STANDARD OPERATING PROCEDURE FOR DG SET START(EMERGENCY SU

JOB TITAL:- DG SET START(EMERGENCY SUPPLY)

MODE OF
STEP PREVENTIVE CHECK OPERATION
OPERATION
Check ACDB Incomer- Hand TRIP by TNC
1(From station transformer) switch of 22 KV Station Manual trip
1 is OFF & Rack Out Transformer VCB
2 Hand Trip ACB of Manual trip
Incomer-1

3 ACB of incomer-1 is Manual


rack out.
4 Check battery voltage D.G switch on Manual
Check oil level
Check water level.

5 Check indication of bus- ACB of incomer-2 is Manual


coupler is on. rack in.
Check spring charged
indication.
6 Close ACB of Incomer-2 Manual
G SET START(EMERGENCY SUPPLY)

AFTER CHECK REMARK


1.Check LED indication for
VCB off
2.Check Load on
Ammeter.
1. Check LED indication of
ACB is off.
2. Check contact is open.
3. Check spring charged
indication.

Check D.G on indication


Check load on indication.
Check multifunction monitor
Check power command.
1. Check LED indication of
ACB is off.
2.Check contact of ACB

1. Check LED indication of


ACB is on.
2. Check all indication of
supply.(R,Y,B)
3. Check line voltage in MFM
4. Check load in MFM
STANDARD OPERATING PROCEDURE FOR DG SET STOP(EMERGE

JOB TITAL:- DG SET STOP(EMERGENCY SUPPLY)

PREVENTIVE MODE OF
OPERATION
STEP CHECK OPERATION
Check ACDB
Incomer- 1(From
1
station transformer) is
OFF & Rack Out
2 Hand Trip ACB of Manual trip
Incomer-2

3 ACB of incomer-2 is Manual


rack out.
4 Emergency Stop Manual

5 Check indication of bus- ACB of incomer-1 is Manual


coupler is on. rack in.
Check spring charged
indication.

7 Close ACB of Incomer-1 Manual

Hand CLOSE by TNC


switch of 22 KV
Manual
Station Transformer
6 VCB
FOR DG SET STOP(EMERGENCY SUPPLY)

AFTER CHECK REMARK


1.Check LED indication
for ACB I/C-1 OFF

2.Check Voltage in ACDB


panel.
1. Check LED indication of
ACB is off.
2. Check contact is open.
3. Check spring charged
indication.

Check battery voltage


Check oil level
Check coolant level.
1. Check LED indication of
ACB is off.
2.Check contact of ACB

1. Check LED indication of


ACB is on.
2. Check all indication of
supply.(R,Y,B)
3. Check line voltage in MFM
4. Check load in MFM

1. Check LED indication of


VCB is ON. 2.
Check load on ammeter.