Programming Guide
Software Version 4.1
Includes DGP641BL/RB
Programming Guide
DGP-848
Zone Programming................................................................................................................................................................ 5
Keyswitch Programming........................................................................................................................................................ 8
Other Settings...................................................................................................................................................................... 17
Zone Labels......................................................................................................................................................................... 17
Dialer Options...................................................................................................................................................................... 24
Communication Settings...................................................................................................................................................... 30
DGP2-641BL/RB Programming........................................................................................................................................... 46
Trouble Display.................................................................................................................................................................... 52
Module Type & Details Serial # Module Type & Details Serial #
71:________________________ ___________
When option [7] in section [502] is enabled for 1- Zone Assigned to Partition1 (Default)
Enter the 8-digit [SERIAL NUMBER] of the Combus 2- Zone Assigned to Partition 2
PGM1 to act as a zone input for two-wire smoke 3- Zone Assigned to Partition 3
detectors, the control panel will recognize PGM1 Detector or Module to which the hardwired 4- Zone Assigned to Partition 4
as input number 255. detection device is connected.
-5-
Zone Description Module Section 8-digit Serial Number Input# Section Define Assign Zone Options
1 [001] [101] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
Programming Guide
2 [002] [102] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
3 [003] [103] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
4 [004] [104] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
5 [005] [105] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
6 [006] [106] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
7 [007] [107] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
8 [008] [108] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
9 [009] [109] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
10 [010] [110] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
11 [011] [111] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
12 [012] [112] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
Zone Description Module Section 8-digit Serial Number Input# Section Define Assign Zone Options
13 [013] [113] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
14 [014] [114] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
15 [015] [115] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
16 [016] [116] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
17 [017] [117] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
18 [018] [118] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
19 [019] [119] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
DGP-848
20 [020] [120] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
21 [021] [121] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
22 [022] [122] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
-6-
23 [023] [123] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
Programming Guide
24 [024] [124] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
25 [025] [125] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
26 [026] [126] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
27 [027] [127] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
28 [028] [128] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
29 [029] [129] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
30 [030] [130] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
31 [031] [131] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
32 [032] [132] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
33 [033] [133] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
34 [034] [134] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
Zone Description Module Section 8-digit Serial Number Input# Section Define Assign Zone Options
35 [035] [135] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
36 [036] [136] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
37 [037] [137] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
38 [038] [138] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
39 [039] [139] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
40 [040] [140] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
41 [041] [141] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
DGP-848
42 [042] [142] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
43 [043] [143] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
44 [044] [144] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
-7-
45 [045] [145] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
Programming Guide
46 [046] [146] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
47 [047] [147] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
48 [048] [148] 1 2 3 4 5 6 7 8
________________ __________ __/__/__/__/__/__/__/__ __/__/__ ___ ___
To clear a zone’s numbering (sections [001] to [048]):
For LCD keypads:
1.Enter a section number between [001] and [048].
2.Press [0] and then [ENTER] to save and exit.
Enter 8-digit [SERIAL NUMBER] of the 2- Maintained Keyswitch [8] *Instant Arming
Module to which the keyswitch is 3- Generates Utility Key Event on
Open only * Select only one. If all are off
connected. 4- Generates Utility Key Event on keyswitch will regular arm
Open & Close
-8-
Keyswitch
Keyswitch Location Module Section 8-digit Serial Number Input# Section Define Assign
Options
Programming Guide
Schedule Programming
Each Schedule determines when users are permitted access. Holidays are programmed in sections [381] to [392]. Schedule
00 = access granted at all times.
Section Schedule Intervals Start Time (from) End Time (to) Days (turn ON or OFF)
S M T W T F S H
Interval A ___ ___: ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[361] 01
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[362] 02
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[363] 03
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[364] 04
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
Interval A ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
[365] 05
Interval B ___ ___ : ___ ___ ___ ___ : ___ ___ 1 2 3 4 5 6 7 8
The Start and End Time of an Interval cannot cross over into another day. For example, to program a shift from
10:00 p.m. one day to 6:00 a.m. the next morning, you must program Interval 1A: Start Time 22:00 and End
Time 23:59 then program Interval 1B Start Time 00:00 and End Time 06:00. The schedule will not be interrupted
between 23:59 and 00:00.
Holiday Programming
The holidays are determined in these sections. When [H] is enabled in sections [361] to [375], access is permitted to users
during the days programmed in sections [381] to [392].
Section Month Days Programmed (turn ON or OFF access):
First Screen Second Screen Third Screen Fourth Screen
Days 01 to 08 Days 09 to 16 Days 17 to 24 Days 25 to 31
[381] January 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7*
[382] February 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 * * *
[383] March 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7*
[384] April 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 **
[385] May 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7*
[386] June 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 **
[387] July 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7*
[388] August 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7*
[389] September 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 **
[390] October 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7*
[391] November 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 **
[392] December 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7*
*option not used in this screen
Note 1* Any Arming Force Stay Instant Strobe Silent Audible Fire Alarm
Method Arm Arm Arm (until alarm is Alarm Alarm (until alarm is
1 = Status 1 cancelled) (until alarm is (until alarm is cancelled or
cancelled or cancelled or bell is cut off)
bell is cut off) bell is cut off)
Note 1* Ready Exit Delay Entry Delay Trouble Alarm Zone Master or Keypad
2 = Status 2 Status Memory Bypassed Installer Lockout
(armed or not) Programming
Note 1* Intellizone Fire Delay Auto Arm N/A Any Tamper Zone Low Fire Loop Zone
3 = Status 3
Delay Battery Supervision
NOTE 1*:
0 = Occurs in all partitions enabled in the system (see section [500]).
1 = Partition 1 3 = Partition 3
2 = Partition 2 4 = Partition 4
8 = Occurs in at least one partition enabled in the system.
† : If you select a group and set all options to OFF, all users/zones/selections of that group will be enabled (result is “ANY” of
that group). For example, if you select A0 and set all 8 options to OFF, the PGM will activate/deactivate whenever a user
between 1 and 8 arms the system.
DGP-848 - 14 - Programming Guide
Second Feature Select Programming
First Digit Digit 1 2 3 4 5 6 7 8
0 Chime Chime Chime Chime Siren Siren Siren Siren
Partition 1 Partition 2 Partition 3 Partition 4 Partition 1 Partition 2 Partition 3 Partition 4
1 N/A N/A N/A N/A Smoke Ground Kissoff N/A
Reset Start
2 System Dialer Module Combus N/A N/A N/A Timer Loss
Trouble Trouble Trouble Trouble
3 AC Fail Battery fail Aux. Limit Bell Limit No Bell ROM Error N/A N/A
4 = Status 4
4 TLM Fail to Fail to Fail to Fail to Fail to N/A N/A
Com1 Com2 Com3 Com4 Com PC
5 Module Module Module Module Fail Printer Fault Module AC Module Module Aux.
Tamper ROM Error TLM to Com Fail Battery Fail fail
Phone#
6 Missing Missing Any N/A N/A N/A Global Com- Combus Module Com-
Keypad Module bus Failure Overload bus Com Fail
Other Settings
Zone Labels
For instructions on how to enter letters and special characters when using an LCD or Grafica keypad, refer to the LCD
keypad’s Installation Manual or Grafica’s User Manual. A complete Grafica user manual is available on our website at
www.paradox.com.
Section Zone # Zone Label Section Zone # Zone Label
System Options
Bold = Default setting
Section [500]: System Options
Option OFF ON
[1] Partition 1 N Disabled N Enabled
[2] Partition 2 N Disabled N Enabled
[3] Partition 3 N Disabled N Enabled
[4] Partition 4 N Disabled N Enabled
[5] Bell/Siren Output in Partition 1 N Disabled N Enabled
[6] Bell/Siren Output in Partition 2 N Disabled N Enabled
[7] Bell/Siren Output in Partition 3 N Disabled N Enabled
[8] Bell/Siren Output in Partition 4 N Disabled N Enabled
[1] [2]
N Yes N No
Generate Supervision Failure if detected on a
[3]
Bypassed Wireless Zone
N Disabled N Enabled
Restrict Arming on Wireless Transmitter
[4]
Supervision Failure
[5] [6]
N Disabled N Enabled
Ring Back: keypad beeps if disarmed after
[8]
alarm
N Disabled N Enabled
Ring Back: keypad beeps if disarmed after
[8]
alarm
N Disabled N Enabled
Ring Back: keypad beeps if disarmed after
[8]
alarm
N Disabled N Enabled
Ring Back: keypad beeps if disarmed after
[8]
alarm
N Disabled N Enabled
Bell/Siren upon Communication Failure if
[8]
system is armed
*Since “Request for Exit” events can occur often, the Event Buffer may fill up quickly.
[561] __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
MONITORING STATION/PAGER TELEPHONE NUMBER 1 (press [ENTER] if less than 32 digits)
[562] __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
MONITORING STATION/PAGER TELEPHONE NUMBER 2 (press [ENTER] if less than 32 digits)
[563] __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
MONITORING STATION/PAGER TELEPHONE NUMBER 3 (press [ENTER] if less than 32 digits)
[564] __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
MONITORING STATION/PAGER TELEPHONE NUMBER 4 (press [ENTER] if less than 32 digits)
For North American installations using either SIA or Contact ID reporting formats, enter *70 and then either P (4-second
pause) or W (wait for second dial tone) before the phone number in sections [560] to [564] to disable call-waiting.
Table 2: Special Telephone Number Keys
Function LCD Grafica Function LCD Grafica
* [STAY] Clear [CLEAR] Left action key (Clear)
# [FORCE] [#] Delete [TRBL] —
Switch to Tone Dialing (T) [ARM] (press key until desired Delete from cursor to the end [ACC] —
Wait for second dial tone (W) [DISARM] letter/symbol appears) Insert space [MEM] —
4-second pause (P) [BYP]
Ademco slow, Silent Knight fast, SESCOA, Ademco express or Pager formats:
Key-in desired 1 or 2-digit hexa values from 0 to FF.
Ademco format:
Use sections [790] to [795] to program a set of default Ademco report codes from the Automatic Report Code List on page
36. Then to program the remaining report codes or to change some of the defaults, enter the individual sections and key-in
the desired 2-digit hexa values found in the Contact ID Report Code List on page 38.
SIA format:
Use sections [790] to [795] to program a set of default SIA report codes from the Automatic Report Code List on page 36.
Codes that have not been set to default can be set to default manually by entering FF in the appropriate section. To disable
reporting of an event, enter 00 in the appropriate section.
[601]: __ /__ Access code 5 [609]: __ /__ Access code 37 [617]: __ /__ Access code 69
__ /__ Access code 6 __ /__ Access code 38 __ /__ Access code 70
__ /__ Access code 7 __ /__ Access code 39 __ /__ Access code 71
__ /__ Access code 8 __ /__ Access code 40 __ /__ Access code 72
[602]: __ /__ Access code 9 [610]: __ /__ Access code 41 [618]: __ /__ Access code 73
__ /__ Access code 10 __ /__ Access code 42 __ /__ Access code 74
__ /__ Access code 11 __ /__ Access code 43 __ /__ Access code 75
__ /__ Access code 12 __ /__ Access code 44 __ /__ Access code 76
[603]: __ /__ Access code 13 [611]: __ /__ Access code 45 [619]: __ /__ Access code 77
__ /__ Access code 14 __ /__ Access code 46 __ /__ Access code 78
__ /__ Access code 15 __ /__ Access code 47 __ /__ Access code 79
__ /__ Access code 16 __ /__ Access code 48 __ /__ Access code 80
[604]: __ /__ Access code 17 [612]: __ /__ Access code 49 [620]: __ /__ Access code 81
__ /__ Access code 18 __ /__ Access code 50 __ /__ Access code 82
__ /__ Access code 19 __ /__ Access code 51 __ /__ Access code 83
__ /__ Access code 20 __ /__ Access code 52 __ /__ Access code 84
[605]: __ /__ Access code 21 [613]: __ /__ Access code 53 [621]: __ /__ Access code 85
__ /__ Access code 22 __ /__ Access code 54 __ /__ Access code 86
__ /__ Access code 23 __ /__ Access code 55 __ /__ Access code 87
__ /__ Access code 24 __ /__ Access code 56 __ /__ Access code 88
[606]: __ /__ Access code 25 [614]: __ /__ Access code 57 [622]: __ /__ Access code 89
__ /__ Access code 26 __ /__ Access code 58 __ /__ Access code 90
__ /__ Access code 27 __ /__ Access code 59 __ /__ Access code 91
__ /__ Access code 28 __ /__ Access code 60 __ /__ Access code 92
[607]: __ /__ Access code 29 [615]: __ /__ Access code 61 [623]: __ /__ Access code 93
__ /__ Access code 30 __ /__ Access code 62 __ /__ Access code 94
__ /__ Access code 31 __ /__ Access code 63 __ /__ Access code 95
__ /__ Access code 32 __ /__ Access code 64 __ /__ Access code 96
[629]: __ /__ Access code 5 [637]: __ /__ Access code 37 [645]: __ /__ Access code 69
__ /__ Access code 6 __ /__ Access code 38 __ /__ Access code 70
__ /__ Access code 7 __ /__ Access code 39 __ /__ Access code 71
__ /__ Access code 8 __ /__ Access code 40 __ /__ Access code 72
[630]: __ /__ Access code 9 [638]: __ /__ Access code 41 [646]: __ /__ Access code 73
__ /__ Access code 10 __ /__ Access code 42 __ /__ Access code 74
__ /__ Access code 11 __ /__ Access code 43 __ /__ Access code 75
__ /__ Access code 12 __ /__ Access code 44 __ /__ Access code 76
[631]: __ /__ Access code 13 [639]: __ /__ Access code 45 [647]: __ /__ Access code 77
__ /__ Access code 14 __ /__ Access code 46 __ /__ Access code 78
__ /__ Access code 15 __ /__ Access code 47 __ /__ Access code 79
__ /__ Access code 16 __ /__ Access code 48 __ /__ Access code 80
[632]: __ /__ Access code 17 [640]: __ /__ Access code 49 [648]: __ /__ Access code 81
__ /__ Access code 18 __ /__ Access code 50 __ /__ Access code 82
__ /__ Access code 19 __ /__ Access code 51 __ /__ Access code 83
__ /__ Access code 20 __ /__ Access code 52 __ /__ Access code 84
[633]: __ /__ Access code 21 [641]: __ /__ Access code 53 [649]: __ /__ Access code 85
__ /__ Access code 22 __ /__ Access code 54 __ /__ Access code 86
__ /__ Access code 23 __ /__ Access code 55 __ /__ Access code 87
__ /__ Access code 24 __ /__ Access code 56 __ /__ Access code 88
[634]: __ /__ Access code 25 [642]: __ /__ Access code 57 [650]: __ /__ Access code 89
__ /__ Access code 26 __ /__ Access code 58 __ /__ Access code 90
__ /__ Access code 27 __ /__ Access code 59 __ /__ Access code 91
__ /__ Access code 28 __ /__ Access code 60 __ /__ Access code 92
[635]: __ /__ Access code 29 [643]: __ /__ Access code 61 [651]: __ /__ Access code 93
__ /__ Access code 30 __ /__ Access code 62 __ /__ Access code 94
__ /__ Access code 31 __ /__ Access code 63 __ /__ Access code 95
__ /__ Access code 32 __ /__ Access code 64 __ /__ Access code 96
[707]: __ /__ Bell Output (disconnect [709]: __ /__ Module fail to com. [711]: __ /__ Tel# 1 fail to com.
or overload) __ /__ Printer fault __ /__ Tel# 2 fail to com.
__ /__ Timer Loss __ /__ Module AC failure __ /__ Tel# 3 fail to com.
__ /__ Fire Loop Trbl. __ /__ Module battery failure __ /__ Tel# 4 fail to com.
__ /__ N/A
Section # Description
Sets all the report codes in the following sections to the
default values from the “Automatic Report Codes List”:
[790] ALL CODES [600] to [718]
[791] ARMING & DISARMING CODES [600] to [654]
[792] ALARM & ALARM RESTORE CODES [655] to [680]
[793] TAMPER & TAMPER RESTORE CODES [681] to [705]
[794] TROUBLE & TROUBLE RESTORE CODES [706] to [716]
[795] SPECIAL CODES [717] to [718]
Disarm with Master Code (##) 1 4A1 - Open by user OP - Opening Report
Disarm with User Code (##) 1 4A1 - Open by user OP - Opening Report
Disarm with Keyswitch (##) 1 4A9 - Keyswitch Open OS - Opening Keyswitch
Disarm after alarm* with Master Code (##) 1 4A1 - Open by user OP - Opening Report
Disarm after alarm* with User Code (##) 1 4A1 - Open by user OP - Opening Report
Disarm after alarm* with Keyswitch (##) 1 4A1 - Keyswitch Open OS - Opening Keyswitch
Cancel alarm** with Master Code (##) 1 4A6 - Open by User OR - Disarm from Alarm
Cancel alarm** with User Code (##) 1 4A6 - Open by User OR - Disarm from Alarm
Cancel alarm** with Keyswitch (##) 1 4A6 - Keyswitch Open OS - Opening Keyswitch
TLM trouble restore 3 351 - Telco 1 fault restore LR - Phone Line restoral
AC Failure restore 3 3A1 - AC loss restore AR - AC Restoral
Battery Failure restore 3 3A9 - Battery test restore YR - System Battery Restoral
Auxiliary supply trouble restore 3 3AA - System trouble restore YQ - Power Supply restored
Bell output current limit restore 3 321 - Bell 1 restore YH - Bell Restored
Bell absent restore 3 321 - Bell 1 restore YH - Bell Restored
Clock programmed 3 625 - Time/Date Reset JT - Time Changed
Fire loop trouble restore 3 373 - Fire trouble restore FJ - Fire Trouble Restore
Bus fault restore 3 333 - Expansion module failure restore ER - Expansion Restoral
Module tamper restore 3 145 - Expansion module tamper restore TR - Tamper Restoral
Module ROM_RAM_error restore 3 3A4 - Rom checksum bad restore YG - Parameter Changed
Module TLM restore 3 352 - Telco 2 fault restore LR - Phone Line Restoral
Printer fault restore 3 336 - Local printer failure restore VR - Printer Restore
Module AC restore 3 3A1 - AC loss restore AR - AC Restoral
Module battery restore 3 3A9 - Battery test failure restore YR - System Battery Restoral
Module Auxiliary supply restore 3 3AA - System trouble restore YQ - Power Supply Restored
Fail to communicate with monitoring station 1 354 - Fail to communicate YC - Communication Fails
Module RF low battery 1 384 - RF transmitter low battery XT - Transmitter Battery Trouble
Module RF battery restore 3 384 - RF transmitter battery restore XR - Transmitter Battery Restoral
Module RF supervision trouble 1 381 - Loss of supervision - RF US - Untype Zone Supervision
Module RF supervision restore 3 381 - Supervision restore - RF UR - Untyped Zone Restoral
To program user labels, refer to the LCD Keypad System Manager’s Manual.
Access Control User Access Control User Options (default: all options Off)
Options Set desired [1] Access Card is activated
Feature Select options [2] Can disarm with Access Card
Programming [3] Access Card with Extended Unlocked Period
[4] [5] [6] [7] Feature
Press the [S] key on off off off Can Regular Arm with Access Card
on on off off Can Stay Arm with Access Card
on off on off Can Instant Arm with Access Card
Enter on off off on Can Force Arm with Access Card
Access Card
[8] Can open armed Access Control Doors
Software Reset
Performing a software reset will set certain parameters to default values. To do so:
1. Make sure the RESET jumper on the control panel is on.
2. Enter Programming Mode (see page 1).
3. Enter the 3-digit [SECTION] corresponding to the software reset you wish to perform:
Section # Description
Entering this section will reset all programmable sections from [001] to [896] (except sections [451] to [498],
[555], [556], [560], [790] to [795], and [800]) to default values. The Zone Labels, Panel ID, PC Password, PC
[970]
Telephone Number, Installer Code, System Master Code, Event Buffer, and Automatic Report Codes will not
be reset.
Entering this section resets the following Access Control sections: [301] to [332], [340] to [355], [361] to [375],
[974]
[381] to [392], and [537].
Entering this section will reset all Zone and Keyswitch programming sections from [001] to [056], and [101] to
[975]
[156] to default values.
Entering this section will reset the following sections to default values: [200] to [261], [270] to [274], [400] to
[976]
[409], and [440] to [442].
[977] Entering this section will reset sections from [500] to [522] to default values.
Entering this section will reset the following communication sections to default values: [521] to [536], [550] to
[978]
[554], [561] to [564], and [600] to [718].
[979] Entering this section will reset all user code sections from [801] to [896] to default values.
[STAY] Test Report: Sends the “Test Report” report code programmed in section [717] to the monitoring station.
[FORCE] Call WinLoad Software: Will dial the PC telephone number programmed in section [560] in order to initiate
communication with a computer using the WinLoad Upload/Download software.
[ARM] Answer WinLoad Software: Will force the control panel to answer a call made by the monitoring station that is
using the WinLoad upload/download software.
[DISARM] Cancel Communication: Cancels all communication with the WinLoad Software or with the monitoring station
until the next reportable event.
[MEM] Installer Test Mode: The installer test mode will allow you to perform walk tests where the bell or siren will
squawk to indicate opened zones. Press [MEM] again to exit. Partitions can not be armed if the Installer Test
Mode is enabled.
[TRBL] Start Module Scan: The keypad will display the serial number of each module on the bus.
[ACC] For LCD Keypads (DGP2-641BL/RB) only
Combus Voltmeter: Verify if the combus is supplying sufficient power. A reading of 12.3V indicates that the
voltage is too low. The voltage may drop during the control panel battery test.
1. Using Table 3, calculate the total amount of power required by each device, module, and accessory in the system. Please
take into account devices connected to the control panel’s PGM outputs. Since the BELL output has its own power supply,
do not include the sirens connected to it in the calculation.
2. If the Grand Total is less than 700mA, go to step 3. If the value is greater, you will require an external power supply (see
External Power Supply on page 45) to provide the additional power needed. Proceed with step 3.
3. Due to the degradation of a power signal over long distances, EACH length or run of wire in the system can support only
a specific amount of power. Using Table 4, determine how much power each length of wire can support. Please note that
the total amount of power can never surpass 700mA
.
Table 4: Power Limitations For Each Run of Wire
Gauge: 18AWG Surface: 0.823mm2 Gauge: 22AWG Surface: 0.326mm2 Gauge: 24AWG Surface: 0.205mm2
Length of each Available Power Length of each Available Power Length of each Available Power
run of wire (mA) run of wire (mA) run of wire (mA)
30m(100ft.) 700 30m(100ft.) 700 30m(100ft.) 700
61m(200ft.) 700 61m(200ft.) 682 61m(200ft.) 429
91m(300ft.) 700 91m(300ft.) 454 91m(300ft.) 286
122m(400ft.) 700 122m(400ft.) 341 122m(400ft.) 214
152m(500ft.) 690 152m(500ft.) 273 152m(500ft.) 171
183m(600ft.) 575 183m(600ft.) 227 183m(600ft.) 143
213m(700ft.) 493 213m(700ft.) 195
244m(800ft.) 431 244m(800ft.) 170
274m(900ft.) 383 274m(900ft.) 151
305m(1000ft.) 345 305m(1000ft.) 136
457m(1500ft.) 230
610m(2000ft.) 172
762m(2500ft.) 138
914m(3000ft.) 115
152m (500ft) from control panel 610m (2000ft) from control panel
152m (500ft) from control panel’s AUX. output 152m (500ft) from power supply
Therefore this run = max. 273mA Therefore this run = max. 273mA
Do not use the same transformer for the control panel and the external power supplies. Modules should never
be installed more than 914m (3000 ft) from the control panel.
Within the Same Building: Strip the outer jacket at one end of the shielded cable to expose the shield and connect the
shield to the control panel ground (not the dialer ground), while leaving the shield at the other end of the cable open (floating).
Across Separate Buildings: Strip the outer jacket at one end of the shielded cable to expose the shield. In the same
building that houses the control panel, connect the exposed shield to a cold water pipe or any other earth ground available,
while leaving the shield at the other end of the cable open (floating). The same configuration applies for any subsequent
building.
DGP2-641BL V1.1
DGP2-641RB V2.0
The keypad’s serial number can be found on the keypad’s PC board. The keypad’s serial number can also be viewed by pressing and holding the [0] key,
entering the [INSTALLER CODE] and then entering section [000].
U = Default setting
SECTION [001] : Keypad Partition Assignment SECTION [002]: Assigning Doors to Partitions †
Option OFF ON Option OFF ON
[1] Partition 1 N Disabled U Enabled [1] Door Assigned to Partition1 N Disabled U Enabled
[2] Partition 2 N Disabled U Enabled [2] Door Assigned to Partition 2 U Disabled NEnabled
[3] Partition 3 N Disabled U Enabled [3] Door Assigned to Partition 3 U Disabled NEnabled
[4] Partition 4 N Disabled U Enabled [4] Door Assigned to Partition 4 U Disabled NEnabled
[5] Partition 5 (DGP-NE96 only) N Disabled U Enabled [5] Door Assigned to Partition 5 (DGP-NE96 only) U Disabled NEnabled
[6] Partition 6 (DGP-NE96 only) N Disabled U Enabled [6] Door Assigned to Partition 6(DGP-NE96 only) U Disabled NEnabled
[7] Partition 7 (DGP-NE96 only) N Disabled U Enabled [7] Door Assigned to Partition 7 (DGP-NE96 only) U Disabled NEnabled
[8] Partition 8 (DGP-NE96 only) N Disabled U Enabled [8] Door Assigned to Partition 8 (DGP-NE96 only) U Disabled NEnabled
SECTION [005] : Beep on Trouble SECTION [006]: PGM and Tamper Options
Option OFF ON Option OFF ON
[1] System & Clock Trouble Beep U Disabled N Enabled [1] PGM State‡ U N.O. N N.C.
U Deactivation N PGM Timer
N Enabled
[2] PGM Deactivation Mode‡
[2] Communicator Trouble Beep U Disabled
Event
[3] Module & Combus Trouble Beep U Disabled N Enabled [3] PGM Base Time‡ U 1 second N 1 minute
[4] All Zone Trouble Beep U Disabled N Enabled [4] PGM Override‡ U Disabled N Enabled
[5] to [6] Future Use N N/A N N/A [5] Keypad Tamper U Disabled N Enabled
[7] Time Format U 24Hr clock N 12Hr clock [6] to [8] Future Use N N/A N N/A
[8] Future Use N N/A N N/A
[008] __/__/__ (000 to 255; see option [3] in section [006]) PGM Timer ‡ 005
[009] __/__/__ (000 to 255 seconds added to section [008]) Door Unlocked Period Extension † 015
[010] __/__/__ (000 to 255 seconds) Door Left Open Interval † 060
[011] __/__/__ (000 to 25 seconds) Door Left Open Pre-Alarm Timer † 015
[012] __/__/__ (000 to 25 seconds) Beep Timer for Door Left Open Alarm † 005
[013] __/__/__ (000 to 25 seconds) Beep Timer for Door Forced Open Alarm † 005
Only Event Groups 000 to 055 and 070 can be used to program the module’s PGM.
Message Programming
Each section from [101] to [148], [200] to [204] and [301] to [396] contains one message with a maximum of 16 characters. The sections contain the
following messages:
Sections [101] to [148] = “Zone 01” to “Zone 48” respectively
Section [200] = “Paradox Security”
Sections [201] to [204] = “First Area”, “Second Area”, “Third Area”, and “Fourth Area”
Sections [301] to [396] = “Code 01” to “Code 96” respectively
After entering the section corresponding to the desired message, the message can be re-programmed to suit your installation needs as detailed in
Table 4. For example, section [101] “Zone 01” can be changed to “FRONT DOOR”.
[520] Copy the LCD keypad sections [001] to [396] and all labels and messages to the Memory Key.
The memory key will only function with a keypad that has the DGP2 or DNE prefix in the model number. Only the PMC-4 memory key will
function with DGP2 and DNE keypads.
Combus Voltmeter
To verify if the combus is supplying sufficient power, press and hold the [0] key, enter the [INSTALLER CODE] and press the [ACC] button. A reading of 10.5V or
lower indicates that the voltage is too low. The voltage may drop during the control panel battery test.
Reset jumper
Warning:
Disconnect the
battery before
replacing the fuse.
Warning:
Disconnect
telephone line
before servicing
AUX POWER
Refer to transformer requirements below for Auxiliary Power Output.
Also, refer to Calculating Power Requirements (on page 42). To
connect additional wiring to auxiliary power, use the red (+) and black
(-) keypad connectors. Auxiliary power will shut down if current
exceeds 1.1A.
For UL and C-UL warnings, refer to the Warnings section in the Digiplex Reference and Installation Manual.
Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limited to the purchase price of the
defective product. Your use of this product signifies your acceptance of this warranty.
BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional
warranties that are binding on the Seller.
© 2003-2005 Paradox Security Systems Ltd. All rights reserved. Specifications may change without prior notice. One or more
of the following US patents may apply: 6215399, 6111256, 5751803, 5721542, 5287111, 5119069, 5077549, 5920259 and
5886632. Canadian and international patents may also apply.
Digiplex, Grafica, InTouch, Magellan, and WinLoad are trademarks or registered trademarks of Paradox Security Systems
Ltd. or its affiliates in Canada, the United States and/or other countries.
For technical support in Canada or the U.S., call 1-800-791-1919 for English or 1-866-912-0600 for French, Monday to Friday
from 8:00 a.m. to 8:00 p.m. EST. For technical support outside Canada and the U.S., call 00-1-450-491-7444, Monday to Friday
from 8:00 a.m. to 8:00 p.m. EST. Please feel free to visit our website at www.paradox.com.