Sei sulla pagina 1di 10

For

 Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  


For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

                                                                                                                 Power  Systerms  

Per  Unit  Systems:  

1. What  is  the  per  unit  reactance  of  an  alternator  if  the  capacity  is  doubled  and  voltage  is  
halved?  
a) Increases  by  4  times                                                                        b)  reduces  by  8  times  
c) Increases  by  8  times                                                                        d)  decreases  by  4  times                              (Ans:  C)  
2. The  per  unit  impedance  of  a  synchronous  machine  is  0.242.  If  the  base  voltage  in  increased  
by  1.1  times  then  per  unit  impedance  value  will  be  
a) 0.266                  b)  0.244                      c)  0.220                              d)  0.2                                                                                            (Ans:  d)  
3. Two  identical  generators  of  100  MVA,  33  kV  are  connected  in  parallel  as  shown  in  the  figure,  
they  are  interconnected  through  reactor,  Faults  occur  at  F1  and  F2  at  two  different  locations.  
The  ratio  of  equivalent  fault  reactance  at  F1  w.r.t  F2  is  _________  

 
 

a) 1.8                          b)  0.55                              c)  3.6                                    d)  0.27                                                                                              (Ans:  a)  


4. For  the  power  system  shown  in  the  fig  below,  the  specifications  of  the  components  are  the  
following  :  

 
G1  =  25  kV,  100  MVA,  X  =  9%  
G2  =  25  kV,  100  MVA,  X  =  9%  
T1  =  25  kV/220  kV,  90  MVA,  X  =  12%  
T2  =  220  kV/25  kV,  90  MVA,  X  =  12%  
Line  1  :  200  kV,  X  =  150  ohms  
Choose  25  kV  as  the  base  voltage  at  the  generator  G1,  and  200  MVA  as  the  MVA  base.  The  
impedance  diagram  is    

   

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

 
 

   
                        (Ans:b)  
5.  A  3  –  phase  star  connected  load  is  drawing  power  at  a  voltage  of  0.9  pu  and  0.8  power  factor  
lagging.  The  three  phase  base  power  and  base  current  are  100  MVA  and  437.38A  respectively.  The  
line  –  to  –line  load  voltage  in  kV  is  ______                                                                                                                                                      (Ans  :  118.8)  

6.  A  sustained  3-­‐phase  fault  occurs  in  the  power  system  shown  in  the  fig.  The  current  and  voltage  
phasors  during  the  fault  (on  a  common  reference),  after  the  natural  transients  have  died  down,  are  
also  shown.  Where  is  the  fault  located?  

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

 
a) Location  P                    b)  Location  Q                c)  Location  R                          d)  Location  S                                    (Ans:  b)  

7.  Three  –  phase  to  ground  fault  takes  place  at  locations  F1  and  F2  in  the  system  shown  in  the  fig.  

 
         If  the  fault  takes  place  at  location  F1,  then  the  voltage  and  the  current  at  bus  A  are  Vf1  and  IF1  
respectively.  If  the  fault  takes  place  at  location  F2,  then  the  voltage  and  the  current  at  bus  A  are  VF2  
and  IF2  respectively.  The  correct  statement  about  voltages  and  currents  during  faults  at  F1  and  F2  is    

a) VF1  leads  IF1  and  VF2  leads  IF2                      b)    VF1  leads  IF1  and  VF2  lags  IF2    

C)    VF1  lags  IF1  and  VF2  leads  IF2                                  d)  VF1  lags  IF1  and  VF2  lags  IF2                                                                  (Ans:  c)  

8.  Five  alternators  each  rated  5  MVA,  13.2  kV  with  25%  of  reactance  on  its  own  base  are  connected  
in  parallel  to  a  busbar.  The  short-­‐circuit  level  in  MVA  at  the  busbar  is  _______                                      (Ans:  100)  

9.  For  the  configuration  shown  in  the  fig.  the  breaker  connecting  a  large  system  to  bus  2  is  initially  
open.  The  system  3-­‐phase  fault  level  at  bus  3  under  this  condition  is  not  known.  After  closing  the  
system  breaker,  the  3-­‐phase  fault  level  at  bus  1  was  found  to  be  5.0  pu  .  What  will  be  the  new  3-­‐
phase  fault  level  at  system  bus  3  after  the  interconnection?    All  per  unit  values  are  on  common  base.  
Prefault  load  currents  are  neglected  and  prefault  voltages  are  assumed  to  be  1.0  p.u  at  all  buses.  

 
 

Eg  =  1.0  p.u.,        XT  =  0.2  p.u.,        XLine  =  0.3  p.u.,          Xd  =  0.2  p.u.                                                                                                    (Ans:  11.4285)  

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

Statement  for  Linked  Answer  Question:  (10  and  11  only)  

Two  generator  units  G1  and  G2  are  connected  by  15  kV  line  with  a  bus  at  the  mid-­‐point  as  shown  
below,  

 
G1  =  250  MVA,  15  kV,  positive  sequence  reactance  X  =  25%  on  its  own  base.  

G2  =  100  MVA,  15  kV,  positive  sequence  reactance  X  =  10%  on  its  own  base.  

L1  and  L2  =  10  km,  positive  sequence  reactance  X  =  0.225  ohms/km.  

10.  For  the  above  system,  the  positive  sequence  diagram  with  the  p.u  values  on  the  100  MVA  
common  base  is    

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

                                                                                                                                                                                                                                             
(Ans:  a)  

11.  In  the  above  system,  the  three-­‐phase  fault  MVA  at  the  bus  3  is  

             a)  82.55  MVA                          b)  85.11  MVA                  c)  170.91  MVA            d)  181.82  MVA                                                  (Ans:  d)  

12.  In  the  circuit  shown,  the  switch  is  closed  at  t  =  0.  The  value  of  Ɵ  in  degrees  which  will  give  the  
maximum  value  of  DC  offset  of  the  current  at  the  time  of  switching  is  

 
 

a) -­‐30                                                  b)  60                                                    c)  -­‐45                                        d)  90                                                                                      (Ans:  c)  

13.  The  reference  voltage  for  phase  a  is  defined  as  V  (t)  =𝑉!   cosωt.  A  symmetrical  3-­‐Φ  fault  occurs  at  
centre  of  the  line  i.e.at  point  F.  The  wave  form  corresponding  to  phase  a  fault  current  from  bus  X  
reveals  that  decaying  D.C.  offset  current  is  negative  and  in  magnitude  at  its  maximum  initial  value.  

(𝑍!   =  0.006+j0.06  p.u.  and  f=50  hz  ).  The  instant  (t0)  of  the  fault  will  be  

 
           a)  4.682  ms                                  b)  9.667  ms                              c)  14.667  ms                d)  19.667  ms                                                        (Ans:  a)  

14.  A  50  Hz  alternator  is  rated  500  MVA,  20  kV,  with  Xd  =  1.0  per  unit  and    𝑋!!! =  0.2  per  unit.  It  
supplies  a  purely  resistive  load  of  400  MW  at  20  kV.  The  load  is  connected  directly  across  the  
generator  terminals  when  a  symmetrical  fault  occurs  at  the  load  terminals.  The  initial  rms  current  in  
the  generator  in  per  unit  is  

       a)  7.22                                  b)  5.05                                  c)  3.22                                  d)  2.25                                                                                                      (Ans:  b)  

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

15.  A  50  MVA,  10  kV,  50  Hz,  star-­‐connected,  unloaded  three-­‐phase  alternator  has  a  synchronous  
reactance  of  1  p.u.  and  a  sub-­‐transient  reactance  of  0.2  p.u.  If  a  3-­‐phase  short  circuit  occurs  close  to  
the  generator  terminals,  the  ratio  of  initial  and  final  values  of  the  sinusoidal  component  of  the  short  
circuit  current  is  ________                                                                                                                                                                                                                          (Ans:  5.0)  

16.  The  magnitude  of  3-­‐phase  fault  currents  at  buses  A  and  B  of  a  power  system  are  10  pu  and  8  pu,  
respectively.  Neglect  all  resistances  in  the  system  and  consider  the  pre-­‐fault  system  to  be  unloaded.  
The  pre-­‐fault  voltage  at  all  buses  in  the  system  is  1.0  pu.  The  voltage  magnitude  at  bus  B  during  a  
three-­‐phase  fault  at  bus  A  is  0.8  pu.  The  voltage  magnitude  at  bus  A  during  a  three-­‐phase  fault  at  bus  
B,  in  pu,  is  ____________?                                                                                                                                                                                                                            (Ans:  0.84)  

17.  A  500  MVA,  20  kV,  60  Hz  synchronous  generator  having  𝑋!" =0.2pu  is  supplying  a  passive  load  of  
400MW  at  20  Kv.  The  load  is  purely  resistive.  Then  the  value  of  post  fault  current  at  the  generator  
terminals  is                                            (Ans  :    5.06∠-­‐80.9  pu    )  

18.  A  2-­‐bus  system  and  corresponding  zero  sequence  network  are  shown  in  the  figure.  

 
 

 The  transformer  T1  and  T2  are  connected  

                                     (Ans:  b)  

19.  For  the  network  as  shown  in  the  fig.  the  zero  sequence  reactance  in  p.u  are  indicated.  The  Zero  
sequence  driving  point  reactance  of  the  node  3  is    

 
     

a) 0.12  pu                    b)  0.30  pu                                c)  0.10  pu                                    d)  0.  20  pu                                                                                (Ans:  c)  

20.  In  an  unbalanced  three-­‐phase  system,  phase  current  Ia  =  1∠(-­‐900)  pu,  negative  sequence  current  
Ib2  =  4∠  (-­‐1500)  pu,  zero  sequence  current  Ic0  =  3∠900.  The  magnitude  of  phase  current  Ib  in  pu  is                

                       a)  1.00                          b)7.81                                          c)  11.53                                            d)  13.00                                                                                          (Ans:  c)  

21)  Three  identical  star  connected  resistors  of  1.0  p.u  are  connected  to  an  unbalanced  3  phase  
supply.  The  load  neutral  is  isolated.  The  symmetrical  components  of  the  line  voltages  in  p.u  are:  

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

                                                                           Vab1  =  X∠Ɵ1,  Vab2  =  Y∠Ɵ2  

If  all  the  p.u  calculations  are  with  the  respective  base  values,  the  phase  to  neutral  sequence  voltages  
are    

a) Van1  =  X∠(Ɵ1    +  300),    Van2  =  Y∠(Ɵ2  –  300)    

b) Van1  =  X∠(Ɵ1    -­‐  300),    Van2  =  Y∠(Ɵ2  +  300)    


! !
c) Van1  =    𝑋∠(Ɵ1    -­‐  300),  Van2  =    𝑌∠(Ɵ2  +  300)  
! !

! !
d) Van1  =    𝑋∠(Ɵ1    -­‐  600),  Van2  =    𝑌∠(Ɵ2  -­‐  600)                                                                                                                                    (Ans:  b)  
! !

22)  A  three-­‐phase  alternator  generating  unbalanced  voltages  is  connected  to  an  unbalanced  load  
through  a  3-­‐phase  transmission  line  as  shown  in  fig.  The  neutral  of  the  alternator  and  the  star  point  
of  the  load  are  solidly  grounded.  The  phase  voltages  of  the  alternator  are  Ea=10∠00V,  Eb  =  10∠-­‐900V,  
Ec  =  10∠1200  V.  The  +ve  sequence  component  of  the  load  current  is  

                                                                                       
a) 1.310∠-­‐1070  A          b)  0.332∠-­‐1200  A                c)  0.996∠-­‐1200  A                d)  3.510∠-­‐810  A                        (Ans:  d)  

23)  The  parameters  of  transposed  overhead  transmission  lie  are  given  as:  

           Self-­‐reactance  Xs  =  0.4  Ω/km  and  Mutual  reactance  Xm  =  0.1  Ω/km    The  positive  sequence                  
reactance  x1  and  zero  sequence  reactance  x0,  respectively,  in  Ω/km  are  

a) 0.3,  0.2                                  b)  0.5,  0.2                                          c)  0.5,  0.6                                          d)  0.3,  0.6                                                (Ans:  d)  

24)  The  series  impedance  matrix  of  a  short  three-­‐phase  transmission  line  in  phase  coordinate  is          

.  If  the  positive  sequence  impedance  is  (1+j10)  Ω,  and  the  zero  sequence  is  
(4+j31)  Ω,  then  the  imaginary  part  of  Zm  (in  Ω)  is  _____  (up  to  2  decimal  places).                                  (Ans:  7)  

25)  Suppose  we  define  a  sequence  transformation  between  “a-­‐b-­‐c”  and  “p-­‐n-­‐o”  variables  as  follows:  

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

                                     

Where    and  k  is  a  constant  now,  if  it  is  given  that:  

                                   

And                          then,  

a)                                          b)            

C)                            d)              (Ans:  b)  

26)  A  3-­‐phase  transmission  line  is  shown  in  figure:  

 
Voltage  drop  across  the  transmission  line  is  given  by  the  following  equation:  

                                                 
Shunt  capacitance  of  the  line  can  be  neglect.  If  the  line  has  positive  sequence  impedance  of  15Ω  and  
zero  sequence  impedance  of  48Ω,  then  the  values  of  Zs  and  Zm  will  be  

             a)  Zs  =  31.5  Ω;  Zm  =  16.5Ω                                        b)  Zs  =  26  Ω;  Zm  =  11Ω  

c)  Zs  =  16.5  Ω;  Zm  =  31.5Ω                                        d)  Zs  =  11  Ω;  Zm  =  26Ω                                                                                            (Ans:  b)  

27)  The  positive,  negative  and  zero  sequence  reactance’s  of  a  wye-­‐connected  synchronous  
generator  are  0.2  p.u,  0.2  p.u  and  0.1  p.u  respectively.  The  generator  is  on  open  circuit  with  a  

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

terminal  voltage  of  1  p.u.  The  minimum  value  of  the  inductive  reactance,  in  Pu,  required  to  be  
connected  between  neutral  and  ground  so  that  the  fault  current  does  not  exceed  3.75  Pu  if  a  single  
line  to  ground  fault  occurs  at  the  terminals  is  _______.  (Assume  fault  impedance  to  be  zero).  (Give  
the  answer  up  to  be  one  decimal  place).                                                                                                                                                                                    (Ans:  0.1)  

28)  Two  identical  unloaded  generators  are  connected  in  parallel  as  shown  in  the  figure.  

                                               
Both  the  generators  are  having  positive,  negative  and  zero  sequence  impedance  of  j0.4  p.u,  j0.3  p.u  
and  j0.15  p.u.,  respectively.  If  the  pre-­‐fault  voltage  is  1  p.u.,  for  a  line-­‐to-­‐ground  (L-­‐G)  fault  at  the  
terminals  of  the  generators,  the  fault  current,  in  p.u,.  is  ______?                                                                                                        (Ans:  6)  

29)  The  positive,  negative  and  zero  sequence  impedances  of  a  3-­‐phase  generator  are  Z1,  Z2  and  Z0  
respectively.  For  a  line-­‐to-­‐line  fault  with  fault  impedance  Zf,  the  fault  current  is  If1  =  kIf,  where  If  is  the  
fault  current  with  zero  fault  impedance.  The  relation  between  Zf  and  k  is    

a)                                                    b)                          

c)                                                                                d)                                                                                    (Ans:  a)  

30)  A  30  MVA,  3-­‐phase,  50  Hz,  13.8  kV,  star-­‐connected  synchronous  generator  has  positive,  negative  
and  zero  sequence  reactance’s,  15%,  15%  and  5%  respectively.  A  reactance  (Xn)  is  connected  
between  the  neutral  of  the  generator  and  ground.  A  double  line  to  ground  fault  takes  place  involving  
phases  ‘b’  and  ‘c’,  with  a  fault  impedance  of  j0.1  p.u.  The  value  of  Xn  (in  p.u)  that  will  limit  the  
positive  sequence  generator  current  to  4270  A  is  ______                                                                                                                      (Ans:  1.07)    

31)  A  30  kV,  50  Hz,  50  MVA  generator  has  the  positive,  negative  and  zero  sequence  reactance’s  of  
0.25  pu,  0.15  pu,  0.05  pu,  respectively.  The  neutral  of  the  generator  is  grounded  with  a  reactance  so  
that  the  fault  current  for  a  bolted  LG  fault  and  that  of  a  bolted  three-­‐phase  fault  at  the  generator  
terminal  are  equal.  The  value  of  grounding  reactance  in  ohms  (round  off  to  one  decimal  place)  is  ___
                      (Ans:  1.8)  

32)  The  sequence  components  of  the  fault  current  are  as  follows:  I  positive  =  j1.5  pu,  Inegative=  -­‐j0.5  pu,  
Izero=  -­‐j1  pu.  The  type  of  fault  in  the  system  is    

         a)  LG                                                                    b)  LL                                          c)  LLG     d)  LLLG                                                                      (Ans:  c)  

33)  A  100  MVA,  11kV,  50Hz  turbo  generator  is  having  a  symmetrical  fault  at  its  terminals.  The  short-­‐
circuit  capacity  is  500  MVA.  The  neutral  of  the  alternator  is  grounded  through  a  reactance  of  0.05  
pu.  The  zero-­‐sequence  reactance  of  the  generator  is  25%  of  its  positive-­‐sequence.  The  short-­‐circuit  
capacity  for  a  line  to  ground  fault  is  _______  MVA.                                                                                                                                                (Ans:  500)                        

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  
For  Doubts/Clarifications  Email  us  at  gate.knrao@gmail.com  
For  Regualr  Updates  Telegram  Channel:  GATE  Lectures  by  KN  Rao  https://t.me/knrao123  

Problem Sets will keep on updated… For most


recent Problem Set Visit www.knrao.in

YouTube  Channel  Playlist  for  Machines:  www.bit.ly/knraomcs  


YouTube  Channel  Playlist  for  Power  Systems:  www.bit.ly/knraops  

Potrebbero piacerti anche