Taller OMICRON

Pruebas en entornos IEC61850 y redes de


comunicación de subestaciones

© DieGas, OMICRON 14 March 2017


IEC 61850 environments: What to test?

© OMICRON Page 2
New possibility for protection test with SCADA
assessment signals.

Client/Server
Module

© OMICRON Page 3
Test Universe: Client / Server

Why Client/Server testing?


> Does my SCADA
communication work?
> Set the IED to mode
(test test/blocked off on on/blocked)
> Are the reports to SCADA system issued?
> Embedded into protection testing template. Preparation of the test &
assesment
> What is happening in the data model of the IED?
Your benefits

> Testing the SCADA communication in protection systems


> Handling the modes (test test/blocked off on on/blocked)
> Preparation of the test & assessment automatically
> New possibilities: using the entire data model for protection testing

© OMICRON Page 5
Technical realization

> IEC 61850 Client/Server Module offers a lot of new use cases
> Test Universe communicates directly with the IED

Ethernet/USB

IEC Network

IED
IEC communication Voltages & Currents

© OMICRON Page 6
Client/Server testing with the TU Module

> Set test mode and behavior


> Enable/disable reports

IEC Network

IEC communication

> Report notifications


> Read values

© OMICRON Page 7
Step 1: set IED

Set to Mode after reading

Enable reports for SCADA communication

© OMICRON Page 8
Step 2: define faults and expected results

Fault values

Expected values in data model

© OMICRON Page 9
Usage of IED‘s information for testing

• Fault values
• Direction information
• Earth fault
• Measurement values
• Tap changers
• .....

© OMICRON Page 10
End: reset IED

Reset back to
the original values

© OMICRON Page 11
Time Signal View

Visualizing the details of event (e.g. reports)

© OMICRON Page 12
Assesment and view in Client/Server monitor

Asses the data automatically (Report received)

More details can be added to Test Report

© OMICRON Page 13
Report View

© OMICRON Page 14
New philosophy for Digital Substation test

© OMICRON 14 March 2017


Background: IEC 61850 testing old vs. new

© OMICRON Page 16
Solution: Test Mode

> Testing of every logical node like PROTECTION.PDIS1


> Testing of every logical device like PROTECTION
> More than a simple „Test mode“:
> on; on/blocked; test; test/ blocked; off

invalid
invalid
on
on-blocked
test Incoming data
Incoming signal processed as valid
test-blocked
off
valid
not processed

© OMICRON Page 17
Complex dependencies defined in the standard

© OMICRON Page 18
Simulation indication with GOOSE and Sampled Values

> How to distinguish between “real” signals and simulated one?


> Sets the entire IED (“physical device”) in simulation mode LPHD.Sim = True

IED GoID=1 GoID=1 CMC


Simulation = FALSE Simulation = TRUE

Subscribe GoID=1
LPHD.Sim = FALSE
IED LPHD.Sim = TRUE

© OMICRON Page 19
New capabilies with IEDScout
IEDScout

Graphical-Intuitive

Self-describing
IEDScout key features

> Easy and powerful


> Descriptive IEC61850 names (you do no need memorize the meaning of LN)
> Extract of relevant services: find the reports, goose, datasets, files, settings groups
within datamodel
> Friendly data monitoring: easy data interpretation
> Highly commented communication transaction sniffing
> Easy filter for goose retransmission
> Data model association between sniffing and browsing
> IED simulation
> Useful for SCADA test without physical IED
> Creation of virtual substation in the Lab
> Network IEC61850 traffic generation
> New features IEDScout 4.2
> File transfer: Only one tool for download oscillography files from different IED brands
> Settings groups: enable the possibility for change protection setting or change
between different settings groups
DANEO 400
Hybrid signal analyzer for power utility automation systems

© OMICRON 14 March 2017


Your benefits

> Simultaneous recording of analog and


binary signals and network traffic
> Distributed, time-synchronized
measurements with multiple units
> IEC 61850 GOOSE and Sampled Values
support
> Aggregated and time-aligned
presentation for a rapid overview of
measurements
> Analysis of network performance Recording signals in a substation

> Insight view on IEEE 1588 time sources


> Unattended operation for e.g.
troubleshooting

© OMICRON Page 24
One device – different users

Protection and
automation
specialist using
IEC 61850

Network
Troubleshooter communication
specialist

© OMICRON Page 25
FAT or SAT scenarios in local substations

© OMICRON Page 26
Distributed testing of wide area data exchange

© OMICRON Page 27
Troubleshooting

© OMICRON Page 28
Measuring packet delay in a combined Ethernet/HSR
network

© OMICRON Page 29
Propagation Delay Measurement

© OMICRON Page 30
Web interface

> Controlling a single device


> Quick access
> Any device with a
web browser

> Selected features


> Networking functions
> Observing network traffic
> Recording network traffic
> Downloading recordings

> Check status


> Unattended operation

> PTP sniffer


> for exploring time sources
and easy synchronization

© OMICRON Page 31
Capabilities
TEST UNIVERSE IEDScout SVScout DANEO ISIO

Function

Client / Server

Goose

Sampled Values

PTP

Ethernet Timing

SCL handle

Pcap Hanlde

Fault Register