STANDARDS AUSTRALIA
Amendment No. 3
to
AS 1288—2006
Glass in buildings—Selection and installation
Licensed to Mrs Emily Eklic on 22 March 2017. Personal use licence only. Storage, distribution or use on network prohibited.
REVISED TEXT
The 2006 edition of AS 1288 is amended as follows; the amendments should be inserted in the appropriate
places.
SUMMARY: This Amendment applies to the Foreword, Clauses 1.3, 3.3.3, 4.2, 6.5.3 and Appendix A.
Published on 2016-02-29.
AMDT Foreword
No. 3
FEB Second paragraph, delete ‘Building Code of Australia’ and replace with ‘National
2016 Construction Code (NCC)’.
the ultimate limit state design pressure for the combined loads.
NOTE: Appendix A provides guidance for determining the ultimate and serviceability limit state
design wind pressures from the procedures given in AS 4055 and AS/NZS 1170.2. It should be
ensured that the assumptions used in these simplified determinations are applicable for the glass
being designed.
AMDT Appendix A
No. 3
FEB Delete Appendix A and replace with the following:
2016
APPENDIX A
SIMPLIFIED METHOD FOR DETERMINING ULTIMATE AND
SERVICEABILITY LIMIT STATE DESIGN WIND PRESSURES
(Informative)
A1 GENERAL
The design wind pressures set out in this Appendix have been determined from the
procedures given in AS 4055 for housing, or AS/NZS 1170.2 for other buildings. The
definitions for wind regions, terrain category and topographic classification are given in the
abovementioned Standards. Although the design wind pressures set out in this Appendix
were determined from a general application of the procedures given in AS 4055 for
housing, or AS/NZS 1170.2 for other buildings, they might be more conservative than those
given by specific calculation using those Standards. Therefore, this Appendix should be
used as a conservative interpretation of AS 4055 or AS/NZS 1170.2. The design wind
pressures given in this Appendix should not be used if there are any changes to either
AS 4055 or AS/NZS 1170.2 after the date of publication of this Appendix.
TABLE A2
ULTIMATE AND SERVICEABILITY LIMIT STATE DESIGN WIND PRESSURES FOR HOUSING ONLY
the relevant design wind speeds and terrain/height multipliers given in AS/NZS 1170.2 with an
average roof height of 10 m.
The ULS and SLS design wind pressures given in Table A4 have been determined for
corner locations in buildings and may be conservative if applied to other locations. Lower
design wind pressures could be obtained for other locations in the buildings by using the
criteria specified in AS/NZS 1170.2.
TABLE A3
BUILDING GEOMETRY LIMITATIONS
APPLICABLE TO TABLES A4 AND A5
Aspect Limit
Design wind pressure Windows in walls and roofs only
Average roof height ≤10.0 m
Floor plan Rectangular or combination of rectangular
units
Internal pressures Two or three walls equally permeable, other
walls impermeable
Building importance level in SLS—25 years
accordance with the NCC ULS—500 years
Building shielding NS—No shielding
PS—Partial shielding (minimum one building
of equal height providing shielding)
Topographic multiplier See AS/NZS 1170.2 (Table 4.4)
Wind direction All directions
TABLE A4
ULTIMATE AND SERVICEABILITY LIMIT STATE DESIGN WIND PRESSURES
FOR WINDOWS IN WALLS OF BUILDINGS WITH LIMITATIONS AS DETAILED
IN TABLE A3
Ultimate and serviceability design wind pressure, kPa
TC3 ULS 1.07 1.13 1.25 1.32 1.45 1.52 1.87 1.97 2.48 3.30
SLS 0.73 0.76 0.85 0.89 0.98 1.03 1.27 1.33 1.67 2.23
TC2.5 ULS 1.32 1.39 1.54 1.62 1.78 1.87 2.30 2.42 3.04 4.06
SLS 0.89 0.94 1.04 1.09 1.20 1.26 1.55 1.64 2.06 2.74
TC2 ULS 1.56 1.64 1.82 1.91 2.10 2.21 2.72 2.86 3.59 4.80
A
SLS 1.05 1.11 1.23 1.29 1.42 1.49 1.84 1.93 2.43 3.24
TC1.5 ULS 1.96 2.06 2.28 2.40 2.63 2.77 3.41 3.59 4.51 6.02
SLS 1.32 1.39 1.54 1.62 1.78 1.87 2.30 2.42 3.05 4.07
TC1 ULS 1.96 2.06 2.28 2.40 2.63 2.77 3.41 3.59 4.51 6.02
SLS 1.32 1.39 1.54 1.62 1.78 1.87 2.30 2.42 3.05 4.07
TC3 ULS 1.72 1.81 2.01 2.11 2.32 2.44 3.00 3.16 3.97 5.30
SLS 0.81 0.85 0.94 0.99 1.09 1.14 1.41 1.48 1.86 2.48
TC2.5 ULS 2.12 2.23 2.47 2.60 2.85 3.00 3.69 3.88 4.88 6.51
SLS 0.99 1.04 1.16 1.22 1.33 1.40 1.73 1.82 2.28 3.05
TC2 ULS 2.50 2.63 2.92 3.07 3.37 3.54 4.36 4.59 5.76 7.70
B
SLS 1.17 1.23 1.37 1.44 1.58 1.66 2.04 2.15 2.70 3.60
TC1.5 ULS 2.50 2.63 2.92 3.07 3.37 3.54 4.36 4.59 5.76 7.70
SLS 1.17 1.23 1.37 1.44 1.58 1.66 2.04 2.15 2.70 3.60
TC1 ULS 3.14 3.30 3.66 3.85 4.22 4.44 5.47 5.75 7.23 9.65
SLS 1.47 1.55 1.71 1.80 1.98 2.08 2.56 2.69 3.39 4.52
TC3 ULS 3.40 3.57 3.96 4.17 4.57 4.81 5.92 6.23 7.83 10.45
SLS 1.17 1.23 1.37 1.44 1.58 1.66 2.04 2.15 2.70 3.60
TC2.5 ULS 4.17 4.39 4.87 5.12 5.62 5.91 7.27 7.65 9.62 12.84
SLS 1.44 1.51 1.68 1.77 1.94 2.04 2.51 2.64 3.32 4.43
TC2 ULS 4.93 5.19 5.75 6.05 6.63 6.98 8.59 9.04 11.36 15.17
C
SLS 1.70 1.79 1.98 2.09 2.29 2.41 2.96 3.12 3.92 5.23
TC1.5 ULS 4.93 5.19 5.75 6.05 6.63 6.98 8.59 9.04 11.36 15.17
SLS 1.70 1.79 1.98 2.09 2.29 2.41 2.96 3.12 3.92 5.23
TC1 ULS 6.18 6.51 7.21 7.59 8.32 8.75 10.78 11.34 14.25 19.02
SLS 2.13 2.24 2.49 2.62 2.87 3.02 3.72 3.91 4.92 6.56
(continued)
TABLE A4 (continued)
SLS 1.83 1.93 2.14 2.25 2.46 2.59 3.19 3.36 4.22 5.63
TC2 ULS 7.95 8.36 9.27 9.76 10.70 11.25 13.85 14.57 18.32 24.46
D
SLS 2.16 2.28 2.52 2.65 2.91 3.06 3.77 3.96 4.98 6.65
TC1.5 ULS 7.95 8.36 9.27 9.76 10.70 11.25 13.85 14.57 18.32 24.46
SLS 2.16 2.28 2.52 2.65 2.91 3.06 3.77 3.96 4.98 6.65
TC1 ULS 9.97 10.49 11.63 12.24 13.42 14.12 17.38 18.28 22.98 30.68
SLS 2.71 2.85 3.16 3.33 3.65 3.84 4.73 4.97 6.25 8.35
LEGEND:
ULS = Ultimate limit state
SLS = Serviceability limit state
NOTES:
1 The design wind pressures have been calculated using the regional wind speeds of AS/NZS 1170.2 with an
average recurrence interval of 500 years for ULS and 25 years for SLS.
2 The design wind pressures have been calculated on the basis of generalized assumptions. Detailed
calculations based on specific buildings might yield higher or lower pressures.
3 The multipliers and factors used are as follows:
(a) Direction multiplier (M d ) .................................................................................. 1.0 (any direction).
(b) Terrain/height multiplier (Mz,cats ) based on an average building height of 10 m:
(i) For Terrain Category 3 ............................................................................................... 0.83.
(ii) For Terrain Category 2.5 ............................................................................................ 0.92.
(iii) For Terrain Category 2 ................................................................................................. 1.0.
(iv) For Terrain Category 1.5 ............................................................................................ 1.06.
(v) For Terrain Category 1 ............................................................................................... 1.12.
(c) Shielding multiplier (M s ):
(i) For all terrain categories (no shielding) ......................................................................... 1.0.
(ii) For all terrain categories (partial shielding) ............................................................... 0.975.
(d) Topographic multiplier (M t ) for slopes:
(i) <0.05 (flat ground) ....................................................................................................... 1.0.
(ii) 0.05 ........................................................................................................................... 1.08.
(iii) 0.1 ............................................................................................................................. 1.16.
(iv) 0.2 ............................................................................................................................. 1.32.
(v) 0.3 ............................................................................................................................. 1.48.
(vi) 0.45 ........................................................................................................................... 1.71.
(e) Net aerodynamic shape factor C fig :
(i) For regions A and B, and C and D (SLS only) ............................................................. 1.35.
(ii) For regions C and D (ULS only) ................................................................................... 1.8.
(f) Combination factor K c .......................................................................... 0.9 (external and internal).
4 In order to use the pressures in this Table, all of the cladding elements including windows, doors and garage
doors need to be designed to resist the design winds.
Licensed to Mrs Emily Eklic on 22 March 2017. Personal use licence only. Storage, distribution or use on network prohibited.
TABLE A5
ULTIMATE AND SERVICEABILITY LIMIT STATE DESIGN WIND PRESSURES FOR ROOFS OF BUILDINGS
WITH LIMITATIONS AS DETAILED IN TABLE A3
TABLE A5 (continued)
TABLE A5 (continued)
TABLE A5 (continued)