Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
®
VOLUME THREE NUMBER THREE
HVAC
I S S U E S A N D A N S W E R S F O R T H E C O N S U L T I N G / S P E C I F Y I N G C O M M U N I T Y
In this issue...
How are you specifying
System Part Load Value: A Case
your customers’ chillers?
Did you know that the
For Chiller System Optimization
lifetime cost of a typical
500-ton chiller could be as Introduction to do? Well, the first thing of the large number of
is to recognize the limita- novice customers who
high as $1.8 million? OK. So we are agreed, tions of the standard. IPLV are not trained in the fine
Would you be surprised the IPLV formula published and NPLV should be used details of refrigeration
to know that different in ARI Standard 550/590- as a starting point, not an equipment, a uniform,
makes of chillers may 1998 has its limitations. It end point. The second is single-number method of
meet your performance isn’t representative of any to understand that by their comparison is appropriate.
specifications, but that particular project, it’s based very simplicity, that is to Chilled water systems,
energy costs may actually on only one chiller operat- identify part-load perfor- on the other hand, are
differ by as much as $6,500 ing alone, and its part-load mance by a single universal comparatively complicated
a year? In this issue, find weighting may or may not figure, their usefulness as a with multiple pieces of
have any meaning for tool may be unsatisfactory. equipment that have inter-
out why evaluating chiller
central plants with multiple The Seasonal Energy dependent performance
performance by taking
chillers. ARI, in revising Efficiency Ratio (SEER), relationships. Moreover, a
into consideration all of the standard, was trying to developed by ARI for uni- chilled water system requires
the system and location define a uniform, industry- tary equipment, is the same a far greater financial invest-
factors will save your cus- wide measuring stick for sort of indicator. But the ment by the owner to both
tomer money over the life part-load performance. case can be argued that, install and operate the sys-
of the chiller. Likewise, the NPLV formula relatively speaking, unitary tem. This is why engineers
was introduced to do the systems are a technologically serve as consultants
Educate Your Customers: same thing as the IPLV simple market segment, to clients who will
System Part Load Value formula, but at non-ARI
is summarized in Carrier’s one that includes residential become chiller
Standard conditions. customers. Because
SYNOPSIS newsletter, which is
written specifically for building
IPLV and NPLV are only of the product’s sim-
owners and managers. approximate, single-number plicity, and because
To receive copies at no charge, generalizations of
call 1-800-CARRIER and request part-load per-
SYNOPSIS, Vol. 3, No. 3, formance.
or visit our website at That’s all.
www.carrier.com So, what
is an engineer
1
owners. It seems inappropri- market themselves as experts program that simplifies weather data, actual load
ate then to give a client in energy efficiency, and sell chilled water system analysis. characteristics, actual equip-
technical counsel using chiller retrofits on the basis Working together with your ment performance, and the
a method better suited of guaranteed savings. You local Carrier representative, anticipated operating hours
to residential applications. can be certain that when the software allows you and control sequence of
For the consulting energy savings come with to evaluate chiller perfor- multiple chillers. SPLV is
engineer, IPLV or NPLV financial guarantees, the mance by taking into an accurate, representative
can only be a good successful consultants are consideration all of the indication of chiller perfor-
starting point. basing their chiller selection system and location factors mance operating under
on something more than an recommended by ARI. project-specific conditions.
Why Should I Worry? IPLV rating from the catalog. One of the program’s Chiller System Optimizer
unique features is that it also provides the equipment
Start by asking the ques-
tion: “How do chillers get
If I Don’t Use IPLV calculates the System Part schedule criteria used
or Full-load kW/Ton, Load Value (SPLV) as an to specify chillers that
specified?” In many cases
alternative to ARI’s standard are optimized for your
the answer is to make a copy What Should I Use? IPLV and NPLV indicators. specific project.
of an old specification, mark
The footnotes in Like IPLV and NPLV, SPLV is Most important, when
it up in the format that
ARI 550/590-1998 recom- a single numerical indicator calculating life cycle costs,
exists, get it retyped, and
mend performing a of part-load performance. Chiller System Optimizer
then fill in the schedule on
comprehensive analysis The difference is that it is also considers the operation
the drawings. Done. Is that
using actual weather data, calculated specifically for and energy use of system
how it should be done?
building load characteristics, your project using actual auxiliaries such as pumps
That depends.
If your client is focused the number of chillers, oper-
simply on minimizing first ational hours, economizer FIGURE 1
cost, it doesn’t really matter. capabilities, and the energy
drawn by auxiliaries such as Typical System Performance Profile Taken From
Specify a chiller that’s rea- Chiller System Optimizer Output
sonable on energy use, that pumps and cooling towers.
fits the budget, and be But that’s a lot of work,
done with it. But rarely and many consultants cannot Cooling Tons Hrs. Chiller System kW/Ton
is that the case. sell the fees it takes to
Somewhere in most do that much work.
projects, usually on the Unfortunately, consulting
Cooling Ton-hrs Per Year
2
and cooling towers. This TABLE 1
allows the engineer to Performance of a Typical Building System,
evaluate and design a Weather is the Only Factor Changed in Each City
truly optimized system.
Competitor A (R123 Centrifugal) Competitor B (R134a Centrifugal) SPLV
So, How Does Chiller Chiller Full Chiller Chiller Full Chiller
Variation
Between
System Optimizer Load kW/ton NPLV SPLV Load kW/ton NPLV SPLV Chillers
anticipated performance at
certain specific conditions. SEATTLE 0.597 0.506 0.497 0.597 0.534 0.449 -10.69%
3
changed for each city. If the Competitor B chiller accomplished in a matter currency, different inflation
Also, two different makes is installed, it will operate of hours. All you need rates for assorted items,
of centrifugal chillers, were at about 0.445 kW/ton on to know is the peak load energy rates for natural gas,
compared in each city. average. This is nearly17% of your project building electricity and steam, and
The chillers were selected better than the indicated and the load at one or the minimum rate of return.
• Costs for equipment, con-
with identical full-load kW NPLV and more than 25% two other points (e.g.
struction, maintenance,
per ton ratings. To remain better than the full-load the conditions where load water treatment and other
objective in this discussion, rating. Is that what you equals zero). The program factors can be included.
we did not include a expected? Is that what interpolates a load profile • The program automatically
Carrier chiller. your client expected? based on the facility operat- performs the life cycle cost
The results are Would your client be ing hours you define. For analysis between different
surprising. If you take surprised to know that, unusual applications, the options and systems that
the identical specification in spite of both chillers program allows you to spec- you define.
prepared for a project in meeting the engineer’s ify the actual building load
Orlando and use it for a specifications, if he ends profile. Other features: When Should I
project in San Francisco, up with the wrong chiller • Weather is selected from Use Chiller System
the actual performance it will cost him more than actual weather data for 189
may vary by nearly 19%. $6,500 each year2 in higher cities in the United States or Optimizer?
Also, depending upon energy cost? Over the life 180 international locations.
• You can specify exact chiller Chiller System
which make chiller is of the chillers that adds up Optimizer fits into the
performance from selections
selected, the variation in to an additional $163,000! design process in several
prepared by Carrier or
performance can be as Was that in the budget? other manufacturers. In locations. First, during
much as 11% at the same Is it possible that your addition, the program has preliminary design. When
site even if both chillers client would like to be part performance templates of cooling loads have been
meet the specification with of that life cycle decision? actual chillers from Carrier, approximated and the
identical full-load kW per Trane, York and McQuay. engineer is working with
ton ratings. OK, I Agree. The model will also accept the architect to develop
different combinations
But Optimization the building concept,
So, What Does That of chiller size, type and
Chiller System Optimizer
Analysis Still Takes manufacturer up to a total
Mean to Me? of 12 chillers. can help determine the
a Lot of Time. • You can compare different type of chilled water system
Let’s look at the most to use. This allows the
Not any more. In chiller sequencing control
pronounced example, San engineer to define space
the old days, optimizing options.
Francisco. If the engi- • Cooling tower performance requirements for chillers,
neer’s specification defines the chiller and system
can be approximated, or it pumps and cooling towers.
the minimum chiller per- selections would take days can be accurately defined. Second, during detailed
formance as simply 0.597 of tedious calculations.
kW per ton at full load, FIGURE 2
all things being equal,
S P LV
the actual performance
will vary by more than 11%
depending on the make of
25% 50% 75% 100%
chiller selected. Also, note
that the Competitor B Load Load Load Load
chiller with the larger
NPLV (0.534) will actually ARI Standard Weighting Factors 0.120 0.450 0.420 0.010
operate more efficiently
than Competitor A Weighting Factors for Figure 1 Example 0.067 0.308 0.437 0.188
machine (0.506) when eval-
uated as part of the overall
system using site-specific
information. Why? Today, using Carrier’s Carrier has included a
cooling tower performance design, Chiller System
Because NPLV (and IPLV) Chiller System Optimizer
algorithm in the software Optimizer can be used to
is calculated at a very nar- can help you optimize
(provided by Baltimore define the exact criteria
rowly defined profile that is the chiller and system for
Aircoil) to predict the to be used in the chiller
not often representative of a specific project can be
2 Estimate of annual energy cost based on actual tower performance. specifications. Also, in
what is actually happening electrical rates of $0.05 per kilowatt-hour • You are able to define retrofit projects, Chiller
in the system. and $7.50 per kilowatt demand, and
specific economic criteria for System Optimizer helps
includes the energy cost of pumps and
cooling towers. your project: life cycle period,
4
the engineer to specify
chillers and equipment
that will be truly opti-
GLOSSARY
mized, providing the best
return on investment for
their client.
Literally speaking,
the time to use Chiller APLV Application Part Load Value is a single number,
System Optimizer is now. part-load efficiency indicator* calculated using the
Consider this: ARI method referenced to selected conditions.
• The time and expense of APLV was introduced in ARI Standard 550-1988,
performing chilled water
but deleted from the
system optimization the
old fashioned way has 1998 edition.
driven engineers into
using simplified methods IPLV Integrated Part Load Value is a single number,
of specifying chilled water
equipment that aren’t part-load efficiency indicator* calculated using
indicative of true the ARI method at standard rating conditions.
system performance. Introduced in ARI Standard 550-1986, the
• Chiller System Optimizer definition of IPLV was changed in ARI Standard
will allow you to prepare
better analysis for your 550/590-1998 to more closely reflect actual
clients, simply and easily operating experience found in the field for
using software that is not a single chiller.
manufacturer specific.
• For the consulting engineer,
the ability to perform NPLV Non-Standard Part Load Value is a single number,
meaningful optimization part-load efficiency indicator* calculated using the
analysis at minimum cost ARI method referenced to rating
is an important competi-
tive differentiator, and conditions other than ARI standard. The 1998
provides real value to standard adopted NPLV for situations when
your client. a single chiller is not intended to operate at
• Clients are expecting more standard ARI rating conditions.
from engineers. The con-
sulting world is changing
in the wake of performance SPLV System Part Load Value is a project-specific,
contracting, design-build single number, part-load efficiency indicator
programs, and competitive
introduced by Carrier that is calculated using
pressure on fees.
• Chilled water systems are the equation form defined in ARI 550/590- 1998.
becoming more complex, Unlike IPLV or NPLV, the factors used to calculate
and the options available SPLV are project specific and consider multiple-
to choose from are more
varied and confusing chiller applications, actual operating hours, and
than ever. project-specific operating conditions.
• Contact your local Carrier
representative and see for
yourself how Chiller System * ARI Standard 550-88 uses the term “figure of merit”. The
word “indicator” is used as a clarification. The use of a single
Optimization can define number performance value is to provide an indication of
your next project. equipment performance relative to other equipment at
defined operating conditions.
5
6