Micrologic
Control units
5.0 H, 6.0 H and 7.0 H
User manual
01/2009
Micrologic control units Contents
5.0 H, 6.0 H and 7.0 H
Discovering Micrologic H 4
Identification 4
Presentation 5
Setting procedure 6
Setting Micrologic 5.0 H using the dials 8
Setting Micrologic 6.0 H using the dials 9
Setting Micrologic 7.0 H using the dials 10
Selecting the type of neutral protection 11
Main menus 12
Metering 14
History, maintenance and setup 18
Protection 20
Overview of functions 22
Current protection 22
Voltage protection 28
Other protection 29
Load shedding and reconnection 30
Measurements 31
Harmonic measurements 33
Alarms 44
Optional M2C and M6C contacts 45
Event histories 46
Leds and display screens 47
COM communications option 49
Setup 50
Setting up the optional M2C / M6C contacts 50
Setting up the Micrologic control unit 52
Setting up the metering functions 55
Setting up the COM communications option 58
Protection settings 60
Fine adjustment of the long-time I2t, short-time and
instantaneous settings using the keypad 60
Fine adjustment of the long-time Idmtl, short-time and
instantaneous settings using the keypad 61
Fine adjustment of the ground-fault and earth-leakage
protection setting using the keypad 62
Setting the neutral protection 63
Setting the I t , I unbal, I max, U min, U max, U unbal, rP max,
F min, F max, and phase-rotation protection functions
using the keypad 64
Setting load shedding / reconnection 66
Metering 68
Current measurements 68
Voltage measurements 71
Power measurements 73
Energy measurements 75
Harmonic measurements 76
Frequency measurements 82
Maintenance 84
Resetting fault indications 84
Viewing the event histories 85
Operation counter and contact-wear indicator 86
Checking/replacing the battery 87
Tests 88
04443728AA - 01/2009
Micrologic control units Contents
5.0 H, 6.0 H and 7.0 H
Technical appendix 90
Tripping curves 90
Voltage measurements 92
Zone selective interlocking (ZSI) 94
Power supply 95
Changing the long-time rating plug 97
Thermal memory 98
Data available via the COM communications option 99
Threshold and time-delay settings 101
Other settings 104
Measurement setting ranges and accuracy 105
Power factor sign conventions 106
Index 108
04443728AA - 01/2009
04443728AA - 01/2009
Discovering Micrologic H Identification
E71927A
DB119909
Micrologic 5.0 H
connected loads.
They offer current, voltage, frequency, power and 4260A Idmtl
N 1 2 3
energy measurements. 100
0 Ir Isd Ii I
Selective protection + Idmtl
long time
Ir .8 tr 8
alarm
.7 .9 (s) 4 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In @ 6 Ir
Micrologic 5.0 H
E71926A
Micrologic 6.0 H
Selective protection + Idmtl + ground-fault protection,
power measurements and additional protection
X t t
E71928A
DB119909
DB119911
Micrologic 6.0 H
Idmtl
Y
4260A
2
N 1 2 3 I t on
100
Z
2
50 I t off
0
Y: version number
Identification of the control-unit generation:
"0" signifies the first generation.
Micrologic 7.0 H
Selective protection + Idmtl + earth-leakage protection,
Z: type of measurement power measurements and additional protection
b A for "ammeter"
t
E71929A
DB119913
DB119909
50
0 Ir Isd Ii I 0 I∆n I
Ir
.6
long time
.7
.8
.9
tr
(s) 4
.95 2
8
12
16
alarm
Selective protection Earth-leakage protection
+ Idmtl
.5 .98 1 20
.4 1 .5 24
x In @ 6 Ir
earth leakage
04443728AA - 01/2009
Discovering Micrologic H Presentation
1 top fastener
E60235B
E60236A
1
2 terminal block for external connections
3 housing for battery 2
4 screw for long-time rating plug 5.0P
logic
5 long-time rating plug Micro
alarm
time 8 12
Indications
long tr
(s) 4 16
Ir .8 .9
.7 2 20
.95
1 24
.6 .98 .5 6 Ir
.5 1 at
.4 x In
8
12 LED indicating long-time tripping 4
13 LED indicating short-time or instantaneous tripping
14 LED indicating ground-fault or earth-leakage 7 5
tripping 10
6
15 LED indicating additional-protection or 11
auto-protection tripping
16 graphics display
E71930A
E60238A
17 button for reset of fault-trip LED reset Micrologic 5.0 H 18 19 20
and battery test 12 17
13
Navigation 14
15 4260A
18 access button to the "Metering" menu (1)
N 1 2 3
19 access button to the "History, maintenance 16
and setup" menu (1) 21 22 23
100
20 access button to the "Protection" menu (1)
21 button used to scroll down or reduce
the displayed value 50
22 button used to scroll up or increase
the displayed value
23 button used to select or confirm a choice 0
Adjustment dials Micrologic 5.0 H control unit Micrologic 6.0 H control unit
E60239A
E60240A
earth-leakage protection
35 test connector
long time
Ir .8 tr
(s) 4
8
alarm 33
.7 .9 12
.6 .95 2 16
24 .5 .98 1 20
.4 1 .5 24
x In @ 6 Ir
25 short time instantaneous
Isd tsd Ii
3
4
5 (s) .4 .4 .3 6 8 10
2.5 6 .3 .2 4 12
26 2 8 .2 .1 3 15
28
1.5 10 .1 2 0 2 off
27 x Ir on I t off x In
I∆n
setting
∆t
delay
test 34
(A) 5 (ms)
3 7 230 350
2 10
31 1 20
140
35
.5 30 60 800
32 earth leakage
04443728AA - 01/2009
Discovering Micrologic H Setting procedure
DB119915
DB119914
thresholds and tripping delays for overloads, short-
circuits, ground faults and earth leakage. 5.0
Buttons b Open the protective b Make the necessary settings using the dials
b Buttons on the keypad are used for fine adjustments cover. b The screen automatically displays the relevant curve
of the protection thresholds and tripping delays for b Check the set value on the screen, in absolute value
overloads, short-circuits, ground faults and earth in amperes (A) and in seconds (s).
leakage. The value previously set using a dial
automatically becomes the maximum value for the
keypad settings.
Settings using the keypad
b They may also be used to activate other factory-
disabled protection functions available on Micrologic H. b The and buttons under the screen may be
E60252B
These other protection functions are not accessible via used for fine adjustments of the settings made using
the dials. the dials. Micro
logic
5.0
b All the settings not available via the dials are made in
the same manner, using the keypad.
Caution!
With the protective cover open, make all the necessary A new overload (long-time) or short-circuit
settings for your control unit. (short-time and instantaneous) protection setting
made using one of the dials:
All fine adjustments are permanently stored in memory, b deletes all the fine adjustments previously
unless the setting is modified using the adjustment dial. made using the keypad for the overload
(long-time) and short-circuit (short-time and
For remote settings using the communications option, instantaneous) protection
see the "Remote settings" section in the "Com setup" b does not affect the fine adjustments made
menu under "History, maintenance and setup". using the keypad for ground-fault and earth-
leakage protection
b does not affect any other settings made using
the keypad.
04443728AA - 01/2009
Discovering Micrologic H Setting procedure
With the protective cover closed, it is not possible to set View the settings and measurements
the protection functions. However, it is possible to set
DB119916
E60254B
metering functions and alarms, as well as view all
measurements, settings and histories. 5.0
logic logic
5.0
Micro Micro
Caution!
DB119917
04443728AA - 01/2009
Discovering Micrologic H Setting Micrologic 5.0 H
using the dials
DB119919
long time
Ir .8
DB119918
.6
.7 .9
.95
Ir = 0.5 x 2000 = 1000 A
.5 .98
.4 1
Isd = 2 x 1000 = 2000 A
x In
short time instantaneous Ii = 2 x 2000 = 4000 A
Isd Ii
3
4
5 6 8 10
2.5 6 4 12
2 8 3 15
1.5 10 2 off
x Ir x In
1 setting
In 2000 A
A
2000
In =
See pages 22 and 24 for selection of the setting Set the time delays
ranges.
tr = 1 s
DB119910
long time
tr 8
(s) 4 12
2 16
1 20
.5 24
tsd = 0.2 s
@ 6 Ir
short time
tsd
(s) .4 .4 .3
.3 .2
.2 .1
.1 2 0
on I t off
delay
DB119921
DB119922
DB119923
Ir Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
04443728AA - 01/2009
Discovering Micrologic H Setting Micrologic 6.0 H
using the dials
DB119924
long time
Ir .8
DB119918
.7 .9
.6 .95
.5 .98 Ir = 0.5 x 2000 = 1000 A
.4 1
x In
Isd
short time
Ii
instantaneous
Isd = 2 x 1000 = 2000 A
3
4
5 6 8 10
2.5 6 4 12
2 8 3
1.5 10 2
15
off
Ii = 2 x 2000 = 4000 A
x Ir x In
1 setting
Ig
E
B Ig = 640 A
D F
C G
In 2000 A B H
2000
A
A J
In =
ground fault
long time tr = 1 s
tr 8
(s) 4 12
2 16
1 20
.5 24
@ 6 Ir
short time
tsd
tsd = 0.2 s
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
delay tg = 0.2 s
tg
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
ground fault
DB119921
DB119922
DB119923
Ir Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
t t t t
DB119926
DB119927
DB119929
DB119928
Ig Ig
tg tg
0 I 0 I 0 I 0 I
Ig: ground-fault pickup tg: ground-fault tripping delay
04443728AA - 01/2009
Discovering Micrologic H Setting Micrologic 7.0 H
using the dials
DB119930
long time
Ir .8
DB119918
.7 .9
.6 .95
.5 .98 Ir = 0.5 x 2000 = 1000 A
.4 1
x In
Isd
short time
Ii
instantaneous
Isd = 2 x 1000 = 2000 A
3
4
5 6 8 10
2.5 6 4 12
2 8 3
1.5 10 2
15
off
Ii = 2 x 2000 = 4000 A
x Ir x In
1 setting
I∆n
(A) 5
I∆n = 1 A
3 7
2 10
1 20
In 2000 A .5 30
A
2000
In =
earth leakage
See pages 22 to 26 for selection of the setting ranges. Set the time delays
tr = 1 s
DB119931
long time
tr 8
(s) 4 12
2 16
1 20
.5 24
@ 6 Ir
tsd = 0.2 s
E60153A
short time
tsd
(s) .4 .4 .3
.3 .2
.2 .1
.1 2
0
on I t off
delay ∆t = 140 ms
∆t
(ms)
230 350
140
60 800
earth leakage
t t t
DB119921
DB119923
DB119922
Ir Ir
tr tr
Isd Isd
tsd tsd
Ii Ii
0 I 0 I 0 I 0 I
Ir: LT threshold tr: LT tripping delay
Isd: ST pickup tsd: ST tripping delay
Ii: Instantaneous pickup
t t
DB119932
DB119933
I∆n
∆t
0 I 0 I
I∆n: earth-leakage pickup ∆t: earth-leakage tripping
delay
10 04443728AA - 01/2009
Discovering Micrologic H Selecting the type of neutral
protection
On four-pole circuit breakers, it is possible to select the type of neutral protection for
3D+N/2 the fourth pole using the three-position dial on the circuit breaker:
4P 4D
b no neutral protection 4P 3D
4P 3D
b half neutral protection 3D + N/2
b full neutral protection 4P 4D
Caution!
With the 4P 3D setting, the current in the neutral must
not exceed the rated current of the circuit breaker.
04443728AA - 01/2009 11
Discovering Micrologic H Main menus
The Micrologic H control unit offers access to the main screen and three menus:
b the main screen displaying the continuous measurement of the phase currents (I1,
I2, I3) and the neutral current (IN), if it exists
b the "Metering" menu
b the "History, maintenance and setup" menu
b the "Protection" menu.
Main screen
As long as no functions are activated, Micrologic H
E60101A
4260A control units display in real time the current on the most
heavily loaded phase.
The number for that phase is presented in a square.
1 2 3
The current in the neutral is displayed if the neutral CT
is set as internal or external (see "Ineutral (A)" settings
100 in the "Current protection" menu).
50
When a menu button is pressed, a presentation screen "Metering", "History, maintenance and setup"
is displayed and the green LED on the button goes ON.
and "Protection" menus
b "Metering" menu
I (A) screen
U
screen
(V) v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
P (kW)
few minutes
v the LED goes OFF on exiting the menu.
E (kWh)
Harmonic
armoniq.
12 04443728AA - 01/2009
Discovering Micrologic H Main menus
E71711A
Event screen
history
v press the button to return to the previous
Contacts screen
M2C / M6C v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
Micrologic few minutes
setup v the LED goes OFF on exiting the menu.
Metering
setup
Com.
setup
b "Protection" menu
Current screen
protection
v press the button to return to the previous
Voltage screen
protection v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
Other few minutes
protection v the LED goes OFF on exiting the menu.
Load
shedding I
Load
shedding P
b Saving settings
When a setting is made in any of the three menus, the
E71657A
no
yes
04443728AA - 01/2009 13
Discovering Micrologic H Metering
Current measurements
access to the following sections:
E71932B
I (A) I (A)
U (V) Instant.
P (kW)
I1, I2, I3, IN
I1, I2, I3, IN currents
(depending on the type of
system)
E (kWh) Storing and reset of the
Max maximum instantaneous
Harmonic currents
Demand
Voltage measurements
E71933B
I (A)
U (V)
access to the following sections:
Phase sequence.
Phase
rotation
14 04443728AA - 01/2009
Discovering Micrologic H Metering
Power measurements
E71934B
Power factor PF
Power
Harmonic factor
Demand
Energy measurements
E71935B
I (A)
E (kWh)
access to the following sections:
P (kW)
Total apparent energy E.S
04443728AA - 01/2009 15
Discovering Micrologic H Metering
Harmonic measurements
E71936B
I (A)
Harmonic
U (V) access to the following sections:
Waveform
P (kW)
Waveform capture
I1, 2, 3
E
for currents I1, I2 and I3
(kWh)
Waveform capture
Harmonic IN for the neutral current IN
Fundament.
Measurement of
I (A) the fundamental of currents
I1, I2, I3 and IN
Measurement of
U (V) the fundamental of voltages
U12, U23 and U31
and V1N, V2N and V3N
Measurement of
P (W) the fundamental of active
power P, reactive power Q
and apparent power S.
THD
Total harmonic distortion
I (%) of currents I1, I2, I3 and IN
thd
Total harmonic distortion
I (%) of currents I1, I2, I3 and IN
FFT
Amplitude spectrum of odd
I (3, 5, 7,..., 31) current harmonics
up to H31
16 04443728AA - 01/2009
Discovering Micrologic H Metering
Frequency measurement
E71937B
E (kWh)
Harmonic
F (Hz)
04443728AA - 01/2009 17
Discovering Micrologic H History, maintenance
and setup
Press the button to select the "History, maintenance and setup" menu.
Event history
E71711A
18 04443728AA - 01/2009
Discovering Micrologic H History, maintenance
and setup
Micrologic setup
E71714A
Metering setup
E71715A
04443728AA - 01/2009 19
Discovering Micrologic H Protection
Current protection
E71712A
protection
Fine settings of the long-time Idmtl,
Load
shedding I Idmtl (A) short-time and instantaneous protection functions
20 04443728AA - 01/2009
Discovering Micrologic H Protection
Voltage protection
E71719A
Other protection
E71720A
Current
protection
Load shedding depending on current
Voltage Access to load shedding and reconnection
protection Load
Other
shedding I depending on current
protection
Load
shedding I
Load
shedding P
04443728AA - 01/2009 21
Overview of functions Current protection
I2t long-time protection
For the default values, the setting ranges, increment The long-time protection function protects cables against overloads. This function is
steps and setting accuracies, see the technical based on true rms measurements.
appendix. It is possible to select either I2t long-time protection or Idmtl long-time protection.
Thermal memory
b The thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of an
overload or not). The thermal memory optimises the long-time protection function of
the circuit breaker by taking into account the temperature rise in the cables.
b The thermal memory assumes a cable cooling time of approximately 15 minutes.
22 04443728AA - 01/2009
Overview of functions Current protection
Idmtl long-time protection
Idmtl Protection
Long-time current setting Ir and Idmtl tripping delay tr
Micrologic control unit Accuracy 5.0 H, 6.0 H and 7.0 H
Current setting Ir = In (*) x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
tripping between 1.05 and 1.20 Ir other ranges or disable by changing rating plug
04443728AA - 01/2009 23
Overview of functions Current protection
Short-time and instantaneous protection
For the default values, the setting ranges, increment Short-time protection
steps and setting accuracies, see the technical b The short-time protection function protects the distribution system against
appendix. impedant short-circuits
b The short-time tripping delay and the I2t ON and I2t OFF options can be used to
ensure discrimination with a downstream circuit breaker
b This function carries out true rms measurements.
b Intermittent faults are taken into account by Micrologic H and may lead to shorter
tripping times than those set.
If the "without long-time protection" plug is used and the long-time protection function
is disabled, the short-time pickup Isd is automatically multiplied by In instead of Ir as
is the standard case.
Instantaneous protection
b The instantaneous-protection function protects the distribution system against
solid short-circuits. Contrary to the short-time protection function, the tripping delay
for instantaneous protection is not adjustable. The tripping order is sent to the circuit
breaker as soon as current exceeds the set value, with a fixed time delay of 20
milliseconds.
b This function carries out true rms measurements.
Instantaneous pickup Ii
24 04443728AA - 01/2009
Overview of functions Current protection
Neutral protection
For the default values, the setting ranges, increment Three-pole circuit breakers
steps and setting accuracies, see the technical Protection of the neutral is possible on a three-pole circuit breaker by connecting an
appendix. external sensor.
Settings are made using the and buttons on the control unit.
The and buttons on the control unit may then be used for a more precise
setting. The dial setting constitutes the upper limit for adjustments using the keypad.
Micrologic control unit 5.0 H, 6.0 H and 7.0 H
Setting OFF N/2 N
04443728AA - 01/2009 25
Overview of functions Current protection
Ground-fault and earth-leakage
protection
For the default values, the setting ranges, increment Ground-fault protection on Micrologic 6.0 H
steps and setting accuracies, see the technical b An ground fault in the protection conductors can provoke local temperature rise at
appendix. the site of the fault or in the conductors. The purpose of the ground-fault protection
function is to eliminate this type of fault.
b There are two types of ground-fault protection.
Type Description
Residual b The function determines the zero-phase sequence current, i.
e. the vector sum of the phase and neutral currents (depending
on the type of installation)
Source Ground Return b Using a special external sensor, this function directly
measures the fault current returning to the transformer via the
earth cable
b It detects faults both upstream and downstream of the circuit
breaker
b The maximum distance between the sensor and the circuit
breaker is ten metres.
26 04443728AA - 01/2009
Overview of functions Current protection
I t Alarm, current unbalance, maximum
current
For the pickup and dropout thresholds and time delays, Operating principle
see the technical appendix. protection tripped by a maximum value
DB119995
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
I t Alarm
b The alarm function is tripped by the rms value of an earth-leakage current
b This alarm signals an earth-leakage current under the pickup value and does not
produce circuit-breaker tripping.
I b From:
DB119996
E max
v I avg is the average value of the rms currents of the
I avg three phases
I avg = I1 + I2 + I3
3
v E max is the maximum difference between the
0 I1 I2 I3
current of each phase and I avg
b Micrologic H uses the two values above to calculate
the current unbalance:
E max
I unbal =
I avg
Note:
IN max protection does not take into account the neutral-protection setting (N, N/2, 1.6 x N, OFF).
04443728AA - 01/2009 27
Overview of functions Voltage protection
Minimum voltage, maximum voltage,
voltage unbalance
For the pickup and dropout thresholds and time delays, Operating principle
see the technical appendix. protection tripped protection tripped
by a minimum value by a maximum value
t t
DB119946
DB119997
1 3
3 1
2 4
4 2
0 U min 0 U max
U unbal.
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
If the voltage protection functions are activated and the Minimum-voltage protection U min
voltage measurement inputs are still energised, it is b This function calculates the minimum rms value of the three phase-to-phase
impossible to reset and close the circuit breaker. voltages
b Protection is activated when at least one of the three phase-to-phase voltages
(U12, U23, U31) is below the threshold set by the user
b This protection function does not detect phase failure.
28 04443728AA - 01/2009
Overview of functions Other protection
Reverse power, min. frequency,
max. frequency, phase rotation
For the pickup and dropout thresholds and time delays, Operating principle
see the technical appendix. protection tripped protection tripped
by a minimum value by a maximum value
t t
DB119949
DB119950
1 3
3 1
2 4
4 2
0 F min 0 F max
rP max
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
Note:
the direction of flow is set by the user in the "Power sign" section of the "Micrologic setup" menu
under "History, maintenance and settings".
b + corresponds to the normal direction of flow, i.e. from the top terminals on the circuit breaker
to the bottom terminals
b - is the opposite.
If the voltage protection functions are activated and the Minimum and maximum-frequency protection
voltage measurement inputs are still energised, it is
impossible to reset and close the circuit breaker. F min. and F max
These functions monitor the value of the frequency on the distribution system.
Phase-rotation alarm
This alarm is activated if two of the three phases are inverted.
Note:
the alarm is activated following a fixed 300-millisecond time delay. If one of the phases is absent,
the alarm will not operate. If the 400 Hz frequency is set, the alarm cannot be activated.
04443728AA - 01/2009 29
Overview of functions Load shedding
and reconnection
For the pickup and dropout thresholds and time delays, Load shedding and reconnection depending on current
see the technical appendix. The pickup curve for load shedding and reconnection depending on current is
parallel to the LT I2t and Idmtl curves. If a "without long-time protection" rating plug is
installed, the load shedding/reconnection function based on current cannot be
activated.
b I2t protection: the neutral is taken into account
b Idmtl: the neutral is not taken into account.
This function does not trip the circuit breaker, but can be used to set off an alarm
linked to an M2C or M6C contact (disconnection and reconnection of non-priority
loads).
The load-shedding and reconnection function is determined by thresholds and time
delays.
DB119999 t
Long-time
protection
curve
3
1
4
0 I
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
3
1
4
2
0 P
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
30 04443728AA - 01/2009
Overview of functions Measurements
Current and voltage
Demand current
b Display of the demand current on phases I1, I2, I3 and the neutral IN (depending
on the type of distribution system)
b Selection of the demand calculation method
b Display of the interval over which the value is calculated
b The maximum demand values are displayed and stored in memory
b The stored maximums can be reset at any time.
Note:
the calculation method, the type of calculation window (fixed or sliding) and its duration may be
set in the "Metering setup" menu under "History, maintenance and setup".
Average voltage
Average Uavg of the instantaneous voltages between phases U12, U23 and U31.
Phase rotation
Displays the phase sequence.
Voltage unbalance
Display of the unbalance Uunbal between the three phase-to-phase voltages,
displayed as a percentage.
U b From:
To display the phase-to-neutral voltages, select the "3Φ
DB119998
4w 4CT" option in "System type" in the "Metering E max v U avg is the average value of the rms voltages of the
U avg
setup" menu under "History, maintenance and setup". three phases
04443728AA - 01/2009 31
Overview of functions Measurements
Power, energy and frequency
For the setting ranges and measurement accuracies, Instantaneous power and power factor
see the technical appendix. Micrologic H offers a number of different measurements.
b Total power measurements:
v instantaneous active power P in kW
v instantaneous reactive power Q in kvar
v instantaneous apparent power S in kVA
b Measurement of the power factor PF.
Demand power
b Display of the demand values for the active power P, reactive power Q and
apparent power S
b Selection of the demand calculation method
b Display of the interval over which the value is calculated
b The maximum demand values are displayed and stored in memory
b The stored maximums can be reset at at any time.
Note:
b the calculation method, the type of calculation window (fixed or sliding) and its duration may
be set in the "Metering setup" menu under "History, maintenance and setup".
b the synchronisation function (Synchro.Com) is available only with the COM communication
option; with this function, the demand power is determined on the basis of a signal synchronised
by the communication module.
b these settings apply to all demand powers (active power P, reactive power Q and apparent
power S). If the settings are modified, the demand values are systematically recalculated.
Energy
Micrologic H offers a number of different measurements:
b total energy:
v total active energy E.P in kWh
v total reactive energy E.Q in kvarh
v total apparent energy E.S in kVAh
b energy consumed (Energy in), positively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
b energy supplied (Energy out), negatively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
b energy values can be reset.
Note:
b the Energy in and Energy out values are incremented according to the power sign set in the
"Metering setup" menu under "History, maintenance and setup".
b as standard, the total calculated energy values are "absolute total values".
They represent the sum of the energy in and out values:
v EP = Σ EP in + Σ EP out
v EQ = Σ EQ in + Σ EQ out
b as an option (access exclusively via the COM communications option), energy can be
calculated algebraically:
v EP = Σ EP in - Σ EP out
v EQ = Σ EQ in - Σ EQ out
These values are called "signed" energies.
Frequency
The frequency of the distribution system is displayed in Hz.
32 04443728AA - 01/2009
Overview of functions Harmonic measurements
Origin and effects
Definition of harmonics
A periodic signal is a combination of:
v the original sinusoidal signal at the fundamental frequency
v other sinusoidal signals (the harmonics) with frequencies that are whole-number
multiples of the fundamental frequency
v a DC component, where applicable.
Any periodic signal can therefore be represented as the sum of a number of terms:
∞
y(t) = Yo + Σ Yn 2 sin(nωt - ϕn)
n=1
where:
DB120067
I peak
b Yo is the value of the DC component (generally equal to zero and considered as
Total I rms such hereinafter)
b Yn is the rms value of the nth harmonic
b ω is the angular frequency of the fundamental
Fundamental
50 Hz I1 b ϕn is the phase displacement of the harmonic component at t = 0.
Harmonic
5 (250 Hz)
I5 For example, the current and voltage waveforms distributed on the European
electrical power grid have the following characteristics:
I7
Harmonic
7 (350 Hz)
b the fundamental frequency is 50 hertz (Hz)
Harmonic I9 b the 2nd harmonic has a frequency of 100 Hz
9 (450 Hz)
b the 3rd harmonic has a frequency of 150 Hz
b the 4th harmonic has a frequency of 200 Hz
b…
04443728AA - 01/2009 33
Overview of functions Harmonic measurements
Origin and effects
Standby generator
Origin of harmonics
DB120068
Power-factor
Inb Variable-speed A load is said to be non-linear when the current that it draws does not have the
drives
correction same waveform as the voltage. Typical examples of non-linear loads are those using
power electronics. Such loads are increasingly numerous and their share in overall
Ind
Fluorescent or electrical consumption is growing.
HV/LV discharge lamps
A
Ine Devices using rectified Examples are:
∑ In and current (televisions,
distorted computers, etc.) b industrial equipment including welding machines, arc furnaces, induction
voltage
furnaces, rectifiers, etc.
Harmonic disturbances
transmitted to distribution Linear loads
b variable speed drives for asynchronous or DC motors
system and other users (do not cause b office equipment including computers, photocopy machines, fax machines, etc.
harmonics)
b household equipment including televisions, microwave ovens, neon lighting,
UPSs, etc.
Effects of harmonics
The flow of harmonics in distribution systems can cause serious problems:
b increased currents flowing in the system and overloads
b additional losses and premature ageing of equipment
b disturbances to loads due to voltage harmonics
b disturbances in communication networks.
The above effects can also have major financial impact due to:
b the cost of equipment (premature replacement, oversizing)
b increased power losses and the need to subscribe to higher power levels
b losses in productivity (unnecessary tripping of protection devices).
34 04443728AA - 01/2009
Overview of functions Harmonic measurements
Origin and effects
A number of international studies have produced data used to estimate the typical
harmonic values encountered in utility distribution systems. Below is a table
presenting the levels of harmonics that, in the opinion of many utility companies,
should not be exceeded.
Note:
the individual harmonic content of a harmonic of order n is defined as the percentage of its rms
value with respect to the rms value of the fundamental. This value is displayed on the graphic
screen of the Micrologic H.
04443728AA - 01/2009 35
Overview of functions Harmonic measurements
Quality indicators
Micrologic H control units can quantify and evaluate the harmonic distortion of
current and voltage waves using the quality indicators listed below:
b measurement of the fundamental signal
b phase displacement of the fundamental signals
b harmonic distortion THD and thd
b cos ϕ
b power factor
b K factor
b distortion power
b distortion factor
b crest factor
b amplitude spectrum of even and odd harmonics up to order 31
b displacement spectrum with respect to V1N of even and odd harmonics up to
order 31.
These indicators are the indispensable tools used to determine any required
corrective action.
36 04443728AA - 01/2009
Overview of functions Harmonic measurements
Quality indicators
Fundamental
Micrologic H control units can determine the value of the fundamental signals for:
b currents: I1, I2, I3 and IN (in amperes)
b voltages:
v phase-to-neutral V1N, V2N, V3N (in volts)
v phase-to-phase U12, U23, U31 (in volts)
b power:
v active P (kW)
v reactive Q (kVAR)
v apparent S (kVA).
∞ 2
Irms = ΣI
n=1 n
b The rms voltage is the square root of the sum of the squares of the rms current
values for each harmonic from the fundamental to an infinite order.
∞ 2
Urms = ΣU
n=1 n
( )-
2
ΣI
n=2 n
Irms
2
THD(I) = THD(I) = 1
Ifund
Ifund
Note:
b Ifund is the fundamental current.
b Irms is the rms current.
b Micrologic H control units measure the THD for currents I1, I2, I3 and IN
(in amperes), taking into account harmonic orders up to 31.
b The total harmonic distortion of current characterises the distortion of the current
waveform.
b Loads causing distortion are identified by measuring the THD(I) on the incoming
and outgoing circuits.
04443728AA - 01/2009 37
Overview of functions Harmonic measurements
Quality indicators
∞ 2
ΣU
n=2 n
THD(U) =
Ufund
Note:
Ufund is the fundamental voltage.
38 04443728AA - 01/2009
Overview of functions Harmonic measurements
Quality indicators
∞ 2
ΣI
n=2 n
thd(I) =
Irms
Note:
Irms is the rms current.
b Micrologic H control units measure the thd(I) for currents I1, I2, I3 and IN, taking
into account harmonic orders up to 31.
Defined by standard IEC 61000-2-2, total harmonic distortion thd(I) is a single value
that expresses the distortion of the current flowing at a given point in a distribution
system.
∞ 2
ΣU
n=2 n
thd(U) =
Urms
Note:
Urms is the rms voltage.
04443728AA - 01/2009 39
Overview of functions Harmonic measurements
Quality indicators
Cos ϕ
Cos ϕ is the ratio between the active power Pfund and the apparent power Sfund of
the fundamental (1).
Pfund
cos ϕ =
Sfund
Note:
b Pfund is the active power of the fundamental.
b Sfund is the apparent power of the fundamental.
Power factor PF
The power factor is the ratio between the active power P and the apparent power S.
P
PF =
S
Note:
b P is the active power.
b S is the apparent power.
b the power factor must not be confused with the cos ϕ. The power factor is equal to the cos ϕ
only when the signal is perfectly sinusoidal (no harmonics).
b If the measured power factor is not equal to the cos ϕ (the power factor is lower),
that may be an initial indication of harmonic disturbances in an installation.
b The power factor PF is the means to evaluate the oversizing required for the
power sources in an installation.
b There is a relation between the power factor and the total harmonic distortion of
current THD(I). When the voltage signal is (virtually) sinusoidal, the power factor
may be roughly calculated using the equation below:
cos ϕ
PF z
2
(
1 + thd(I))
When plotted, the above equation produces the graph below showing the PF to
cos ϕ ratio, depending on the THD(I)
PF/cos ϕ
DB120035
1,2
0,8
0,6
0,4
0,2
40 04443728AA - 01/2009
Overview of functions Harmonic measurements
Quality indicators
K factor
The K factor is a quality indicator that indicates high-order harmonics.
∞ 2 2
Σn
n=2
I
n
K factor =
Irms
Note:
I is the amplitude of the current.
Distortion power
When there are harmonics, the relation S2 = P2 + Q2 is no longer valid.
The distortion power D is defined by the equation below:
D= S2 - P2 - Q2
Distortion factor
The distortion factor is the relation between the power factor and the cos ϕ.
Crest factor
The crest factor is the relation between the peak value of the current or voltage and
the corresponding rms value.
Ipeak Upeak
Crest factor = or crest factor =
Irms Urms
Note:
b Irms is the rms current.
b Urms is the rms voltage.
b Possible values:
v for a sinusoidal signal, the crest factor is equal to 2
v for a non-sinusoidal signal, the crest factor may be less than or greater than 2.
b The crest factor is used to characterise the capacity of a source (UPS or
generator) to supply high instantaneous currents. In particular, it draws attention to
the presence of exceptional peak values with respect to the rms value.
Computer equipment, for example, draws highly distorted current with a crest factor
that can reach 3 or even 5.
b Typical crest factors for the currents drawn by non-linear loads are much higher
than 2. They are often equal to 1.5 or 2 and can reach 5 in critical cases.
b A very high crest factor means that there can be high temporary overcurrents,
which, when detected by the protective devices, may result in nuisance tripping.
04443728AA - 01/2009 41
Overview of functions Harmonic measurements
Quality indicators
The communication module can be used to determine FFT amplitude spectrum of odd harmonic
for each harmonic order up to 31:
b the amplitude spectrum orders from 3 up to 31
b the displacement spectrum with respect to the phase- Each type of distorting device has its own harmonic-current "fingerprint", with
to-neutral voltage V1N. different amplitudes and displacements.
These values, in particular the amplitude for each harmonic order, are essential for
the analysis of power quality.
b FFT (Fast Fourier Transform) frequency spectrum
The Micrologic H control unit can display the FFT amplitude spectrum of odd
harmonics from the 3rd up to 31st.
The Micrologic H control unit presents the amplitude of each harmonic order with
respect to its frequency in the form of a histogram, called a spectral analysis.
DB120036
s(t) H%
1 100
t 33
20
0 1 2 3 4 5 6 h
In Un
in (%) = 100 or un (%) = 100
Ifund Ufund
Note :
b I fund is the fundamental current.
b U fund is the fundamental voltage
In Un
in (%) = 100 or un (%) = 100
IN rms UN rms
Note:
b I N rms is the Neutral rms current.
b U N rms is the Neutral rms voltage.
b The Micrologic H control unit indicates the FFT amplitude spectrum and the
individual distortion level for harmonic orders from 3 to 31 for:
v each current I1, I2, I3 and IN
v each phase-to-phase voltage U12, U23 and U31.
b The Micrologic H control unit also indicates for each current or voltage the
corresponding level of total harmonic distortion THD (thd for Neutral current).
42 04443728AA - 01/2009
Overview of functions Harmonic measurements
Waveform and waveform capture
The communication module may be used to: Micrologic H control units can capture and store current and voltage waveforms
b set up "Measurement" or "Protection" alarms using digital sampling techniques similar to those used in oscilloscopes.
b capture and analyse waveforms; capture may be
tripped by the alarms Waveform capture is the means to detect weak points in the system and the
b captured waveforms are recorded over 4 cycles equipment. Using the information available in the captured waveform, it is possible to
(resolution of 64 points per cycle). determine the level of harmonics as well as the direction and amplitude of the flow of
harmonic power.
b Users of Micrologic H control units can record manually via the keypad the
following waveforms:
v the four currents I1, I2, I3 and IN
v the three phase-to-neutral voltages V1N, V2N and V3N.
04443728AA - 01/2009 43
Overview of functions Alarms
For information on the communications option and the b An alarm may be viewed using:
portable test kit, see the respective user guides. v the "Alarm history" menu
v the COM communications option
v the portable test kit.
b The commands in the "Protection" menu are used to attribute a specific operating
mode to each of the protection functions:
v OFF: protection disabled
v Alarm: the function issues an alarm, but does not trip the circuit breaker
v Trip + Alarm: the function issues an alarm and trips the circuit breaker.
b The protection functions against overloads (long time), short circuits (short time
and instantaneous) and ground faults (ground-fault and earth-leakage currents)
automatically result in tripping and cannot be deactivated (Trip mode only).
b The "I t Alarm" and phase rotation alarms can be set exclusively to OFF or Alarm
mode.
b The other protection functions for current, voltage, power and frequency may be
set to any of the three modes, OFF, Alarm or Trip + Alarm.
b The load shedding and reconnection function may be set to ON or OFF.
b The resettable alarms linked to device tripping are activated when the Ir, Isd/Ii
or I t thresholds are overrun.
The Ir alarm is reset one second after tripping. The Isd/Ii and t alarms are reset by
pressing the button.
Different pickup and dropout thresholds Current protection Off Alarm Trip + Alarm
Ir
DB120000
b
Isd / li b
Pickup T1
It b
b Delayed alarms are activated when the pickup and dropout thresholds are overrun
and the corresponding time delays have expired.
Dropout T2
Current protection Off Alarm Trip + Alarm
I t Alarm b b
Ir, Isd, Ii, I alarms I unbal b b b
I1 max b b b
Other alarms I2 max b b b
I3 max b b b
IN max b b b
Identical pickup and dropout thresholds Voltage protection Off Alarm Trip + Alarm
DB120001
U min b b b
U max b b b
Pickup / T1 T2 U unbal b b b
Dropout Other protection Off Alarm Trip + Alarm
rP max b b b
F min b b b
F max b b b
Ir, Isd, Ii, I alarms Phase rotation b b
Shedding/reconnection Off On
Other alarms Current I b b
Power P b b
b History logging
v Alarm mode: as soon as a given protection threshold is overrun, an alarm is
recorded in the "Alarm history"
v Trip mode: as soon as a given protection threshold is overrun, the circuit breaker
trips and the fault is recorded in the "Trip history".
b The "Protection setup" menu under "History, maintenance and setup" is used to
enable or disable the Trip mode that is displayed in the protection-setting screens.
On leaving the factory, the protection functions are set to Alarm mode.
b The "M2C / M6C contacts" menu under "History, maintenance and setup" is used
to link an M2C or M6C contact to an alarm. M2C and M6C contacts may not be used
together. They require a 24 V external power supply.
b The COM communications module can be used to transmit alarms to a supervisor.
44 04443728AA - 01/2009
Overview of functions Optional M2C and M6C contacts
474
484
Ir threshold T1 tr delay
17
19
21
23
25
1
5
7
9
E60491C
Ir LED Press
Internal alarm
Non-latching contact
Time-delay Reset possible before
S1 S2 24V 0V Com contact delay 1 to 360 s end of delay
Q1 Q2 Q3
Latching Reset possible
S3 S4 S5 S6 contact only after T2 = 1 s
12
14
16
18
20
22
24
2
6
8
Internal alarm
Non-latching contact
Time-delay Reset possible before
contact delay 1 to 360 s end of delay
Latching Reset possible
contact only after pressing
Pickup
Dropout
Internal alarm
Non-latching contact
Time-delay Reset possible before
contact delay 1 to 360 s end of delay
Latching Reset possible
contact only after T2
04443728AA - 01/2009 45
Overview of functions Event histories
Alarm history
b The alarm history is the means to display at any time the parameters measured
during the last ten alarms.
b For each alarm, the following parameters are recorded:
v alarm cause
v alarm threshold
v date
v time (hours, minutes and seconds).
Operation counter
This function is available only via the COM communications option.
b Micrologic H:
v stores and displays the total number of operations (incremented each time the
circuit breaker opens) since the initial installation of the circuit breaker
v stores and displays the total number of operations since the last reset.
Note:
if the control unit is changed, the circuit breaker must be defined again. In this case, see "Breaker
selection" in the "Micrologic setup" menu under "History, maintenance and setup".
46 04443728AA - 01/2009
Overview of functions Leds and display screens
E60444A
E89205A
Micrologic 5.0 H
Alarm
4260A
off
N 1 2 3
100
50
E89207B
Trip
22/11/1999
02:04:04
Umin 100V
Reset
by test/reset
button
04443728AA - 01/2009 47
Overview of functions Leds and display screens
b Fault-trip LEDs
b The LEDs indicate the type of fault that tripped the circuit breaker
b The LEDs are located in the upper part of the front panel (red Ir, Isd, Ii, Ig, I2n and
Ap LEDs)
b When activated, a LED remains ON until it is locally reset.
E89208A
E89209A
Micrologic 5.0 H Micrologic 5.0 H
E89211A
Micrologic 5.0 H Micrologic 5.0 H
self-protection built into the device) trips the circuit
breaker and turns the Ap LED on.
48 04443728AA - 01/2009
Overview of functions COM communications option
Communication options
E89212B
Digipact and ModBus are the indispensable elements when integrating Micrologic H
Chassis
in the Digivision and SMS Powerlogic installation-management systems which
communicate via the BatiBus and ModBus protocols.
External gateways are available for communication over other networks, including
COM module on ProfiBus, Ethernet, etc.
chassis (optional)
The communications option makes possible the following remote functions:
b device identification:
v address
v device type
v control-unit type
v type of long-time rating plug
Circuit breaker
b Measurement values:
v currents
Micrologic H v voltages, frequencies, power, etc.
control unit
b Fault values:
v fault type
v interrupted current.
b Indicators:
v contact wear, counters, etc.
v maintenance register.
04443728AA - 01/2009 49
Setup Setting up the optional
M2C / M6C contacts
Alarm Alarm
E71601A
E60146A
E60226A
type
type S2 S2
S1
S2 Ir Ir
then then
Select a contact. Select an alarm. Confirm.
E71603A
E71604A
M2C / M6C S2 S2
Setup
S1 Mode Mode
S2 latching latching
contact contact
then then
Select a contact. Select a latching mode: Confirm.
b non-latching
b latching
b time-delay
b locked to 1
b locked to 0.
50 04443728AA - 01/2009
Setup Setting up the optional
M2C / M6C contacts
S2 S2 S2
E71605A
E71606A
E71607A
Mode Mode Mode
time delay time delay time delay
then
Select the time delay. Adjust. Confirm.
Reset (- / +) Reset (- / +)
then
Reset the contacts to 0… or cancel the reset,
then confirm.
04443728AA - 01/2009 51
Setup Setting up the Micrologic
control unit
Micrologic
Select the display language
setup E71608A
E71938B
Language
Select. Confirm.
To return to English
1. Return to the main 2. Select the "History, 4. Select the "Language"
screen by pressing any of maintenance and setup" menu by moving the
the three buttons menu by pressing cursor up on the first
menu.
Confirm by pressing
or press the button 3. Select the "Micrologic
setup" menu by moving
the cursor up on the first
followed by any of the menu. Move the cursor
three buttons down on the third menu
and confirm
by pressing
E71611B
E71612B
18 : 30 : 03 18 : 30 : 03 18 : 30 : 03
52 04443728AA - 01/2009
Setup Setting up the Micrologic
control unit
E71613B
E71614B
If time is not synchronised by the supervisor via the
Date Date
communication module, a drift of up to one hour per
year may be observed.
01 / 01 / 2000 01 / 01 / 2000
Time Time
18 : 30 : 03 18 : 30 : 03
then then
Enter the year. Set the time in the same
manner.
E71616C
E71617C
setup selection selection selection
Breaker Standard Standard Standard
selection
UL IEC IEC
The circuit-breaker code is required to identify the Circuit breaker Circuit breaker Circuit breaker
device and activate the contact-wear counter.
Masterpact Masterpact Masterpact
Note this code if the control unit must be changed
type type type
(example 03E7). NT08N NT H1 NT H1
Enter this code when setting up a new control unit 03E7 03E7 03E7
on the circuit breaker. H Logicxxxxxx H Logicxxxxxx H Logicxxxxxx
For a new device, the code is set to zero.
When the main circuit-breaker contacts are replaced, then then then
Select the standard. Choose and confirm. Select the circuit breaker.
this code must be reset to zero.
E71619C
E71620BC
04443728AA - 01/2009 53
Setup Setting up the Micrologic
control unit
E71642B
E71643B
E71644B
setup Power Power Power
Power
sign
sign sign sign
By default, Micrologic H uses P+ for the power flowing
from top to bottom terminals. The selected direction of
P- P+ P+
flow is valid for:
b measurement of power and the power factor
b measurement of energy
b load shedding and reconnection depending on
power.
E71625A
E71626A
setup
VT ratio
Primary Primary Primary
690V 690V 690V
If the supply voltage for the control unit exceeds 690 V,
an external voltage transformer must be installed. Secondary Secondary Secondary
then then
Select either the: Enter the voltage. Go on to the next setting.
b primary voltage
b secondary voltage.
E71628A
E71629A
54 04443728AA - 01/2009
Setup Setting up the metering
functions
Note:
it is advised not to use the "3-phase, 4-wire, 4-CT" type of measurement unless the neutral is
effectively connected to the control unit (four-pole circuit breaker with an external voltage-
measurement input).
E71631A
E71632A
type type type
3Φ 4w 3Φ 3w 3Φ 3w
3CT 3CT 3CT
E89200C
E89201C
setup
Current demand demand demand
demand
Calculation Calculation Calculation
method method method
Thermal method based in I2t calculation. block
thermal block block
interval
interval interval
Window type Window type Window type
sliding sliding sliding
Interval Interval Interval
15 min 15 min 15 min
04443728AA - 01/2009 55
Setup Setting up the metering
functions
E89213C
E89214C
E89215C
demand demand demand
Calculation Calculation Calculation
method method method
block block block
interval interval interval
Window type Window type Window type
sliding sliding sliding
Interval Interval Interval
15 min 20 min 20 min
Select the command Select the calculation method for demand power
Metering
Power Power Power
E89216C
E89217C
E89218C
setup
Power demand demand demand
demand
Calculation Calculation Calculation
The synchronisation function "Synchro.Com" is method method method
available only with the COM communication option. block block block
With this function, the demand power is determined on thermal interval
interval interva
the basis of a signal synchronised by the
communication module. Window type Window type Window type
sliding sliding sliding
Thermal method based on I2t calculation.
Interval Interval Interval
Sliding window:
power demand is refreshed every 15 secondes.
15 min 15 min 15 min
Fixed window:
power demand is refreshed at the end of the time Select. Choose between: Confirm.
interval. b thermal
b block interval
b sync. to comms
E89220C
E89221C
56 04443728AA - 01/2009
Setup Setting up the metering
functions
E98320A
E89222C
E89223C
demand demand demand
Calculation Calculation Calculation
method method method
block block block
interval interval interval
Window type Window type Window type
fixed fixed fixed
Interval Interval Interval
15 min 20 min 20 min
E89226B
E89227B
setup Sign Sign Sign
Sign convention convention convention
convention
See page 106 for the description of power factor sign
conventions.
04443728AA - 01/2009 57
Setup Setting up the COM
communications option
Select the command When a COM communications option is used, it is necessary to:
b set up the COM communications option
Com. b authorise remote setting of the Micrologic control unit
setup b authorise remote control of the circuit breaker.
Com.
parameter View and set up the communications option
E71723A
E71724A
Modbus Modbus
E71725A
Modbus
As soon as the Digipact or Modbus communications
option is connected, the control unit recognises it and Com Com Com
displays the type of module on the graphic screen. Address Address Address
Automatic time updates are possible only with the
Modbus system. 47 45 45
Baud-rate Baud-rate Baud-rate
9600 9600 9600
Parity Parity Parity
None None None
then
Select an existing Adjust. Confirm.
parameter.
Adjust all the other parameters for the communications option in the same manner.
DIGIPACT MODBUS
(read only) (read and set up)
Address 1 - 255 1 - 47
Baud rate 9600 bauds
19200 bauds
Parity Even
None
E71728A
then
Select existing setting. Choose. Confirm.
58 04443728AA - 01/2009
Setup Setting up the COM
communications option
E71729A
E71730A
E71731A
the default access code is 0000 and is requested by Remote Remote Remote
the supervisor. settings settings settings
Access Access Access
permit permit permit
Yes Yes Yes
Select the existing access Enter the first digit. Confirm and proceed in
code setting. the same manner for the
other digits.
Remote
E71733A
E71734A
setup Remote
control control control
Remote
control
04443728AA - 01/2009 59
Protection settings Fine adjustment of the long-time
I2t, short-time and instantaneous
settings using the keypad
Select the command.
E71738A
Current I(A)
protection Trip
E60276A
E60275A
E60149A
I(A) I(A) I(A)
Trip Trip Trip
1000 A 998 A 998 A
1.0 s 1.0 s 1.0 s
then
Select a setting. Adjust the value. Confirm.
E60277A
then
Adjust the other settings Quit the setting screen. Confirm.
and confirm.
60 04443728AA - 01/2009
Protection settings Fine adjustment of the long-time
Idmtl, short-time and instantaneous
settings using the keypad
Select the command
E71739A
Current Idmtl (A)
protection
Trip
Idmtl (A) 1000 A long-time current setting Ir
long-time tripping delay tr
1.0 s
EIT Idmtl protection:
DT, SIT, VIT, EIT, HVF
2000 A short-time pickup Isd
0.2 s short-time tripping delay tsd
4000 A instantaneous pickup Ii
Idmtl (A)
E60151A
E71718A
E60278A
Idmtl (A) Idmtl (A)
Trip Trip
1000 A 1000 A
Change I(A)
1.0 s 1.0 s
settings with
Idmtl(A)? EIT VIT
2000 A 2000 A
0.2 s 0.2 s
No 4000 A 4000 A
Yes
E60280A
04443728AA - 01/2009 61
Protection settings Fine adjustment of the ground-
fault and earth-leakage protection
setting using the keypad
Select the command
DB120019
I
DB120020
Current (A) I (A)
protection
Trip Trip
I (A)
1200A threshold 1200A
then
Select a setting.
DB120021
DB120022
DB120023
I (A) I (A) I (A)
Trip Trip Trip
then
Adjust the value. Confirm. Go to the next setting.
DB120025
DB120025
62 04443728AA - 01/2009
Protection settings Setting the neutral protection
E89237B
E89238B
E89239B
protection Ineutral (A) Ineutral (A) Ineutral (A)
Ineutral (A) Neutral CT Neutral CT Neutral CT
then
Select. Choose between: Confirm.
b internal
b external
b none.
E89242B
Ineutral (A)
E89241B
breaker
Four-pole OFF: no neutral protection
N / 2: half neutral protection
N: full neutral protection
Neutral CT Neutral CT Neutral CT
Three-pole OFF: no neutral protection
N / 2: half neutral protection External External External
N: full neutral protection
1.6 x N: oversized neutral protection
then
Select. Choose. Confirm.
E71657A
E89242B
Ineutral (A)
Neutral CT
Do you want
External to save new
settings?
Protection no
N/2 yes
Note:
On four-pole circuit breakers, setting of the neutral using the keypad is limited by the dial setting.
04443728AA - 01/2009 63
Setting the I , I unbal, I max, U min,
I
Protection settings
U max, U unbal, rP max, F min, F max,
and phase-rotation protection
functions using the keypad
Select the corresponding menu
E71661B
type of protection
Current
protection
operating mode
I Alarm Pick up
(Off, Alarm or Trip)
I unbal (%)
pickup threshold
pickup time delay
Umin
E60292B
E60171B
E60293B
(V) Umax (V) Umax (V) Umax (V)
Umax (V) Off Alarm Alarm
Pick up Pick up Pick up
Uunbal (%) 690V 690V 690V
5.00s 5.00s 5.00s
Other
protection Drop out Drop out Drop out
690V 690V 690V
rPmax (W) 0.50s 0.50s 0.50s
Fmin (Hz)
then
Select the first setting. Choose Off or Alarm. Confirm.
Fmax (Hz)
E60292B
E89294B
Phase
rotation Umax (V) Umax (V)
Off Trip
Pick up Pick up
In trip mode, the dropout threshold is equal to the 690V 690V
pickup threshold.
5.00s 5.00s
The dropout time delay is fixed and equal to 1 second.
Drop out
690V
0.50s
then
Select the first setting. Choose Trip.
64 04443728AA - 01/2009
Setting the I , I unbal, I max, U min,
I
Protection settings
U max, U unbal, rP max, F min, F max,
and phase-rotation protection
functions using the keypad
E89293B
E89295B
Umax (V) Umax (V)
Trip
Do you want Pick up
to set the
690V
protection to
Trip mode? 5.00s
no
yes
then
Confirm.
For protection tripped by a maximum value, the dropout b Set the pickup and dropout thresholds and time delays
threshold is always less than or equal to the pickup
E71666A
E71667A
threshold.
then
Select the existing Adjust. Confirm.
dropout threshold setting
When all the settings have been made, quit the screen
E71668A
E71668A
E71657A
then
Set the other parameters. Quit the setting screen. Confirm
04443728AA - 01/2009 65
Protection settings Setting load
shedding / reconnection
E71673B
Load type of shedding (I or P)
Load shedding
shedding I
operating mode (On, Off)
Load
shedding P Pick up
pickup threshold
pickup time delay
Drop out
dropout threshold
dropout time delay
66 04443728AA - 01/2009
Protection settings Setting load
shedding / reconnection
E71670A
E71671A
E71672A
shedding P shedding P shedding P
Off On On
Pick up Pick up Pick up
1000kW 1000kW 1000kW
3600s 3600s 3600s
Drop out Drop out Drop out
1000kW 1000kW 1000kW
10s 10s 10s
then
Select the first setting. Select: Confirm.
b Off: load shedding
disabled
b On: load shedding
enabled.
E71674A
E71675A
E71676A
Load Load Load
shedding P shedding P shedding P
On On On
Pick up Pick up Pick up
1000kW 1000kW 1000kW
3600s 3600s 3600s
Drop out Drop out Drop out
980kW 985kW 985kW
10s 10s 10s
then
Select the existing Adjust. Confirm.
dropout threshold.
When all the settings have been made, quit the screen
E71677A
E71677A
E71657A
Load Load
by pressing one of the menu-access buttons.
This saves the new values. shedding P shedding P
On On
Pick up Pick up Do you want
to save new
1000kW 1000kW
settings?
3600s 3600s
Drop out Drop out
985kW 985kW
no
10s 10s yes
then
Set the other parameters. Quit the setting screen. Confim.
04443728AA - 01/2009 67
Metering Current measurements
Only the measurements for the phase (1, 2, 3) and Continuous current measurement
neutral currents are displayed on the main screen. The bargraph displays the value in amperes of the most heavily loaded phase.
E60184A
E60185A
E60187A
The neutral current is displayed if the neutral CT is set
to internal or external (see "Ineutral (A)" settings in the
"Current protection" menu).
4260A 3850A 3410A
1 2 3 1 2 3 1 2 3
100 100 100
50 50 50
0 0 0
The and buttons may be used to display the currents on the three phases.
If the operator no longer uses the buttons for a few seconds, the bargraph returns to
the display of the most heavily loaded phase.
E60189A
then
Select. View.
I inst. Imax
E60190A
E60191A
Reset ( - / + )
then
Select. View.
68 04443728AA - 01/2009
Metering Current measurements
Imax Imax
E60192A
E60191A
instant. instant.
I1 = 0A I1 = 5600 A
I2 = 0A I2 = 4800 A
I3 = 0A I3 = 4700 A
IN = 0A IN = 800 A
I = 0A I = 28 A
Reset ( - / + ) Reset ( - / + )
E71679A
Demand.
I1, I2, I3, IN 13min
I1 = 3950 A
Max I2 = 4270 A
I3 = 3890 A
IN = 340 A
then
Select. View.
04443728AA - 01/2009 69
Metering Current measurements
Demand
E71681A
E71680A
Imax
Demand
I1, I2, I3, IN
15min
I1 = 4020 A
Max
I2 = 4450 A
I3 = 4300 A
IN = 600 A
Reset ( - / +)
then
Select. View.
E71683A
Imax Imax
Demand Demand
15min 15min
I1 = 0A I1 = 4020 A
I2 = 0A I2 = 4450 A
I3 = 0A I3 = 4300 A
IN = 0A IN = 600 A
Reset ( - / +) Reset ( - / +)
70 04443728AA - 01/2009
Metering Voltage measurements
E60193A
E89257B
U (V) Uinst.
The phase-to-neutral voltages are displayed if the Instant.
selected system type is 3-phase, 4-wire (see page 55). U12 = 400 V
Average 3Φ U23 = 404 V
U31 = 401 V
Unbal 3Φ
Phase U1N = 230 V
rotation U2N = 229 V
U3N = 233 V
then
Select. View.
Uavg.
E89258B
U (V)
Instant. 3Φ
Average 3Φ
402 V
Unbal 3Φ
Phase
rotation
then
Select. View.
U (V)
Instant.
3Φ
Average 3Φ
1%
Unbal 3Φ
Phase
rotation
then
Select. View.
04443728AA - 01/2009 71
Metering Voltage measurements
E89260A
E89261A
U (V) Phase
rotation
Instant.
Average 3Φ
Unbal 3Φ
∆Φ : 1, 2, 3
Phase
rotation
then
Select. View.
72 04443728AA - 01/2009
Metering Power measurements
E60199B
E71690A
(kW) Pinst.
Instant. P, Q, S
P (kW)
Power 2180
To ensure reliable power and power-factor factor
measurements, the "Power sign" and "Sign
convention" parameters must be set. Q (kvar)
-650
S (kVA)
2280
then
Select. View.
E71692A
Pinst. factor
P, Q, S
Power
factor 1.00
then
Select. View.
Demand
P, Q, S P (kW)
2350
Max
Q (kvar)
-820
S (kVA)
2640
then
Select. View.
04443728AA - 01/2009 73
Metering Power measurements
Pmax
E71695A
Demand
E71696B
Demand
P, Q, S P (kW)
2450
Max
Q (kvar)
-800
S (kVA)
2700
Reset (- / +)
then
Select. View.
Pmax Pmax
E71697B
E71698B
Demand Demand
P (kW) P (kW)
0 2450
Q (kvar) Q (kvar)
0 -800
S (kVA) S (kVA)
0 2700
Reset (- / +) Reset (- / +)
74 04443728AA - 01/2009
Metering Energy measurements
E71699A
E (kWh) b total energy
b energy in (positive component in the total energy)
To ensure reliable energy measurements, the "Power b energy out (negative component in the total energy).
E total
sign" and "Sign convention" parameters must be set.
E in
E out
Reset
energy
then
Select.
E total E in E out
E71700B
E71701B
E71702B
E.P (kWh) E.P (kWh) E.P (kWh)
20168 +21320 168
E.S (kVAh)
22926
View the total energy View the energy View the energy
values. in values. out values.
E71705A
E71703A
E (kWh) Reset
E total Energy To reset
energy
E in press
Are you enter
sure ?
E out
Reset
Energy No
Yes
then then
Select. Select yes or no. If yes, confirm.
04443728AA - 01/2009 75
Metering Harmonic measurements
Waveform capture
E89263A
E89262B
Waveform I1,2,3
Waveform I1,2,3 I1
IN
U12,23,31 I2
I3
then
Select. View.
Waveform IN
I1,2,3
IN
U12,23,31
then
Select. View.
Waveform U12,23,31
I1,2,3
IN
U12,23,31
then
Select. View.
76 04443728AA - 01/2009
Metering Harmonic measurements
Fundamentals
E89268B
E89269B
Harmonic Fundament I(A)
Fundament
Fundament. I (A)
I1 = 92 A
U (V)
I2 = 126 A
P (W)
I3 = 62 A
IN = 1A
then
Select. View.
E89271B
Fundament U(V)
Fundament
I (A)
U12 = 281 V
U (V) U21 = 333 V
U31 = 276 V
P (W) V1N = 139 V
V2N = 185 V
V3N = 190 V
then
Select. View.
E89273B
Fundament P,Q,S
Fundament
I (A) P (kW)
-9
U (V)
Q (kvar)
P (W) 47
S (kVA)
52
then
Select. View.
04443728AA - 01/2009 77
Metering Harmonic measurements
THD
Select the command Measure the total harmonic distortion (THD) of the
Harmonic current (with respect to fundamental)
E89274A
E89275B
THD ITHD(%)
THD
I (%) I1 = 7.0 %
U (%) I2 = 5.8 %
I3 = 6.2 %
IN = 2.1 %
then
Select. View.
E89277B
THD UTHD(%)
I (%) U12 = 1.0 %
U23 = 1.2 %
U (%) U31 = 1.4 %
V1N = 2.2 %
V2N = 2.0 %
V3N = 2.0 %
then
Select. View.
78 04443728AA - 01/2009
Metering Harmonic measurements
thd
Select the command Measure the total harmonic distortion (thd) of the
Harmonic current (with respect to rms value)
E89278A
E89279B
thd Ithd (%)
thd
I (%) I1 = 6.8 %
U (%) I2 = 7.2 %
I3 = 5.6 %
IN = 8.1 %
then
Select. View.
E89281B
then
Select. View.
04443728AA - 01/2009 79
Metering Harmonic measurements
FFT amplitude spectrum
E89282A
E89283A
E89284B
FFT FFT
I1 FFT
FFT
THD=6.3
I (3,5,7,….,31) I1 (3,.,31) 8.0%
Note :
FFT= Fast Fourier Transform
U(3,5,7,….,31) I2 (3,.,31)
I3 (3,.,31)
IN (3,.,31)
3 5 7 9 11
then then
Select. Select a current. View the individual
distortion of the 3rd
harmonic
E89285B
E89286B
I1 FFT I1 FFT
THD=6.3 THD=6.3
5.0% 1.0%
3 5 7 9 11 23 25 27 29 31
80 04443728AA - 01/2009
Metering Harmonic measurements
FFT amplitude spectrum
E89287A
E89288A
E89289B
FFT FFT
U12 FFT
THD=3.2
I (3,5,7,….,31) U12 (3,.,31) 3.0%
U(3,5,7,….,31) U23 (3,.,31)
U31 (3,.,31)
3 5 7 9 11
then then
Select. Select a voltage. View the individual
distortion of the 3rd
harmonic
E89290B
E89291B
3 5 7 9 11 23 25 27 29 31
04443728AA - 01/2009 81
Metering Frequency measurements
E60110A
F (Hz)
60.0
View.
82 04443728AA - 01/2009
04443728AA - 01/2009 83
Maintenance Resetting fault indications
Caution! The fault indication is maintained until it is reset on the control panel.
If the circuit breaker remains closed and the Ap LED Press the reset button.
remains ON after the reset, open the circuit breaker
and contact the after-sales support department.
E89292B
Micrologic 7.0 H
Fault
22/11/1999
02:04:04
Umin 100V
Reset
by test/reset
button
84 04443728AA - 01/2009
Maintenance Viewing the event histories
E71706A
E71707A
history Trip
history 22/11/1999
Trip
history 02:04:04
U min Umin 160V
27/01/1999
Ir
27/06/1998
Ir
18/02/1998
then
Select a fault. View.
E71709A
history
history 27/01/1999
Alarm
history 13:06:09
I2 max I2 max 3400A
27/01/1999
In max
23/03/1998
U max
12/02/1998
then
Select an alarm. View.
04443728AA - 01/2009 85
Maintenance Operation counter and
contact-wear indicator
E71736A
E71737A
E71735A
history Number of Number of Number of
operations operations operations
Operation
counter Total Total Total
17824 17824 17824
Operations Operations Operations
since last since last since last
reset reset reset
6923 0 6923
then
Reset… … or cancel the reset,
then confirm.
history
Contact
wear
Contact
wear
86 04443728AA - 01/2009
Maintenance Checking/replacing the battery
E89248A
Micrologic 7.0 H
1 2 3
Press and hold down the test button on the control unit to check the LEDs and the
battery. The battery information is displayed if the control unit is equipped with an
external power supply or if the circuit breaker is ON.
E71751A
If the battery needs to be changed, order a new battery Replacing the control-unit battery
with the Schneider Electric catalogue number 33593. 1. remove 2. remove the battery
b Lithium battery the battery cover
b 1.2 AA, 3.6 V, 800 mA/h
DB119959
DB119960
+
DB119961
DB119962
04443728AA - 01/2009 87
Maintenance Tests
DB120037
5.0 H
logic
Micro
If the circuit breaker does not trip, contact the after-sales support department.
Refer to the manual that comes with the test kits. Mini test kit and portable test kit
The test connector is used to connect the mini or the portable test kit to check that
the control unit is operating correctly.
DB120038
DB120039
5.0 H 5.0 H
logic logic
Micro Micro
88 04443728AA - 01/2009
04443728AA - 01/2009 89
Technical appendix Tripping curves
DB120005
90 04443728AA - 01/2009
Technical appendix Tripping curves
DB119968
04443728AA - 01/2009 91
Technical appendix Voltage measurements
Micrologic H is equipped with a three-phase voltage power supply that, with respect
to the distribution system, may be considered a delta load. The three-phase power
supply reinjects voltage on an open phase.
The voltage-protection functions react as indicated below.
Minimum-voltage protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit reinjects
voltage on the failed phase and measures a phase-to-phase voltage higher than the
actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
Voltage-unbalance protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit reinjects
voltage on the failed phase and measures a phase-to-phase voltage higher than the
actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
Phase failure
Detection of phase failure is not possible on the basis of the minimum-voltage and
voltage-unbalance protection functions.
The Micrologic power supply requires at least two phases (between 100 and 690 V).
In diagrams 1, 3 and 4, if two phases have failed, Micrologic H measures for the
three phases the value of the single voltage present (e.g. U12 = U23 = U31 = 410 V).
92 04443728AA - 01/2009
Technical appendix Voltage measurements
b Diagram 1
Contactor
DB120006
Fuses
Motor
Open
b Diagram 2
Contactor
DB120007
Fuses
Motor
Open
b Diagram 3
Contactor
DB120008
Motor
Open
Fuses
b Diagram 4
DB120009
Load
Fuses
Other
measurement
and protection
systems
04443728AA - 01/2009 93
Technical appendix Zone selective interlocking (ZSI)
Operating principle
E60450B
Note:
on device no. 1, the tsd and tg tripping delays must not be set to zero because this would make
discrimination impossible.
2
A
Connections between control units
A logic signal (0 or 5 volts) can be used for zone selective interlocking between the
upstream and downstream circuit breakers.
b Micrologic 5.0 A, 6.0 A, 7.0 A
b Micrologic 5.0 P, 6.0 P, 7.0 P
b Micrologic 5.0 H, 6.0 H, 7.0 H.
An interface is available for connection to previous generations of trip units.
Caution!
Wiring
b Maximum impedance: 2.7 Ω / 300 metres
lf the protection function is not used on circuit breakers
b Capacity of connectors: 0.4 to 2.5 mm2
equipped for ZSI protection, a jumper must be installed
b Wires: single or multicore
to short terminals Z3, Z4 and Z5. If the jumper is not b Maximum length: 3000 metres
installed, the short-time and ground-fault tripping b Limits to device interconnection:
delays are set to zero, whatever the position of the v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2) can be connected to a
adjustment dial. maximum of ten inputs
v a maximum of 100 devices may be connected to the common ZSI - IN (Z3) and to
an input ZSI - IN CR (Z4) or GF (Z5).
DB120010
upstream 1 Z1
circuit-breaker Z2 tsd = 0.3
Terminals Z1 to Z5 correspond to the identical Z3
indications on the circuit-breaker terminal blocks. Z4
Z5
point B
2 Z1
Z2
Z3 tsd = 0. 2
Z4
Z5
point A
Z1 downstream Z1
Z2 circuit-breaker Z2
Z3 Z3
Z4 Z4
Z5 Z5
Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.
94 04443728AA - 01/2009
Technical appendix Power supply
Battery module
Use of a BAT battery module, mounted in series with the AD power-supply module,
ensures a continous supply of 24 V DC power for 12 hours if the AD module fails.
Wiring diagrams
v reliable or backed-up auxiliary system
E60449A
L4
L3 Input
AC
220V
0V t
OutpuC +
AD 22 – 24VD
G2
G1
F2
F1 +
-
L4 H4
L3 Input H3 InputC +
220V
AC
- 24VD
0V t
OutpuC + 24V
t
OutpuC
-
AD 22 – 24VD
G2 BAT + 24VD
H1
G1 H2
F2
F1 +
-
2 Q3
Q1 Q
25
21 23
17 19
L4
M6C
L3 Input
AC
220V
0V t
OutpuC +
AD 22 – 24VD
G2
G1
04443728AA - 01/2009 95
Technical appendix Power supply
b If the 24 V DC external power supply (AD module) is used, the maximum cable
length between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10
metres.
b The communications bus requires its own 24 V DC power source (E1, E2).
This source is not the same as the 24 V DC external power-supply module
(F1-, F2+).
With this option, the internal voltage-measurement inputs are disconnected. The
PTE option is required for voltages greater than 690 V (in which case a voltage
transformer is required).
When the PTE option is implemented, the supply circuit of the voltage-measurement
input must be protected against short-circuits. Installed as close as possible to the
busbars, this protection function is ensured by a P25M circuit breaker (1 A rating)
with an auxiliary contact (cat. no. 21104 and 21117).
The supply circuit of the voltage-measurement input is reserved exclusively for the
control unit and must never be used to supply other circuits.
96 04443728AA - 01/2009
Technical appendix Changing the long-time
rating plug
DB119975
5.0 H 5.0 H
logic logic
Micro Micro
Caution! 4. snap out the rating plug 5. clip in the new rating plug
If no long-time rating plug is installed, the control unit
DB119976
5.0 H
logic
Micro
alarm
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 @ 6 Ir
.5 1
.4 x In
alarm
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 @ 6 Ir
.5 1
.4 x In
04443728AA - 01/2009 97
Technical appendix Thermal memory
Thermal memory
The thermal memory is the means to take into account temperature rise and cooling
caused by changes in the flow of current in the conductors.
Control units with a thermal memory record the temperature rise caused by each
overload, even very short ones. This information stored in the thermal memory
reduces the tripping time.
b For all protection functions, prior to tripping, the temperature-rise and cooling time
constants are equal and depend depend on the tr tripping delay:
v if the tripping delay is short, the time constant is low
v if the tripping delay is long, the time constant is high.
b For long-time protection, following tripping, the cooling curve is simulated by the
control unit. Closing of the circuit breaker prior to the end of the time constant
(approximately 15 minutes) reduces the tripping time indicated in the tripping curves.
98 04443728AA - 01/2009
Technical appendix Data available via the COM
communications option
04443728AA - 01/2009 99
Technical appendix Data available via the COM
communications option
Setup / Maintenance
b Setting of the control-unit date and time
b Password for the measurement module
b Control-unit ID code
b Control-unit ID name
b Selection of the measurement calculation algorithm
b Sign convention for the active power
b Total-energy measurement mode
b Interval for the demand-current calculation window
b Power quality indication
b Demand-power calculation mode
b Interval for the demand-power calculation window
b Battery-charge indication
b Trip and alarm histories
b Operation counter and contact-wear indicator
b Assignment and setup of programmable contacts
b Event log and maintenance register
b Power factor sign conventions
b Monitoring parameters
b Monitoring priorities levels
b Waveform capture.
Protection
b Circuit-breaker rated current
b Type of neutral protection
b Long-time I2t protection settings
b Long-time Idmtl protection settings
b Short-time protection settings
b Instantaneous-protection settings
b Ground-fault protection settings
b Earth-leakage protection settings
b Current-unbalance, It alarm and maximum-current protection settings
b Voltage-protection settings
b Setting for other protection functions.
Short-time protection
Type Range Factory setting Step Accuracy
Isd pickup 1.5 to 10 Ir maximum 10 A ±10 %
tsd tripping delay 0 - 0.1 - 0.2 - 0.3 - 0.4 s maximum 0.1 s
Instantaneous protection
Type Range Factory setting Step Accuracy
Ii pickup 2 to 15 In or off maximum 10 A ±10 %
Neutral protection
Type Range Factory setting
Three-pole device Off, N/2, N, 1.6 x N off
Four-pole device Off, N/2, N N/2
Current protection
Type Range Factory setting Step Accuracy
Current unbalance I unbal
Pickup threshold 5 % to 60 % 60 % 1% -10 %, +0 %
Dropout threshold 5 % of pickup threshold pickup threshold 1% -10 %, +0 %
Pickup time delay 1 s to 40 s 40 s 1s -20 %, +0 %
Dropout time delay 10 s to 360 s 10 s 1s -20 %, +0 %
Ground-fault I t alarm
Pickup threshold 20 A to 1200 A 120 A 1A ±15 %
Dropout threshold 20 A to pickup threshold pickup threshold 1A ±15 %
Pickup time delay 1 s to 10 s 10 s 0.1 s -20 %, +0 %
Dropout time delay 1 s to 10 s 1s 0.1 s -20 %, +0 %
Earth-leakage I t alarm
Pickup threshold 0.5 A to 30 A 30 A 0.1 A -20 %, +0 %
Dropout threshold 0.5 A to pickup threshold pickup threshold 0.1 A -20 %, +0 %
Pickup time delay 1 s to 10 s 10 s 0.1 s -20 %, +0 %
Dropout time delay 1 s to 10 s 1s 0.1 s -20 %, +0 %
Maximum current I1 max, I 2 max, I 3 max, IN max
Pickup threshold 0.2 In to In In 1A ±6.6%
Dropout threshold 0.2 In to pickup threshold pickup threshold 1A ±6.6%
Pickup time delay 15 s to 1500 s 1500 s 1s -20 %, +0 %
Dropout time delay 15 s to 3000 s 15 s 1s -20 %, +0 %
Voltage protection
Type Range Factory setting Step Accuracy
Minimum voltage U min
Pickup threshold 100 V to U max pickup threshold 100 V 5V -5 %, +0 %
Dropout threshold pickup threshold to U max pickup threshold 5V -5 %, +0 %
pickup threshold
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 %
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 %
Maximum voltage U max
Pickup threshold U min pickup threshold to 1200 V 725 V 5V -0 %, +5 %
Dropout threshold 100 V to pickup threshold pickup threshold 5V -0 %, +5 %
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 %
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 %
Voltage unbalance U unbal
Pickup threshold 2 % to 30 % 30 % 1% -20 %, +0 %
Dropout threshold 2 % to pickup threshold pickup threshold 1% -20 %, +0 %
Pickup time delay 1 s to 40 s 40 s 1s -20 %, +0 %
Dropout time delay 10 s to 360 s 10 s 1s -20 %, +0 %
Other protection
Type Range Factory setting Step Accuracy
Reverse power rP max
Pickup threshold 5 to 500 kW 500 kW 5 kW ±2.5%
Dropout threshold 5 kW to pickup threshold pickup threshold 5 kW ±2.5%
Pickup time delay 0.2 s to 20 s 20 s 0.1 s -0 %, +20 % (1)
Dropout time delay 1 s to 360 s 1s 0.1 s -0 %, +20 %
Maximum frequency F max
Pickup threshold F min pickup threshold to 440 Hz 65 Hz 0.5 Hz ±0.5 Hz
Dropout threshold 45 Hz to pickup threshold pickup threshold 0.5 Hz ±0.5 Hz
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 % (2)
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 % (2)
Minimum frequency F min
Pickup threshold 45 Hz to F max pickup threshold 45 Hz 0.5 Hz ±0.5 Hz
Dropout threshold pickup threshold to F max pickup threshold 0.5 Hz ±0.5 Hz
pickup threshold
Pickup time delay 1.2 s to 5 s 5s 0.1 s -0 %, +20 % (2)
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 % (2)
Phase rotation
Pickup threshold Ph1, Ph2, Ph3 or Ph1, Ph3, Ph2 Ph1, Ph2, Ph3 none none
Dropout threshold pickup threshold pickup threshold none none
Pickup time delay 0.3 s 0.3 s none -0 %, +50 %
Dropout time delay 0.3 s 0.3 s none -0 %, +50 %
(1) +30 % on dial 0.2 s
(2) +30 % up to 1.5 s
Micrologic setup
Type Range Factory setting Step
Language German English UK
English US
English UK
Italian
French
Spanish
Chinese
Date / time 1s
Circuit-breaker "no def"
selection
Neutral TC no TC
VT ratio
Primary voltage min. 100 V, max. 1150 V 690 V 1v
Secondary voltage min. 100 V, max. 690 V 690 V 1v
System 50/60 Hz 50/60 Hz
frequency or
400 Hz
Measurement setup
Type Range Factory setting Step
System type 3 Φ, 3 w, 3 CT 3 Φ, 4 w, 4 CT
3 Φ, 4 w, 3 CT
3 Φ, 4 w, 4 CT
Demand-current
Calculation method thermal or block interval
block interval
Type of window fixed or sliding sliding
Calculation interval 5 to 60 minutes 15 minutes 1 minute
Demand-power
Calculation method thermal or block interval
block interval or
sync. to comms
Type of window fixed or sliding sliding
Calculation interval 5 to 60 minutes 15 minutes 1 minute
Power sign P+ P+
P- (flow from top to
bottom)
Sign convention IEEE IEEE
IEEE alternate
IEC
Communication setup
Type Range Factory setting
Com parameter MODBUS
Adress 1-47 47
Baud rate 9600 19200 bauds
to 19200 bauds
Parity even even
none
Remote settings
Access authorisation yes / no yes
Access code 0000 to 9999 0000
Remote control manual automatic
automatic
Protection setup
Type Range Factory setting
Current protection alarm / trip / OFF OFF
voltage protection
other protection
b The accuracy of the current measurements depends Measurement setting ranges and accuracy
on both the value displayed (or transmitted) and the
circuit-breaker rating, where: Type Range Accuracy at 25 °C
Accuracy = 0.5 % In + 1.5 % reading Instantaneous current
I1, I2, I3 0.05 x In to 20 x In ±1.5 %
Example: IN 0.05 x In to 20 x In ±1.5 %
For a circuit breaker with a 4000 A rating and a current I t ground 0.05 x In to In ±10 %
displayed on Micrologic of 49 A, the accuracy is: I t earth leakage 0 to 30 A ±1.5 %
0.5 % x 4000 + 1.5 % x 49 = ±21 A I1 max, I2 max, I3 max 0.05 x In to 20 x In ±1.5 %
IN max 0.05 x In to 20 x In ±1.5 %
I t max ground 0.05 x In to In ±10 %
I t max earth leakage 0 to 30 A ±1.5 %
Demand current
I1, I2, I3 0.05 x In to 20 x In ±1.5 %
IN 0.05 x In to 20 x In ±1.5 %
I1 max, I2 max, I3 max 0.05 x In to 20 x In ±1.5 %
IN max 0.05 x In to 20 x In ±1.5 %
Phase-to-phase voltages
U12 170 to 1150 V ±0.5 %
U23 170 to 1150 V ±0.5 %
U31 170 to 1150 V ±0.5 %
Phase-to-neutral voltages
V1N 100 to 1150 V ±0.5 %
V2N 100 to 1150 V ±0.5 %
V3N 100 to 1150 V ±0.5 %
Average voltage
U avg 170 to 1150 V ±0.5 %
Voltage unbalance
U unbal 0 to 100 % ±0.5 %
Instantaneous power
P 0.015 to 184 MW ±2 %
Q 0.015 to 184 Mvar ±2 %
S 0.015 to 184 MVA ±2 %
Power factor
PF -1 to +1 ±2 %
Demand power
P 0.015 to 184 MW ±2 %
Q 0.015 to 184 Mvar ±2 %
S 0.015 to 184 MVA ±2 %
P max 0.015 to 184 MW ±2 %
Q max 0.015 to 184 Mvar ±2 %
S max 0.015 to 184 MVA ±2 %
Total energy
E.P -1010 GWh to +1010 GWh ±2 %
E.Q -1010 Gvarh to +1010 Gvarh ±2 %
E.S -1010 GVAh to +1010 GVAh ±2 %
Total energy in
E.P -1010 GWh to +1010 GWh ±2 %
E.Q -1010 Gvarh to +1010 Gvarh ±2 %
Total energy out
E.P -1010 GWh to +1010 GWh ±2 %
E.Q -1010 Gvarh to +1010 Gvarh ±2 %
Frequency
F 45 Hz to 440 Hz ±0.1 %
Fundamentals
I 0.005 x In to 1.5 x In ±1.5 % (1)
U 30 to 1150 V ±0.5 %
P, Q, S 0.15 to 13.8 kW ±2 %
THD, thd
I 2 to 1000% ±5 %
U 2 to 1000% ±5 %
FFT
I 0 to 1000% ±5 %
U 0 to 1000% ±5 %
(1) Over the range 0.7 x In to 1.5 x
DB120011
Flow of active and
reactive power Q
DB119979
DB119980
DB119981
A
Activation 27, 28, 29, 30, 44
Active, reactive, apparent energy 32, 75
Active, reactive, apparent power 73
AD power-supply module 95
Address 58
Alarm 44, 47
Alarm history 46, 85
B
Baud rate 58
Buttons 5, 6
C
Circuit-breaker selection 53
COM communication option 49, 58, 99
Contact 45, 50
Contact wear 86
Control unit identification 4
Control-unit battery 5, 87
Cos ϕ 40
Crest factor 41
Current demand calculation 31, 55
D
Date and time 52
Demand current 55, 69
Demand power 32, 56
Digipact 58
Direction of power flow 54
Distortion factor 41
Distortion power 41
Dropout 27, 28, 29, 30, 44
DT 23, 61
E
Earth-leakage protection 26
Earth-leakage protection tripping delay ∆ 26
EIT 23, 61
F
F max 29, 64
F min 29, 64
Fault 84
Frequency 32, 54, 82
FTT 42, 80
Full neutral protection 25, 63
Fundamental 77
Graphic display 5
Ground-fault / Earth-leakage fault protection test 88
Ground-fault protection 26
H
Half neutral protection 25, 63
Harmonics 33
History, setup and maintenance menu 13, 18
HVF 6, 23
I
I t 62
I t Alarm 27, 64
I avg 27
I max 27, 64
I unbal 64
I∆n pickup 26
I2t 22, 60
Idmtl 23, 61
Ig pickup 26
Ii pickup 24
Infrared link 5
Instantaneous current 68
Instantaneous protection 24
Ir current setting 22, 23
Isd pickup 24
K
K factor 41
L
Language 52
Latching 45, 50
Lead seal for cover 5
LEDs 5, 47, 87
Load shedding / reconnection 30, 66
Long-time I2t protection 22
Long-time Idmtl protection 23
Long-time plug 5, 97
M
M2C / M6C 45, 50
Main screen 12, 68
Maximum demand current 31, 70
Maximum demand power 32, 74
Maximum instantaneous current 31, 68
Metering menu 13, 14
ModBus 58
N
Negatively incremented energy 32, 75
Neutral CT 63
Neutral protection 23, 25
Neutral protection setting 11
No neutral protection 25, 63
O
Operation counter 86
Oversized neutral protection 25, 63
P
Parity 58
Phase rotation 29, 31, 64
Phase sequence 31, 72
Phase-to-neutral and phase-to-phase voltage 31, 71
Portable test kit 88
Positively incremented energy 32, 75
Power demand calculation 32, 56
Power factor 40
Power sign 54
Power supply 95
Protection menu 13, 20
R
Remote control 59
Remote settings 58
Resetting the alarms and fault indications 84
Resetting the contacts 45, 50
Resetting the energy values 75
Resetting the maximum demand current values 70
Resetting the maximum demand power values 74
Resetting the maximum instantaneous current values 68
Resetting the operation counter 86
RMS current 37
rms voltage 37
rP max 29, 64
S
Self-protection 5, 48
Setting dials 5, 6
Short-time protection 24
Sign convention 106
SIT 23, 61
System frequency 54
System type 55
T
Tab 7
Temperature 22, 48, 98
Test connector 5, 88
tg tripping delay 26
THD 37, 78
thd 39, 79
Thermal memory 22, 98
tr tripping delay 22, 23
Transformation ratio 54
Trip 44
Trip history 46, 85
Tripping curves 90
tsd tripping delay 24
U
U max 28
U min 28, 92
U unbal 28, 71, 92
V
VIT 23, 61
Voltage U avg 28, 31
W
Waveform 43
Waveform capture 43, 76