1. DIMENSIONAMIENTO Y METRADO DE CARGAS DE VIGAS Y COLUMNAS.

VIGA PRINCIPAL-PISO TÍPICO

 𝐷𝑒 𝑙𝑎 𝑙𝑜𝑠𝑎 𝑎𝑙𝑖𝑔𝑒𝑟𝑎𝑑𝑎:
𝑙𝑛 𝑚á𝑥 𝑙𝑛 𝑚á𝑥
ℎ= 𝑣
20 23
𝑙𝑛 𝑚á𝑥 = 6.3 𝑚

𝑙𝑛 𝑙𝑛
ℎ= ~ = 0.63~0.57 = 0.60 𝑚
10 11
𝐵 = 6.95 𝑚

𝑏2 = 0.35 𝑚

𝐵
𝑏= = 0.35 𝑚
20
𝐼1 = 𝐼2

ℎ2 = 0.60 𝑚

finalmente:

ℎ = 0.60 𝑚

𝑏 = 0.35 𝑚

3
[CONCRETO ARMADO I] ING. CIVIL

Metrado

CARGA MUERTA

Peso propio 0.50


Acabados 0.70
Tabiquería 1.04
Losa Aligerada 2.77
WD= 5.01 Tn/m

CARGA VIVA

S/C 1.74
WL= 1.74 Tn/m

WU= 9.97 Tn/m

VIGA PRINCIPAL-TECHO

b t
Col. Perimetral 0.35 0.60
Aligerado (h=0.30 m) 0.42
S/C 0.10
Tabiquería 0.05

𝑙𝑛 = 6.3 𝑚

𝐵 = 6.95 𝑚

𝑏2 = 0.35 𝑚

𝑙𝑛 𝑙𝑛
ℎ= ~ = 0.63~0.57 = 0.60 𝑚
10 11
𝐵
𝑏= = 0.35 𝑚
20
𝐼1 = 𝐼2

ℎ2 = 0.60

ℎ = 0.60 𝑚

𝑏 = 0.35 𝑚

Metrado:

4
[CONCRETO ARMADO I] ING. CIVIL

CARGA MUERTA

Peso Propio 0.50


Acabado 0.70
Tabiqueria 0.35
Losa aligerada 2.77
WD= 4.32 Tn/m

CARGA VIVA

S/C: 0.70
WL= 0.70 Tn/m

Wu= 7.23 Tn/m

VIGA SECUNDARIA- PISO TÍPICO

b t
Col. Perimetral 0.35 0.6
Aligerado (h=0.30 m) 0.42
S/C 0.25
Tabiquería 0.15

𝑙𝑛 = 6.6 𝑚

𝐵 = 6.45 𝑚

𝑏2 = 0.35 𝑚

𝑙𝑛 𝑙𝑛
ℎ= ~ = 0.66~0.60 = 0.60 𝑚
10 11
𝐵
𝑏= = 0.32 𝑚
20
𝐼1 = 𝐼2

ℎ2 = 0.58

ℎ = 0.60 𝑚

𝑏 = 0.35 𝑚

METRADO :TRAMO B--D

CARGA MUERTA

Peso Propio 0.50


Acabado 0.65

5
[CONCRETO ARMADO I] ING. CIVIL

Tabiqueria 0.97
Losa aligerada 2.56
WD= 4.68 Tn/m

CARGA VIVA

S/C: 1.61
WL= 1.61 Tn/m

Wu= 9.29 Tn/m

METRADO: TRAMO A-B Y D-E

CARGA MUERTA

Peso Propio 0.50


Acabado 0.65
Tabiqueria 0.97
Losa aligerada 2.32
WD= 4.44 Tn/m

CARGA VIVA

S/C: 1.61
WL= 1.61 Tn/m

Wu= 8.96 Tn/m

VIGA SECUNDARIA- TECHO

b t
Col. Perimetral 0.35 0.6
Aligerado (h=0.30 m) 0.42
S/C 0.10
Tabiquería 0.05
Losa maciza h=0.15

𝑙𝑛 = 6.6 𝑚

𝐵 = 6.45 𝑚

𝑏2 = 0.35 𝑚

𝑙𝑛 𝑙𝑛
ℎ= ~ = 0.66~0.60 = 0.60 𝑚
10 11

6
[CONCRETO ARMADO I] ING. CIVIL

𝐵
𝑏= = 0.32 𝑚
20
𝐼1 = 𝐼2

ℎ2 = 0.58

ℎ = 0.60 𝑚

𝑏 = 0.35 𝑚

METRADO :TRAMO B--D

CARGA MUERTA

Peso Propio 0.50


Acabado 0.65
Tabiqueria 0.32
Losa aligerada 2.56
WD= 4.03 Tn/m

CARGA VIVA

S/C: 0.65
WL= 0.65 Tn/m

Wu= 6.74 Tn/m

METRADO: TRAMO A-B Y D-E

CARGA MUERTA

Peso Propio 0.50


Acabado 0.65
Tabiqueria 0.32
Losa aligerada 2.32
WD= 3.79 Tn/m

CARGA VIVA

S/C: 0.65
WL= 0.65 Tn/m

Wu= 6.41 Tn/m

7
[CONCRETO ARMADO I] ING. CIVIL

DIMENSIONAMIENTO Y METRADO DE CARGAS EN COLUMNAS

 COLUMNA PERIMETRAL

METRADO DE CARGAS

Á𝑟𝑒𝑎 𝑇𝑟𝑖𝑏𝑢𝑡𝑎𝑟𝑖𝑎: (6.6𝑚)𝑥(2.8𝑚) = 18.48𝑚2

𝑀𝑒𝑡𝑟𝑎𝑑𝑜 𝑑𝑒 𝐶𝑎𝑟𝑔𝑎𝑠 𝑝𝑎𝑟𝑎 𝑒𝑙 𝑑𝑖𝑚𝑒𝑛𝑠𝑖𝑜𝑛𝑎𝑚𝑖𝑒𝑛𝑡𝑜 𝑑𝑒 𝑙𝑎 𝑐𝑜𝑙𝑢𝑚𝑛𝑎 𝑐𝑒𝑛𝑡𝑟𝑎𝑙:

−𝐿𝑜𝑠𝑎 𝐴𝑙𝑖𝑔𝑒𝑟𝑎𝑑𝑎: (0.42)𝑥(3)𝑥(18.48) = 47.04 𝑇𝑛

−𝑇𝑎𝑏𝑖𝑞𝑢𝑒𝑟í𝑎: (2)𝑥(0.15)𝑥(18.48) = 22.010625 𝑇𝑛

−𝑇𝑎𝑏𝑖𝑞𝑢𝑒𝑟í𝑎(𝐴𝑍𝑂𝑇𝐸𝐴): (1)𝑥(0.05)𝑥(18.48) = 0.924 𝑇𝑛

−𝐴𝑐𝑎𝑏𝑎𝑑𝑜: (3)𝑥(0.12)𝑥(18.48) = 5.544 𝑇𝑛

−𝑉𝑖𝑔𝑎 𝑋: [(2.4)𝑥(6.6)𝑥(0.6𝑥0.3)]𝑥3 = 8.5536𝑇𝑛

−𝑉𝑖𝑔𝑎 𝑌: [(2.4)𝑥(2.8)𝑥(0.6𝑥0.3)]𝑥3 = 8.19 𝑇𝑛

− 𝑆⁄𝐶 : (2)𝑥(0.25)𝑥(18.48) + (1)𝑥(0.1)𝑥(18.48) = 11.088 𝑇𝑛

𝑨𝒔𝒖𝒎𝒊𝒎𝒐𝒔 𝑪𝒐𝒍𝒖𝒎𝒏𝒂 𝒑𝒆𝒓𝒊𝒎𝒆𝒕𝒓𝒂𝒍 (𝟎. 𝟑𝟓𝒙𝟔𝟎)

−𝐶𝑜𝑙𝑢𝑚𝑛𝑎: (2.4)𝑥[(0.35)𝑥(0.60)]𝑥(3.4 + 2𝑥2.7) = 4. .44 𝑇𝑛

𝑾𝑻 = 𝑷𝒔 = 𝟖𝟔. 𝟕𝟓𝟕𝟔 𝑻𝒏 ; 𝑆𝑒𝑎 𝜆 = 1.25, 𝑛 = 0.25 𝑝𝑎𝑟𝑎 𝑐𝑜𝑙. 𝑝𝑒𝑟𝑖𝑚𝑒𝑡𝑟𝑎𝑙

𝜆𝑥𝑃𝑠
−𝐴𝑐 = = 𝟐𝟎𝟓𝟐. 𝟓𝟕 𝒄𝒎𝟐 ≈ (0.35)𝑥(0.60) = 𝟐𝟏𝟎𝟎 𝒄𝒎𝟐
𝑛𝑥𝑓´𝑐

∴ 𝑪𝒐𝒍𝒖𝒎𝒏𝒂 𝒑𝒆𝒓𝒊𝒎𝒆𝒕𝒓𝒂𝒍 = (𝟎. 𝟑𝟓𝒎𝒙𝟎. 𝟔𝟎𝒎)

 COLUMNA ESQUINA

METRADO DE CARGAS

−Á𝑟𝑒𝑎 𝑇𝑟𝑖𝑏𝑢𝑡𝑎𝑟𝑖𝑎: (1.4𝑚)𝑥(2.8𝑚) = 3.92𝑚2

𝑀𝑒𝑡𝑟𝑎𝑑𝑜 𝑑𝑒 𝐶𝑎𝑟𝑔𝑎𝑠 𝑝𝑎𝑟𝑎 𝑒𝑙 𝑑𝑖𝑚𝑒𝑛𝑠𝑖𝑜𝑛𝑎𝑚𝑖𝑒𝑛𝑡𝑜 𝑑𝑒 𝑙𝑎 𝑐𝑜𝑙𝑢𝑚𝑛𝑎 𝑝𝑒𝑟𝑖𝑚𝑒𝑡𝑟𝑎𝑙:

−𝐿𝑜𝑠𝑎 𝑚𝑎𝑐𝑖𝑧𝑎: (3)𝑥(2.4)𝑥(3.92) = 28.224𝑇𝑛

−𝑇𝑎𝑏𝑖𝑞𝑢𝑒𝑟í𝑎: (2)𝑥(0.15)𝑥(3.92) = 1.176 𝑇𝑛

8
[CONCRETO ARMADO I] ING. CIVIL

−𝑇𝑎𝑏𝑖𝑞𝑢𝑒𝑟í𝑎(𝐴𝑍𝑂𝑇𝐸𝐴): (1)𝑥(0.05)𝑥(3.92) = 0.196 𝑇𝑛

−𝐴𝑐𝑎𝑏𝑎𝑑𝑜: (3)𝑥(0.12)𝑥(3.92) = 1.176 𝑇𝑛

−𝑉𝑖𝑔𝑎 𝑋: [(2.4)𝑥(1.4)𝑥(0.6𝑥0.3)]𝑥3 = 1.814 𝑇𝑛

−𝑉𝑖𝑔𝑎 𝑌: [(2.4)𝑥(2.8)𝑥(0.6𝑥0.3)]𝑥3 = 3.63 𝑇𝑛

− 𝑆⁄𝐶 : (2)𝑥(0.2)𝑥(3.92) + (1)𝑥(0.1)𝑥(3.92) = 1.96 𝑇𝑛

𝑨𝒔𝒖𝒎𝒊𝒎𝒐𝒔 𝑪𝒐𝒍𝒖𝒎𝒏𝒂 𝒆𝒔𝒒𝒖𝒊𝒏𝒂 (𝟎. 𝟑𝟓𝒙𝟎. 𝟔)

−𝐶𝑜𝑙𝑢𝑚𝑛𝑎: (2.4)𝑥[(0.35)𝑥(0.6)]𝑥(3.4 + 2𝑥2.7) = 4.44 𝑇𝑛

𝑾𝑻 = 𝑷𝒔 = 𝟒𝟐. 𝟏 𝑻𝒏 ; 𝑆𝑒𝑎 𝜆 = 1.5, 𝑛 = 0.15 𝑝𝑎𝑟𝑎 𝑐𝑜𝑙. 𝑝𝑒𝑟𝑖𝑚𝑒𝑡𝑟𝑎𝑙

𝜆𝑥𝑃𝑠
−𝐴𝑐 = = 𝟐𝟎𝟎𝟒. 𝟓𝟑 𝒄𝒎𝟐 ≈ (0.35)𝑥(0.6) = 𝟐𝟏𝟎𝟎 𝒄𝒎𝟐
𝑛𝑥𝑓´𝑐

∴ 𝑪𝒐𝒍𝒖𝒎𝒏𝒂 𝒆𝒔𝒒𝒖𝒊𝒏𝒂 = (𝟎. 𝟑𝟓𝒎𝒙𝟎. 𝟔𝟎𝒎)

 Diseño del pórtico del Eje 4 y pórtico del Eje D (columnas y vigas):
Eje 4

9
[CONCRETO ARMADO I] ING. CIVIL

DISEÑAR LAS VIGAS UTILIZANDO LA ENVOLVENTE.

a) DISEÑO DE VIGA DEL 1 AL 2 NIVEL


FLEXION
Del análisis estructural con el programa ETABS obtenemos los diagramas de
momentos a lo largo de la viga. Tomaremos los momentos de la viga del nivel
1 y este será el mismo diseño para el nivel 2.

−3.667 𝑇𝑜𝑛 𝑚 −21.4585 𝑡𝑜𝑛 𝑚 −30.4093𝑡𝑜𝑛 𝑚 −21.4170𝑡𝑜𝑛 𝑚 −3.3160𝑡𝑜𝑛 𝑚

A 4.2287 𝑡𝑜𝑛 𝑚 17.7140 𝑡𝑜𝑛 𝑚 C 17.7333 𝑡𝑜𝑛 𝑚 D 4.2352𝑡𝑜𝑛 𝑚


B

CORTE:

10
[CONCRETO ARMADO I] ING. CIVIL

 Del análisis estructural con el programa ETABS obtenemos los diagramas de


fuerza cortante a lo largo de la viga. Tomaremos los cortantes de la viga del nivel
1 y este será el mismo diseño para el nivel 2.

TRAMO E-D

TRAMO D-C

TRAMO C-B

TRAMO B-A

11
[CONCRETO ARMADO I] ING. CIVIL

b) DISEÑO DE VIGA DEL 3 NIVEL


FLEXION

Del análisis estructural con el programa ETABS obtenemos los diagramas de momentos
a lo largo de la viga. Tomaremos los momentos de la viga del nivel 3.

−1.8291 𝑇𝑜𝑛 𝑚 −12.9092 𝑡𝑜𝑛 𝑚 −21.8697 𝑚 −14.7205 𝑡𝑜𝑛 𝑚 −1.8143𝑡𝑜𝑛 𝑚

A 2.9412 𝑡𝑜𝑛 𝑚 12.1253 𝑡𝑜𝑛 𝑚 C 13.9071 𝑡𝑜𝑛 𝑚 D 3.5355 𝑡𝑜𝑛 𝑚


B

CORTE:
 Del análisis estructural con el programa ETABS obtenemos los diagramas de
fuerza cortante a lo largo de la viga. Tomaremos los cortantes de la viga del nivel
3.

TRAMO E-D

TRAMO D-C

TRAMO C-B

12
[CONCRETO ARMADO I] ING. CIVIL

TRAMO B-A

PORTICO 4

DISEÑO DE VIGA DEL NIVEL 1 AL 2:

Eje Y – TRAMO E- D:

0.60
Mmax+ = 6.7709 Tn-m

Mmax- = -0.6606Tn-m

f'c = 210 Kg/cm2 0.35

fy = 4200 Kg/cm2

b = 35 cm

d= 51 cm

 Usamos el valor de Mu = 6.7709 Tn-m

Se sabe que:

13
[CONCRETO ARMADO I] ING. CIVIL

𝐴𝑠 ×𝑓𝑦 𝑀𝑢
𝑎= As = 𝑎
0.85×𝑓′𝑐 ×𝑏 0.9×𝑓𝑦 ×(𝑑− )
2

Procedemos a calcular los límites de la cantidad de acero:

14 0.7√𝑓′𝑐 14 0.7√280
𝐴𝑠𝑚𝑖𝑛 = 𝑚𝑎𝑥 ( 𝑏𝑑 ; 𝑏𝑑 ) = 𝑚𝑎𝑥 ( 0.35𝑥60 ; 0.35𝑥60 )
𝑓𝑦 𝑓𝑦 4200 4200

𝐴𝑠𝑚𝑖𝑛 = 𝑚𝑎𝑥(5.95 ; 4.311 ) = 5.95

a (cm) As (cm2)
0.85 ∗ 𝑓 ′ 𝑐 ∗ 𝛽1 ∗ 𝜉𝑐
𝜌𝑏 = → 𝜌𝑏 = 0.02125 10.2 3.902491038
𝑓𝑦 ∗ (𝜉𝑐 ∗ 𝐸𝑠 + 𝑓𝑦)
2.62352339 3.60496457

2.42350559 3.597723332

2.41863753 3.597547456
𝐴𝑠𝑚𝑎𝑥 = 0.75𝜌𝑏 𝑏𝑑 = 0.75 ∗ 0.02125 ∗ 35 ∗ 51 =
28.45 2.4185193 3.597543185

2.41851643 3.597543081

𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑠 < 𝐴𝑠𝑚𝑎𝑥 → 5.95 < 𝐴𝑠 < 28.45 2.41851636 3.597543079

2.41851636 3.597543079

2.41851636 3.597543079
As menor que Asmin por lo tanto asumimos As = Asmax 2.41851636 3.597543079

2.41851636 3.597543079
𝐴𝑠 = 28.45

Necesitamos refuerzo en compresion

𝑎𝑚𝑎𝑥 = 19.125

𝑀𝑢𝑚𝑎𝑥 = 4.456 tn = 𝑀𝑢1

𝐴𝑠𝑚𝑎𝑥 = 28.45 = 𝐴𝑠1

𝑀𝑢 = 𝑀𝑢1 + 𝑀𝑢2 → 𝑀𝑢2 = 2.315 𝑡𝑛

𝑀𝑢2 = 𝜙 ∗ 𝐴𝑠2 ∗ 𝑓𝑦 ∗ (𝑑 − 𝑑′ ) → 𝐴𝑠2 = 13.09 𝑐𝑚2

14
[CONCRETO ARMADO I] ING. CIVIL

𝛽1
𝑓 ′ 𝑠 = 𝐸𝑠 ∗ 𝜉𝑐 ∗ (1 − 𝑑′ ∗ ) → 𝑓 ′ 𝑠 = 4400
𝑎

Ya que f’s>fy, asumimos que f’s = fy. Por lo que al hacer el equilibrio:

𝐴′ 𝑠 ∗ 𝑓 ′ 𝑠 = 𝐴𝑠2 ∗ 𝑓𝑦 → 𝐴′ 𝑠 = 𝐴𝑠2

𝐴′ 𝑠 = 13.09𝑐𝑚2

𝐴𝑠 = 41.04𝑐𝑚2

Usaremos el siguiente refuerzo: 8∅1" y 2∅1" + 1∅3/4"

Obteniendo el siguiente perfil:

Eje Y – TRAMO D – C:

0.60
Mmax+ = 11.5886 Tn-m

Mmax- = -26.5858Tn-m

f'c = 210 Kg/cm2 0.35

fy = 4200 Kg/cm2

b = 35 cm

d= 51 cm

15
[CONCRETO ARMADO I] ING. CIVIL

 Usamos el valor de Mu = 11.5886 Tn-m

Se sabe que:

𝐴𝑠 ×𝑓𝑦 𝑀𝑢
𝑎= As = 𝑎
0.85×𝑓′𝑐 ×𝑏 0.9×𝑓𝑦 ×(𝑑− )
2

Procedemos a calcular los límites de la cantidad de acero:

14 0.7√𝑓′𝑐
𝐴𝑠𝑚𝑖𝑛 = 𝑚𝑎𝑥 ( 𝑏𝑑 ; 𝑏𝑑 )
𝑓𝑦 𝑓𝑦
a (cm) As (cm2)
14 0.7√280
= 𝑚𝑎𝑥 ( 0.35𝑥60 ; 0.35𝑥60 )
4200 4200 10.8 6.308162954

4.240781818 5.909387618

𝐴𝑠𝑚𝑖𝑛 = 𝑚𝑎𝑥(5.95 ; 4.311 ) = 5.95 3.972697558 5.894158791

3.962459691 5.893578773

3.962069763 5.893556684

0.85 ∗ 𝑓 ′ 𝑐 ∗ 𝛽1 ∗ 𝜉𝑐 3.962054914 5.893555843


𝜌𝑏 = → 𝜌𝑏 = 0.02125
𝑓𝑦 ∗ (𝜉𝑐 ∗ 𝐸𝑠 + 𝑓𝑦)
3.962054348 5.893555811

3.962054327 5.89355581

3.962054326 5.89355581

𝐴𝑠𝑚𝑎𝑥 = 0.75𝜌𝑏 𝑏𝑑 = 0.75 ∗ 0.02125 ∗ 35 ∗ 51 = 28.45

𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑠 < 𝐴𝑠𝑚𝑎𝑥 → 5.95 < 𝐴𝑠 < 28.45

As menor que Asmin por lo tanto asumimos As = Asmax

𝐴𝑠 = 28.45

16
[CONCRETO ARMADO I] ING. CIVIL

Necesitamos refuerzo en compresion

𝑎𝑚𝑎𝑥 = 19.125

𝑀𝑢𝑚𝑎𝑥 = 4.456 tn = 𝑀𝑢1

𝐴𝑠𝑚𝑎𝑥 = 28.45 = 𝐴𝑠1

𝑀𝑢 = 𝑀𝑢1 + 𝑀𝑢2 → 𝑀𝑢2 = 2.315 𝑡𝑛

𝑀𝑢2 = 𝜙 ∗ 𝐴𝑠2 ∗ 𝑓𝑦 ∗ (𝑑 − 𝑑′ ) → 𝐴𝑠2 = 13.09 𝑐𝑚2

𝛽1
𝑓 ′ 𝑠 = 𝐸𝑠 ∗ 𝜉𝑐 ∗ (1 − 𝑑′ ∗ ) → 𝑓 ′ 𝑠 = 4400
𝑎

Ya que f’s>fy, asumimos que f’s = fy. Por lo que al hacer el equilibrio:

𝐴′ 𝑠 ∗ 𝑓 ′ 𝑠 = 𝐴𝑠2 ∗ 𝑓𝑦 → 𝐴′ 𝑠 = 𝐴𝑠2

𝐴′ 𝑠 = 13.09𝑐𝑚2

𝐴𝑠 = 41.04𝑐𝑚2

Usaremos el siguiente refuerzo: 8∅1" y 2∅1" + 1∅3/4"

Obteniendo el siguiente perfil:

Eje Y – TRAMO C – B:

17
[CONCRETO ARMADO I] ING. CIVIL

0.60
Mmax+ = 13.0423 Tn-m

Mmax- = -29.4498Tn-m

f'c = 210 Kg/cm2 0.35

fy = 4200 Kg/cm2

b = 35 cm

d= 51 cm

 Usamos el valor de Mu = 13.0423 Tn-m

Se sabe que:

𝐴𝑠 ×𝑓𝑦 𝑀𝑢
𝑎= As = 𝑎
0.85×𝑓′𝑐 ×𝑏 0.9×𝑓𝑦 ×(𝑑− )
2

Procedemos a calcular los límites de la cantidad de acero:

14 0.7√𝑓′𝑐 14 0.7√280
𝐴𝑠𝑚𝑖𝑛 = 𝑚𝑎𝑥 ( 𝑏𝑑 ; 𝑏𝑑 ) = 𝑚𝑎𝑥 ( 0.35𝑥60 ; 0.35𝑥60 )
𝑓𝑦 𝑓𝑦 4200 4200

𝐴𝑠𝑚𝑖𝑛 = 𝑚𝑎𝑥(5.95 ; 4.311 ) = 5.95

18
[CONCRETO ARMADO I] ING. CIVIL

0.85 ∗ 𝑓 ′ 𝑐 ∗ 𝛽1 ∗ 𝜉𝑐 a (cm) As (cm2)


𝜌𝑏 = → 𝜌𝑏 = 0.02125
𝑓𝑦 ∗ (𝜉𝑐 ∗ 𝐸𝑠 + 𝑓𝑦)
10.8 7.099473077

4.77275501 6.684948176

4.49408281 6.666950082

4.48198325 6.666170824
𝐴𝑠𝑚𝑎𝑥 = 0.75𝜌𝑏 𝑏𝑑 = 0.75 ∗ 0.02125 ∗ 35 ∗ 51 = 28.45
4.48145938 6.666137089

4.4814367 6.666135629
𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑠 < 𝐴𝑠𝑚𝑎𝑥 → 5.95 < 𝐴𝑠 < 28.45
4.48143572 6.666135566

4.48143567 6.666135563
𝐴𝑠 = 6.67𝑐𝑚2
4.48143567 6.666135563
Obteniendo el siguiente perfil:

Eje Y – TRAMO B- A:

0.60
Mmax+ = 1.3181 Tn-m

Mmax- = -4.8768 Tn-m

f'c = 210 Kg/cm2 0.35

fy = 4200 Kg/cm2

b = 35 cm

d= 51 cm

19
[CONCRETO ARMADO I] ING. CIVIL

 Usamos el valor de Mu = 6.7709 Tn-m

Se sabe que:

𝐴𝑠 ×𝑓𝑦 𝑀𝑢
𝑎= As = 𝑎
0.85×𝑓′𝑐 ×𝑏 0.9×𝑓𝑦 ×(𝑑− )
2

Procedemos a calcular los límites de la cantidad de acero:

14 0.7√𝑓′𝑐 14 0.7√280
𝐴𝑠𝑚𝑖𝑛 = 𝑚𝑎𝑥 ( 𝑏𝑑 ; 𝑏𝑑 ) = 𝑚𝑎𝑥 ( 0.35𝑥60 ; 0.35𝑥60 )
𝑓𝑦 𝑓𝑦 4200 4200

𝐴𝑠𝑚𝑖𝑛 = 𝑚𝑎𝑥(5.95 ; 4.311 ) = 5.95

0.85 ∗ 𝑓 ′ 𝑐 ∗ 𝛽1 ∗ 𝜉𝑐
𝜌𝑏 = → 𝜌𝑏 = 0.02125 a (cm) As (cm2)
𝑓𝑦 ∗ (𝜉𝑐 ∗ 𝐸𝑠 + 𝑓𝑦)
10.8 0.71749733

0.48235115 0.64864459

𝐴𝑠𝑚𝑎𝑥 = 0.75𝜌𝑏 𝑏𝑑 = 0.75 ∗ 0.02125 ∗ 35 ∗ 51 = 28.45 0.43606359 0.64836546

0.43587594 0.64836433

𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑠 < 𝐴𝑠𝑚𝑎𝑥 → 5.95 < 𝐴𝑠 < 28.45 0.43587518 0.64836432

0.43587517 0.64836432

0.43587517 0.64836432

As menor que Asmin por lo tanto asumimos As = Asmax 0.43587517 0.64836432

0.43587517 0.64836432

𝐴𝑠 = 28.45

Necesitamos refuerzo en compresion

𝑎𝑚𝑎𝑥 = 19.125

20
[CONCRETO ARMADO I] ING. CIVIL

𝑀𝑢𝑚𝑎𝑥 = 4.456 tn = 𝑀𝑢1

𝐴𝑠𝑚𝑎𝑥 = 28.45 = 𝐴𝑠1

𝑀𝑢 = 𝑀𝑢1 + 𝑀𝑢2 → 𝑀𝑢2 = 2.315 𝑡𝑛

𝑀𝑢2 = 𝜙 ∗ 𝐴𝑠2 ∗ 𝑓𝑦 ∗ (𝑑 − 𝑑′ ) → 𝐴𝑠2 = 13.09 𝑐𝑚2

𝛽1
𝑓 ′ 𝑠 = 𝐸𝑠 ∗ 𝜉𝑐 ∗ (1 − 𝑑′ ∗ ) → 𝑓 ′ 𝑠 = 4400
𝑎

Ya que f’s>fy, asumimos que f’s = fy. Por lo que al hacer el equilibrio:

𝐴′ 𝑠 ∗ 𝑓 ′ 𝑠 = 𝐴𝑠2 ∗ 𝑓𝑦 → 𝐴′ 𝑠 = 𝐴𝑠2

𝐴′ 𝑠 = 13.09𝑐𝑚2

𝐴𝑠 = 41.04𝑐𝑚2

Usaremos el siguiente refuerzo: 8∅1" y 2∅1" + 1∅3/4"

Obteniendo el siguiente perfil:

21
[CONCRETO ARMADO I] ING. CIVIL

2. ANÁLISIS ESTRUCTURAL DE UN PÓRTICO. INCLUYENDO LAS


CARGAS DE GRAVEDAD Y LAS CARGAS DE SISMO, UTILIZANDO LAS
COMBINACIONES CORRESPONDIENTES.

22
[CONCRETO ARMADO I] ING. CIVIL

23
[CONCRETO ARMADO I] ING. CIVIL

24
[CONCRETO ARMADO I] ING. CIVIL

Unique Load Element


Story Column Name Case/Combo Station P V2 V3 T M2 M3 Element Station
Story5 C2 24 Comb1 0 -38 0.45 0 0 0 0.41 24 0
Story5 C2 24 Comb1 1.33 -37 0.45 0 0 0 -0.2 24 1.325
Story5 C2 24 Comb1 2.65 -36 0.45 0 0 0 -0.8 24 2.65
Story5 C2 24 Comb2 0 -33 5.7 0 0 0 6.3 24 0
Story5 C2 24 Comb2 1.33 -32 5.7 0 0 0 -1.3 24 1.325
Story5 C2 24 Comb2 2.65 -31 5.7 0 0 0 -8.8 24 2.65
Story5 C2 24 Comb3 0 -33 -4.9 0 0 0 -5.6 24 0
Story5 C2 24 Comb3 1.33 -33 -4.9 0 0 0 0.91 24 1.325
Story5 C2 24 Comb3 2.65 -32 -4.9 0 0 0 7.41 24 2.65
Story5 C2 24 Comb4 0 -21 5.58 0 0 0 6.17 24 0
Story5 C2 24 Comb4 1.33 -20 5.58 0 0 0 -1.2 24 1.325
Story5 C2 24 Comb4 2.65 -20 5.58 0 0 0 -8.6 24 2.65
Story5 C2 24 Comb5 0 -21 -5 0 0 0 -5.7 24 0
Story5 C2 24 Comb5 1.33 -21 -5 0 0 0 0.93 24 1.325
Story5 C2 24 Comb5 2.65 -20 -5 0 0 0 7.58 24 2.65
Story4 C2 25 Comb1 0 -83 -0 0 0 0 0.06 25 0
Story4 C2 25 Comb1 1.33 -82 -0 0 0 0 0.12 25 1.325
Story4 C2 25 Comb1 2.65 -81 -0 0 0 0 0.18 25 2.65
Story4 C2 25 Comb2 0 -71 9.52 0 0 0 13 25 0
Story4 C2 25 Comb2 1.33 -70 9.52 0 0 0 0.4 25 1.325
Story4 C2 25 Comb2 2.65 -69 9.52 0 0 0 -12 25 2.65
Story4 C2 25 Comb3 0 -72 -9.6 0 0 0 -13 25 0
Story4 C2 25 Comb3 1.33 -71 -9.6 0 0 0 -0.2 25 1.325
Story4 C2 25 Comb3 2.65 -70 -9.6 0 0 0 12.6 25 2.65
Story4 C2 25 Comb4 0 -41 9.5 0 0 0 13 25 0
Story4 C2 25 Comb4 1.33 -41 9.5 0 0 0 0.37 25 1.325
Story4 C2 25 Comb4 2.65 -40 9.5 0 0 0 -12 25 2.65
Story4 C2 25 Comb5 0 -42 -9.6 0 0 0 -13 25 0
Story4 C2 25 Comb5 1.33 -42 -9.6 0 0 0 -0.2 25 1.325
Story4 C2 25 Comb5 2.65 -41 -9.6 0 0 0 12.5 25 2.65
-
Story3 C2 26 Comb1 0 128 0.12 0 0 0 0.13 26 0
-
Story3 C2 26 Comb1 1.33 127 0.12 0 0 0 -0 26 1.325
-
Story3 C2 26 Comb1 2.65 126 0.12 0 0 0 -0.2 26 2.65
-
Story3 C2 26 Comb2 0 109 12.9 0 0 0 18.9 26 0
-
Story3 C2 26 Comb2 1.33 108 12.9 0 0 0 1.82 26 1.325
-
Story3 C2 26 Comb2 2.65 107 12.9 0 0 0 -15 26 2.65
-
Story3 C2 26 Comb3 0 110 -13 0 0 0 -19 26 0

25
[CONCRETO ARMADO I] ING. CIVIL

-
Story3 C2 26 Comb3 1.33 109 -13 0 0 0 -1.9 26 1.325
-
Story3 C2 26 Comb3 2.65 109 -13 0 0 0 14.9 26 2.65
Story3 C2 26 Comb4 0 -62 12.8 0 0 0 18.8 26 0
Story3 C2 26 Comb4 1.33 -61 12.8 0 0 0 1.82 26 1.325
Story3 C2 26 Comb4 2.65 -61 12.8 0 0 0 -15 26 2.65
Story3 C2 26 Comb5 0 -63 -13 0 0 0 -19 26 0
Story3 C2 26 Comb5 1.33 -63 -13 0 0 0 -1.9 26 1.325
Story3 C2 26 Comb5 2.65 -62 -13 0 0 0 15 26 2.65
-
Story2 C2 27 Comb1 0 173 0.49 0 0 0 0.96 27 0
-
Story2 C2 27 Comb1 1.33 172 0.49 0 0 0 0.32 27 1.325
-
Story2 C2 27 Comb1 2.65 171 0.49 0 0 0 -0.3 27 2.65
-
Story2 C2 27 Comb2 0 147 15.3 0 0 0 23.8 27 0
-
Story2 C2 27 Comb2 1.33 146 15.3 0 0 0 3.48 27 1.325
-
Story2 C2 27 Comb2 2.65 145 15.3 0 0 0 -17 27 2.65
-
Story2 C2 27 Comb3 0 148 -14 0 0 0 -22 27 0
-
Story2 C2 27 Comb3 1.33 148 -14 0 0 0 -2.9 27 1.325
-
Story2 C2 27 Comb3 2.65 147 -14 0 0 0 16.2 27 2.65
Story2 C2 27 Comb4 0 -82 15.1 0 0 0 23.4 27 0
Story2 C2 27 Comb4 1.33 -82 15.1 0 0 0 3.36 27 1.325
Story2 C2 27 Comb4 2.65 -81 15.1 0 0 0 -17 27 2.65
Story2 C2 27 Comb5 0 -84 -15 0 0 0 -23 27 0
Story2 C2 27 Comb5 1.33 -84 -15 0 0 0 -3.1 27 1.325
Story2 C2 27 Comb5 2.65 -83 -15 0 0 0 16.4 27 2.65
-
Story1 C2 28 Comb1 0 219 0.2 0 0 0 0.21 28 0
-
Story1 C2 28 Comb1 1.68 218 0.2 0 0 0 -0.1 28 1.675
-
Story1 C2 28 Comb1 3.35 217 0.2 0 0 0 -0.5 28 3.35
-
Story1 C2 28 Comb2 0 185 17 0 0 0 41.2 28 0
-
Story1 C2 28 Comb2 1.68 184 17 0 0 0 12.6 28 1.675
-
Story1 C2 28 Comb2 3.35 183 17 0 0 0 -16 28 3.35
-
Story1 C2 28 Comb3 0 188 -17 0 0 0 -41 28 0

26
[CONCRETO ARMADO I] ING. CIVIL

-
Story1 C2 28 Comb3 1.68 187 -17 0 0 0 -13 28 1.675
-
Story1 C2 28 Comb3 3.35 186 -17 0 0 0 15.2 28 3.35
-
Story1 C2 28 Comb4 0 103 17 0 0 0 41.1 28 0
-
Story1 C2 28 Comb4 1.68 103 17 0 0 0 12.7 28 1.675
-
Story1 C2 28 Comb4 3.35 102 17 0 0 0 -16 28 3.35
-
Story1 C2 28 Comb5 0 106 -17 0 0 0 -41 28 0
-
Story1 C2 28 Comb5 1.68 105 -17 0 0 0 -13 28 1.675
-
Story1 C2 28 Comb5 3.35 104 -17 0 0 0 15.4 28 3.35

3. DISEÑAR LAS VIGAS UTILIZANDO LA ENVOLVENTE.

c) DISEÑO DE VIGA DEL 1 AL 3 NIVEL

fy 4200
Φ 0.9
f'c 280
d 46
b 30
h 55

 Diseño por flexión:


Del programa Etabs obtenemos los siguientes valores para nuestros momentos(ton.m):

27
[CONCRETO ARMADO I] ING. CIVIL

Luego por medio de nuestras iteraciones hallamos nuestras áreas de acero:

1. Área de acero 1:

a As(cm2)
9.2 19.89
11.70 22.79
13.40 23.28
13.69 23.37
13.75 23.38
13.75 23.38
13.76 23.39
13.76 23.39
2. Área de acero 2:
a As(cm2)
9.2 8.56
5.03 9.05
5.32 9.08
5.34 9.08
5.34 9.08
5.34 9.08
5.34 9.08
3. Área de acero 3:

a As(cm2)
9.2 23.82
14.01 25.29
14.88 25.57
15.04 25.63
15.07 25.64
15.08 25.64
15.08 25.64

4. Área de acero 4:

a As(cm2)
9.2 7.32
4.31 6.91
4.07 6.89
4.05 6.89
4.05 6.89
4.05 6.89
4.05 6.89

28
[CONCRETO ARMADO I] ING. CIVIL

5. Área de acero 5:

a As(cm2)
9.2 23.48
13.81 24.86
14.63 25.12
14.78 25.17
14.81 25.18
14.81 25.19
14.82 25.19
14.82 25.19

6. Área de acero 6:

a As(cm2)
9.2 7.54
4.44 7.13
4.19 7.11
4.18 7.11
4.18 7.11
4.18 7.11
4.18 7.11
4.18 7.11

7. Área de acero 7:

a As(cm2)
9.2 19.19
11.29 19.69
11.58 19.76
11.62 19.77
11.63 19.77
11.63 19.77
11.63 19.77
11.63 19.77

29
[CONCRETO ARMADO I] ING. CIVIL

De las áreas de acero obtenemos lo siguiente:

Asmin(cm2) 4.6
Asmáx(cm2) 29.33

Distribución del acero longitudinal: Φ

 Diseño por cortante:

30
[CONCRETO ARMADO I] ING. CIVIL

Con nuestros datos hallamos:

𝑉𝑐 = 0.53 ∗ √280 ∗ 30 ∗ 46 = 12.24 𝑡𝑜𝑛 𝑉𝑠 ≤ 2.1 ∗ √280 ∗ 30 ∗ 46 = 48.49 𝑡𝑜𝑛


𝑑 𝑑
= 11.5 = 23
Si: 𝑉𝑠 > 25.4 𝑡𝑜𝑛 → 𝑠 { 4 𝑉𝑠 < 25.4 𝑡𝑜𝑛 → 𝑠 { 2
30𝑐𝑚 60𝑐𝑚
Hallamos un valor para Vud para una distancia igual a 0.46 cm:

𝑉𝑢𝑑 = 19.19 = 0.85(12.24 + 𝑉𝑠 ) → 𝑉𝑠 = 10.34 𝑡𝑜𝑛

Luego hallamos s:

𝑠 = 26.53 𝑐𝑚 → 20 𝑐𝑚

Ahora asumimos un s= 20 cm:

2 ∗ 0.71 ∗ 4200 ∗ 46
𝑉𝑠 = = 13.72 𝑡𝑜𝑛
20
𝑉𝑢𝑑 = 0.85(12.24 + 13.72) = 22.07 𝑡𝑜𝑛

𝑙1 = 0.1045 𝑚

Por lo tanto, la distribución de nuestros estribos (2 ramas) es:

1@0.05, 𝑟𝑒𝑠𝑡𝑜 @0.20 𝑐𝑎𝑑𝑎 𝑒𝑥𝑡𝑟𝑒𝑚𝑜

Con nuestros datos hallamos:

𝑉𝑐 = 0.53 ∗ √280 ∗ 30 ∗ 46 = 12.24 𝑡𝑜𝑛 𝑉𝑠 ≤ 2.1 ∗ √280 ∗ 30 ∗ 46 = 48.49 𝑡𝑜𝑛

31
[CONCRETO ARMADO I] ING. CIVIL

𝑑 𝑑
= 11.5 = 23
Si: 𝑉𝑠 > 25.4 𝑡𝑜𝑛 → 𝑠 { 4 𝑉𝑠 < 25.4 𝑡𝑜𝑛 → 𝑠 { 2
30𝑐𝑚 60𝑐𝑚
Hallamos un valor para Vud para una distancia igual a 0.46 cm:

𝑉𝑢𝑑 = 20.40 = 0.85(12.24 + 𝑉𝑠 ) → 𝑉𝑠 = 11.76 𝑡𝑜𝑛

Luego hallamos s:

𝑠 = 23.33 𝑐𝑚 → 20 𝑐𝑚

Ahora asumimos un s= 20 cm:

2 ∗ 0.71 ∗ 4200 ∗ 46
𝑉𝑠 = = 13.72 𝑡𝑜𝑛
20
𝑉𝑢𝑑 = 0.85(12.24 + 13.72) = 22.07 𝑡𝑜𝑛

𝑙1 = 0.1045 𝑚

Por lo tanto, la distribución de nuestros estribos (2 ramas) es:

1@0.05, 𝑟𝑒𝑠𝑡𝑜 @0.20 𝑐𝑎𝑑𝑎 𝑒𝑥𝑡𝑟𝑒𝑚𝑜

Con nuestros datos hallamos:

𝑉𝑐 = 0.53 ∗ √280 ∗ 30 ∗ 46 = 12.24 𝑡𝑜𝑛 𝑉𝑠 ≤ 2.1 ∗ √280 ∗ 30 ∗ 46 = 48.49 𝑡𝑜𝑛


𝑑 𝑑
= 11.5 = 23
Si: 𝑉𝑠 > 25.4 𝑡𝑜𝑛 → 𝑠 { 4 𝑉𝑠 < 25.4 𝑡𝑜𝑛 → 𝑠 { 2
30𝑐𝑚 60𝑐𝑚
Hallamos un valor para Vud para una distancia igual a 0.46 cm:

𝑉𝑢𝑑 = 20.64 = 0.85(12.24 + 𝑉𝑠 ) → 𝑉𝑠 = 12.04 𝑡𝑜𝑛

32
[CONCRETO ARMADO I] ING. CIVIL

Luego hallamos s:

𝑠 = 22.79 𝑐𝑚 → 20 𝑐𝑚

Ahora asumimos un s= 20 cm:

2 ∗ 0.71 ∗ 4200 ∗ 46
𝑉𝑠 = = 13.72 𝑡𝑜𝑛
20
𝑉𝑢𝑑 = 0.85(12.24 + 13.72) = 22.07 𝑡𝑜𝑛

𝑙1 = 0.1045 𝑚

Por lo tanto, la distribución de nuestros estribos (2 ramas) es:

1@0.05, 𝑟𝑒𝑠𝑡𝑜 @0.20 𝑐𝑎𝑑𝑎 𝑒𝑥𝑡𝑟𝑒𝑚𝑜

d) DISEÑO DE VIGA DEL 4 AL 5 NIVEL

33
[CONCRETO ARMADO I] ING. CIVIL

FLEXION:

 Del análisis estructural con el programa ETABS obtenemos los diagramas de


momentos a lo largo de la viga. Tomaremos los momentos de la viga del nivel 4
y este será el mismo diseño para el nivel 5.

−22.561 𝑡𝑜𝑛 𝑚 −25.934 𝑡𝑜𝑛 𝑚 −25.602 𝑡𝑜𝑛 𝑚 −20.934𝑡𝑜𝑛 𝑚

A 12.736 𝑡𝑜𝑛 𝑚 11.674 𝑡𝑜𝑛 𝑚 C 11.214𝑡𝑜𝑛 𝑚 D


B

 Consideraremos 2 capas de refuerzo:

𝑑 = ℎ − 6 = 55 − 6 = 49

 Datos:

h (cm) 55
d (cm) 49
b (cm) 30
f'c (kg/cm2) 280
fy (kg/cm2) 4200
Sabemos que:

𝐴𝑆 × 𝑓𝑦
𝑎=
0.85 × 𝑏 × 𝑓𝑐′

𝑀𝑈
𝐴𝑆 = 𝑎
∅𝑓𝑦 (𝑑 − 2)

0.7√280 14
𝐴𝑆𝑀𝐼𝑁 = max [ (30)(49); (30)(49)] = 4.9 𝑐𝑚2
4200 4200

𝐴𝑆𝑀𝐴𝑋 = 0.75𝜌𝑏

280 6000
𝐴𝑆𝑀𝐴𝑋 = 0.75 × 0.85 × × 0.85 × ( ) × 30 × 49 = 31.238 𝑐𝑚2
4200 6000 + 4200

34
[CONCRETO ARMADO I] ING. CIVIL

Por iteraciones: Extremo A

MU (kg/cm2) 2256100

a (cm) As (cm2)
9.80 13.53
7.96 13.26
7.80 13.23
7.78 13.23
7.78 13.23
3
𝐴𝑆 = 13.23 → 5 ∅ "
4

Tramo medio de AB

MU
1273600
(kg/cm2)

a (cm) As (cm2)
9.80 7.64
4.49 7.21
4.24 7.19
4.23 7.19
4.23 7.19
3
𝐴𝑆 = 7.19 → 3 ∅ "
4

Apoyo B:

MU (kg/cm2) 2593400

a (cm) As (cm2)
9.80 15.56
9.15 15.44
9.08 15.43
9.08 15.43
3
𝐴𝑆 = 15.43 → 6 ∅ "
4

Tramo medio de BC:

MU (kg/cm2) 1167400

a (cm) As (cm2)
9.80 7.00
4.12 6.58
3.87 6.56
3.86 6.56

35
[CONCRETO ARMADO I] ING. CIVIL

3.86 6.56
3
𝐴𝑆 = 6.56 → 3 ∅ "
4

Apoyo C

MU (kg/cm2) 2560200

a (cm) As (cm2)
9.80 15.36
9.03 15.23
8.96 15.21
8.95 15.21
8.95 15.21
3
𝐴𝑆 = 15.21 → 6 ∅ "
4

Tramo medio de CD:

MU (kg/cm2) 1121400

a (cm) As (cm2)
9.80 6.73
3.96 6.31
3.71 6.29
3.70 6.29
3
𝐴𝑆 = 6.29 → 3 ∅ "
4

Apoyo D

MU (kg/cm2) 2093400

a (cm) As (cm2)
9.80 12.56
7.39 12.22
7.19 12.20
7.17 12.20
3
𝐴𝑆 = 12.20 → 5 ∅ "
4

DISTRIBUCION DEL ACERO LONGITUDINAL


3 3
6∅ " 6∅ "
4 4
3
5∅ "→ 3
4 ←5∅ "
4
3
3∅ "
4

36
[CONCRETO ARMADO I] ING. CIVIL

CORTE:

 Del análisis estructural con el programa ETABS obtenemos los diagramas de


fuerza cortante a lo largo de la viga. Tomaremos los cortantes de la viga del nivel
4 y este será el mismo diseño para el nivel 5.

A C D
B

TRAMO AB:

DATOS:

d 49
b 30
f'c 280
fy 4200

Sabemos que el cortante último es:

𝑉𝑈 = ∅(𝑉𝐶 + 𝑉𝑆 )

Además, el aporte del concreto es:

𝑉𝐶 = 0.53√280(30)(49) = 13.037 𝑡𝑜𝑛

37
[CONCRETO ARMADO I] ING. CIVIL

Luego hallamos el cortante ultimo a una distancia d:

𝑉𝑈 = 19.4798 𝑡𝑜𝑛

19.4798 20.3767
=
𝑋 6.4 − 𝑋
𝑋 = 3.128 𝑚

19.4798 𝑉𝑈𝑑
=
3.128 3.128 − 0.49
𝑉𝑈𝑑 = 16.428 𝑡𝑜𝑛

Finalmente hallamos el aporte del acero al cortante:

𝑉𝑈𝑑 = ∅(𝑉𝐶 + 𝑉𝑆 )

16.428 = 0.85(13.037 + 𝑉𝑆 )

𝑉𝑆 = 6.29 𝑡𝑜𝑛

Comparamos contra el aporte de acero máximo.

𝑉𝑆 = 6.29 𝑡𝑜𝑛 ≤ 2.1√280(30)(49) = 51.655 𝑡𝑜𝑛

Además, tenemos que:

𝑉𝑆 = 6.29 𝑡𝑜𝑛 < 1.1√280(30)(49) = 27.058 𝑡𝑜𝑛

𝑑
→ 𝑒𝑠𝑝𝑎𝑐𝑖𝑎𝑚𝑖𝑒𝑛𝑡𝑜 𝑚𝑎𝑥𝑖𝑚𝑜 = = 24.5 𝑐𝑚
2
Luego determinamos nuestro espaciamiento:

𝐴𝑆 × 𝑓𝑦 × 𝑑 2(0.71)(4200)(49)
𝑆= = = 46.46 𝑐𝑚
𝑉𝑆 6.29(103 )

Comparamos con:

38
[CONCRETO ARMADO I] ING. CIVIL

𝑑
𝑒𝑠𝑝𝑎𝑐𝑖𝑎𝑚𝑖𝑒𝑛𝑡𝑜 𝑚𝑎𝑥𝑖𝑚𝑜 = = 24.5 𝑐𝑚
2
𝑆 = 46.46 𝑐𝑚 > 24.5 𝑐𝑚

∴ 𝑆 = 20 𝑐𝑚

Para determinar la distancia hasta donde el espaciamiento será S = 20 cm


deberíamos aumentar el espaciamiento a 25 cm, sin embargo 25 cm > 24.5 𝑐𝑚 por lo
tanto dejaremos S = 20 hasta la mitad de la viga X = 3.2 m.

DISTRIBUCION DE ESTRIBOS:

3
∅ ": 1@0.05; 𝑟𝑒𝑠𝑡𝑜@0.02 𝑐/𝐸𝑥𝑡𝑟𝑒𝑚𝑜
8

TRAMO BC:

DATOS:

d 49
b 30
f'c 280
fy 4200

Sabemos que el cortante último es:

𝑉𝑈 = ∅(𝑉𝐶 + 𝑉𝑆 )

Además, el aporte del concreto es:

𝑉𝐶 = 0.53√280(30)(49) = 13.037 𝑡𝑜𝑛

39
[CONCRETO ARMADO I] ING. CIVIL

Luego hallamos el cortante ultimo a una distancia d:

𝑉𝑈 = 20.275 𝑡𝑜𝑛

20.275 20.1944
=
𝑋 6.5 − 𝑋
𝑋 = 3.25 𝑚

20.275 𝑉𝑈𝑑
=
3.25 3.25 − 0.49
𝑉𝑈𝑑 = 17.22 𝑡𝑜𝑛

Finalmente hallamos el aporte del acero al cortante:

𝑉𝑈𝑑 = ∅(𝑉𝐶 + 𝑉𝑆 )

17.22 = 0.85(13.037 + 𝑉𝑆 )

𝑉𝑆 = 7.22 𝑡𝑜𝑛

Comparamos contra el aporte de acero máximo.

𝑉𝑆 = 7.22 𝑡𝑜𝑛 ≤ 2.1√280(30)(49) = 51.655 𝑡𝑜𝑛

Además, tenemos que:

𝑉𝑆 = 7.22 𝑡𝑜𝑛 < 1.1√280(30)(49) = 27.058 𝑡𝑜𝑛

𝑑
→ 𝑒𝑠𝑝𝑎𝑐𝑖𝑎𝑚𝑖𝑒𝑛𝑡𝑜 𝑚𝑎𝑥𝑖𝑚𝑜 = = 24.5 𝑐𝑚
2
Luego determinamos nuestro espaciamiento:

𝐴𝑆 × 𝑓𝑦 × 𝑑 2(0.71)(4200)(49)
𝑆= = = 40.47 𝑐𝑚
𝑉𝑆 7.22(103 )

Comparamos con:

𝑑
𝑒𝑠𝑝𝑎𝑐𝑖𝑎𝑚𝑖𝑒𝑛𝑡𝑜 𝑚𝑎𝑥𝑖𝑚𝑜 = = 24.5 𝑐𝑚
2

40
[CONCRETO ARMADO I] ING. CIVIL

𝑆 = 40.47 𝑐𝑚 > 24.5 𝑐𝑚

∴ 𝑆 = 20 𝑐𝑚

Para determinar la distancia hasta donde el espaciamiento será S = 20 cm


deberíamos aumentar el espaciamiento a 25 cm, sin embargo 25 cm > 24.5 𝑐𝑚 por lo
tanto dejaremos S = 20 hasta la mitad de la viga X = 3.25 m.

DISTRIBUCION DE ESTRIBOS:

3
∅ ": 1@0.05; 𝑟𝑒𝑠𝑡𝑜@0.02 𝑐/𝐸𝑥𝑡𝑟𝑒𝑚𝑜
8
TRAMO CD:

DATOS:

d 49
b 30
f'c 280
fy 4200

Sabemos que el cortante último es:

𝑉𝑈 = ∅(𝑉𝐶 + 𝑉𝑆 )

Además, el aporte del concreto es:

𝑉𝐶 = 0.53√280(30)(49) = 13.037 𝑡𝑜𝑛

41
[CONCRETO ARMADO I] ING. CIVIL

Luego hallamos el cortante ultimo a una distancia d:

𝑉𝑈 = 19.585 𝑡𝑜𝑛

19.585 18.69
=
𝑋 6−𝑋
𝑋 = 3.07 𝑚

20.275 𝑉𝑈𝑑
=
3 3 − 0.49
𝑉𝑈𝑑 = 16.96 𝑡𝑜𝑛

Finalmente hallamos el aporte del acero al cortante:

𝑉𝑈𝑑 = ∅(𝑉𝐶 + 𝑉𝑆 )

16.96 = 0.85(13.037 + 𝑉𝑆 )

𝑉𝑆 = 6.92 𝑡𝑜𝑛

Comparamos contra el aporte de acero máximo.

𝑉𝑆 = 6.92 𝑡𝑜𝑛 ≤ 2.1√280(30)(49) = 51.655 𝑡𝑜𝑛

Además, tenemos que:

𝑉𝑆 = 6.92 𝑡𝑜𝑛 < 1.1√280(30)(49) = 27.058 𝑡𝑜𝑛

𝑑
→ 𝑒𝑠𝑝𝑎𝑐𝑖𝑎𝑚𝑖𝑒𝑛𝑡𝑜 𝑚𝑎𝑥𝑖𝑚𝑜 = = 24.5 𝑐𝑚
2
Luego determinamos nuestro espaciamiento:

𝐴𝑆 × 𝑓𝑦 × 𝑑 2(0.71)(4200)(49)
𝑆= = = 42.23 𝑐𝑚
𝑉𝑆 6.92(103 )

Comparamos con:

42
[CONCRETO ARMADO I] ING. CIVIL

𝑑
𝑒𝑠𝑝𝑎𝑐𝑖𝑎𝑚𝑖𝑒𝑛𝑡𝑜 𝑚𝑎𝑥𝑖𝑚𝑜 = = 24.5 𝑐𝑚
2
𝑆 = 42.23 𝑐𝑚 > 24.5 𝑐𝑚

∴ 𝑆 = 20 𝑐𝑚

Para determinar la distancia hasta donde el espaciamiento será S = 20 cm


deberíamos aumentar el espaciamiento a 25 cm, sin embargo 25 cm > 24.5 𝑐𝑚 por lo
tanto dejaremos S = 20 hasta la mitad de la viga X = 3 m.

DISTRIBUCION DE ESTRIBOS:

3
∅ ": 1@0.05; 𝑟𝑒𝑠𝑡𝑜@0.02 𝑐/𝐸𝑥𝑡𝑟𝑒𝑚𝑜
8

Diseño de la columna central

Los datos de la columna son:

𝑏 = 0.35 𝑚

𝑡 = 0.55 𝑚

𝑓 ′ 𝑐 = 280𝑘𝑔/𝑐𝑚2

𝑓𝑦 = 4200𝑘𝑔/𝑐𝑚2

El valor de 𝑃𝑈 y 𝑀𝑋 se calcularon utilizando el programa Etabs, y los valores asignados


son los valores máximos que resultaron de la comparación de todas las combinaciones de
carga utilizadas en el programa.

43
[CONCRETO ARMADO I] ING. CIVIL

Por lo que:

𝑀𝑋 = 41.22 𝑡𝑜𝑛 − 𝑚

𝑃𝑈 = 218.91 𝑡𝑜𝑛

Calculamos la cuantía de acero de la columna, apoyándonos en los ábacos

55 − 12
𝑔= = 0.78 ≈ 0.8
55
218.91𝑥103
𝑘= = 0.41
280𝑥35𝑥55
𝑒 41.22𝑥105
𝑘 = = 0.14
𝑡 280𝑥35𝑥552
Empleando el ábaco para 𝑔 = 0.8

44
[CONCRETO ARMADO I] ING. CIVIL

La cuantía de acero es, aproximadamente:

𝜌 = 2.3%

Cálculo del área bruta, área de acero y la carga concéntrica

𝐴𝑔 = 35𝑥55 = 1925 𝑐𝑚2

𝐴𝑠𝑡 = 0.023𝑥1925 = 44.275 𝑐𝑚2


As1 20.27 cm2 d1 6.00 cm
As2 3.96 cm2 d2 20.33 cm
As3 3.96 cm2 d3 34.67 cm
As4 20.27 cm2 d4 49.00 cm

Astotal 48.48 cm2


0.85𝑥280(1925 − 44.275) + 4200(44.275)
𝑃0 = = 633.57 𝑡𝑜𝑛
1000
0.1∅𝑃0 = 0.1𝑥0.7𝑥633.57 = 44.35 𝑡𝑜𝑛

∅𝑃𝑛 = 0.7(0.8𝑥633.57) = 354.80 𝑡𝑜𝑛

Condición

354.80 𝑡𝑜𝑛 > 218.91 𝑡𝑜𝑛


Calculamos las áreas de acero y sus
∅𝑃𝑛 > 𝑃𝑈 distancias de la fibra superior hasta el
centro de la varilla respectiva
Distribuimos el acero en la viga,
obteniéndose:

45
[CONCRETO ARMADO I] ING. CIVIL

Calculamos el centroide plástico

55
0.85𝑥280𝑥35𝑥55𝑥 ( ) + 4200(20.27𝑥6 + 3.96𝑥20.33 + 3.96𝑥34.67 + 20.27𝑥49)
𝑋𝑇 = 2
0.85𝑥280𝑥35𝑥55 + 4200𝑥48,48

𝑋𝑇 = 27.50 𝑐𝑚

Las distancias de los centros de las respectivas varillas al eje plástico son

y1 21.50
y2 7.17
y3 7.17
y4 21.50

Compresión

0.85𝑥280𝑥(1925 − 48.48) + 4200(48.48)


𝑃0 = = 650.23 𝑡𝑜𝑛
1000

𝑃𝑛 = 0.8𝑥650.23 = 520.18 𝑡𝑜𝑛

Tracción

𝑃𝑛 = 4200𝑥48.48𝑥10−3 = 203.62 𝑡𝑜𝑛

Falla balanceada

Cálculo de el 𝐶𝑏

𝑑 = 49 𝑐𝑚

𝐶𝑏 = 28.82 𝑐𝑚

46
[CONCRETO ARMADO I] ING. CIVIL

Cálculo de las fuerzas de compresión y tracción

Es1 2.38E-03 fs1 (kg/cm2) 4200.00 Cs1 (ton) 85.13


Es2 8.84E-04 fs2 (kg/cm2) 1767.35 Cs2 (ton) 7.00
Es3 6.08E-04 fs3 (kg/cm2) 1216.33 Ts3 (ton) 4.82
Es4 2.10E-03 fs4 (kg/cm2) 4200.00 Ts4 (ton) 85.13

Calculamos la fuerza de compresion del concreto

𝐶𝐶 = 0.85𝑥280𝑥35𝑥(0.85𝑥28.82)𝑥10−3 = 204.09 𝑡𝑜𝑛

Restamos las fuerzas de compresión con las de tracción y tomamos momentos respecto
al eje plástico y obtenemos

𝑃𝑛𝑏 = 206.27 𝑡𝑜𝑛

𝑀𝑛𝑏 = 31.28 𝑡𝑜𝑛. 𝑚

Falla frágil

Tomamos un valor de

𝐶 = 35 𝑐𝑚

Calculamos las fuerzas de compresión y tracción

Es1 2.49E-03 fs1 (kg/cm2) 4200.00 Cs1 (ton) 85.13


Es2 1.26E-03 fs2 (kg/cm2) 2514.29 Cs2 (ton) 9.96
Es3 2.86E-05 fs3 (kg/cm2) 57.14 Ts3 (ton) 0.23
Es4 1.20E-03 fs4 (kg/cm2) 2400.00 Ts4 (ton) 48.65

Calculamos la fuerza de compresión del concreto

47
[CONCRETO ARMADO I] ING. CIVIL

𝐶𝐶 = 0.85𝑥280𝑥35𝑥(0.85𝑥20)𝑥10−3 = 247.82 𝑡𝑜𝑛

Restamos las fuerzas de compresión con las de tracción y tomamos momentos con respecto al
eje plástico y obtenemos:

𝑃𝑛𝑏 = 294.49 𝑡𝑜𝑛

𝑀𝑛𝑏 = 39.86 𝑡𝑜𝑛. 𝑚

Falla dúctil

Consideramos:

𝐶 = 20 𝑐𝑚

Calculamos las fuerzas de compresión y tracción

Es1 2.10E-03 fs1 (kg/cm2) 4200 Cs1 (ton) 85.13


Es2 5.00E-05 fs2 (kg/cm2) 100 Cs2 (ton) 0.40
Es3 2.20E-03 fs3 (kg/cm2) 4200 Ts3 (ton) 16.63
Es4 4.35E-03 fs4 (kg/cm2) 4200 Ts4 (ton) 85.13

Calculamos la compresión del concreto

𝐶𝐶 = 0.85𝑥280𝑥35𝑥(0.85𝑥20)𝑥10−3 = 141.61 𝑡𝑜𝑛

Restamos las fuerzas de compresión, menos las de tracción y tomamos momentos respecto al
eje plástico y obtenemos:

𝑃𝑛𝑏 = 124.58 𝑡𝑜𝑛

𝑀𝑛𝑏 = 25.69 𝑡𝑜𝑛. 𝑚

El gráfico del diagrama de interacción sería:

Pn Mn
-203.62 0.00
124.58 25.69
206.27 31.28
294.49 39.86
520.18 0.00

48
[CONCRETO ARMADO I] ING. CIVIL

Diagrama de interacción
600.00

500.00

400.00

300.00

200.00
Pn(Tn)

100.00

0.00
0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00 45.00
-100.00

-200.00

-300.00
Mn(Tn.m)

Comprobación con Etabs

Point P tonf M2 tonf-m M3 tonf-m


1 521.83 0 0.00
2 521.83 0 26.80
3 462.09 0 38.34
4 386.51 0 48.85
5 302.02 0 57.89
6 199.28 0 66.89
7 147.89 0 64.91
8 86.73 0 58.66
9 10.24 0 46.62
10 -96.61 0 24.54
11 -205.75 0 0.00

49
[CONCRETO ARMADO I] ING. CIVIL

Diagrama de interacción
600.00

500.00

400.00

300.00

200.00

100.00

0.00
0.00 10.00 20.00 30.00 40.00 50.00 60.00 70.00 80.00
-100.00

-200.00

-300.00

50