Sei sulla pagina 1di 16

WAPDA

NATIONAL TRANSMISSION AND DESPATCH COMPANY


SPECIFICATION P-

500kV CIRCUIT BREAKER

DESIGN DEPARTMENT
CIRCUIT BREAKERS

01 GNERAL

These Specifications cover the requirements for design, manufacture, and testing
of 550 kV circuit breakers.

The circuit breakers shall be single pole, SF6 type, with self-contained power
operated mechanism. Circuit breaker shall be designed, manufactured and tested
in accordance with latest edition of IEC 62271-100, IEC 60694 and up-to-date
experience incorporating any latest improvements in design and manufacture as
currently employed in the industry.

The circuit breakers shall feature independent pole operation. Independent pole
operation refers to the use of separate mechanism for each pole of the breaker so
that a failure of one pole to operate will not restrict the operation of the other
poles. The operating circuits for the three mechanisms shall be identical and
arranged for the three pole operation with suitable provisions for single pole
operation. Circuit breaker shall be outdoor type, and shall be supplied complete
with operating mechanism and all accessories and spare parts as required.

The design of the circuit breakers shall be such as to minimize over voltages due
to current chopping. The breaker shall be able to withstand the stresses created by
evolving faults. The circuit breaker, with the contacts in either fully open or
closed position, shall be capable of withstanding without puncture or flashover of
any of its parts, the values specified for low frequency and full wave impulse
voltage, when applied to the terminals of the breakers. The rated lightning
impulse withstand voltage level of all parts shall be based upon a pressure equal
to the minimum pressure of the interrupting medium required for a successful
interruption at the circuit breaker rating.

02 STANDRDS

The circuit breakers shall be designed, manufactured, and tested in accordance


with the latest edition of IEC publications.

In case the requirements laid down herein differ those given in the above
publications in any particular case, the circuit breakers shall comply with the
requirements listed herein referred to that item.

03 RATINGS

The circuit breakers shall be rated conforming to the requirements of latest edition
of IEC 62271-100 and IEC 60694 except as other- wise specified herein and as
follows.:-
(1) Nominal system voltage, kV, rms 500
(2) Rated voltage, (Ur) kV, rms 550

(3) Rated insulation level


:
(a) Rated one minute power frequency,
Withstand voltage, kV, rms.
- Phase to earth and between phases 620
- Across open breaker 800

(b) Rated switching impulse withstand


Voltage, kV, peak.
- Phase to earth 1175
- Between phases 1760
- Across open breaker 900(+450)

(c) Rated lightning impulse withstand


Voltage, kV, peak.
- Phase to earth and between phase 1550
- Across open breaker 1550 (+315)

(4) Rated normal frequency, Hz. 50

(5) Rated current at 50 Hz and


50 deg. C. not less than, A.

(a) Bay circuit breaker (Amps) 3150


(b) Shunt reactor circuit breaker (Amps) 2000

(6) Rated short-time withstand


current, kA, rms 40

(7) Rated peak withstand


current, kA, peak 100

(8) Rated duration of short


circuit, second 1

(9) Rated short- circuit breaking


current at rated voltage and
50 deg. C, not less than Ka, rms. 40

(10) Percentage of DC component, % 50

(11) Rated short-circuit making


current, kA, peak. 100

(12) Rated operating sequence O-0.3 sec-CO-3min-CO


(13) Rated out-of-phase
breaking current, kA,rms 10

(14) Rated line charging


breaking current, A 500

(15) Rated cable charging


breaking current, A 500

(16) Classification for re-strike


Performance during capacitive
current switching Class C2

(17) Rated break time, ms. 40

(18) Visible or audible corona


(1.1xUr//3)kV, rms
line to ground, 50 Hz None

(19) Closing resistors, ohms 400

(20) Resistor insertion time,


minimum, ms. 7.5

(21) First pole-to-clear factor 1.3

1.5 for test duty T10

(22) Classification for number of


mechanical operations the circuit
breaker shall be capable to perform Class M2

(23) Minimum creepage


distance, mm. 13750

(24) No of breaks per pole 2, 3 or 4

(25) Percentage of spare auxiliary


switches:

- Normally open 25%


- Normally closed 25%
04 SWITCHING REQUIREMENTS

The circuit breaker shall be suitable for switching transmission lines for any type
of fault. The circuit breakers shall also be capable of switching the shunt reactors.
Shunt reactors of 37 MVAR(at 500 kV) or 22 MVAR (at 500 kV) ratings are
normally used in NTDC/WAPDA system. The bidder shall be required to provide
documentary evidence to prove that the offered circuit breaker(s) shall be suitable
for transmission line and shunt reactor switching.

The circuit breakers shall b e suitable for single shot, high speed, single and three
pole automatic reclosures.

The circuit breakers shall be capable of interrupting the charging current of


transmission lines upto the value specified under sub-clause 9.03 above at rated
voltage. The requirements of capacitive current switching shall be as outlined in
IEC publication 62271-100.

The circuit breaker shall meet the requirements of simultaneity of poles specified
in Clause 5.101 of IEC 62271-100, First Edition.

The break time at 25 percent current rating with normal control voltage applied,
shall not exceed the rated break time. No restrikes at the main contacts shall be
permitted under any operating duty.

The maximum noise level of the circuit breaker, when operated to close or open
the three poles simultaneously shall be less than 140 dB(A) at 1 meter horizontal
distance at the perimeter of circuit breaker with cabinet closed.

The circuit breaker shall be designed to accommodate the voltage transients


which occur as a result of switching shunt reactor magnetizing currents.

The circuit breaker shall be suitable to meet the requirements for full out-of-phase
switching. The interrupting capability shall not be less than 25% of rated short
circuit current at a voltage across one phase of value equal to two times the
maximum rated phase voltage.

The circuit breaker shall be capable of handling the Short-line fault conditions
associated with line switching in accordance with IEC Publication 62271-100.

05 PERFORMANCE REQUIREMENTS

05.01 Temperature Rise: The temperature rise of any part of the circuit breakers shall
not exceed the temperature rise limits specified in Table 3 of IEC Publication
60694. The reference ambient temperature shall be 50 degree C.

05.02 Pre-insertion Resistors: Pre-insertion resistors shall be provided in 500 kV bay


circuit breakers to limit switching surges, or if necessary, to distribute the stress
between breaks or modify the voltage recovery rate. Rating of resistors shall be
400 ohms per pole equally divided between the breaks. Minimum pre-insertion
time shall be 7.5 ms which should be adjustable to 12 ms. The closing resistor
shall have the thermal capability for an out-of-phase making operation or two
times the fault making operations.

05.03 Voltage Equalization: The voltage across series connected interrupting contacts
of circuit breaker shall be made as nearly equal as economical design permits by
shunting interrupting contacts with suitable capacitors.

05.04 Radio and Telephone Interference:All equipment shall be designed and


constructed so as not to cause interference with radio reception or telephone
communication circuits in accordance with the most modern practice. Limits of
radio influence voltage is 500 micro volts when breakers are tested at 1.1xUr/3
line to ground voltage as per IEC 60694.

06 CONTROLS AND AUXILIARIES

06.01 Tripping and Closing Requirements: The circuit breaker closing and tripping
circuits shall be rated for 220V D.C. Electrical tripping facilities for the operating
mechanism of each pole shall be duplicated to include, but not necessarily limited
to the following:

(1) Two electrically independent and identical trip coils for each pole of
the breaker and arranged to minimize the probability of failure of one
trip coil affecting the operation of the second trip coil.

(2) Two electrically independent and identical sets of wiring, terminals


and protecting equipment for connection to two 220V DC (for 550 kV
circuit breakers) independent closing and tripping power circuits.

(3) Auxiliary switches and auxiliary circuits shall be capable of carrying at


least 10A continuously without exceeding the temperature limits
specified in table.3 of IEC 60694, second edition (1996-05) at
temperature of 50C ambient.

(4) The control system shall include circuitry to trip the breaker by
energizing both sets of trip coils if pole-disagreement should occur and
alarm shall be initiated in the control room. A timer shall be furnished
in the control cubicle to permit allowable phase discrepancy condition
during single pole auto- reclosing. The setting range of timer shall be
between 0.5 seconds to 2.0 seconds.

(5) The closing device shall be capable of closing the breaker for any
value of voltage between 85% and 110% of rated control voltage and
tripping device shall be capable of tripping the breakers for any value
of voltage between 70% and 110% of rated control voltage.
06.02 SF6 Gas Requirements: The Contractor shall supply all relays, switches and
accessories to provide for fail-safe operation of the circuit breakers during
conditions of low gas density. The density shall be sensed in two stages, the first
stage indicating an alarm. The second stage shall prevent closing or tripping of the
breakers in case the SF6 gas density is too low, for safety reasons, and shall also
give annunciation on control board. The design shall ensure the identification of
the breaker pole with low SF6 gas density. One temperature-compensated density
meter for each pole of circuit breakers shall be provided properly enclosed in a
suitable enclosure.

The SF6 gas sealing system must guarantee minimal leakage under extreme
temperature conditions and effectively restrict the entry of moisture or other
gases. Maximum permissible leakage rate shall be 1% per annum. The material
used for sealing system shall not deteriorate due to the exposure of the gas,
vapours, temperature variations and mechanical forces during the long-term
service. Maintenance of the sealing system should generally be possible without
dismantling the breaker pole and draining the SF6 gas. The breaker design shall
prevent liquefaction and partial condensation of moisture of the insulating parts of
the breaker operating mechanism and SF6 containers.

SF6 gas conforming to IEC Publication 60376 shall be used.

06.03 Additional Requirements: All circuit breakers shall be designed for closure and
tripping by remote and local electrical controls. Local electrical control shall be
from the outdoor control cubicle by means of a local CLOSE-TRIP control
switch. A LOCAL-REMOTE transfer switch provided within the outdoor control
cubicle shall select the control location. The ‘local’ operation of the circuit
breaker shall be possible only when associated disconnectors are open. A two
position ‘Maintenance – OFF’ switch shall also be provided in the outdoor
marshalling kiosk for operating the breaker when it is under maintenance. This
switch shall normally be in ‘OFF’ position. In Maintenance position, the breaker
shall be locally operable provided the associated disconnecting switches are open.
The breaker shall also be disconnected from the remote control and protection
system when the switch is placed in ‘Maintenance Position’.

Necessary provisions shall be made to exhibit indications in the control room


when the LOCAL-REMOTE transfer switch is in the LOCAL position.

All out put contacts including breaker auxiliary switch contacts shall be wired out
to terminal blocks. The circuit breakers shall be mechanically and electrically trip
free and have an anti-pumping feature.

06.04 Interlocking System: Electro-mechanical interlocking shall be supplied with


each breaker. Electro-mechanical interlocking shall be provided to prevent
operations of the associated disconnectors when circuit breaker is closed.

It shall not be possible to operate a 500 kV bay with outer breakers open and
centre breaker closed. However, a key operated switch shall be provided on the
control board for each 500 kV breaker to bypass this interlock whenever required.
07 CONSTRUCTION

07.01 General: Main assemblies shall be of modular design having same opening
distance between the fixed and moving contacts. Any interrupter shall be
removable without affecting the other interrupter or support column insulator in
any manner so that it shall be unnecessary to drain SF6 from the whole pole when
only one interrupter has to be inspected or replaced.

The circuit breaker shall be autonomous in gas supply, and no permanent external
gas accumulators or piping shall be required. For refilling purposes, portable SF6
gas bottles shall be furnished. Refilling shall be possible while circuit breaker is in
service.

The construction of the circuit breaker and the associated equipment shall ensure
safety of personnel. The isolation from live parts shall be by elevation. All
moving parts shall be suitably covered.

07.02 Phase-Spacing between Poles: The circuit breaker shall be installed with not less
than the specified distance between poles. The minimum distance between poles
of 500 kV circuit breakers are specified in Specification Drawings.

07.03 External Insulation: The external insulation shall be designed, manufactured and
tested in accordance with relevant IEC Publication. These shall be SF6 gas
insulated type. The porcelain shall be of the wet process, homogeneous, free from
cavities and other defects. Circuit breaker support columns shall be designed to
withstand internal pressure of at least three times the maximum operating
pressure. The colour of porcelain shall be chocolate brown.

07.04 Ground Terminals: Each mounting column, of each pole of the circuit breaker
shall be provided with two copper grounding lugs suitable for 185 sq.mm
standard copper conductor. Terminals shall be capable of carrying rated short time
current of the breaker.

07.05 Finish: On all outside surfaces of metal parts, one coat of metal primer and two
coats of outdoor paint shall be applied. During application, special attention shall
be given to welded seams. All exposed nuts and bolts shall be treated to prevent
corrosion.

08 OPERATING MECHANISM

The operating mechanism and appurtenances shall conform to IEC Standard


Publication No.62271-100. Each three pole breaker unit shall have independent
control mechanism, hydraulic/compressed air installation controls, valves,
receivers, safety valves, pressure switches, manometers etc. The circuit breaker
operating mechanism shall be spring, hydraulic or pneumatic type including types
involving composite arrangement of these motor mechanisms. Operating pressure
for pneumatically/hydraulically operated circuit breakers shall be obtained
through a 230V, single phase/400V, three phase motor-actuated pump/compressor
to operate the mechanism. The motor shall operate satisfactorily if voltage varies
by 85% to 110% of motor rated voltage. The pump/compressor shall be controlled
automatically by a set of multipole pressure switches maintaining the pressure
within approximately 100% of nominal rated value.

A remote flashing visual indication and an audible alarm shall be actuated at the
control board whenever pressure increases above predetermined value of pressure
or falls below the minimum operating pressure of the circuit breakers. Pressure
relief devices shall be provided to operate in case the pressure exceeds 115% of
nominal rated value. The motor and pump/compressor shall be of sufficient size
to charge the accumulator from its minimum to maximum pressure and to charge
the accumulator form zero to maximum operating pressure within minimum
possible time. The accumulator shall be of sufficient capacity to permit three
close-open operations when fully charged before the pressure drops sufficiently to
restart the pump/compressor. A pressure gauge to indicate the pressure shall be
provided at suitable location with red mark to indicate 100% of nominal rated
value.

The circuit breakers equipped with spring charged operating mechanism shall be
closed by the stored energy of charged springs. The mechanism shall be designed
such that the failure of spring will not prevent tripping and will not cause tripping
or closing. The energy stored in notor-comprssed spring shall be sufficient for an
OPEN-CLOSE-OPEN operation at rated short circuit current. The charging motor
shall be direct current. The motor shall not require more than 15 seconds to
recharge the closing springs after a close-open operation. Means shall be provided
to prevent operation of the mechanism when maintenance work is being done.

The operating mechanism shall be capable of performing the duty cycle as


specified in Clause 9.03 of these Technical Provisions.

Working parts of the mechanism shall be of corrosion resisting materials, and all
bearings, which require frequent greasing shall be equipped with pressure-type
grease fittings and shall be readily accessible without dismantling the mechanism
or housings. The mechanism and control system shall be strong, robust, positive,
fast and shall not have objectionable rebound or require critical adjustments or
frequent maintenance.

The mechanism shall be designed so that the failure of any component will not
prevent tripping if there is a tripping command, and will not cause tripping or
closing when there is no control command.

Provision shall be made on the circuit breakers for the attachment of a device to
record the operation of valves, contacts, etc., so that timing tests can be made to
verify the sequence of operation. For purposes of inspection and adjustment,
means shall be provided to permit local operation of the breaker, so designed that
the contacts of the breaker may be operated slowly for adjustment.
Mechanical position indicator to indicate the position of each pole of the breaker
shall be provided. Open position shall be indicated by using letter “O” with green
colour as background while closed position shall be indicated by letter “C” with
red as background colour. Separate operation counter shall be provided for each
pole of the circuit breaker.

Motor over-running indication feature shall be incorporated to signal the


excessive running of the motor of hydraulic pump/compressor due to any gas
leakage.

09 PROVISIONS FOR SCADA AND REMOTE CONTROL


FUNCTIONS

Provisions shall be made for remote ‘open’ and ‘close’ operations, position
indications and failure alarm (at remote stations) for each circuit breaker as
specified in Section-16 of these Technical Provisions.

Identified terminals in the control boards shall be wired to auxiliary contacts of


the circuit breakers. The auxiliary contacts shall comprise separate parts for NO
and NC potential free contacts for open and close positions respectively.

10 OUTDOOR CUBICLES AND COMPONENTS

10.01 General: Outdoor cubicles of all the circuit breakers shall be vermin proof and
weather proof, of protection Class IP54. The master control housing shall contain
all breaker indicating devices, mcbs for AC and DC circuits, closing and tripping
controls, and alarm relays for all the necessary mechanical and electrical
apparatus and accessories required. All mcbs shall be provided with auxiliary
contacts and sensitive earth fault protection for personnel safety. Separate mcbs
shall be provided for heating and lighting circuits.

There shall be a neoprene gasket between the door and frame to prevent the
ingress of moisture. Each of the cubicles shall be mounted so as to be accessible
from ground level. Structural backing shall be provided, where required, in such a
manner that the complete assembly shall be rigid, self-supporting and free of
vibration, twist and weave.

10.02 Cubicle Interior: No equipment shall be mounted less than 300 mm above the
floor of the cubicle or 150 mm from the roof. Any unused areas of panels shall be
kept free of wiring to permit the installation of possible future components.

10.03 Doors and Latches: Each cubicle shall be equipped with a hinged door with
hinges on the left.

The door shall have its edge bent inwards for rigidity. There shall be a three-point
latch and activating handle. The handle and door shall have matching projections
with a 12.5 mm diameter hole suitable for locking the cubicle door with a
padlock.

10.04 Lighting, Outlets and Telephone Jacks: Interior lighting operating from a door
switch shall be provided within each cubicle assembly.

A 240V, 5A single phase three pin convenience outlet along with its MCB to fit
standard prong plugs shall be installed inside each cubicle assembly.

A telephone jack shall be provided in each cubicle assembly. A hook for


supporting head set shall be provided conveniently close to the jack. Telephone
wiring upto control desks, relay room and PLC room in the control building shall
be provided for work during erection and maintenance.

10.05 Ground Bus: A copper ground bud bar shall be provided with tapped holes and
screws and shall be connected to the shields or associated earth continuity
conductors of all incoming cables.

10.06 Control Circuit: 220V, DC miniature circuit breakers shall be provided for
protecting DC control circuits of circuit breakers.

10.07 Terminal blocks and Terminals: Terminal blocks for control wiring shall be
molded disconnecting type with marking strips and covers. White marking strips
shall be provided for circuit designation. Each connected terminal of each block
shall have the circuit designation. Each connected terminal of each block shall
have the circuit designation. Terminal studs and wires shall be numbered or
otherwise marked in accordance with the applicable schematic and wiring
diagrams with permanent contrasting marking fluid.

Terminal blocks shall be arranged with sufficient room for easy connection of
incoming cables. Parallel rows of terminal blocks shall be spaced at least 150 mm
apart. At least 20% spare terminals shall be provided in each block or group of
blocks.

Blocks shall be mounted in vertical columns along the sides of cubicles or on


vertical panels specially provided for terminal blocks.

10.08 Component Wiring: Wiring between terminals of various devices shall be point
to point (no splicing or ‘T’ connection shall be allowed). All internal wiring shall
be neatly truncated in wiring troughs.

All groups of bundled conductors to hinged doors and panels shall use extra-
flexible wire arranged so that a twisting, rather than a bending motion is imparted
to the moving conductor bundle.

All wires shall be identified at both ends according to the interconnection


diagrams.
10.9 Heaters: Space heaters of sufficient capacity alongwith thermostat, humidistat,
control switches and circuit breakers shall be supplied for each control cabinet to
reduce condensation which may occur. ‘Auto-Off-Manual’ selector switch shall
be provided for selecting the operating mode of the haters.

10.10. Schematic Diagram: A schematic diagram of the control circuit block of the
circuit breaker shall be provided.

11 MOTORS

All motors shall conform to IEC standards for motors and as specified herein:

Fractional horsepower motors shall be rated for 230 V, single phase, 50 Hz


supply. All other and reversing motors shall be rated for 400 V, three phase, 50
Hz.

The motors shall be squirrel-cage induction type, direct on line starting, normal
starting torque, low starting current.

The motor shall be single speed having a continuous service factor of 1.0.

Motors for circuit breakers equipped with spring charged operating mechanism
will be rated for 220 V DC.

12 STRUCTURES

The structural steel supports for the circuit breakers as well as al necessary related
steel materials shall be designed in accordance with design parameters and
instructions given in Section 5 of these Provisions. Supporting structures,
mounting bolts, nuts and accessories shall be as specified in Clause 5.04.02.
Separate supporting structure shall be provided for each pole.

13 MATERIAL AND WORKMANSHIP

The material and workmanship throughout shall be of the best quality in


accordance with accepted modern practices. The design shall be such that
installation, replacements and general maintenance may be undertaken with a
minimum of time and expense. Each complete unit shall be designed for
continuous operation at full-rated capacity and liberal factors of safety shall be
used throughout the design. All screw threads and bolt sizes shall comply with
ISO Standards for metric threads.

14 SHOP CLEANING AND PAINTING

All interior and exterior surfaces of tanks, enclosures, cabinets and other metal
parts which are not galvanized and are exposed to oil or weather shall be
thoroughly cleaned by degreasing and abrasive blasting, or other equivalent
means to remove all grease, scale, corrosion, and foreign substances, subject to
the approval of the Engineer. All interiors and exteriors except tanks which shall
receive the Manufacturer’s standard treatment, shall be given at least one priming
coat and one finish coat of light coloured paint or enamel. Interiors of operating
compartments shall have a finish coat of gloss white. All exteriors shall be given
not less than 3 coats of paint consisting of primer and finish enamel. The finish
coat shall have high grey colour. The total dry film thickness of the 3 or more
coats of paint shall not be less than 0.09mm, of which not less than 50% shall be
finish enamel.

All machine-finished or bright surfaces shall be thoroughly cleaned, coated with a


suitable, easily removable, corrosion resisting compound and wrapped or
otherwise protected from damage during shipment.

Four liters of finish paint shall be furnished for re-finishing damaged surfaces
after erection.

15 TESTS

15.01 General:The circuit breakers shall be subjected to tests in the shop and at site in
the presence of the Engineer for conformity to the requirements of the
Specifications.

Six (6) certified copies of the tests made, and of the results thereof after the tests
are made, shall be furnished by the Contractor to the Engineer for approval. The
results of these tests shall be in such form as to provide means of determining
compliance with the applicable Specifications for the material tested. If any item
of the plant is of a new design or if essential parts have been redesigned,
additional test reports to verify this data shall be submitted for Engineer’s
approval.

Tests required herein shall be carried out in accordance with the latest issue of
IEC Publication of IEC-62271-100 and IEC 60694.

15.02 Type Tests : One representative circuit breaker with associated equipment out of
the circuit breakers of the same design which shall be supplied, shall be
assembled complete in the factory and type tests shall be carried out in
accordance with the latest issue of IEC Publications 62271-100 and IEC60694.
However, duly certified and complete test reports for tests carried out by an
independent authority on similar circuit breaker shall be acceptable in lieu of
actual tests. Six copies of the test reports shall be submitted for Engineer’s review
and approval.

The required type tests are as follows:-


(1) Dielectric tests.
(2) Radio interference voltage (RIV) tests.
(3) Measurement of the resistance of the main circuit.
(4) Temperature rise tests.
(5) Short-time withstand current and peak withstand current tests.
(6) Tightness tests.
(7) Electromagnetic compatibility (EMC) tests.
(8) Mechanical and environmental tests.
(9) Short circuit making and breaking tests.
(10) Capacitive current switching tests.
(11) Verification of the degree of protection.
(12) Extended mechanical endurance tests.
(13) Static terminal load test.
(14) Critical current tests.
(15) Short-line fault test.
(16) Out-of-phase making and breaking tests.
(17) Single phase and double earth fault tests, if applicable.
(18) Shunt reactor current switching tests.
(19) Contacts Opening/Closing Time: The circuit breaker shall be tested to
demonstrate that all main contacts in different poles open or close within
the times specified in clause 5.101 of IEC 62271-100.

15.03 Routine Tests: Routine tests shall be carried out on all circuit breakers and
porcelain enclosures and supports furnished under this Contract at the factor y
after final assembly, in accordance with the latest issue of IEC Publication 56. Six
copies of the certified test reports shall be submitted for Engineer’s review and
approval in accordance with these Bidding Documents. No equipment shall be
shipped until the required routine tests have been approved by the Engineer.

(1) Dielectric test on the main circuit.


(2) Dielectric test on auxiliary and control circuits.
(3) Measurement of the resistance of the main circuit.
(4) Tightness test.
(5) Design and visuals checks.
(6) Mechanical operating tests.

15.04 Porcelain Enclosures and Supports: Each porcelain enclosure and supports or
insulating tube or piping which is, or may be, subjected to internal pressure from
the breaker shall be given a pressure test of not less than 2 times the maximum
pressure to which it could be subjected in service, held for a period of one minute.

16 NAME PLATES
A non–corrodible metal nameplate shall be attached to each circuit breaker and its
operating devices in a position, which shall be clearly visible to a person standing
on the ground. The nameplate should list the data specified in Clause 5.10 of IEC
Publication 62271-100.

A nameplate shall also be attached to each piece of equipment giving full


identification and rating data by its manufacturer as specified in Sub-Clause 5.10
of IEC Publication 60694.

17 DRAWINGS AND DESCRIPTIVE DATA

17.01 Tender Drawings:The following drawings, information and descriptive data


shall be supplied with the Bid:-

(1) The requisite information required to be supplied with the Tender in


accordance with Sub-clause 9.101 of IEC Publication 62271-100 and shall
be supplied in the manner and form given therein.

(2) Outline drawings, photographs, descriptive sheets and sketches to describe


clearly the construction and operation of the circuit breaker.

(3) The details of the minor and the general maintenance requirements for
servicing and replacement of the contacts, and the requirements of
maintenance on the number of switching operations at:

(a) Full short circuit capacity (100 percent).


(b) Half short circuit capacity (50 percent).
(c) Quarter short circuit capacity( 25 percent)

(4) The minimum electrical clearance between stationary and moving


conducting parts when the circuit breaker is in the normal open position.

(5) The minimum phase spacing.

(6) Full description of any device incorporated in a circuit breaker to limit or


control the rate of rise of restriking voltage across the circuit breaker
contacts.

(7) The details of the operating mechanism, literature and catalogue data
showing full details of the opening and closing sequences of the
mechanism under all conditions.

(8) Type test reports.

(9) Instruction manual.

(10) Experience records for the offered type of breakers.

17.02 Approval of Drawings/Documents:

(1) Technical Data of circuit breakers as per Schedule- A to Bid.

(2) Approval Drawings shall show the detailed physical arrangements of the
breaker, high voltage connections, wiring and schematic diagrams of the
control scheme.

(3) Also provided shall be the transport, storage, installation, erection,


maintenance and operation instruction books. These instructions to be
written in accordance with IEC Publications 62271-100 and 60694.

(4) Impact loading of circuit breaker during the opening and closing
operations.

(5) Test reports.

(6) Any other information that the Engineer may require.

Potrebbero piacerti anche