MECHANICAL AND PLUMBING ABBREVIATIONS HVAC SYMBOLS HVAC PIPING SYMBOLS

SUPPLY DIFFUSER OR SUPPLY GRILLE CD CONDENSATE & EQUIPMENT DRAIN


INSULATED METAL PANEL
(NO AIRFLOW IN SHADED REGION)
ABBREV. DESCRIPTION ABBREV. DESCRIPTION ABBREV. DESCRIPTION RL REFRIGERANT LIQUID
RETURN DIFFUSER BOOT TAP OR 45 DEGREE ENTRY FITTING
A/E ARCHITECT AND ENGINEER RS REFRIGERANT SUCTION
FHC FIRE HOSE CABINET OC ON CENTER R or D
AC OR ACU AIR CONDITIONING UNIT OR AIR COMPRESSOR FIN FINISH OD OUTSIDE DIAMETER EXHAUST DIFFUSER R (RISE), D (DROP) ARROW IN DIRECTION OF AIR FLOW DIRECTION OF PIPE SLOPE (DOWN)
ACCU AIR COOLED CONDENSING UNIT FLA FULL LOAD AMPS OFCI OWNER FURNISHED/CONTRACTOR INSTALLED
ACD AIR CONDITIONING CONDENSATE DRAIN FLR FLOOR OFOI OWNER FURNISHED/OWNER INSTALLED MANUAL VOLUME DAMPER AD ACCESS DOOR
AD ACCESS DOOR FODT FUEL OIL DAY TANK OM OXYGEN MANIFOLD
ADJ ADJUSTABLE OR ADJACENT FOP FUEL OIL PUMP OPER OPERATOR FD FIRE DAMPER WITH ACCESS DOOR 90 DEGREE ELBOW WITH TURNING VANES
AFCV AIRFLOW CONTROL VALVE FOR FUEL OIL RETURN OPNG OPENING
AFF ABOVE FINISHED FLOOR FOS FUEL OIL SUPPLY OSD OPEN SITE DRAIN SD
SMOKE DAMPER WITH ACCESS DOOR
AFMS AIR FLOW MEASURING STATION FOST FUEL OIL STORAGE TANK STANDARD RADIUS ELBOW WITH CENTER RADIUS LINE SYMBOLS
AHU AIR HANDLING UNIT FOV FUEL OIL VENT P PUMP, PNEUMATIC OR PRESSURE F/SD EQUAL TO 1-1/2 TIMES WIDTH OF DUCT
FIRE/SMOKE DAMPER WITH ACCESS DOOR LIGHT/SCREENED SOLID OR DASHED LINES INDICATE EXISTING TO REMAIN
APD AIR PRESSURE DROP FP FIRE PROTECTION PC PLUMBING CONTRACTOR
APPROX APPROXIMATE FPB FAN POWERED BOX PD PRESSURE DROP OR PERFORATED DIFFUSER MD HEAVY DASHED LINES INDICATE EXISTING TO BE REMOVED
AUTOMATIC MOTOR OPERATED DAMPER INTERNALLY INSULATED DUCTWORK
AR AIR RECEIVER FPC FIRE PROTECTION CONTRACTOR PE PNEUMATIC ELECTRIC HEAVY CONTINUOUS LINES INDICATE NEW WORK
ARCH ARCHITECT FPM FEET PER MINUTE PF PREFILTERS BDD
AS AIR SEPARATOR BACK DRAFT DAMPER 20"X12" Ø FLAT OVAL SPIRAL DUCT (WIDTH X HEIGHT) LIGHT DOT LINES INDICATE FUTURE WORK
FPS FEET PER SECOND PG PROPYLENE GLYCOL
ATM ATMOSPHERE FPST FIRE PROTECTION STORAGE TANK PHC PREHEAT COIL
AV ACID VENT AD AFMS AIR FLOW MEASURING STATION 18" Ø ROUND SPIRAL DUCT
FS FLOW SWITCH PIV POST INDICATOR VALVE
AVMS AIR VOLUME MEASURING STATION FT FEET OR FLASH TANK PLT PLASTER TRAP
AW ACID WASTE FTG FOOTING OR FITTING POC POINT OF CONNECTION 20"X12" RECTANGULAR DUCT (WIDTH X HEIGHT)
FTR FIN TUBE RADIATION PPH POUNDS PER HOUR DUCT TURNED UP (SOLID LINES)
B BOILER
PPM PARTS PER MILLION
BCU BLOWER COIL UNIT FLOOR PLAN SYMBOLS
G GAS, NATURAL PRD PRESSURE RELIEF DOOR SPIN-IN FITTING WITH MANUAL VOLUME DAMPER AND
BDD BACKDRAFT DAMPER
GA GAUGE PREFAB PREFABRICATED FLEXIBLE DUCT CONNECTION
BHP BRAKE HORSEPOWER DUCT TURNED DOWN (DASHED LINES) TYP
GAL GALLON PRES PRESSURE SECTION WITH TOP NUMBER INDICATING
BI BACKWARD INCLINED 1
GALV GALVANIZED PRV PRESSURE REDUCING VALVE SECTION DESIGNATION AND BOTTOM NUMBER
BLDG BUILDING A101 INDICATING DRAWING THAT SECTION IS CUT ON
GC GENERAL CONTRACTOR PSI POUNDS PER SQUARE INCH
BOT BOTTOM PLAN VIEW OR DRAWING THAT SECTION IS DRAWN ON
GH GRAVITY HOOD PSIG POUNDS PER SQUARE INCH GAUGE
BP BRINE PUMP CONICAL FITTING
GPH GALLONS PER HOUR PVC POLYVINYL CHLORIDE RETURN BRANCH DUCT TO
BST BULK SALT STORAGE SECTION
GPM GALLONS PER MINUTE RETURN GRILLE/DIFFUSER
BTU BRITISH THERMAL UNIT TYP
GV GAS NATURAL VENT RA RETURN AIR OR RELIEF AIR 1 DETAIL WITH TOP LETTER INDICATING DETAIL DESIGNATION
BTUH BTU PER HOUR WITH FLEX 20"X12"
RAD RADIATED DUCT A101 AND BOTTOM NUMBER INDICATING DRAWING THAT DETAIL
H HUMIDIFIER, HUMIDITY OR HEIGHT RAT RETURN AIR TEMPERATURE SQUARE TO ROUND TRANSITION IS REFERENCED ON OR DRAWING THAT DETAIL IS DRAWN ON

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A
CA COMPRESSED AIR HC HEATING COIL R/H REHEAT PLAN VIEW
CAP CAPACITY HCP HEATING COIL PUMP (HOT WATER) RD ROOF DRAIN
SUPPLY BRANCH DUCT TO A. GENERAL NOTE

Phone: (217) 793-2299


CAV CONSTANT AIR VOLUME HD HEAD REC RECEIVER SECTION

Fax: (217) 793-3311


CC COOLING COIL HE HEAT EXCHANGER RECIR RECIRCULATING SUPPLY GRILLE/DIFFUSER TB-X TYPICAL TERMINAL BOX WITH REHEAT COIL, TWO 1. PLAN NOTE LIST

www.trcww.com
CCP COOLING COIL PUMP HGT HEIGHT REF REFRIGERATOR WITH FLEX WAY CONTROL VALVE, BOX DESIGNATION
CDS CONDENSATE PUMP DISCHARGE HO HUB OUTLET RF RETURN AIR FAN DUCT 1 PLAN NOTE
CENTRIF CENTRIFUGAL HOA HAND-OFF-AUTOMATIC RG RETURN GRILLE PLAN VIEW
CFM CUBIC FEET PER MINUTE HORZ HORIZONTAL RH RELIEF HOOD OR RELATIVE HUMIDITY TB-X TYPICAL TERMINAL BOX WITH REHEAT COIL, THREE T THERMOSTAT - "N" INDICATING NIGHT SETBACK THERMOSTAT
N
CFOI CONTRACTOR FURNISHED/OWNER INSTALLED HOSP HOSPITAL RHC REHEAT COIL SECTION EXHAUST BRANCH DUCT TO WAY CONTROL VALVE, BOX DESIGNATION
CH CHILLER HP HORSEPOWER OR HEATPUMP RLA RUNNING LOAD AMPS EXHAUST GRILLE/DIFFUSER H HUMIDISTAT
CI CAST IRON HPR HIGH PRESSURE CONDENSATE RETURN RM ROOM WITH FLEX
CO CLEAN OUT HPS HIGH PRESSURE STEAM ROM REVERSE OSMOSIS VENT DUCT CONNECTION OF NEW WORK TO EXISTING
TYPICAL CHILLED BEAM (24"X48")
CO2 CARBON DIOXIDE HR HOUR ROP REVERSE OSMOSIS PUMP
SIDEWALL SUPPLY, RETURN OR EXHAUST GRILLE
COL COLUMN HRC HEAT RECOVERY COIL ROST REVERSE OSMOSIS STORAGE TANK
COM CARBON DIOXIDE MANIFOLD HTR HEATER RP RADIANT PANELS
COMP COMPRESSOR HVAC HEATING, VENTILATION AND AIR CONDITIONING RPG RETURN PERFORATED GRILLE SUPPLY, RETURN, OR EXHAUST SLOT DIFFUSER
90 DEGREE TEE (ROUND OR FLAT OVAL ONLY)
CONC CONCRETE HW DOMESTIC HOT WATER RPM REVOLUTIONS PER MINUTE
CONN CONNECTION HWC DOMESTIC HOT WATER RECIRC RPZ REDUCED PRESSURE BACKFLOW STAINLESS WELDED DUCTWORK PER SPECIFICATION
CONST CONSTRUCTION HWCP HOT WATER CIRCULATING PUMP REQ'D REQUIRED DRAWING INDEX
CONT CONTINUOUS HWP HEATING HOT WATER PUMP RV ROOF VENTILATOR
CP CONDENSATE PUMP HWR HEATING HOT WATER RETURN DRAWING NO. DRAWING DESCRIPTION
CPD CONDENSATE PUMP DISCHARGE HWS HEATING HOT WATER SUPPLY S SANITARY OR SEWER
CUH CABINET UNIT HEATER HX HEAT EXCHANGER SA SUPPLY AIR OR SOUND ATTENUATOR H100 HVAC SYMBOLS & ABBREVIATIONS
CW COLD WATER HZ HERTZ SB STEAM BOILER H210 LEVEL ONE HVAC PLAN
CWM COLD WATER MAKE-UP SC STEAM COIL CONTROL SYMBOLS
CWP CHILLED WATER PUMP IA INSTRUMENT AIR SCC STEAM CONDENSATE COOLER H210A LEVEL ONE & ROOF HVAC PLAN - CONFERENCE
HUMIDITY TRANSMITTER VARIABLE SPEED MOTOR
CWR CHILLED WATER RETURN IAC INSTRUMENT AIR COMPRESSOR SCCH SUBCOOLED CHILLER TTT AIR FLOW MEASURING STATION HH VSC
(PNEUMATIC) CONTROLLER H220 LEVEL TWO HVAC PLAN
CWS CHILLED WATER SUPPLY IAD INSTRUMENT AIR DRYER, EQAD SCFM STANDARD CUBIC FEET PER MINUTE
ID INSIDE DIAMETER OR DIMENSION SCH SCHEDULE LOW LIMIT SAFETY VELOCITY PRESSURE SENSOR H230 LEVEL THREE HVAC PLAN
AFS AIR FLOW SWITCH TLL VP
D DIFFUSER OR DAMPER IFB INTEGRAL FACE AND BYPASS SCW SOFT COLD WATER (DOMESTIC) THERMOSTAT (ELECTRONIC)
H240 ROOF LEVEL HVAC PLAN
DB DECIBELS OR DRY BULB IHOM IN-HOUSE OXYGEN MANIFOLD SD SUPPLY DIFFUSER OR SMOKE DAMPER VIBRATION SWITCH
DC DUCT COIL IN INCHES SEC SECTION AL ALARM VS H500 ENLARGED UNIT HVAC PLAN
MAGNETIC INDUCTIVE FLOW
DCV DOUBLE CHECK VALVE INCL INCLUDE SENS SENSIBLE MS METER SENSOR
DCWBP DOMESTIC COLD WATER BOOSTER PUMP INSUL INSULATED SEP SEWAGE EJECTOR PUMP H601 HVAC SCHEDULES
BDD BACK DRAFT DAMPER 120/60/1 VD VOLUME DAMPER (MANUAL)
DD DUAL DUCT INT INTERIOR SF SUPPLY AIR FAN BY EC H602 HVAC SCHEDULES
DDC DIRECT DIGITAL CONTROL INV INVERT SG SUPPLY GRILLE VORTEX SHEDDING AIR
DE DEAERATOR I.P.S. INTERNATIONAL PIPE SIZING SHT SHEET S MANUAL SWITCH (ELECTRIC) VXT H701 AIR FLOW DIAGRAM
CO SENSOR FLOW TRANSMITTER
DEFL DEFLECTION ISOL ISOLATION SHW SOFT HOT WATER CO2 2
H801 HVAC DETAILS
DEG DEGREE SK SINK 120/60/1 MDM MODEM
DEPT DEPARTMENT JT JOINT SMBH SENSIBLE MBH BY EC VORTEX SHEDDING H802 HVAC DETAILS
VSM FLOW METER
DHWBP DOMESTIC HOT WATER BOOSTER PUMP SMC SHEET METAL CONTRACTOR
CS CURRENT SENSOR MCC MOTOR CONTROL CENTER 120/60/1 H803 HVAC DETAILS
DI DEIONIZED WATER KAIC SHORT CIRCUIT RATING SP STATIC PRESSURE OR STORM PUMP
BY EC
DIA DIAMETER KEC KITCHEN EQUIPMENT CONTRACTOR SPEC SPECIFICATIONS H900 HVAC CONTROLS
DISC DISCONNECT KW KILOWATTS SQ SQUARE DD DUCT DETECTOR STR MOTOR STARTER 20 20 PSIG MAIN AIR
DISCH DISCHARGE SQFT SQUARE FEET
DS DOWNSPOUT L LENGTH SRV SAFETY RELIEF VALVE CURRENT TO OPERATOR'S WORK
I/S OWS PRESSURE GAUGE
DSWBP DOMESTIC SOFT WATER BOOSTER PUMP LAC LAB AIR COMPRESSOR ST STEAM TRAP PNEUMATIC TRANSDUCER STATION
DUC DOOR UNDER CUT LAD LAB AIR DRYER STD STANDARD
DWG DRAWING LAN LOCAL AREA NETWORK STM STORM ES DAMPER END SWITCH (BINARY) OAD OUTDOOR AIR DAMPER HC HOLDING COIL
DW DISTILLED WATER LAT LEAVING AIR TEMPERATURE STR STARTER
DWBP DOMESTIC WATER BOOSTER PUMP LAV LAVATORY STRUCT STRUCTURAL DIFFERENTIAL PRESSURE OUTDOOR AIR VOLUME PROBE,
ΔAP VPS H HUMIDISTAT (SPACE)
DWH DOMESTIC WATER HEATER LBD LINEAR BAR DIFFUSER SV STEAM VENT SENSOR (ANALOG) TRANSDUCER AND MONITOR
LBS POUNDS SW SWITCH
DIFFERENTIAL PRESSURE SWITCH
EA EXHAUST AIR LD LINEAR DIFFUSER SYS SYSTEM ΔP PR PNEUMATIC RELAY S SWITCH (PNEUMATIC)
SENSOR (BINARY)
EAT ENTERING AIR TEMPERATURE LF LINEAR FOOT SZ SPRINKLER ZONE
EBH ELECTRIC BASEBOARD HEATER LFD LAMINAR FLOW DIFFUSER DIFFERENTIAL PRESSURE SWITCH
ΔP (HL) PE PRESSURE-ELECTRIC SWITCH T THERMOSTAT (SPACE)
EC ELECTRICAL CONTRACTOR LFT LEAVING FLUID TEMPERATURE T THERMOSTAT (HIGH LIMIT) (BINARY)
ECC ENVIRONMENTAL CONTROL CONTRACTOR LOC LOCATION TB TERMINAL BOX
PRESSURE CONTROLLER THERMOSTAT (SPACE)
ECG EGG CRATE GRILLE LPR LOW PRESSURE CONDENSATE RETURN TCC TEMPERATURE CONTROL CONTRACTOR ΔP (LL) PC TN
(LOW LIMIT) (BINARY) (PNEUMATIC) NIGHT CYCLE
ED EXHAUST DIFFUSER LPS LOW PRESSURE STEAM TDH TOTAL DISCHARGE HEAD
EDC ELECTRIC DUCT COIL LVG LEAVING TDV TRIPLE DUTY VALVE PRESSURE SENSOR
EP ELECTRO-PNEUMATIC SWITCH P (ELECTRONIC) 0-30 PSIG AIR GAUGE
EER ENERGY EFFICIENCY RATIO LVP LAB VACUUM PUMP TEMP TEMPERATURE
EF EXHAUST AIR FAN LWT LEAVING WATER TEMPERATURE THW TEMPERED HOT WATER PRESSURE TRANSMITTER
ELECTRO-PNEUMATIC
EFT ENTERING FLUID TEMPERATURE TLL TEMPERATURE LOW LIMIT EPT PT LAN LOCAL AREA NETWORK
TRANSDUCER (PNEUMATIC)
EG EXHAUST GRILLE OR ETHYLENE GLYCOL MA MEDICAL AIR TMV THERMOSTAT MIXING VALVE
ELEC ELECTRIC MAC MEDICAL AIR COMPRESSOR TMBH TOTAL MBH EAD RAD TEMPERATURE CONTROL
EXHAUST AIR DAMPER RETURN AIR DAMPER TCC
ELEV ELEVATION MAD MEDICAL AIR DRYER TSP TOTAL STATIC PRESSURE CONTRACTOR
EMER EMERGENCY MAI MEDICAL AIR INTAKE TYP TYPICAL
EMG EXTRUDED METAL GRILLE MAT MIXED AIR TEMPERATURE FBD FACE & BY-PASS DAMPER SD SMOKE DETECTOR (NOTE: TCC & ECC ARE USED INTERCHANGEABLY)
ENCL ENCLOSURE MAX MAXIMUM UH UNIT HEATER
ENTR ENTERING MB MOP BASIN UNO UNLESS NOTED OTHERWISE ENVIRONMENTAL CONTROL
FDD FAN DISCHARGE DAMPER S/S START/STOP SWITCH ECC
EOM END OF MAIN DRIP MBH BTU/HR X 1000 UR URINAL CONTRACTOR
EQA EQUIPMENT AIR MC MECHANICAL CONTRACTOR UVL ULTRA VIOLET LIGHT
EQAC EQUIPMENT AIR COMPRESSOR MCA MINIMUM CIRCUIT AMPACITY FID FAN INLET DAMPER EC ELECTRICAL CONTRACTOR
STEAM FLOW MEASUREMENT ORIFICE
EQAI EQUIPMENT AIR INTAKE MCC MOTOR CONTROL CENTER V VENT OM PLATE & MASS FLOW COMPUTER
EQUIP EQUIPMENT MD MOTORIZED DAMPER VAC VACUUM VXD 120/60/1 P PNEUMATIC
FAN INLET VORTEX DAMPER OR
EQV EQUIPMENT VACUUM MECH MECHANICAL VAV VARIABLE AIR VOLUME BY EC
EQVP EQUIPMENT VACUUM PUMP MFR MANUFACTURER VB VACUUM BREAKER E
EQV V EQUIPMENT VACUUM VENT MH MANHOLE VD VOLUME DAMPER (MANUAL) FC FLOW CONTROLLER TC OVERRIDE TIMER OR ELECTRICAL WIRING
ERP ELECTRIC RADIANT PANEL MIN MINIMUM VEL VELOCITY
ERV ENERGY RECOVERY VENTILATOR MISC MISCELLANEOUS VSC VARIABLE SPEED CONTROLLER TEMPERATURE CONTROLLER ANALOG INPUT
FS FLOW SENSOR TC AI-X
ES EMERGENCY SHOWER MOCP MAXIMUM OVERCURRENT PROTECTION VTR VENT THROUGH ROOF (PNEUMATIC) (DDC CONTROLLER)
ESP EXTERNAL STATIC PRESSURE OR ELEVATOR SUMP PUMP MPSR MEDIUM PRESSURE CONDENSATE RETURN VV VACUUM VENT TEMPERATURE SENSOR ANALOG OUTPUT
ET EXPANSION TANK MPS MEDIUM PRESSURE STEAM HOA HAND-OFF-AUTO SWITCH T AO-X
(ELECTRONIC) (DDC CONTROLLER)
EUH ELECTRIC UNIT HEATER MTD MOUNTED W WASTE, WATTS OR WIDTH
EW EMERGENCY EYEWASH MV MEDICAL VACUUM WAGD WASTE ANESTHESIA GAS DISPOSAL PUMP HUMIDITY CONTROLLER TEMPERATURE TRANSMITTER BINARY INPUT
HTC TT BI-X
EWC ELECTRIC WATER COOLER MVP MEDICAL VACUUM PUMP WB WET BULB (PNEUMATIC) (PNEUMATIC) (DDC CONTROLLER)
EWT ENTERING WATER TEMPERATURE W/ WITH HUMIDITY HIGH LIMIT BINARY OUTPUT
EXH EXHAUST N NORTH OR NITROGEN W/O WITHOUT HTE M TERMINAL BOX ACTUATOR BO-X
(ELECTRIC) (DDC CONTROLLER)
EXIST EXISTING NA NOT APPLICABLE WC WATER CLOSET OR WATER COLUMN
EXT EXTERIOR NC NORMALLY CLOSED OR NOISE CRITERIA WCO WALL CLEAN OUT HUMIDITY SENSOR
H TM TURBINE METER
F DEGREES FAHRENHEIT NIC NOT IN CONTRACT WFMD WATER FLOW MEASURING DEVICE (ELECTRONIC)
F&B FACE & BYPASS NM NITROGEN MANIFOLD WG WATER GAUGE
F&T FLOAT AND THERMOSTATIC TRAP NO NORMALLY OPEN, NITROUS OXIDE, OR NUMBER WGT WEIGHT
F/A FIRE ALARM NOM NOMINAL OR NITROUS OXIDE MANIFOLD WH WALL HYDRANT
F/SD FIRE AND SMOKE DAMPER NTS NOT TO SCALE WM WATER METER NOTE: ALL SYMBOLS AND ABBREVIATIONS MAY NOT BE USED ON THIS PROJECT
FC FLEXIBLE CONNECTION WP WEATHERPROOF
FCU FAN COIL UNIT O OXYGEN WPD WATER PRESSURE DROP
FD FLOOR DRAIN OR FIRE DAMPER OA OUTSIDE AIR WS WATER SOFTENER
FH FIRE HOSE OR FUME HOOD OAT OUTSIDE AIR TEMPERATURE
# POUND

T E OF T E X
TA A

S
ROBERT A. BOELLNER

PR

R
R

EE
E

D
OF
E S GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
1 1.8 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19.2 20

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A
K

Phone: (217) 793-2299


Fax: (217) 793-3311
www.trcww.com
MATCH LINE
SEE SHEET
H110A

A
MATCH LINE
SEE SHEET
H110A

OF T E
TE XA
TA

S
1 LEVEL ONE HVAC PLAN
H210 1/8" = 1'-0"

PR

R
R

EE
E

D
OF
E S GI S T E R E

IN
SI O G
NAL EN

SIGNED: 01-28-2016
EXPIRES: 06-30-2016
0.7 0.6 0.5 0.4 0.3 0.2 1 0.1 1.8 2 3

MATCH LINE
SEE SHEET
H210
14x14 EA UP
TO KEF-1
0.7 0.6 0.5 0.4 0.3 0.2 1 0.1 1700 CFM
K

SPRINGFIELD, ILLINOIS, 62711


MATCH LINE

3200 PLEASANT RUN, SUITE A


SEE SHEET

Phone: (217) 793-2299


Fax: (217) 793-3311
H210

www.trcww.com
K J
RD-1 RD-1 SD-1 RD-1 SD-1
KEF-1
300 335 360 345 360
24x10 SA DN
CONFERENCE C FROM K-MAU-1

8Ø SA
J

10Ø SA
LOBBY 143

10Ø SA
SD-1 145
1600 CFM
14x14 SA
200 1095 CFM 20x16 SA
K-MAU-1 1455 CFM
APPROX WEIGHT: RD-1 SD-1
300 200 20x16 SA
1300 lbs 10Ø SA
RD-1 SD-1 RD-1 2175 CFM
SD-1 375 CFM
8Ø SA 375 345 375 345

10Ø SA
ED-1 FCU-1A-03
460 2175 CFM
SD-1 ED-1 SD-1 RD-1 SD-1
200 65 360 345 360
12"Ø EA 3/4"Ø
20x14 RA 8x8 DISWASHER
DEF-1 8Ø SA 3/4"Ø 28x12 EA UP 18x16 OA DN
12x8 OA 3/4" RH-1 EXHAUST UP TO
12x10 SA 6"Ø EA 12x10 EA TO ERV-1 FROM ERV-1 DEF-1
460 CFM
600 CFM 525 CFM 2140 CFM 2145 CFM
6" RD-1 DROP 14x10 EA
G TO BELOW RD-1
20x12 EA 760 CFM
ERV-1 FCU-1A-05 1380 CFM 245
G.1 12x10 RA

8Ø EA
APPROX WEIGHT: 600 CFM ED-1

10"Ø EA
G 2250 lbs 18x12 SA 16x12 RA RD-1 200
28x12 EA DN 12x10 EA
6x6 OA 12x12 SA 1325 CFM 250
65 CFM 560 CFM
G.1 FD OA INTAKE VESTIBULE
660 CFM
EXHAUST SD 147 18x12 OA
10Ø SA FCU-1A-02
18x16 SA DN AC-1 ED-1 16x10 EA 1355 CFM SD-1
1325 CFM
RS/RL RS/RL (AIR CURTAIN) 12x10 RA SD-1 330 855 CFM 10x8 OA 265
RD-1 10Ø SA 330 CFM RD-1
330

10"Ø OA
250 250
G.9 FCU-1A-04 (TYP.3)
ACCU-ERV-1 600 CFM 14x10 OA
8x6 OA CONFERENCE B 765 CFM
(FOR ERV-1) F 142
130 CFM FEC
12x10 SA 12x8 OA 10x10 OA
G.9 ACCU-1 ACCU-2 600 CFM
6" RD-1 DROP 20x14 RA 500 CFM
TO BELOW 460 CFM
(FOR CONFERENCE (FOR MAIN HOTEL 8Ø SA 3/4"Ø 3/4"Ø CD
F AREAS) COMMON AREAS) 10"Ø OA
6"Ø EA
SD-1 RD-1 SD-1 RD-1
ED-1
335 360 345

FCU-1A-01
200

2175 CFM
65

10Ø SA
SD-1 12"Ø EA 20x14 SA 8x8 EA
LOBBY
146 360 460 CFM 2175 CFM 280 CFM
8Ø SA SD-1 10"Ø OA
SD-1 RD-1 360
250 250 CFM

10Ø SA

10Ø SA
360 345 360
ED-1 SD-1 (TYP.2)
RD-1 SD-1
460 250
300 200

8Ø SA

10Ø SA
14x14 SA 20x16 SA

10Ø SA
1095 CFM 1815 CFM 8x8 EA
280 CFM
SD-1 RD-1 6Ø EA 6Ø EA
200 300 SD-1 RD-1 RD-1
(TYP.4) (TYP.4)
375 345 345
D CONFERENCE A SD-1
141 360 ED-2
70
(TYP.8)
D C

C
MATCH LINE
SEE H210

MATCH LINE
SEE SHEET
H210
2 ROOF HVAC PLAN - CONFERENCE 1 LEVEL ONE HVAC PLAN -CONFERENCE
H210A 1/8" = 1'-0" H210A 1/8" = 1'-0"

T E OF T E X
TA A

S
S
ROBERT A. BOELLNER

PR

R
R

EE
E

D
OF
ES GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
1 1.8 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19.2 20

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A

Phone: (217) 793-2299


MATCH LINE
SEE SHEET

Fax: (217) 793-3311


www.trcww.com
H110A

J J

H H

G G

F F

E E

D D

C C

B B
MATCH LINE
SEE SHEET
H110A

1 LEVEL TWO HVAC PLAN


H220 1/8" = 1'-0"

T E OF T E X
TA A

S
PR

R
EE
E

D
R
OF
ES GIS T E R E I

N
SI O G
NAL EN

SIGNED: 02-16-2016
EXPIRES: 06-30-2016
1 1.8 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19.2 20

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A
VTAC-1 VTAC-1 VTAC-1 VTAC-1

Phone: (217) 793-2299


J

Fax: (217) 793-3311


www.trcww.com
PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1
H KING KING
SUITE SUITE
312 314
G
KING KING KING KING KING KING QUEEN
QUEEN QUEEN ACCESSIBLE KING
WIDE 316 318 320 322 324 QUEEN
302 KING KING KING KING ED-2 ED-2 ED-2 ED-2 330
332 334
304 306 308 310 50 50 8x8 EA UP 8x8 EA UP 50 50
8x8 EA UP 200 CFM 200 CFM
8x8 EA UP 10x10 EA UP
200 CFM 200 CFM 300 CFM
10x10 EA UP STAIR B
STAIR A KING
300 CFM ST-B3
ST-A3 ED-2 ED-2 SUITE
ED-2 ED-2 ED-2 ED-2 ED-2 8x8 EA UP ED-2 ED-2 ED-2 50 50 328 ED-2 ED-2 ED-2
KING
50 50 50 50 50 200 CFM 50 50 50 SUITE 50 50 50
8x6 EA UP
6x6 EA UP 6x6 EA UP 326
150 CFM
100 CFM 100 CFM
F
8x8 OA 10x10 OA RS / RL
8Ø OA CORRIDOR ELEV 14x10 EA 10x8 OA SD-1 CORRIDOR 8Ø OA SD-1
SD-1 SD-1 340 CFM 765 CFM 500 CFM 340 CFM 170 170
170 CFM 300 LOBBY 300 170 CFM
170 170 315 ED-2 FD
E 300
6x6 EA UP 14x10 OA RS / RL 8x6 EA UP
100 CFM 840 CFM 150 CFM KING
ED-2 8"Ø OA
ED-2 ED-2 ED-2 ED-2 6x6 EA UP ED-2 ED-2 SUITE ED-2 ED-2
50 160 CFM ED-2 ED-2 ED-2 KING
50 50 50 50 100 CFM ELEVATOR 50 50 333 50 50
50 50 50 SUITE
8x8 EA UP E-3 10x10 EA UP
ICE 331
200 CFM 317 300 CFM
8x8 EA UP OA 30x14 UP
ED-1 QUEEN QUEEN 10x10 EA UP
200 CFM & 28x14 DN 10x10 EA UP
300 300 CFM 335
300 CFM
ED-2 ED-2 ED-2 EA 32x14 UP 10x10 EA UP ED-2 ED-2
6x6 EA UP DOUBLE
50 50 50 & 30x14 DN ED-2 450 CFM 50 50
100 CFM QUEEN QUEEN QUEEN QUEEN QUEEN
KING KING KING KING ED-1 321 323 50 337
QUEEN QUEEN
305 307 309 311 ACCESSIBLE KING SD-1 160
329
SUITE QUEEN QUEEN QUEEN SUITE
KING 160
KING 313 319 327
SUITE SUITE
D 301 303 KING
PTAC-1 PTAC-1 PTAC-1 PTAC-1 SUITE PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1 PTAC-1
315
HOUSE KEEPING
336 VTAC-1 VTAC-1
C VTAC-1 VTAC-1

B
VTAC-1 VTAC-1

1 LEVEL 3 HVAC PLAN


H230 1/8" = 1'-0"

OF T E
TE XA
TA

S
ROBERT A. BOELLNER

PR

R
EE
E

D
R
OF
E S GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
1 1.8 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19.2 20

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A

Phone: (217) 793-2299


Fax: (217) 793-3311
www.trcww.com
H
SCU-STAIR A SCU-ELEC
G
A
ACCU-ERV-2 A A SCU-STAIR B
ERV-2 (FOR ERV-2)
TEF-1 APPROX WEIGHT:
2450 lbs TEF-1
200 CFM
32x14 EA 300 CFM
LINEN CHUTE
VENT 3700 CFM
30x14 SA
4000 CFM TEF-1
200 CFM
TEF-1
TEF-1 TEF-1 TEF-1
TEF-1 TEF-1 TEF-1 100 CFM
200 CFM 300 CFM 150 CFM
200 CFM 100 CFM 200 CFM
F
RS / RL
DN

E FD
TEF-1 TEF-1 RS / RL TEF-1 TEF-1
TEF-1 TEF-1
TEF-1 SD DN 150 CFM
100 CFM 100 CFM 300 CFM 450 CFM
100 CFM 300 CFM

30x14 SA DN
32x14 EA DN
TEF-1 TEF-1 TEF-1
200 CFM 100 CFM 300 CFM

FIREPLACE
VENT

1 ROOF HVAC PLAN


H240 1/8" = 1'-0"

OF T E
TE XA
TA

S
ROBERT A. BOELLNER

PR

R
EE
E

D
R
OF
E S GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
DESIGN NOTE:
A. CONTRACTOR TO MAKE SURE THRU - THE - WALL
CONSTRUCTION INSTALLATION IS COMPLETE WITH FRAME
ASSEMBLY INCLUDING ACCESS PANEL, MANUAL FRESH AIR
DAMPER, WALL SLEEVE, EXTERIOR LOUVER WITH FRAME.

B. FOR PROPER AIR FLOW, MINIMUM SPACING BETWEEN THE


INSIDE CLOSET WALL & UNIT AIR INTAKE TO BE 4".

ED-1
50

8x8 EA UP
PTAC-1

6"Ø EA

6"Ø EA
ACCESSIBLE
ED-1 QUEEN
50 QUEEN
126

6x6 EA UP

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A

Phone: (217) 793-2299


Fax: (217) 793-3311
www.trcww.com
ACCESSIBLE KING 6x6 EA UP
SUITE
313

6"Ø EA
VTAC-1 VTAC-1 ED-2
50

7 KING SUITE ALTERNATE 6 ACCESSIBLE KING SUITE 5 ACCESSIBLE QUEEN QUEEN


H500 1/4" = 1'-0" H500 1/4" = 1'-0" H500 1/4" = 1'-0"

8x8 EA UP 10x10 EA UP
PTAC-1
6"Ø EA

6"Ø EA

ED-1
ED-1 50 8x8 EA UP
50

6"Ø EA

ED-1
50
ACCESSIBLE KING
334

QUEEN QUEEN
329
ED-1
KING 50
KING SUITE

6"Ø EA
303
309

PTAC-1 PTAC-1 VTAC-1


8x6 EA UP

QUEEN QUEEN
3 KING SUITE
1 KING 2
H500 1/4" = 1'-0"
4 ACCESSIBLE KING GUESTROOM
H500 1/4" = 1'-0" H500 1/4" = 1'-0" H500 1/4" = 1'-0"

T E OF T E X
TA A

S
S
ROBERT A. BOELLNER

PR

R
R

EE
E

D
OF
ES GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
PR
S
OF
R
TA

E
T

SI O

D
E OF T E X

NAL EN
A

G
ES GI S T E R E I

N S
SIGNED: 12-14-2015
ROBERT A. BOELLNER

EXPIRES: 06-30-2016

EE
R

3200 PLEASANT RUN, SUITE A


SPRINGFIELD, ILLINOIS, 62711
Phone: (217) 793-2299
Fax: (217) 793-3311
www.trcww.com
PR
S
OF
R
TA

E
TE

SI O
OF T E

E S GI S T E R E

D
NAL EN
XA

IN S
SIGNED: 02-16-2016
EXPIRES: 06-30-2016

EE
R

3200 PLEASANT RUN, SUITE A


SPRINGFIELD, ILLINOIS, 62711
Phone: (217) 793-2299
Fax: (217) 793-3311
www.trcww.com
OUTSIDE AIR

EXHAUST AIR
30x14 OA
4000 CFM 32x14 OA
TOP OF FLAT ROOF 3690 CFM

8x8 OA 10x10 OA 14x10 OA


340 CFM 500 CFM 840 CFM 10x8 OA 8Ø
14x10 OA
340 CFM 170 CFM
760 CFM

10"Ø EA

8"Ø EA
8"Ø OA

8"Ø OA

10Ø EA

8"Ø OA

8"Ø OA

8"Ø OA
170 CFM

170 CFM

300 CFM

300 CFM

160 CFM

160 CFM

170 CFM

170 CFM
28x14 OA
CORRIDOR ICE HOUSEKEEPING 3160 CFM 30x14 OA
CORRIDOR
300 317 336 2940 CFM
LEVEL - 3 300

10x10 OA 12x10 OA

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A
390 CFM 630 CFM 8x8 OA 8Ø

Phone: (217) 793-2299


Fax: (217) 793-3311
10x10 OA 240 CFM 120 CFM

www.trcww.com
550 CFM

8"Ø OA
120 CFM

120 CFM
6"Ø EA

8"Ø EA
8"Ø OA

8"Ø OA

8"Ø OA

8"Ø OA
120 CFM

120 CFM

100 CFM

300 CFM

150 CFM

150 CFM
10"Ø EA
26x14 OA
2390 CFM

18x 8 EA
22x14 OA 750 CFM
CORRIDOR ICE HOUSEKEEPING 2465 CFM 14x 8 OA CORRIDOR
LEVEL - 2 A 200 217 236 200 A
570 CFM

6 Ø EA
A 8x8 EA 10x10 EA 14x10 EA 18x10 EA 22x10 EA

440 CFM
12x8 EA
990 CFM 1355 CFM
12x10 OA 18x12 OA 12x 8 OA
FCU-STAIR A 22x12 OA
220 CFM
FCU-ELEC 1895 CFM FCU-STAIR B
6x 6 OA

6"Ø EA
40 CFM

60 CFM

60 CFM
6"Ø OA

310 CFM
10"Ø EA
8"Ø OA
125 CFM

210 CFM

40 CFM

60 CFM

90 CFM

175 CFM

310 CFM
8"Ø EA

6"Ø EA
115 CFM

175 CFM

60 CFM
8"Ø EA

8"Ø OA

8"Ø OA
115 CFM

140 CFM

125 CFM

175 CFM

210 CFM

100 CFM
8"Ø EA

6"Ø EA

6"Ø EA
50 CFM

90 CFM

55 CFM
6x6 OA
6"Ø OA

6x6 OA

6x6 OA
6x6 OA

100 CFM
8"Ø EA

310 CFM
10"Ø EA
10x8 OA

125 CFM
8"Ø OA
75 CFM
6"Ø EA
8"Ø OA
175 CFM
8"Ø EA

6"Ø OA
110 CFM

185 CFM

185 CFM

100 CFM
50 CFM
6"Ø EA
6x6 OA
8"Ø OA
6x6 OA
6x6 OA

8x8 EA

8x6 EA
110 CFM

8x6 OA
75 CFM

300 CFM
6"Ø EA

10"Ø EA
6x6

70 CFM
6"Ø EA

55 CFM

55 CFM

70 CFM
6"Ø EA
6"Ø OA

6"Ø OA
DEN/
ELECTRICAL M W ELEVATOR M LIVING GUEST
BUSINESS W
STAIR-A MEETING ROOM CORRIDOR LANUDRY ROOM TOILET BREAK ROOM TOILET PANTRY OFFICE WORK ROOM RETAIL SERVERY CORRIDOR B BREAKFAST STORANGE C LOBBY ICE FITNESS ROOM LANUDRY CORRIDOR B STAIR-B
CENTER TOILET TOILET
LEVEL - 1 ST-A1 103 102 104 110B 105 109C 107 112 109B 109A 113A 114 138 101B 117B 116 115 120 141 142 140 101A 122 138

1 OA & EA AIR FLOW SCHEMATIC - MAIN HOTEL AREA


H701 NTS

OUTSIDE AIR
ERV-1 EXHAUST AIR
OA - 2145 CFM
EA - 2140 CFM
CONFERENCE
LEVEL ROOF
28x12 EA
14x10 EA 2140 CFM
8x6 OA 760 CFM 18x16 OA
130 CFM 2145 CFM
14x10 OA
765 CFM

65 CFM

65 CFM

65 CFM

65 CFM
6x6 OA

6x6 OA
6x6 EA

6x6 EA

200 CFM

265 CFM

460 CFM
460 CFM

460 CFM

460 CFM
330 CFM

330 CFM
10"Ø OA
250 CFM

280 CFM

280 CFM

250 CFM

12"Ø OA

12x8 OA
10"Ø EA
12x8 EA

12x8 EA
10x8 OA
10"Ø OA

10"Ø OA

8"Ø EA
8x8 EA

8x8 EA
LOBBY LOBBY TOILET TOILET CORRIDOR CONFERENCE A CONFERENCE B CONFERENCE C
146 145 141 142 143
LEVEL - 1

2 OA & EA AIR FLOW SCHEMATIC - CONFERENCE AREA


H701 NTS

T E OF T E X
TA A

S
ROBERT A. BOELLNER

PR

R
EE
E

D
R
OF
E S GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
PLENUM TO BE EXTERNALLY
ROUND BRANCH INSULATED
DUCT TO MAIN DRAIN LINE SHALL BE AT LEAST
(SEE SCHEDULE SHEETMETAL PLENUM SHALL BE SUPPORTED
THE SAME SIZE AS THE NIPPLE
FOR SIZE) INDEPENDENTLY FROM STRUCTURE (NOT
ON THE DRAIN PAN
SUPPORTED BY CEILING) INSIDE OF PLENUM
SHALL BE PAINTED FLAT BLACK
MAXIMUM HEIGHT
INSULATED FLEXIBLE
ABOVE ROOF
DUCTWORK
PLENUM BOX HEIGHT =
DUCTWORK/DIFFUSER SHALL BE ROUND DUCT DIA. + 4" CLEAN OUT 2
SUPPORTED INDEPENDENTLY
FROM STRUCTURE (NOT BIRD SCREEN
DUCTWORK/DIFFUSER SHALL BE SUPPORTED PITCH DOWN ENTIRE
SUPPORTED BY CEILING). DRAIN PAN 1
INDEPENDENTLY FROM STRUCTURE TOWARD DRAIN A
A

CONDENSATE MINIMUM HEIGHT ABOVE ROOF.


SQUARE DIFFUSER (NOT SUPPORTED BY CEILING) INSIDE CLEAN OUT DRAIN SHALL BE
OF PLENUM TO BE PAINTED FLAT BLACK. C MINIMUM.
SQUARE DIFFUSER OBSTRUCTED INSTALLATION
CONTINUOUS WELD
ROUND BRANCH DUCT TO MAIN INSULATE ENTIRE B ALUMINUM HOOD
(SEE SCHEDULE FOR SIZE) EXTERNALLY DRAIN ASSEMBLY
B

INSULATE PLENUM. WITH ELASTOMERIC.


INTERNAL INSULATION SEE ROOF CURB DETAIL
ROUND BRANCH INSULATED FLEXIBLE DUCTWORK IS NOT ALLOWED. 1"
DUCT TO MAIN
(SEE SCHEDULE PLENUM BOX FLOOR
HEIGHT = ROUND DRAIN CUT OUT LID OF FLOOR SINK AND DEPRESS SEE PLAN FOR
FOR SIZE)
DUCT DIAMETER + 4" TRAP INTO FLOOR SINK IF REQUIRED TO SIZE OF DUCT
INSULATED FLEXIBLE CONDENSATE DRAIN TRAP DETAIL MEET HEIGHT REQUIREMENTS.
DUCTWORK ADJUST AIR FLOW SLOTS ROOF LINE
PER SCHEDULE AND PLANS.
SLOT DIFFUSER UNIT TYPE A B
(THREE SLOT SHOWN)
DUCTWORK/DIFFUSER
SHALL BE SUPPORTED
SLOT DIFFUSER INSTALLATION DRAW THROUGH P + 1" P/2 + 1"
INDEPENDENTLY FROM
STRUCTURE ROOF DECK
(NOT SUPPORTED BY BLOW THROUGH 2" MIN. 2P
DUCT RADIUS TO
CEILING) GOOSENECK DETAILS
DIFFUSER MIN. 2

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A
DUCT DIAMETERS
30° MIN. P = STATIC PRESSURE AT DRAIN PAN PLAN NOTE

Phone: (217) 793-2299


Fax: (217) 793-3311
1 MINIMUM HEIGHT FOR RELIEF IS 18"/MINIMUM FOR OUTDOOR AIR INTAKE IS 36".

www.trcww.com
A B C
UNIT P (IN W.G.) (IN) (IN) (IN)
SQUARE TO ROUND TRANSITION, 2 MAXIMUM HEIGHT ABOVE ROOF IS 48".
EXTERNALLY INSULATE BACK OF DIFFUSER
FCU- X 0.8 1.8 1.4 0.75
SQUARE DIFFUSER EDITOR'S NOTES:

AHU- X 3.0 4.0 2.5 1.5 1. INCLUDE SEPARATE ROOF CURB DETAIL.
PLAN NOTES 2. EDIT AND COORDINATE MAXIMUM HEIGHT ABOVE ROOF WITH
DUCT SIZE AND ARCHITECTURAL REQUIREMENTS.
A MINIMUM OF FIVE (5) FEET LENGTH OF FLEXIBLE DUCT SHALL BE PROVIDED TO EACH DIFFUSER. DUCTWORK SHALL CONTAIN 180°
OF BENDING. FLEXIBLE DUCTWORK LENGTH SHALL NOT EXCEED EIGHT(8) FEET EXCEPT WHERE SPECIFICALLY NOTED. FLEX DUCT
EDITOR'S NOTES:
SHALL NOT CONTACT CEILING AND SHALL BE PROPERLY SUPPORTED SO AS TO HAVE NO KINKS.
1. VERIFY THAT SUFFICIENT HEIGHT IS AVAILABLE TO PROPERLY INSTALL TRAP ASSEMBLY.
TIE-WRAP CONNECT FLEX DUCT HELICAL COIL TO ROUND METAL DIFFUSER NECK AND TO ROUND METAL DUCTWORK AT OTHER END

3 GOOSENECK DETAILS
2. DESIGNER SHALL FILL IN VALUES AND SCHEDULE ALL AHU TRAP DIMENSIONS. NOTE DIRTY FILTER LOADING WHEN
OF FLEX DUCT. PULL FLEX DUCT VAPOR BARRIER OVER LOWER TIE-WRAP AND INSTALL SECOND TIE-WRAP OVER THE VAPOR
DETERMINING PRESSURE AT DRAIN PAN.
BARRIER. INSULATE METAL DUCT OR DIFFUSER OVER TOP OF SECOND TIE-WRAP AND INSTALL INSULATOR'S TAPE ON EDGES.
3. COORDINATE A WIDE, DEEP FLOOR SINK WITH PLUMBING IF NECESSARY TO DEPRESS TRAP.
4. DIMENSION A IS MEASURED TO THE PAN WATER INLET WHICH COULD BE HIGHER THAN THE CONNECTION ON THE EXTERIOR NOT TO SCALE
PROVIDE A MINIMUM OF 18" OF STRAIGHT, VERTICALLY ORIENTED, FLEXIBLE DUCT AT THE DIFFUSER NECK. IF UNABLE TO PROVIDE STRAIGHT DUCT RUN THEN
OF THE UNIT IF THERE IS A BOTTOM ENTRANCE INTO THE PAN.
PROVIDE OBSTRUCTED INSTALLATION PLENUM IN ACCORDANCE WITH THIS DETAIL.
5. EDIT CODE MINIMUM SIZE BASED ON COOLING COIL CAPACITY:
MBH SIZE
UP TO 240 3/4"
EDITOR'S NOTES:
241 TO 480 1"
481 TO 1,080 1-1/4"
1. VERIFY LENGTH OF FLEX DUCTWORK DESIRED PER PROJECT AND EDIT HERE AND IN SPECS.
1,081 TO 1,500 1-1/2"
2. EXTERNAL INSULATION ON BACK OF SQUARE DIFFUSERS CAN BE TRADED FOR OTHER VALUE IF BUILDING IS TIGHTLY CONSTRUCTED
1,501 TO 3,000 2"
AND NOT ON TOP FLOOR.

1 SQUARE DIFFUSER INSTALLATION 2 CONDENSATE DRAIN TRAP DETAIL


NOT TO SCALE NOT TO SCALE

FRAMED WALL OPENING OF SIZE TO PASS DUCT AND FRAMED WALL OPENING OF SIZE TO
LEAVE ROOM FOR SEALANT TO MEET UL-LISTING. PASS DUCT AND LEAVE ROOM FOR SEALANT.

A
DUCT DUCT

FILL ANNULAR GAPS CONTINUOUS BEAD OF RTV SILICONE


EACH SIDE OF DUCT ON CONTINUOUS 1" WIDTH MASTIC SEALER
EACH SIDE OF WALL WITH
COUNTER FLASHING
1 NONCOMBUSTIBLE
SEALANT. NAILER
3 FINISHED WALL GRANULAR BASE FLASHING
FINISHED WALL
SURFACE 3 PLY FIBERGLASS ROOF FELT
SURFACE OF UNINSULATED DUCT THROUGH INTERIOR
WALL BLOCKING EXTERIOR WALL 2
26"X20"

RATED ASSEMBLY NON-RATED WALLS OR SMOKE-RESISTANT SEALED WITH STEEP ASPHALT


AS REQUIRED
UNINSULATED DUCT THROUGH CORRIDOR WALLS PREFABRICATED EQUIPMENT CURB
LOCATE WALL FAN PER 2
INTERIOR FIRE RATED WALLS
ELEVATIONS ON DRAWINGS BDD FRAMED WALL OPENING OF SIZE
FRAMED WALL OPENING OF SIZE TO LEAVE ROOM FOR DUCT BIRD SCREEN
WALL LOUVER TO PASS DUCT AND INSULATION INSULATION, AND SEALANT.
BY G.C. AND LEAVE ROOM FOR SEALANT
METAL STRAP TO MEET UL-LISTING.
3/4"Ø SLEEVE ANCHORS WIND BAND
(HOT DIP GALV.) SEAL
26"X20" WATERTIGHT AROUND ALL DUCT DUCT
FRONT VIEW WALL PENETRATIONS
PLAN VIEW CURB CAP
DUCT INSULATION DUCT INSULATION
TO BE CONTINUOUS TO BE CONTINUOUS ATTACH TO FAN CURB
THROUGH WALL. THROUGH WALL.
26"X20"

INSULATED ROOF CURB

ROOF SEE ARCHITECTURAL PLANS FOR


L3"X3"X5/16" ANGLE FLASHING DETAILS
HOT DIP GALV. AT
4'-0" O.C.
1
SECURE UNIT FILL ANNULAR GAPS EACH SIDE OF
TO OUTSIDE WALL 3/4"Ø SLEEVE ANCHORS FINISHED WALL DUCT ON EACH SIDE OF WALL
WIRE MOTOR GUARD METAL STRAP SURFACE OF 3
(HOT DIP GALV.) FINISHED WALL WITH NONCOMBUSTIBLE SEALANT. MOTORIZED SHUTTER
(HOT DIP GALV.) RATED ASSEMBLY SURFACE
INSULATED DUCT THROUGH INTERIOR INSULATED DUCT THROUGH INTERIOR
2
FIRE RESISTANCE RATED WALLS NON-RATED WALLS OR SMOKE-RESISTANT
EXTERIOR WALL POWER CONDUIT
BLANK-OFF CORRIDOR WALLS
INSULATED PANEL DUCT PENETRATION DETAILS EXHAUST DUCT TRANSITION TO
MEET OPENING SIZE
PLAN NOTES
WALL EXHAUST FAN DETAILS SIDE VIEW
1 INSTALL FIRESTOP SYSTEM AS SPECIFIED IN DIVISION 7. INSTALL RETAINING ANGLES AS REQUIRED BY SYSTEM LISTING.
DUCT WORK SUPPORT DETAILS
EDITOR'S NOTES: 2 INCLUDES FIRE BARRIERS, SMOKE BARRIERS, AND FIRE PARTITIONS AS DEFINED IN THE LOCAL APPLICABLE CODES AND ON THE PLANS.

1. BACKDRAFT DAMPER (BDD) CAN BE CHANGED TO A MOTORIZED DAMPER IF REQUIRED. 3 LOCATE FIRESTOP LABEL ON EACH SIDE OF PENETRATION SO THAT IT IS VISIBLE FROM AN ACCESSIBLE LOCATION ABOVE CEILING.

4 WALL EXHAUST FAN DETAILS 5 DUCT WORK SUPPORT DETAILS 6 DUCT PENETRATION DETAILS 7 ROOFTOP UPBLAST EXHAUST FAN DETAIL
NOT TO SCALE NOT TO SCALE NOT TO SCALE NOT TO SCALE

T E OF T E X
TA A

S
S
ROBERT A. BOELLNER

PR

R
R

EE
E

D
OF
ES GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
AIR-COOLED
DUCTWORK RISER - SEE MECHANICAL SHEET METAL SCREWS 4" ON CENTER CONDENSING UNIT
HVAC FLOOR PLANS FOR EXACT SIZE
1-1/2"X1-1/2"X1/8" ANGLE - INSTALL ON BOTH
LONG DIMENSION SIDES OF DUCTWORK. FOR HOT GAS BYPASS VALVE WITH
INSIDE SURFACE OF SHAFT WALLS RHG INTEGRAL SOLENOID VALVE
EXTEND ANGLE 3" BEYOND DUCTWORK DUCTWORK OVER 60" USE 2"X2"X1/8" ANGLE.
REFRIGERANT SHUT-OFF VALVES (TYP.)
9" MIN ALL OTHER SIDES

12" 4"X4"X1/4" ANGLE FRAMING UNDER METAL DECK. TO CONDENSING


INSTALL PRIOR TO CUTTING DECK. (TYPICAL) UNITS CARTRIDGE FILTER DRYER
HOT GAS BYPASS LINE
FLOOR RL
COMPRESSOR(S)
AIR FLOW DIRECTION EXPANSION DISTRIBUTOR
LIQUID LINE
VALVE SUCTION HEADER
SEAL HOLE AFTER DUCTWORK INSTALLATION HOLE IN STRUCTURAL FLOOR
WITH FIREPROOFING MATERIAL SEE DRAWINGS FOR ROUTING PROVIDE DRAIN PAN UNDER UNITS
FIRE DAMPER WHERE SHOWN AND CALLED FOR. SOLENOID VALVE OF REFRIGERANT PIPING
REFER TO MECHANICAL FOR DAMPER LOCATIONS. RHG MOUNTED INDOORS AND ROUTE
DUCTWORK RISER (TYPICAL) SIGHT RL
FIRE DAMPER OR FIRE/SMOKE DAMPER REFERENCE FLOOR FIRE DAMPER INSTALLATION DETAIL. TO DX COIL DISCHARGE TO FLOOR DRAIN.
AS NOTED ON PLANS. INSTALL PER UL GLASS RS
DX COIL
1 LISTING AND CONTRACT REQUIREMENTS.
EXPANSION VALVE CONDENSING UNIT INSTALLATION
LOW PRESSURE DUCT RISER SUPPORT EQUALIZER LINE
°
AIR FLOW DIRECTION 45 RS RS

TO CONDENSING SUCTION LINE


UNITS TO COMPRESSOR EXPANSION VALVE
(SLOPE TO COMPRESSOR) THERMAL BULB
9"
DUCT SIZE AS SHOWN ON PLANS
DUCTWORK RISER - SEE MECHANICAL ROOFTOP AHU INSTALLATION
HVAC FLOOR PLANS FOR EXACT SIZE ARRANGE RISER SO REINFORCER TRANSVERSE
JOINT IS AT RISER SUPPORT POINT
PLAN NOTES
2"X2"X1/4" ANGLE - INSTALL ON BOTH LONG
PLAN NOTES DIMENSION SIDES OF DUCTWORK. 1 UNIT SHALL BE PIPED PER A/E APPROVED MANUFACTURER'S PIPING DIAGRAM SUBMITTAL.

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A
FLOOR
1 45 DEGREE ENTRY FITTING. HEIGHT OF FITTING AT RISER SHALL BE 9" TALLER THAN DUCT HEIGHT 2 ALL OF HOT GAS BYPASS LINE TO BE WELL INSULATED.

Phone: (217) 793-2299


SHOWN ON PLANS. WIDTH OF FITTING AT RISER SHALL BE 18" WIDER THAN DUCT WIDTH SHOWN

Fax: (217) 793-3311


ON PLANS OR AS WIDE AS RISER, WHICHEVER IS LESS. 3 MAXIMUM HOT GAS BYPASS LINE LENGTH TO BE 60'-0".

www.trcww.com
SEAL HOLE AFTER DUCTWORK INSTALLATION HOLE IN STRUCTURAL FLOOR
WITH FIREPROOFING MATERIAL
FIRE DAMPER WHERE SHOWN AND CALLED FOR.
REFER TO MECHANICAL FOR DAMPER LOCATIONS.

1 DUCT AT SHAFT DETAILS


DUCTWORK RISER REFERENCE FLOOR FIRE DAMPER INSTALLATION DETAIL.

NOT TO SCALE
MEDIUM AND HIGH PRESSURE DUCT RISER SUPPORT

3 REFRIGERANT PIPING DETAIL


2 DUCTWORK RISER SUPPORT DETAILS NOT TO SCALE

NOT TO SCALE

SEE NOTE 5

SLEEVE, SEE NOTES 2 AND 6


DUCT INSULATION
ACCESS
PANEL DUCT INSULATION
6x6 MIN.
24x24 MAX.
DUCT
ACCESS
CONNECTION
PANEL
FIRE SEE NOTE 4
6x6 MIN. FIRE BARRIER OR PARTITION
DAMPER
24x24 MAX.
DUCT
CONNECTION
SEE NOTE 4

PERIMETER ANGLE (NOT


FIRE BARRIER OR PARTITION FASTENED TO PARTITION) FIRE
SEE NOTE 3 PERIMETER ANGLE (NOT DAMPER SEE NOTE 5
FASTENED TO PARTITION)
SEE NOTE 3 SLEEVE, SEE NOTES 2 AND 6
NOTES:
SLEEVE, SEE NOTE 2
1. COMPLY W/ SMACNA "FIRE, SMOKE AND RADIATION DAMPER INSTALLATION GUIDE FOR HVAC "SYSTEMS"
DUCT
AND NFPA 90A "INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS".
CONNECTION
2. GALVANIZED SLEEVE GAGE SHALL NOT BE LESS THAN CONNECTING DUCT FOR BREAKAWAY CONNECTED
SEE NOTE 4
DUCT. BREAKAWAY DUCT CONNECTION MAY BE OMITTED IF SLEEVE IS 16 GA. MINIMUM.
3. GALVANIZED STEEL PERIMETER ANGLE NOT LESS THAN 1-1/2x1-1/2x14 GAGE WITH 1" MINIMUM OVERLAP ON
ON ALL SIDES. NOTES:
4. BREAKAWAY DUCT CONNECTION, REFER TO SMACNA FIGURE 2-2 "UL ACCEPTED DUCT-SLEEVE CONNECTIONS" 1. COMPLY W/ SMACNA "FIRE, SMOKE AND RADIATION DAMPER INSTALLATION GUIDE FOR HVAC "SYSTEMS"
OF FIRE, SMOKE AND RADIATION DAMPER INSTALLATION GUIDE. UL TESTED DUCT SEALANT MAY BE USED. AND NFPA 90A "INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS".
BREAKAWAY DUCT CONNECTION MAY BE OMITTED IF SLEEVE IS 16 GA. MINIMUM. 2. GALVANIZED SLEEVE GAGE SHALL NOT BE LESS THAN CONNECTING DUCT FOR BREAKAWAY CONNECTED
5. PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH FIRE STOPPING MATERIAL. DUCT. BREAKAWAY DUCT CONNECTION MAY BE OMITTED IF SLEEVE IS 16 GA. MINIMUM.
6. FIRE DAMPER SLEEVE TO EXTEND 6" MINIMUM ON EACH SIDE. 3. GALVANIZED STEEL PERIMETER ANGLE NOT LESS THAN 1-1/2x1-1/2x14 GAGE WITH 1" MINIMUM OVERLAP ON
ON ALL SIDES.
4. BREAKAWAY DUCT CONNECTION, REFER TO SMACNA FIGURE 2-2 "UL ACCEPTED DUCT-SLEEVE CONNECTIONS"
OF FIRE, SMOKE AND RADIATION DAMPER INSTALLATION GUIDE. UL TESTED DUCT SEALANT MAY BE USED.
BREAKAWAY DUCT CONNECTION MAY BE OMITTED IF SLEEVE IS 16 GA. MINIMUM.
5. PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH FIRE STOPPING MATERIAL.
6. FIRE DAMPER SLEEVE TO EXTEND 6" MINIMUM ON EACH SIDE.

VERTICAL FIRE DAMPER DETAIL HORIZONTAL FIRE DAMPER DETAIL


4 NOT TO SCALE 5 NOT TO SCALE

T E OF T E X
TA A

S
ROBERT A. BOELLNER

PR

R
EE
E

D
R
OF
E S GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
NUMBER AND CONFIGURATION
OF
VANES PER SMACNA STANDARDS

AIRFLOW DIRECTION (SUPPLY)


TOP RUNNER NOT SHOWN
FOR

AIRFLOW DIRECTION (SUPPLY)


CLARITY
DOUBLE SIDED TURNING VANES

AIRFLOW DIRECTION (RETURN / EXHAUST)


AIRFLOW DIRECTION (RETURN / EXHAUST)

45° MANUAL LOCKABLE


DAMPER W/ HANDLE
45° MANUAL LOCKABLE
DAMPER W/ HANDLE
W

D RUNNER
1/4 x W ( 4" MINIMUM)

1/4 x W ( 4" MINIMUM) ACCESS PANEL (12/12 MINIMUM)

TURNING VANES, TYPICAL

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A
WHERE
SHORT RADIUS ELLS ARE NOT

Phone: (217) 793-2299


Fax: (217) 793-3311
INDICATED

www.trcww.com
TURNING VANE DETAIL
1
ROUND BRANCH DUCT CONNECTION 2 RECTANGULAR BRANCH DUCT CONNECTION 3 NOT TO SCALE

NOT TO SCALE NOT TO SCALE

CONTINUOUS BEAD OF RTV SILICONE


CONTINUOUS 1" WIDTH MASTIC SEALER
NOTE: COUNTER FLASHING
FLEXIBLE DUCT CONNECTIONS SHALL BE INSTALLED TO ADC STANDARDS AND SEALED TO UL STANDARDS PER
AMC NAILER
603 AND 604.2.1. AS A MINIMUM, THE CONTRACTOR SHALL SECURE THE FLEXIBLE DUCT TO GRILLE AND METAL GRANULAR BASE FLASHING
DUCT
3 PLY FIBERGLASS ROOF FELT
WITH DRAWBANDS, AND WRAP 3" WIDE ALUMINUM TAPE EQUAL TO HARDCAST "FOIL GRIP" AROUND DRAWBAND
SEALED WITH STEEP ASPHALT
AND
EXPOSED END OF FLEXIBLE DUCT INSULATION. PREFABRICATED EQUIPMENT CURB
DUCT STRAP SUPPORT WRAP ROUND PIPE DUCT RECTANGULAR DUCT
VAPOR SEAL AROUND DUCT AND SECURE BALANCING DAMPER
STRAP BELLMOUTH
TO PROVIDE
PENETRATION STRUCTURE ROUND DUCT
EXTENSION FOR HANDLE TO
CLEAR INSULATION
FLEXIBLE DUCT ( MAX. STREAMLINE TAP
LENGTH - 5'-0" )

DRAWBAND FLASHING COLLAR

INSULATE TOP
FILL ANNULAR SPACE
AND DRAWBAND CURB IN
SIDES OF GRILLE
CURB WITH
DUCT WRAP W/ VAPOR BARRIER ROOF
INSULATION
DIFFUSER CEILING
SECURE EDGE OF INSULATION
TO
T-BAR GRID WITH ALUMINUM
TAPE

DIFFUSER CONNECTION TO ROUND DUCT


4 NOT TO SCALE
RECTANGULAR DUCT

5 DUCT
NOT TO SCALE
PENETRATION THRU ROOF DETAIL

OF T E
TE XA
TA

S
ROBERT A. BOELLNER

PR

R
EE
E

D
R
OF
ES GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016
RETURN AIR
EAD COOLING COIL

FILTER DISHWASHER MACHINE 1-075


SEQUENCE OF OPERATION

FILTER
EXHAUST EXHAUST
AIR AIR

1 A GENERAL ALARM SHALL BE INITIATED IF SIGNAL OUTPUT DOES


NOT PROVE COMMANDED EXHAUST FAN OPERATION.

RECOVERY
EXHAUST FAN SUPPLY
OUTSIDE AIR EXHAUST FAN DEF-1

ENERGY

WHEEL
S 2 EXHAUST FAN DEF-1 CONTROLS TO BE INTERLOCKED WITH THE
DISHWASHER EQUIPMENT OPERATION. THE CONTROLS SHALL ALSO
SUPPLY FAN EXHAUST AIR FROM
OAD SD P OAD INTEGRATED SPEED SWITCH EXHAUST BE CONNECTED TO AND INTEROPERABLE WITH THE BUILDING
DISHWASHER HOODS
AUTOMATION SYSTEM .

COOLING COIL
OUTSIDE AIR /

FILTER
VRF 3 EXHAUST FAN DEF-1 VOLUME TO BE VARIED THRU VARIABLE
ECONOMIZER ACCU
RL FREQUENCY DRIVE TO MAINTAIN THE REQUIRED EXHAUST AIR FLOW
TO LAN (BY ECC) FOR DISHWASHER 1-075, WHEN PROVEN TO BE RUNNING.
N.O.
TO SAF SF STARTER ES RS CS
VFD TO NETWORK CONTROL
UNIT (LOW PROTOCOL) 4 WHEN DISHWASHER EQUIPMENT IS NOT OPERATING THE EXHAUST
AL FAN SHALL REMAIN OFF.
RL VFD P T BY E.C.
ACCU RS
DUCT SPACE
PRESSURE TSTAT

SPACE TEMP
1 T
SEQUENCE OF OPERATION SENSOR DISHMACHINE
ITEM #
FLOOR SERVING INDIVIDUAL EQUIPMENT
EXHAUST CFM

SPRINGFIELD, ILLINOIS, 62711


3200 PLEASANT RUN, SUITE A
------- LEVEL 1 300 *

Phone: (217) 793-2299


1. SUPPLY FAN SHALL RUN FOR NORMAL OPERATION.

Fax: (217) 793-3311


SEQUENCE OF OPERATION

www.trcww.com
2. EXHAUST FANS ARE STARTED WITH THE SUPPLY FANS. ON STARTUP THE OUTDOOR * TBC BY KITCHEN CONSULTANT
AIR DAMPER MUST OPEN AND WHEN PROVED OPEN, THE FAN STARTS THRU AND OCCUPIED MODE:
END SWITCH.

3. ALL SUPPLY AND EXHAUST FANS MUST START SIMULTANEOUSLY. LOSS OF DAMPER 1. SPACE CONTROL LOOP IS MAINTAINED AT A FIXED TEMPERATURE BY MODULATING
OPENING WILL STOP EITHER SUPPLY OR EXHAUST FANS. THE NORMALLY OPEN HEATING AND COOLING COIL VALVES IN SEQUENCE. DISHWASHER EXHAUST FAN DEF-1 CONTROL SCHEMATIC
4 NO SCALE
4. ALL H-O-A SWITCHES TO BE IN "AUTO" POSITION FOR ALL NORMAL OPERATION. 2. THE UNIT FAN RUNS CONTINUOUSLY.

5. SUPPLY AND EXHAUST FANS TO BE EQUIPPED WITH CURRENT SENSING RELAYS TO 3. THE OUTDOOR AIR DAMPER OPENS ANYTIME THE FAN OPERATES.
INDICATE CONDITION OF NO AIR FLOW DUE TO INOPERATIVE MOTOR (CURRENT
SENSORS TO BE FIELD ADJUSTED). 4. UNIT SHALL SHUT DOWN AND SEND A PRIORITY ALARM IN THE EVENT THAT WATER
IS DETECTED IN COOLING COIL OVERFLOW.
6. THE ENERGY RECOVERY WHEEL WILL HAVE ALL INTEGRAL CONTROLS SUPPLIED,
INSTALLED AND COMMISSIONED BY THE UNIT SUPPLIER. THE SPEED OF THE WHEEL
IS VARIED THRU THE VSC AND BYPASS DAMPERS MODULATED TO MAINTAIN A
DISCHARGE AIR TEMPERATURE.

7. FURNISH SAFETIES AS FOLLOWS TO STOP SUPPLY FAN AND EXHAUST FAN AND CLOSE UNOCCUPIED MODE:
OUTDOOR AIR AND EXHAUST DAMPERS WHEN ANY OF THESE OCCUR
1. OUTSIDE AIR DAMPER REMAINS CLOSED.
A. SMOKE DETECTOR ALARM.
2. THE UNIT FAN SHUTS OFF AND HEATING/COOLING VALVES CLOSE.
B. SUPPLY AIR STATIC PRESSURE EXCEEDS 2.5 IN. WC.
3. UNIT SHALL CYCLES ON TO MAINTAIN A MAXIMUM OF 80°F AND A MINIMUM OF 60°F IN THE
SPACE
8. FAN SHUTDOWN CLOSES OUTDOOR AIR AND EXHAUST AIR DAMPERS.

9. SUPPLY AIR VOLUME TO BE VARIED THRU VARIABLE FREQUENCY DRIVE T


VRV FAN COIL UNIT CONTROL SCHEMATIC
10. SUPPLY AIR DISCHARGE TEMPERATURE LEAVING THE AIR HANDLING UNIT IS
MAINTAINED AT 50˚-55˚F(ADJ) BY CONTROLLING THE ENERGY RECOVERY WHEEL
1 NO SCALE

AND BYPASS DAMPERS PREHEAT COIL AND COOLING COIL IN SEQUENCE AS


FOLLOWS:
· AHU SUPPLY AIR DISCHARGE TEMPERATURE IS SET AT 55˚F
· ENERGY RECOVERY WHEEL DISCHARGE TEMPERATURE IS SET AT 52˚F
· HEATING COIL PUMP IS DEENERGIZED ABOVE 45˚F OAT
· HEATING COIL AND COOLING COIL CONTROL LOOPS WORK IN SEQUENCE TO
MAINTAIN AHU DISCHARGE OF
55F. ON INCREASING DISCHARGE TEMPERATURE, THE MODULATING HEATING
COIL CONTROL VALVE SHALL SEQUENCE OF OPERATION KEF-1
CLOSE COMPLETE BEFORE GRADUALLY OPENING THE MODULATING COOLING
COIL CONTROL VALVE. ON A GENERAL ALARM SHALL BE INITIATED IF SIGNAL OUTPUT DOES NOT PROVE
1
DECREASING DISCHARGE TEMPERATURE, THE COOLING COIL CONTROL VALVE COMMANDED EXHAUST FAN OPERATION.
WILL CLOSE COMPLETE BEFORE OPENING THE HEATING COIL CONTROL VALVE. EXHAUST AIR EXHAUST
2 KITCHEN EXHAUST FAN CONTROLS TO BE INTERLOCKED WITH THE CORRESPONDING FROM KITCHEN OUTSIDE
KITCHEN HOOD OPERATION. THE CONTROLS SHALL ALSO BE CONNECTED TO AND HOOD
11. ANYTIME A SUPPLY OR EXHAUST FANS STOPS, ITS ISOLATION DAMPER CLOSED. IN INTEROPERABLE WITH THE BUILDING AUTOMATION SYSTEM .
ORDER TO RESTART THE FAN, EITHER ALL THE SUPPLY OR ALL THE EXHAUST FANS TO LAN (BY ECC)
MUST BE STOPPED AND RESTARTED TOGETHER. KITCHEN EXHAUST FAN KEF-1 TO MAINTAIN THE REQUIRED EXHAUST AIR FLOW
3
VOLUME (AS MENTIONED) THRU CORRESPONDING KITCHEN HOODS WHEN PROVEN TO NETWORK STR CS
TO BE RUNNING. CONTROL UNIT (LOW
PROTOCOL) HOA AL
WHEN KITCHEN HOOD EQUIPMENT IS OFF, THE KITCHEN EXHAUST FAN SHALL REMAIN WALL SWITCH
OFF. S 208/3
4
ERV-X CONTROL SCHEMATIC BY EC
1 NO SCALE

KITCHEN EXHAUST FAN CONTROL SCHEMATIC


3 NO SCALE

T E OF T E X
TA A

S
ROBERT A. BOELLNER

PR

R
R

EE
E

D
OF
E S GI S T E R E I

N
SI O G
NAL EN

SIGNED: 12-14-2015
EXPIRES: 06-30-2016