Sei sulla pagina 1di 2

Document No: TFS/RFQ/EH/R0

TECHNICAL DATA SHEET


Revision No: 1

JOB NO TFS-17-130
CLIENT NAME Heraeus Battery Technology GmbH
PROJECT ATFE system

ELECTRIC HEATER
DATA SHEET

1 16/3/2018 Secondary data revised Nikhil Chetan


0 1/3/2018 - Nikhil Chetan
Rev. No Date Description Prepared Checked Approved

DOCUMENTS TO BE PROVIDED BY VENDOR


A Special Certification: CE marking / certification
B Material / Test / Calibration certificate
C Warranty / Guarantee certificate
D GA drawings, Electrical wiring diagram
E Installation, Operation & Maintenance manual
NOTES
E ' * ' Means vendor to Specify / Advice
F Heater shall be suitable for the environmental exposure including ambient temperature extremes and external corrosion conditions.
G Vendor should study the process data and model quoted should be suitable for the mentioned process parameters.
H Vendor to submit a scanned copy of this datasheet duly filled in and any deviation shall be highlighted by vendor, along with quotation.
I Vendor should provide warranty for a period of minimum 12 months from date of commissioning or 18 months from the date dispatch.
ESSENTIAL DATA
1 Tag No EH-501
2 Location H1 : Primary Heating circuit
3 Service Thermic Fluid heating to process plant
4 Quantity 1
5 Type Electrical heating
6 Make *
7 Model *
Material of Contact Parts CS (except Electric heating elements & flange-SS316L)
8
Construction Non-Contact Parts CS
9 Flange standard RF flanged End, DIN std
10 Enclosure Non-Flame proof & CE mark, WP- IP54 or higher
11 Power supply 400 Volts, 3 phases (L1, L2, L3), neutral (N), ground (PE), 50 Hz
12 Installation type Horizontal
13 Approximate Heating Time (minutes) 90 - 100
SECONDARY DATA
14 Process Heating Load (KW) 100 130 rev.1
15 Design Heater capacity (KW) 120 170 rev.1
16 Quantity Of Hot Oil Required (liter) 800 880 rev.1
17 Operating Flow (m3/hr) 4.25 6.50 rev.1
18 Maximum Flow (m3/hr) 4.90 7.50 rev.1
19 Normal Operating Temperature (°C) 250
20 Min. / Max. Operating Temperature (°C) 20 / 280
21 Ambient Temperature (°C) 20
22 Temperature Stability (°C) *
23 Max. Temperature Drop (°C) *
24 Normal Operating Pressure (bar g) 4.6
25 Maximum Pressure (bar g) 5.5
26 Thermic Fluid Composition Therminol 66
27 Specific Heat (kJ/kg.°C) 1.58 @ 25 °C / 2.38 @ 250 °C
28 Density (kg/m3) 1003 @ 25 °C / 849 @ 250 °C
29 Viscosity (cP) 71 @ 25 °C / 0.572 @ 250 °C
ACCESSORIES
30 Control Panel Yes
31 Temperature transmitter Yes
32 Inbuilt Temperature Controller Required
33 Output signal to PLC-SCADA system Yes
34 Hot Oil pump assembly *
35 Expansion Tank *
Heater system inter-connecting piping and
36 *
accessories upto its battery limits
37 Mounting supports Yes
38 Insulation Yes
39 Insulation MOC *
40 Insulation Cladding Yes
41 Insulation MOC *