quality standard IEC 61000-4-30. • Safe data storage by battery buffering ­operation via 4 function keys
Through the communication interfaces, • High interference immunity. • 4 LEDs for status and fault
the measurands can be transmitted to a indications
• Integrated web server for
PC and to the control and protection interaction with PC via HTML
­s ystem, or shown on a display. pages
As an all-in-one device, SICAM P855 Input measuring circuits
offers a combined recording and • 4 x alternating voltage,
­evaluation function in addition to the 3 x alternating current
up to max. 10 A
monitoring function: Measured values
Auxiliary voltage
can be recorded at programmable time • 24 - 250 V DC
intervals with various recorders, e.g. • 110 - 230 V AC, 50 / 60 Hz
power quality and fault recorders. Housing specification
­Long-time data and events are evaluated • Plastic enclosure for
directly in the device according to the top-hat-rail mounting,
optionally flush mounting
power quality standards (e.g. EN 50160), • Dimensions:
and issued as a report. 96 x 96 x 100 mm (W / H / D)
• Degree of protection: max. IP51

15
8DJH switchgear

The 8DJH family for the


medium-voltage distribution grid
Space saving:
Medium-voltage switchgear The compact 8DJH Compact
The 8DJH Compact 8DJH and 8DJH 36 8DJH Compact has been especially
The gas-insulated medium-voltage ­developed for transformer substations
switchgear types 8DJH and 8DJH 36 are in which space requirements are an
the basis for applications in intelligent important issue. This switchgear pro-
transformer substations. These modular vides maximum functionality on mini-
switchgear assemblies allow the variable mum space. With its smaller standing
arrangement of the functions – both surface in comparison to other block-
within a panel block and in more com- type or extendable switchgear types,
plex switchgear layouts. All individual 8DJH Compact leaves more space for
panels and panel blocks can optionally additional low-voltage feeders, more
be extended. Thus, almost all scheme medium-voltage cable feeders, or intelli-
arrangements can be implemented with gent functions. Shorter transformer
8DJH switchgear. cables and reduced expenses for laying
these cables inside the transformer
­substation provide further advantages,
The illustration shows the space
gained for four low-voltage
reducing the investment costs.
­in-line feeders, or an additional
medium-voltage cable feeder,
by installing 8DJH Compact
with a width of 700 mm in
comparison with a conventional
ring-main unit with a width of
1,050 mm

16
8DJH Compact switchgear 8DJH 36 switchgear

Characteristics of the 8DJH family: Compact


8DJH family: Portrait
Thanks to the use of SF6 insulation,
Environmentally independent ­c­ompact dimensions are possible.
• Comprehensive supply of
Hermetically welded switchgear vessels Thus: gas-insulated switchgear for
made of stainless steel as well as single- • E xisting switchgear rooms and sub­ secondary distribution grids
pole solid insulation make the parts station rooms can be used effectively
• High cost-efficiency by
under high voltage of 8DJH switchgear • New constructions cost little climate-independent,
• Insensitive to aggressive ambient • Costly city-area space is saved. durable and maintenance-free
­conditions, such as: switchgear
‒ Saline air Safe for operation and cost-efficient • High switchgear availability
‒ Air humidity Switchgear vessels designed as sealed and personal safety
‒ Dust pressure systems, maintenance-free • Minimized space requirements
‒ Condensation switching devices and enclosed cable by compact dimensions
• T ight to ingress of foreign objects, plugs ensure: • High product quality from
such as: • Maximum supply reliability Siemens, one of the pioneers
‒ Dust, pollution • Personnel safety of gas-insulated switchgear
‒ Liquids • Sealed-for-life design according to • Protection of investment by
‒ Small animals IEC 62271-200 (sealed pressure possible integration in smart
‒ Humidity. ­s ystem) distribution grids
• Installation, operation, extension and • Reliable and competent
replacement without SF6 gas work support on site – from
planning to operation
• No maintenance cycles
• Reduced operating costs
• Cost-efficient investment.

17
The integration of components
into the medium-voltage switchgear

18
The switchgear of the 8DJH series is RTUs can be optionally integrated inside Depending on the purpose, different
optionally equipped with motor operating the switchgear, in additional low-voltage components for monitoring and
mechanisms, short-circuit indicators, compartments or in a separate wall ­control are used: These components
­voltage detecting systems, as well as with ­cubicle via a plug connection. In this way, can also be easily and quickly retro­
further sensors. the switchgear fulfills all preconditions fitted at a later time.
for integration in an intelligent network
infrastructure.

Overview and explanation of the components:


Component Function

Uninterruptible power supply (UPS) The task of the UPS is to continue to ensure
Depending on the requested bridging time the communication and/or the possibility
in case of power failures, an uninterruptible to telecontrol the transformer substation in
power supply based on battery or capacitor case of power failure.
modules is used.

Remote terminal unit Inside the intelligent transformer substation,


The remote terminal unit (RTU) is equipped the RTU serves as a connecting element to
with binary inputs and outputs, various the network control center. It collects all rele-
communication interfaces, and freely pro- vant signals and receives control commands,
grammable user programs. or works autonomously according to prede-
termined control or regulation algorithms.

Communication modem Communication modems are employed


The selection of the communication for safe data transmission from the remote
modem to be used is determined by the terminal unit to the network control center
selected or available telecommunication using the selected telecommunication
technology. technology.

Intelligent SC indicators Intelligent short-circuit / ground fault direc-


Intelligent short-circuit and ground fault indi- tion indicators report short-circuits or ground
cators with or without direction indication faults in the medium-voltage distribution
can be used in all grid types. For communica- grid. Relevant measured values are acquired,
tion with the RTU, a Modbus RTU interface is allowing for an active load management in
available. the distribution grid.

Remotely controllable operating In order to reduce the reclosing times in


mechanisms case of fault, the switch-disconnectors or
Motor operating mechanisms inside the circuit-breakers are equipped with motor
ring-main unit are available in original operating mechanisms for remote control.
equipment manufacturer quality. If
required, retrofitting is easily possible.

Current sensors The current signal serves to detect


Current sensors with low-power trans- short-circuits and ground faults, and can be
former technology are available as closed or used as a measured value for load flow
divisible ring cores. control or for optimal utilization of the grid
capacity.

Voltage sensors The voltage signal serves to detect the


Voltage sensors as resistor dividers are direction of the short-circuit or ground
available as cast-resin plugs for insertion fault, and can be used as a measured value
into the cable T-plug. for load flow control or voltage regulation.

19
Step by step to more intelligence

• Increase of availability • Minimization of downtimes (“h“ => “min“)


• Fast fault localization

1. Monitoring + 2. Telecontrol

• Remote terminal unit with communication • Remote terminal unit with communication
­connection ­connection
• Short-circuit / ground fault direction indicators • Short-circuit / ground fault direction indicators
• Current sensors • Current sensors
• Voltage sensors • Voltage sensors
• Auxiliary switch contacts • Auxiliary switch contacts
• Uninterruptible power supply • Uninterruptible power supply

• Motor operating mechanisms of the


switch-­disconnectors or circuit-breakers

The illustration shows the stepwise expansion levels:


Monitoring, telecontrol and load flow control

20
The 3-level concept The second level contains, besides By installation of intelligent control,
In order to conform to the increased monitoring, also the possibility to measurement and regulation
requirements also in the future, telecontrol the switchgear, thus ­s ystems, conventional transformer
three levels of intelligence can be allowing the minimization of down- substations can be upgraded step
implemented. times. by step. In this way they are per-
In the first level, the focus is on In the third level, the effects of fectly prepared for their integration
substation monitoring, in order to decentralized power supplies are into smart grids. Depending on
increase the availability and to allow managed via automation. Grid the desired expansion level, the
for a fast fault localization. losses can thus be notably reduced. ­necessary components must be
­configured.

• Minimization of losses
• Management of decentralized power supplies

The modular

+ 3. Load flow control


= concept for the
smart grid
of the future

• Remote terminal unit with communication ­


connection
• Short-circuit / ground fault direction indicators
• Current sensors
• Voltage sensors
• Auxiliary switch contacts
• Uninterruptible power supply

• Motor operating mechanisms of the


switch-­disconnectors or circuit-breakers

• Power meter and power quality recorder


• Regulated distribution transformer
• Regulation algorithms, software components
for flow control
• Regulation algorithms for the regulated distribution
transformer

21
1. Monitoring

The expansion levels for the modular concept


1st level: Monitoring
Target: To do this, the following components
Benefits
In the first level, the focus is on trans- are used:
former substation monitoring, in order • Remote terminal unit with communi­
• Higher availability
to allow for a fast fault localization and cation connection
• Faster fault localization to reach a higher availability. However, • Short-circuit / ground fault direction
• Object monitoring of the travel time to the transformer substa- ­indicators
­transformer substation tions is still necessary to eliminate the • Current sensors
• Current and voltage values fault, preventing a substantial reduction • Voltage sensors
from the medium-voltage side of the downtimes. • Auxiliary switch contacts
• Uninterruptible power supply.

22
2. Telecontrol

2nd level: Telecontrol


Target: To do this, the following components
Benefits
Today, typical downtimes of transformer are used:
substations are in the range of hours, as • Remote terminal unit with communi­
• Higher availability
the maintenance teams must identify the cation connection
fault location in the affected ring on site, • Short-circuit / ground fault direction • Faster fault localization
drive to the individual transformer sub- ­indicators • Object monitoring of the
station, and isolate the fault. The appli- • Current sensors ­transformer substation
cation of short-circuit or ground fault • Voltage sensors • Current and voltage values
direction indicators only represents an • Auxiliary switch contacts from the medium-voltage side
improvement for a fast fault localization. • Uninterruptible power supply
• Motor operating mechanisms of the
A further reduction of time is possible switch-disconnectors or circuit-­ • Minimization of downtimes
today by using remote terminal units, breakers. • Reduction of the reclosing
with characteristics especially tailored times
for this task. Downtimes can thus be
reduced from hours to just a few
­minutes.

23
3. Load flow control

3rd level: Load flow control


Target: To do this, the following components
Benefits
Changing directions of the energy flow are used:
as well as load and voltage fluctuations, • Remote terminal unit with communi­
• Higher availability
caused by a continuously rising number cation connection
• Faster fault localization of renewable energy producers, make • Short-circuit / ground fault direction
• Object monitoring of the the distribution grids of today go more ­indicators
­transformer substation and more to their limits, and partially • Current sensors
• Current and voltage values also exceed the allowed voltage limits. • Voltage sensors
from the medium-voltage side The aim of the third level is to counteract • Auxiliary switch contacts
these effects by means of control and • Uninterruptible power supply
regulation algorithms, to adhere to the • Motor operating mechanisms of the
• Minimization of downtimes allowed limits of the distribution grid switch-disconnectors or circuit-­
• Reduction of the reclosing again, and to postpone or even avoid an breakers
times expensive grid expansion. • Power meter and power quality
recorder
• Regulated distribution transformer
• Minimization of losses • Regulation algorithms, software
• Management of effects from ­components for flow control
decentralized power supplies • Regulation algorithms for the regulated
• Reduction of grid losses distribution transformer.
• Regulation of RDT

24
Able to cope with all requirements:
The communication for an
intelligent secondary distribution

Communication concept: Transformer substation – RTU – network control center including time synchronization

Control system

Ethernet
IEC 60870-5-104

NTP *

SICAM
CMIC

RS485
Modbus RTU

Power meter and


power quality
recorder, e.g.
SICAM
P850 / P855

Regulated
distribution trans-
former (RDT), e.g.
FITformer® REG

MV switchgear with
motor operating
mechanisms, e.g.
8DJH with Modbus MCU

Intelligent
short-circuit / ground fault
direction indicator, e.g.
SICAM FCM
* NTP (Network Time Protocol)

25
Configuration examples
Technical features
Rated values up to 17.5 kV, 25 kA, 1 s 24 kV, 20 kA, 3 s
Rated frequency 50 / 60 Hz 50 / 60 Hz
8DJH
Busbar current up to 630 A 630 A
Feeder current up to 630 A 630 A
Busbars Single busbar
Insulation Gas-insulated
Switchgear vessel Hermetically enclosed
Type of switchgear Factory-assembled, type-tested, metal-enclosed switchgear
­according to IEC 62271-200, modular and extendable (option),
panel blocks consisting of 2, 3 and 4 panels
Internal arc classification (option) IAC A FL/FLR 21 kA, 1 s
Dimensions
Block width 620 mm to 1720 mm
depending on number and type of panels
Block height Optionally 1200 mm, 1400 mm or 1700 mm
(each without low-voltage compartment)
Height of LV compartment Optionally 200 mm, 400 mm, 600 mm, 900 mm
Block depth tiefe 775 mm, 890 mm (with pressure relief duct at the rear)

Technical features
Rated values up to 17.5 kV, 25 kA, 1 s 24 kV, 20 kA, 3 s

8DJH Compact Rated frequency 50 / 60 Hz 50 / 60 Hz


Busbar current up to 630 A 630 A
Feeder current up to 630 A 630 A
Busbars Single busbar
Insulation Gas-insulated
Switchgear vessel Hermetically enclosed
Type of switchgear Factory-assembled, type-tested, metal-enclosed switchgear according
to IEC 62271-200, panel blocks consisting of 3, 4 and 6 panels
Internal arc classification (option) IAC A F/FLR 21 kA, 1 s
Dimensions
Block width 620 mm, 700 mm, 930 mm, 1010 mm, 1240 mm, 1400 mm
depending on number and type of panels
Panel height Optionally 1400 mm or 1700 mm
Panel depth 775 mm

Technical features
Rated values up to 36 kV, 20 kA, 3 s
Rated frequency 50 / 60 Hz
8DJH 36
Busbar current up to 630 A
Feeder current up to 630 A
Busbars Single busbar
Insulation Gas-insulated
Switchgear vessel Hermetically enclosed
Type of switchgear Factory-assembled, type-tested, metal-enclosed switchgear
­according to IEC 62271-200, modular and extendable,
individual panels and panel blocks
Internal arc classification (option) IAC A FL/FLR 21 kA, 1 s
Dimensions
Panel width according to panel type 430 mm, 500 mm
Panel height 1600 mm (without low-voltage compartment)
Panel depth 920 mm

26
for intelligent transformer substations
1. Monitoring 2. Telecontrol
Configuration Configuration

Cable feeder Cable feeder


- Auxiliary switch at the three-position switch

- Intelligent short-circuit / ground fault direction indicator


with associated current and voltage sensors
Siemens SICAM FCM
MV switchgear

MV switchgear
Transformer feeder -A
 uxiliary switch at the three-position switch Transformer feeder
with switch-disconnector / with switch-disconnector /
fuse combination fuse combination
-S
 ignaling switch “HV HRC fuse tripped“

Transformer feeder -A
 uxiliary switch at the circuit-breaker Transformer feeder
with circuit-breaker with circuit-breaker

-A
 uxiliary switch at the three-position switch

-D
 efinite-time overcurrent protection Siemens SIPROTEC

Remote terminal unit - Remote terminal unit as compact unit Remote terminal unit
Siemens SICAM CMIC
- Remote terminal unit with extension modules
for binary inputs/outputs Siemens SICAM CMIC,
optionally SICAM EMIC
Communication modem - Mobile communication (GPRS, UMTS), Communication modem
e.g. Siemens SCALANCE M

-W
 iMax, e.g. RUGGEDCOM WIN

- Broadband / high-speed powerline, e.g. MV200

-F
 iber optic, e.g. Siemens SCALANCE X

- xDSL (ADSL, SHDSL), e.g. Siemens SCALANCE M

Uninterruptible - Siemens SITOP power supply units Uninterruptible


power supply power supply
- Siemens DC-UPS SITOP UPS1600 with battery modules

- Siemens DC-UPS SITOP UPS500S with capacitors

Cable feeder

27
3. Load flow control
Configuration

Cable feeder
-A
 uxiliary switch at the three-position switch -A
 uxiliary switch at the three-position switch

- Intelligent short-circuit / ground fault direction indicator - Intelligent short-circuit / ground fault direction indicator
with associated current and voltage sensors with associated current and voltage sensors
Siemens SICAM FCM Siemens SICAM FCM

MV switchgear
-A
 uxiliary switch at the three-position switch Transformer feeder -A
 uxiliary switch at the three-position switch
with switch-disconnector /
fuse combination
-S
 ignaling switch “HV HRC fuse tripped“ -S
 ignaling switch “HV HRC fuse tripped“

-A
 uxiliary switch at the circuit-breaker Transformer feeder -A
 uxiliary switch at the circuit-breaker
with circuit-breaker

-A
 uxiliary switch at the three-position switch -A
 uxiliary switch at the three-position switch

-D
 efinite-time overcurrent protection Siemens SIPROTEC -D
 efinite-time overcurrent protection Siemens SIPROTEC

- Remote terminal unit as compact unit Remote terminal unit - Remote terminal unit as compact unit
Siemens SICAM CMIC Siemens SICAM CMIC
- Remote terminal unit with extension modules - Remote terminal unit with extension modules
for binary inputs/outputs Siemens SICAM CMIC, for binary inputs/outputs Siemens SICAM CMIC,
optionally SICAM EMIC optionally SICAM EMIC
-M
 obile communication (GPRS, UMTS), Communication modem -M
 obile communication (GPRS, UMTS),
e.g. Siemens SCALANCE M e.g. Siemens SCALANCE M

-W
 iMax, e.g. RUGGEDCOM WIN -W
 iMax, e.g. RUGGEDCOM WIN

- Broadband / high-speed powerline, e.g. MV200 - Broadband / high-speed powerline, e.g. MV200

-F
 iber optic, e.g. Siemens SCALANCE X -F
 iber optic, e.g. Siemens SCALANCE X

- xDSL (ADSL, SHDSL), e.g. Siemens SCALANCE M - xDSL (ADSL, SHDSL), e.g. Siemens SCALANCE M

- Siemens SITOP power supply units Uninterruptible - Siemens SITOP power supply units
power supply
- Siemens DC-UPS SITOP UPS1600 with battery modules - Siemens DC-UPS SITOP UPS1600 with battery modules

- Siemens DC-UPS SITOP UPS500S with capacitors - Siemens DC-UPS SITOP UPS500S with capacitors

-M
 otor control unit for easy activation of the Cable feeder -M
 otor control unit for easy activation of the
“disconnecting“ function of the three-position switch, “disconnecting“ function of the three-position switch,
Siemens MCU RI Siemens MCU RI
-M otor control unit for two-pole switching of the -M otor control unit for two-pole switching of the
­“disconnecting“ function of the three-position switch ­“disconnecting“ function of the three-position switch
and / or switching of the “earthing“ function, and / or switching of the “earthing“ function,
Siemens MCU-MH Siemens MCU-MH
-M
 otor control unit for activation of the three-position -M
 otor control unit for activation of the three-position
switch via Modbus-RTU, Siemens MCU-MH-MOD switch via Modbus-RTU, Siemens MCU-MH-MOD
Power meter and -M
 ultifunctional measuring device for acquisition
power quality recorder of power quality measurands in the low-voltage
distribution grid, together with the associated
current transformers, SICAM P850/855
Regulated -R
 egulated distribution transformer according
distribution transformer to the existing high and low voltage or power,
Siemens FITformer® REG
Regulation algorithms
-C
 ontrol and regulation software
and software components

28
Intelligent transformer substation version
with the RTU in the low-voltage
compartment of the switchgear
The solution

In order to install the RTU in a space-saving way


inside the existing substation building without
having to change to a bigger substation type,
there is the following possibility:
The 8DJH is planned with a switchgear height of
1200 mm instead of the normal 1400 mm,
and the RTU is integrated in the 200 mm high
low-voltage compartments mounted on the top.
In this way, the overall switchgear height of
1400 mm remains.
SICAM EMIC installed in the
low-voltage compartment on top
of the 8DJH switchgear

29
Intelligent transformer substation version
with the RTU in a separate RTU cubicle

The solution

For retrofitting or to clearly divide competencies


between the grid operation and the telecontrol depart-
ments, the version with the RTU in a separate RTU
cubicle is particularly suitable. For this purpose, the
RTU cubicle is placed in a separate telecontrol area of
the transformer substation, and connected to the
medium-voltage switchgear via a plug-in connection.
This solution also allows an easy replacement of the
whole RTU cubicle at the end of the service life.

SICAM MIC installed in a ­separate


RTU cubicle inside the transformer
substation

30
30
Intelligent transformer substation version
with the RTU integrated in the switchgear

The solution

In order to design intelligent transformer


­substations in an especially compact and
space-saving way, the version with the RTU
­i­­ntegrated in the front operating mechanism of
the 8DJH is particularly suitable.

SICAM CMIC integrated


in the front operating
­mechanism of the trans-
former feeder of the 8DJH

31
Published by and copyright © 2013:
Siemens AG
Wittelsbacherplatz 2
80333 Munich, Germany

Siemens AG
Infrastructure & Cities Sector
Low and Medium Voltage Division
Medium Voltage & Systems
Mozartstr. 31 C
91052 Erlangen
Germany
www.siemens.de/mediumvoltage

For more information,


please contact our
Customer Support Center.
Tel.: +49 180 524 84 37
Fax: +49 180 524 24 71
(Charges depending on provider)
E-mail: support.ic@siemens.com

Low and Medium Voltage Division


Order No. IC1000-G320-A177-X-7600
Printed in Germany
WS 1013 WU 5.0 74/48637

Printed on elementary chlorine-free bleached paper.

All rights reserved.


Trademarks mentioned in this document are the
property of Siemens AG, its affiliates, or their
respective owners.

For all products containing OpenSSL


IT safety functions, the following applies:
This product includes software developed by the
OpenSSL Project for use in the OpenSSL Toolkit
(www.openssl.org).
This product includes cryptographic software
written by Eric Young (eay@cryptsoft.com).

Subject to change without prior notice.


The information in this document contains general
descriptions of the technical options available,
which may not apply in all cases.
The required technical options should therefore
be specified in the contract for the individual case.

www.siemens.com/mediumvoltage
32

Potrebbero piacerti anche