INSTRUMENT CLOSE LOOP CHECK

I11-B
NON FIELDBUS FIELDBUS
FIELDBUS CHECKLIST
The FOUNDATION Fieldbus shall be tested using a proven Fieldbus Wiring Monitor that can test the voltage, signal levels and
wiring noise. The test shall comply with FOUNDATION™ Fieldbus System Engineering Guidelines (AG-181)

SEGMENT MEASUREMENT DATA ACCEPTANCE


Voltage 9.0V Minimum □OK □N/A
Lowest Device Signal 150-1200mV □OK □N/A
Lowest Device Signal Address N/A □OK □N/A
Lowest Device Signal Date/Time N/A □OK □N/A
Avg Fieldbus Frequency Noise (9-40kHz) 75mV Maximum □OK □N/A

Peak Fieldbus Frequency Noise (9-40kHz) 75mV Maximum □OK □N/A


Peak Fieldbus Frequency Noise
N/A □OK □N/A
Date/Time
Avg Low Frequency Noise (50Hz-4kHz) 150mV Maximum □OK □N/A
Peak Low Frequency Noise (50Hz-4kHz) 150mV Maximum □OK □N/A

Peak Low Frequency Noise Date/Time N/A □OK □N/A

Avg High Frequency Noise (50Hz-4kHz) 150mV Maximum □OK □N/A

Peak High Frequency Noise (50Hz-4kHz) 150mV Maximum □OK □N/A

Peak High Frequency Noise Date/Time N/A □OK □N/A


Shield Short No Shorts □OK □N/A
LAS Address N/A □OK □N/A
Most Recent Add/Drop Address N/A □OK □N/A
Device Add or Drop None □OK □N/A
Date/Time of Device Add/Drop N/A □OK □N/A
Number of Active Devices N/A □OK □N/A
N/A
DEVICE MEASUREMENTS N/A
Device Adress N/A □OK □N/A
Signal Level 150-1200mV □OK □N/A
Added/Dropped Not Added/Dropped □OK □N/A
Retransmits 0 □OK □N/A