Connections Input Type Setting

This figure is the rear side of KRN100-04000-00-0S. Before setting the parameters, set the jumper pin channel 1/2 of

100mm Hybrid Recorder universal input card (KRN-UI2) depending on input specification
as below figure.

KRN100 SERIES
SOURCE
100-240VAC Ch1 Jumper ③ ② ① Terminal
50/60Hz, 55VA direction

INSTRUCTION MANUAL F.G.

Thank you for choosing our Autonics product.


Please read the following safety considerations before use.
Ch2 Jumper
Safety Considerations
※Please observe all safety considerations for safe and proper product operation to avoid hazards.
Jumper Input
※Safety considerations are categorized as follows. Input break alarm
pin specification
Warning Failure to follow these instructions may result in serious injury or death. ① 0 to 20mA, 4 to 20mA Enables only 4 to 20mA
Caution Failure to follow these instructions may result in personal injury or product damage. ② TC, RTD, ±60mV, ±200mV Enables
※The symbols used on the product and instruction manual represent the following ③ ±2V, 1 to 5V, ±5V, -1 to 10V Disables
Slot Description
symbol represents caution due to special circumstances in which hazards may occur.
1 to 6 Connects universal input card (KRN-UI2).
Warning Connects digital input card (KRN-DI6), alarm output User Manual
7 to 10 card (KRN-AR4, KRN-AT6), transmitter power output For the detail information and instructions, please refer to user
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial card (KRN-24V3). manual and user manual for communication.
economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion Download manuals from the enclosed CD-ROM or our web site
apparatus, safety equipment, crime/disaster prevention devices, etc.) C Connects communication output card (KRN-COM).
(www.autonics.com).
Failure to follow this instruction may result in personal injury, fire, or economic loss.
2. The unit must be installed on a device panel before use.
Failure to follow this instruction may result in electric shock. l/O Card
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock . Universal input card Digital input card Alarm output card
4. Do not disassemble or modify the unit. Please contact us if necessary. [KRN-UI2] [KRN-DI6] [KRN-AR4 (relay output)]
Failure to follow this instruction may result in electric shock or fire.
5.Check the terminal numbers before connecting the power source.
Failure to follow this instruction may result in fire. Inner
Caution -
Alarm Output
1. Do not use the unit outdoors. +
Relay Contact
Failure to follow this instruction may result in shortening the life cycle of the unit, or electric shock.
250VAC 3A 1a
2. Use the unit within the rated specifications.
- RESISTIVE LOAD
Failure to follow this instruction may result in shortening the life cycle of the unit, or fire.
3. Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the unit.
Failure to follow this instruction may result in electric shock or fire. +
4. Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat, vibration, or impact may
be present.
Failure to follow this instruction may result in fire or explosion. ※Each channel is isolated and dielectric
5. Keep dust and wire residue from flowing into the unit. strength is 500V.
Failure to follow this instruction may result in fire or product damage. Alarm output card Transmitter power output card Communication output card
6. Check the polarity of the power contact before wiring the unit. [KRN-AT6 (transistor output)] [KRN-24V3] [KRN-COM]
Failure to follow this instruction may result in fire or explosion.
※Please read “Safety Considerations” in KRN100 user manual before using.
Inner USB 2.0
Specifications Alarm Output (Mini B type)
NPN Open RS485 A(+)
Series KRN100 RS485 B(-)
Collector
Power voltage 100-240VAC 50/60Hz 12-24VDC/ RS485 S.G
30mA Max.
Allowable voltage range 85 to 110% of rated voltage 10/100 Base-T
RESISTIVE
Power consumption Max. 55VA LOAD RJ45(Ethernet)

LCD type STN Graphic LCD


Resolution 320×120 Pixel
Screen ※AL1,2,3 and AL4,5,6 are isolated. ※Each 24V output is isolated individually.
Adjusting brightness 4-level (OFF/Min/Standard/Max)
Backlight White LED, 2-level (Temp/Always)
Input channels 2 / 4 / 6 / 8 / 10 / 12-channel (2-channel/card) Screen Layout And Status Display
Universal input Temperature sensor (RTD, thermocouple), analog (voltage, current)
Screen layout is divided as two; upper screen for status display, lower screen for measuring value display, virtual keyboard display,
1 to 4-channel: 25ms/125ms/250ms, 5 to 12-channel: 125ms/250ms parameter setting display.
Sampling period (inner sampling period is operation unit time for average movement filter and alarm output function.) Upper screen displays recorder status and information of recorder as icon.
※Min. sampling period for TC-R, U, S, T sensor is 50ms.
Recording speed in graph mode 10, 20, 40, 60, 120, 240mm/H
Recording speed accuracy F.S. ±0.5%
Storage cycle 1 to 3600 sec (storage interval time to inner log file is 1 sec)
Inner memory 512MB
USB memory User purchased, recognizes max. 32GB, enables to use cable up to 1.5m
Dielectric voltage 2500VAC 50/60Hz for 1 min (power terminal and case) ※Excepts USB Device and Ethernet
Vibration strength
Vibration strength: 10 to 60Hz 4.9m/s2 (each X, Y, Z axis for 1 hour)
(for convey and storage) and
Operating vibration: 10 to 60Hz 1m/s2 (each X, Y, Z axis for 10 min)
operating vibration
Insulated resistance Min. 20MΩ (at 500VDC megger) Section Icon Name Description
Noise ±2kV the square wave noise (pulse width 1㎲) by the noise simulator
Record start icon Marks if for starting recording measuring value of recordable channels.
Time accuracy Within ±2 min/year (enables to use up to 2100 year)
Enables to normal print with going and returning printing max. 5 times within 7 days after Record stop icon Stops recording measuring value.
Mech- Ink cartridge
opening the unit
anism List record icon Flashes during list recording.
Ink dry time Max. 15 minutes 1
Protection IP40 (for front panel) Reservation record icon Flashes during reservation recording.

Recording paper 113mm×9m FEED icon Flashes during feeding recording paper.
Environ- Ambient temperature 0 to 50℃, storage: -20 to 60℃ (without ink cartridge)
Backup data print icon Flashes during backup data printing.
ment Ambient humidity 35 to 85%RH, storage: 35 to 85%RH
Digital mode icon Marks it for digital record mode.
Approval ,
Weight ※1
Approx. 2.4 to 2.7kg (approx. 1.7 to 2.0kg) Graph mode icon Marks it for graph record mode.
※1: The weight includes packaging. The weight in parentheses is for unit only. 2
※Environment resistance is rated at no freezing or condensation. Record memory status
Marks it storage capacity of record memory in digital mode or graph mode.
icon

Dimensions (unit: mm) No recording paper icon Marks it for no recording paper. Please replace new recording paper.

18.6 137 USB


144 168 Marks icon during Modbus RTU communication using USB.
communication icon
Ethernet communication
3 Marks icon during Modbus TCP communication using Ethernet.
icon
RS485 communication
Marks icon during Modbus RTU communication using RS485.
icon
4 Alarm ON icon Marks channel icon which alarm occurs.
137

Digital input(DI) icon Marks the below icon according to input function setting during digital input (DI).

Digital input(DI)- Marks it when digital memo of digital input or front is input in recording
memo icon status.
Digital input(DI)-
Marks it when alarm reset signal of digital input (DI) is input.
alarm reset icon
※This rear side dimension is with Digital input(DI)-
● Panel cut-out 5 Marks it when start record signal of digital input (DI) is input.
installed I/O cards to every slot. start record icon
Min.175 Digital input(DI)-
Marks it when stop record signal of digital input (DI) is input.
stop record icon
Digital input(DI)-
Marks it when LIST output signal of digital input (DI) is input.
LIST output icon
138 +1.0
0

Digital input(DI)-
Marks it when changing record speed signal of digital input (DI) is input.
record speed icon
Min.175

Unlock icon Marks it for unlock status.


138+1.0
0 User(general user)
6 Marks it for user (general user) lock status.
lock icon
Administrator lock icon Marks it for administrator and general user lock status.
Inner and external (USB)
7 Displays data capacity of internal memory as bar graph.
※Use a steel plate which is 2 to 8mm thickness. memory capacity icon
Displays current date and time. In summer time season, (S) mark is also
※The above specifications are subject to change and some models may be discontinued without notice. 8 Date/Time display
displayed at front of year.
QUICK MENU 2) QUICK MENU Setting
QUICK MENU consists of usually used parameters for quickly parameter setting. ① ② ③

Press the key once in RUN mode and it Set the keys following the each parameter. Press After completing the setting, press the SAVE
enters to QUICK MENU. the NEXT ( ) key and it moves to next page. ( ) key at QUICK MENU[4] and save the
QUICK MENU consists of usually used param- E.g.) When changing the temperature unit (℃→℉)
settings. It returns to RUN mode.
1) Parameters of QUICK MENU eters for quickly parameter setting. of CH1, press the SET ( ) key.
Page Parameter Description Linked parameters
CH Select channel for the QUICK MENU[1] setting. ᆞE.g.) In case of CH1, recording as input type=TC-U, low-limit input value=300, standrad record speed= 240mm/h
TYPE Input type [INPUT SETUP]-[Input Type]
QUICK ① ② ③
DOT Decimal point [INPUT SETUP]-[Range/Scale Point]
MENU [1]
UNIT Display/Temperature unit [INPUT SETUP]-[Display/Temp Unit]
PEN COLOR Pen color [INPUT SETUP]-[Pen Color]
CH Select channel for the QUICK MENU[2] setting.
Low-limit input value or [INPUT SETUP]-[Low Range] or
LOW RANGE
graph scale value [INPUT SETUP]-[Low Graph Scale]
QUICK
High-limit input value or [INPUT SETUP]-[High Range] or Press the key in RUN mode to enter Press the SET ( ) key at QUICK MENU [1] Press the NEXT ( ) key once and it moves
MENU [2] HIGH RANGE
graph scale value [INPUT SETUP]-[High Graph Scale] QUICK MENU. to QUICK MENU [2]. Press the SET ( ) key
and below screen is displayed. Set input type
LOW SCALE Low-limit scale value [INPUT SETUP]-[Low Scale] [TYPE] as TC-U by pressing SET ( )
, using , , , keys to set
HIGH SCALE High-limit scale value [INPUT SETUP]-[High Scale]
keys and press the key. low-limit input range [LOW RANGE] as 300 and
PRINT MODE Record mode [RECORD SETUP]-[Record Mode] press the key.
PRINT SPEED Standard record speed [RECORD SETUP]-[Standard Speed]
QUICK
PRINT MEMO Digital memo period [RECORD SETUP]-[Memo Period] ④ ⑤
MENU [3]
BACK LIGHT LCD backlight [SYSTEM SETUP]-[Backlight]
LCD ON/OFF LCD backlight On/Off [SYSTEM SETUP]-[Backlight On/Off]
[FILE/MEMORY SETUP]-
USB REC Memory save
[USB LogData Save]
[FILE/MEMORY SETUP]-
USB COPY Call USB COPY window
QUICK [USB Memory Copy/Move]
MENU [4] [USER/INFORMATION SETUP]- Press the NEXT ( ) key once and it moves Press the NEXT ( ) key once and it moves
UPGRADE Call upgrade window
[Firmware Upgrade]
to QUICK MENU [3]. Press the SET ( ) key to QUICK MENU [4]. Press the SAVE ( )
CANCEL Cancel the settings
and set standard record speed [PRINT SPEED] key to save the settings of QUICK MENU [1] to
SAVE Save the setting of QUICK MENU[1] to [4]. as 240mm/h. [4] and it returns to RUN mode.
※Refer to “KRN100 user manual”.

Parameters
RUN mode

3 sec ※Dot parameters may or may not appear, depending on the other parameter setting.

DIGITAL INPUT COMMUNICATION FILE/MEMORY USER/INFORMATION RECORD BACKUP


INPUT SETUP ALARM SETUP RECORD SETUP SYSTEM SETUP
SETUP SETUP SETUP SETUP DATA
(input setting) (alarm setting) (record setting) (system setting)
(digital input setting) (com. setting) (file/memory setting) (user/info. setting) (backup data record setting)

Select UI Card Select UI Channel Select DI Card Load Set File Record Backup
Modbus Address Record Mode Device Name Password
(universal input card (universal input (digital input card (parameter setting (backup data
(com. address) (record mode) (device name) (password mode)
select ) select) select ) file open) record)
Input Set Copy Alarm Set Copy DI- Type Digital Print type Save Set File
RS485 Port Date/Time Login Admin Backup Data List
(input parameter (copy alarm (digital input (1 line record CH during (parameter setting
(RS485 com. use) (date/time) (admin. log in) (backup data list)
copy) parameter) select) numeric recording) file save)
LCD/Paper Record Alarm type Standard Speed Change Admin
DI- Reset No Baud Rate Date Type Memory Status Start Date and Time
(display and record (alarm operation (standard record Password
(reset alarm number) (com. speed) (date type) (memory capacity) (start time for data save)
measuring value) mode) speed) (password change by admin.)

Alarm Ref Channel Option Speed User Lock


Pen Color DI- Status Parity Bit Summer Time Memory Clear End Date and Time
(alarm reference (option record (user authority
(record color) (operation status) (com. parity bit) (summer time) (memory delete) (end time for data save)
channel) speed) change)
Backup Print Mode
Record Zone Alarm Option Stop Bit Memo Period Summer Time Period USB LogData Save Information
(backup data print
(record zone) (alarm option) (com. stop bit) (digital memo cycle) (summer time period) (USB save function) (system info. check)
mode)
Termination Set Divide Zone Memory Save Option Selection Print Mode
Tag Name Alarm Value Reservation Type Firmware Upgrade
(terminating (record zone (memory save (backup data recording
(channel name) (alarm SV) (reservation record) (firmware upgrade)
resistance) division) option) mode setting)
Input Type Response Wait Time Standard Period Reservation Period USB Memory
Alarm Hysteresis
(input (com. response (standard record (reservation record Copy/Move
(alarm hysteresis)
specifications) waiting time) cycle) period) (data move/copy)
OK, Alarm ON/OFF Delay Option Period Reservation Time
Range/Scale Point Protocol
Cancel (alarm output ON/ (option record (reservation record
(decimal point) (com. protocol)
OFF delay time) cycle) time)
Alarm Alarm No Listing Language
Display/Temp Unit RS485 Com/Write Alarm Sound
(alarm output (language for list
(display/temp. unit) (RS485 com. write) (alarm sound)
alarm number) printing)
High/Low Range Selection Alarm Card Alarm Speed
& Graph Scale Ethernet Port Sampling Rate
(Alarm output card (alarm record
(high/low input value (Ethernet com. use) (sampling period)
and graph scale) select) speed)
Low Scale/ Alarm- Status Power On Status
IP Address Log Speed
High Scale (relay and transistor (record status when
(IP address) (save cycle)
(high/low scale value) output method power ON)
Run Status Backlight
Special Func Subnet Mask
(list printing at start (LCD backlight
(special function) (subnet mask)
recording) brightness)
Two Unit Baklight On/Off
Default Gateway List Out Option
(display vacuum, (LCD backlight ON
(default gateway) (list record option)
static pressure) method)
Ethernet Com Write Zone Dot Line Distance
Ref Channel
(Ethernet com. (dot line for zone
(reference channel)
write) division)
CH Print Distance
Input Bias USB Device Port
(record interval for
(error correction) (USB com. use )
each channel graph
Start Line Print
Span USB Com Write
(start line when
(gradient adjustment) (USB com. write)
starting record)
Range Print Time
Record Method
(input range record
(data storage method)
period)

Filter Type
(input digital filter)

Filter Counter
(number of digital
filters)
Burnout Action
(display setting for
break)

Operation Start/Stop Major Products


Trend graph recording Photoelectric Sensors Temperature Controllers Recorders Thyristor Units
Screen Fiber Optic Sensors Temperature/Humidity Transducers Indicators Pressure Transmitters
→ Bar graph
display Door Sensors SSRs/Power Controllers Converters Temperature Transmitters
→ Digital number
Parameter Door Side Sensors Counters Controllers
setting Area Sensors Timers
information Special
Proximity Sensors Panel Meters
3 sec output Pressure Sensors Tachometer/Pulse(Rate) Meters
QUICK function for http://www.autonics.com
Rotary Encoders Display Units
Usually used MENU RUN mode record
Trusted Partner In Industrial Automation
Connectors/Sockets Sensor Controllers
parameters of Manual feed Switching Mode Power Supplies
parameter setting group (when stop HEADQUARTERS:
Control Switches/Lamps/Buzzers 18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,
are reorganize as recording) I/O Terminal Blocks & Cables South Korea, 48002
QUICK MENU. 3 sec OVERSEAS SALES:
Stepper Motors/Drivers/Motion Controllers
Each parameter setting Parameter #402-303, Bucheon Techno Park, 655, Pyeongcheon-ro,
Graphic/Logic Panels Wonmi-gu, Bucheon, Gyeonggi-do, South Korea, 14502
is linked. setting Digital memo Field Network Devices TEL: 82-32-610-2730 / FAX: 82-32-329-0728
group 3 sec Laser Marking System(Fiber, CO₂, Nd:YAG) E-mail: sales@autonics.com
3 sec Laser Welding/Cutting System
AEP-E-0121B

Potrebbero piacerti anche