Transformer : SN.

190003 GI PAYOSELINCAH
SUMMARY FAT (ROUTINE TEST)

Hasil Pengujian Referensi


No Item Pengujian Lulus/ Tidak IEC/TPG/ITP/SKDIR Keterangan
Nilai/ Data Hasil Uji Nilai
Lulus 0632/2013
1 Measurement of voltage ratio Deviation ≤ 0.44% Lulus IEC 60076-1 Max 0,5%
2 Check of phase displacement YNyn0+d Lulus TPG OK/Not OK YNyn0+d
3 Measurement of winding resistance Recorded data only Lulus SINTRA design rules Recorded value Record data
4 Measurement of short circuit impedance 12.17 % @ nominal tap, 75°C Lulus TPG, IEC 60076-1 12.5 % ± 7.5 % of tolerance tolerance ± 7.5%
5 Measurement of load loss 109.79 kW @ nominal tap, 75°C Lulus TPG < 115 kW +15% of tolerance
6 Measurement of No-load loss 29.3 kW @ 100% Lulus TPG < 30 kW +15% of tolerance Denda = kW x Rp … = Rp …
7 Measurement of harmonics of no-load current Recorded data only Lulus SINTRA design rules recorded value Record data
8 Test on on-load tap-changer No failure Lulus SINTRA design rules OK/Not OK
9 Measurement of DC insulation resistance between each winding to earth Insulation resistance above 6250 MΩ Lulus SINTRA, IEC 60076-1 > 1000 MΩ Record data
10 Measurement of Polarization index between each winding to earth Min PI : 1.74 (fair) Lulus SINTRA design rules Min. Fair (>1.25) Record data
11 Check of core and frame insulation No failure (2 kV for one minutes) Lulus SINTRA design rules OK/Not OK Record data
12 Applied voltage test (AV test) No voltage breakdown occurred during test Lulus TPG, IEC 60076-1 Pass/Not Pass
13 Line terminal AC withstand voltage test (LTAC) No voltage breakdown occurred during test Lulus TPG, IEC 60076-1 Pass/Not Pass
14 Induce voltage test with Partial Discharge measurement (IVPD) ≤ 27 pC during 60 minutes Lulus TPG, IEC 60076-1 < 70 pC
a). Recorded data only for capacitance
b). On winding HV
- 0.11 for UST
- 0.14 for GST - LGND
- 0.19 for GST - LGUARD
15 Determination of capacitances and Measurement of dissipation Lulus SINTRA design rules OK/Not OK, Tan δ ≤ 0.5% @ 20°C on
c). On winding LV
factor (tan delta) of windings- to-earth, between windings and winding and bushing
- 0.09 for UST
bushings - 0.10 for GST - LGND
- 0.18 for GST - LGUARD
d). On Bushing
- 0.28 for Ph. 1U
- 0.29 for Ph. 1V
- 0.29 for Ph. 1W
16 Check of the ratio of built-in current transformer CT HV : -0.47%, CT LV : -0.27% Lulus SINTRA design rules maks error 1%
17 Functional test on control equipment and accessories All devices are working properly Lulus SINTRA design rules OK/Not OK
18 Auxiliary wiring insulation test (AuxW) No failure (2 kV for one minutes) Lulus SINTRA design rules OK/Not OK
- No collapse/failure during testing
19 Full wave Lightning impulse test for the Line terminals (LI) and for - No significant difference between voltage Lulus TPG, IEC 60076-1 Pass/Not Pass
the Neutral terminals (LIN) and current at reduce and full test voltage
20 SFRA measurement Recorded graph only Lulus SINTRA design rules recorded graph Record data
69,7 kV/2.5mm for breakdown voltage & > 60 kV/2.5mm for breakdown voltage &
21 Breakdown voltage and dissipation factor of the insulating oil dissipation factor (0.001388) Lulus SINTRA design rules IEC 60296 (<0.005) for dissipation factor
22 Dissolved gas analysis No failure Lulus IEC 60599 : 1999 table 2 page 21 OK/Not OK No failure on active part during
electrical tests
Lulus No oil leaks out of transformer and no
23 Oil leakage / pressure test No Leakage SINTRA design rules Pass/Not Pass
visible deformation of the tank

25 Degree of Polymerization test of insulating paper 1083 Lulus TPG > 900
26 Auxiliary Losses 1,541 Lulus TPG Max 2.0 kW