Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
instructions
Belt-driven
screw compressors
S 6 ... S 29 series
1 Index
Operating instructions
for the belt-driven
screw compressors
BOGE KOMPRESSOREN
Postfach 10 07 13
D-33507 Bielefeld
Lechtermannshof 26
D-33739 Bielefeld
No. 596.0566.01
Cover charge: P 5,00
Index
Safety instructions for 01. Ensure that no commissioning and maintenance work on the compressor
compressor operation is undertaken until these operating instructions are understood.
02. Only use the compressor for its intended use, as described in these
operating instructions.
03. The owner must ensure
– that only appropriately trained and authorized personnel work on this
compressor.
– that the operating, maintenance and repair personnel has been
made fully familiar with all safety instructions, and that they are being
observed.
– that the compressor is only operated in a safe operating condition.
04. Avoid any operating method which may impair the safety of the com-
pressor.
05. Do not exceed the limit value for the final compression pressure specified
on the type plate.
06. Do not operate the compressor without the attendant protection and
safety devices.
Do not dismantle any built-in safety devices or put them out of operation.
Ensure that all cladding and doors is closed prior to commissioning/
starting up the compressor and is not opened during operation.
07. Place the compressor out of operation as described in these operating
instructions, when dismantling the cladding or safety devices for repair
or maintenance work. Reattach all cladding and safety devices immedi-
ately upon completion of the repair or maintenance work.
08 Only operate the compressor using the additional equipment (options)
recommended or authorized by the manufacturer.
09. Undertake conversions and modifications of the compressor only in
agreement with BOGE, taking all relevant safety regulations into consid-
eration.
The manufacturer is not liable for damages resulting from independent
modifications on the compressor.
10. Never start the compressor when one or serveral parts (e.g. cable, plug)
are damaged, when not in perfect working order, when damage is de-
tected or suspected.
11. Observe all safety and danger signs directly attached on the compressor!
12. The compressed air oil tank is subject to the Pneumatic Tank Directive
and must be inspected at the prescribed intervals.
Safety instructions for 1. Ensure that maintenance work is only carried out by appropriately trained
maintenance and repair persons.
of the compressor 2. Ensure that setting work, malfunction rectification and repair is only car-
ried out by specialists or appropriately trained persons.
3. Prior to maintenance or repair work:
– Switch off the main switch.
– Secure main switch against unintentional switch-on.
– Check to ensure that all parts have been isolated.
– Disconnect the compressor from the compressed air network (relieve
or block pressurized lines).
4. Exercise extreme caution during repair or maintenance work requiring
the compressor to be operational.
Ensure that no persons are located in the hazardous area.
5. Ensure that work on the electrical equipment is only undertaken by
qualified electricians.
6. Work on voltage carrying parts and devices are not permitted. Exceptions
are governed by the appropriate regulations, e.g. DIN VDE 0105.
7. Only use original spare parts, compressor oils and operating
materials released by BOGE during repair or maintenance.
8. The operator is responsible to check the compressor daily for externally
visible damage and defects, and to immediately report any changes
(including operational behaviour).
9. When the automatic restart (AWAL) is activated, the compressor restarts
automatically following a voltage loss.
Prerequisite: The line pressure is lower than the switch-on pressure set
on the operating pressure switch.
Accident prevention The owner of a compressor plant is responsible to ensure that it is properly
regulations installed, operated and maintained.
We urgently recommend that owners in the Federal Republic of Germany
read the following regulations of the Main Association of the Industrial Em-
ployers' Liability Insurance:
– Accident prevention regulation 13.4 “Compressor” (VBG 16)
– Pressure receiver regulation
– Safety requirements EN 1012 „Compressors“
The regulations are available at the following locations:
Berufsgenossenschaft
Carl-Heymanns-Verlag KG, Luxemburger Str. 449, 50939 Köln
Beuth Verlag GmbH, 10772 Berlin
For operation of the compressor plant outside the Federal Republic of Ger-
many, the accident prevention regulations of the owner country must be
observed in addition to the data contained in these operating instructions.
In the event that measures are required above and beyond the legal regula-
tions specified in the Federal Republic of Germany or the data contained in
these operating instructions, then it is of utmost importance that these be
carried out prior to commissioning the compressor plant.
The compressor and its additional equipment must not be installed and
commissioned until the operating instructions are understood.
Symbols used In these operating instructions, important safety instructions and tips are
identified by the following symbols:
ATTENTION!
This symbol indicates information warning of possible hazards which might
destroy or damage the compressor.
WARNING: Voltage!
This symbol indicates information warning of life threatening electrical volt-
age levels.
It indicates work which must be exclusively performed by skilled electricians.
This symbol indicates information and tips concerning the economical and
careful operation of the compressor.
Symbols on the The following symbols and warning signs are fitted on the compressor:
compressor
Warning:
Hot surfaces: Do not touch.
Warning:
The unit is operated by remote control, and might start without warning.
Note:
Instructions for the operating personnel must be read.
Prohibited:
Never open the valve before the air hose (connection to the compressed air
network) is connected.
Intended use BOGE S series screw compressor, including its additional equipment, is ex-
clusively intended for the compression of air.
The air taken in must not contain any explosive or chemically instable gases
or vapours.
Do not exceed the specified final compression temperature.
Inadmissible use Never direct the produced compressed air towards persons. Danger to life!
Transport damage BOGE does not accept any liability for breakage or transport damage.
Please inspect the compressor immediately after delivery and direct dam-
age claims to the last haulier - even when the packing is not damaged!
To safeguard claims against the haulier we recommend leaving the machine,
devices and packing material in the same condition as they were in when
the damage was detected.
In the event of any other complaints, please inform us within six days after
arrival of the delivery.
Data Enter the data of your compressor from the type plate or enclosed data
on the type plate sheet in the illustration below. This will ensure that in the event of enquiries,
you will always have the most important data to hand.
Type
Year of construction
Serial number
F. a. d. m3/min
Maximum service pressure bar
Motor speed min–1
Motor power kW
Service Please do not hesitate to contact BOGE service if you have any questions.
Please call:
++49 / 52 06 / 6 01-0
In the event of inquiries, always specify the following data of your compres-
sor to prevent any delays.:
– Type
– Year of manufacture
– Machine number
ATTENTION!
Only BOGE service technicians or persons authorized by BOGE in writing
may repair or alter the compressor during the warranty period. Otherwise all
warranty claims will expire!
Type S6 S8 S 10 S 15 S 20 S 24 S 29
Dimensions
– Height (silenced) [mm] 720 720 770 770 1150 1150 1150
– Height (super silenced) [mm] 1650 1650 1750 1750 2135 2135 2135
– Width [mm] 850 850 890 890 1200 1200 1200
– Depth [mm] 690 690 810 810 850 850 850
Weight
– silenced [kg] 140 150 170 180 300 315 315
– silenced / super silenced [kg] 170 180 210 220 350 365 365
Compressor
max. final compression temperature [°C] 110 110 110 110 110 110 110
Volume flow according to
PN 2 CPTC 2 at:
– pmax = 18 bar [m3/min] 0,55 0,83 1,18 1,65 2,40 2,80 3,35
– pmax = 10 bar [m3/min] 0,48 0,72 1,06 1,45 2,06 2,45 2,85
– pmax = 13 bar [m3/min] 0,36 0,58 0,91 1,25 1,70 2,05 2,45
Drive motor
Rated power [kW] 4 5,5 7,5 11 15 18,5 22
Rated speed
– 50 Hz [min-1] 3000 3000 3000 3000 3000 3000 3000
– 60 Hz [min-1] 3600 3600 3600 3600 3600 3600 3600
Protection type IP 55 55 55 55 55 55 55
Design IMB 3 3 3 3 3 3 3
ISO class F F F F F F F
Electrical connection
Mains voltage 1) [V] 400 400 400 400 400 400 400
Frequency 1) [Hz] 50 50 50 50 50 50 50
Min. fuse protection 2) [A] 16 20 35 35 50 50 50
Recommended fuse protectoin 2) [A] 20 25 35 35 50 63 63
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 400 V / 50 Hz. The fuse values change in the case of other mains voltages and frequencies.
Typ S6 S8 S 10 S 15 S 20 S 24 S 29
Safety valve
Activation pressure at:
– pmax = 8 bar [bar] 11 11 11 11 11 11 11
– pmax = 10 bar [bar] 11 11 11 11 11 11 11
– pmax = 13 bar [bar] 14 14 14 14 14 14 14
2
) Compressors for other operating pressures Pmin = Pmax – 1 bar
Function principle The air end operates according to the displacement principle. In the housing,
of the air end the main and secondary screws are driven by means of an electric motor
and V-belt.
Both screws have screw-shaped profiles, intermeshing without contact.
Together with the housing wall, these screws form chambers which gradually
reduce in size, seen in air flow direction.
Rotation of the rotors causes the air taken in to be compressed to the final
pressure in the chambers.
During compression oil is continuously injected into the air end. This having
a cooling, sealing and lubricating function.
Air circuit
1
3 4 5
2
8 7 Fig. 2.1:
6
Components of
the air circuit
1 = Intake filter
The intake filter cleans the air suctioned by the air end.
2 = Intake regulator
The intake regulator opens (load operation) or closes (idling operation or
standstill) the suction line depending on the operating condition of the com-
pressor.
3 = Air end
The air end compresses the suctioned air.
4 = Compressed air/oil receiver
The compressed air separates from the oil under the force of gravity in the
compressed air/oil receiver.
5 = Oil separator
The oil separator separates the residual oil contained in the compressed air.
6 = Minimum pressure check valve
The minimum pressure check valve does not open until the system pressure
has increased to 3.5 bar. This causes a rapid build-up of the system pressure
and ensures lubrication in the starting phase. Once the compressor has
been switched off, the check valve prevents the compressed air from flowing
back out of the mains line.
7 = Compressed air after-cooler (air and water cooled)
The compressed air is cooled in the compressed air after-cooler, causing
the water contained in the air to condensate.
8 = Stop valve
The screw compressor may be isolated from the mains by means of the stop
valve.
Oil circuit The oil injected into the air end has the following function:
– It dissipates the compression heat (cooling)
– It seals the gaps between the screws and between the screws and
housing
– It lubricates the bearings
5 6
2
4
Fig. 2.2:
Components of the oil circuit
Supply pressure For the compressor, the pressure downstream of the check valve is termed
the supply pressure. The control system switches the compressor on and off
during operation depending on the supply pressure.
Operating states All screw compressor controls are based on three basic operating states:
1. Load operation
– The compressor delivers its maximum amount of compressed air.
– It consumes its maximum energy.
2. Idling operation
– The compressor runs but does not deliver any compressed air.
– It consumes approx. 75% less energy than in load operation.
– When compressed air is required, it switches to load operation without
delay.
– Idling operation reduces switching frequencies which can damage the
drive motor, and reduces wear of the system.
3. Standstill ready for operation
– The compressor is standing still but ready for operation.
– When compressed air is required, it switches automatically to load
operation.
Operating modes The two most important operating modes are achieved by combining the
three operating states:
1. Intermittent operation
In intermittent operation the energy balance is perfect.
– The compressor operates in load operation.
– Upon reaching the switch-off pressure pmax the compressor switches to
standstill. It does not consume any energy.
– Once the pressure has dropped to the switch-on pressure pmin the com-
pressor switches back to load operation.
2. Continuous operation
Continuous operation limits the drive motor switching cycles and reduces
wear to the system.
– The compressor operates in load operation.
– Upon reaching the switch-off pressure pmax the compressor switches to
idling operation.
– Once the pressure has dropped to the switch-on pressure pmin the com-
pressor switches from idling operation back to load operation.
Operating pressure Operating pressue switch Q controls compressor operation within the set
switch switching limits.
Proportional controller The proportional controller is an additional control device intervening in the
(option) sequences of the intake regulator.
The intake regulator only opens as far as necessary to supply the current
compressed air requirement. Thus the compressor saves compression
energy.
A compressor with proportional controller is able to supply its ’delivered
quantity variable between 0% and 100%. However, the energy consumption
does not reduce accordingly. Therefore, a control is only practical between
50% and 100% of the delivered quantity.
The proportional controller is factory set to a delivered quantity between
50% and 100% of the compressor capacity.
The proportional controller closes when the desired delivered quantity has
dropped below 50% of the compressor capacity. The compressor then oper-
ates in idling operation (continuous operation) or switches off (intermittent
operation).
Delivery volume display The proportional controller is equipped with a delivery volume display.
The delivery volume display is located behind the operating and control field.
The rings indicate the present delivery volume of the compressor.
red
blue red: 25% of the delivery volume
blue: 50% of the delivery volume
green
green: 75% of the delivery volume
green: 100% of the delivery volume
Piston rod completely retracted: 0% of the delivery volume.
General The safety devices guarantee a high degree of operational safety, in connec-
tion with the BOGE ARS monitoring system.
When one of the safety devices responds, the control system reacts as
follows:
– The compressor is immediately switched off.
– A flashing fault number in the left field of the display indicates the cause
of the fault.
ATTENTION!
Do not operate the compressor without built-in safety devices.
Do not dismantle the safety devices or put them out of operation.
Safety temperature Safety temperature limiting device switches off the compressor once the
limiting device maximum admissible final compression temperature has been reached.
The compressor does not switch on when dropping below the minimum
temperature.
– Switch off the compressor (OFF button). Fault is acknowledged.
– Rectify the fault.
– Switch on the compressor (ON button).
Safety valve Safety valve Q on the compressed air/oil receiver prevents the maximum
admissible pressure being exceeded. When the maximum pressure is ex-
ceeded (e.g. incorrect setting of the operating pressure switch), the entire
1 delivery volume of the compressor is ejected.
Monitoring The following monitoring devices are standard for BOGE ARS control sys-
the drive motor tems:
The drive motor is monitored by PTC resistors.
General Please observe the generally accepted safety and accident prevention regu-
lations when transporting the compressor. BOGE accepts no liability for
damage caused by improper transport!!
ATTENTION!
The compressor is delivered filled with oil.
Do not tilt during transport!
Crane transport
ATTENTION!
Do not subject the cladding to force during transport.
Protect the compressor using wooden spacers (see arrows).
Remove the transport timbers.
Screw compressors
S 6 - S 29:
Connections and
spacing, silenced
1 Electrical connection m
2 Compressed air outlet
3 Exhaust air
4 Distance to wall
5 Distance to wall in case of straight compressed
air outlet
6 Distance to wall in case of angular compressed
air outlet
7 Safety clearance according to VDE 0100
section 729
8 Mounting with wall brackets only with angular
compressed air outlet
9 Operation side
10 Servicing side
11 Supply air
12 Condensate
13 Mains supply
Silenced
G B Dimension
[kg] N/cm²] a b c d e f g h i j k l m
S6 140 <10 850 720 540 440 450 580 390 255 620 250 190 280 G 1/2
S8 150 <10 850 720 540 440 450 580 390 255 620 250 190 280 G 1/2
S 10 170 11 890 770 590 490 565 700 430 295 670 300 230 320 G 1/2
S 15 180 12 890 770 590 490 565 700 430 295 670 300 230 320 G 1/2
S 20 300 19,5 1150 930 760 – – 850 – – – 300 340 340 G 3/ 4
S 24 315 20,5 1150 930 760 – – 850 – – – 300 340 340 G1
S 29 315 20,5 1150 930 760 – – 850 – – – 300 340 340 G1
G = Weight
B = The static pressures are below the admisible valves.
Ventilation
Amount of air Fan capacity required Supply air opening
for ventilation room of operation
[m3/h] [m3/h] [m2]
S6 800 1800 0,25
S8 1000 2270 0,3
S 10 1300 3025 0,4
S 15 1700 3700 0,5
S 20 2500 5000 0,62
S 24 3800 7600 0,94
S 29 3800 7600 0,94
The values apply to all sizes.
Screw compressors
S 6 - S 29:
Connections and
spacing, super silenced
1 Electrical connection
2 Compressed air outlet
3 Exhaust air
4 Distance to wall
5 Distance to wall in case of straight compressed
air outlet
6 Distance to wall in case of angular compressed
air outlet
7 Safety clearance according to VDE 0100
section 729
8 Mounting with wall brackets only with angular
compressed air outlet
9 Operation side
10 Servicing side
11 Supply air
12 Condensate
13 Mains supply
super silenced
G B Dimension
[kg] [N/cm²] a b c d e f g h i j k l m
S6 170 11 875 870 690 290 470 580 670 1650 325 250 190 280 G 1/2
S8 180 12 875 870 690 290 470 580 670 1650 325 250 190 280 G 1/2
S 10 210 14 940 970 790 340 585 700 730 1750 350 300 230 320 G 1/2
S 15 220 15 940 970 790 340 585 700 730 1750 350 300 230 320 G 1/2
S 20 350 24 1200 1150 980 395 750 850 990 2120 400 300 340 340 G 3/4
S 24 365 24 1200 1150 980 395 750 850 990 2120 400 300 340 340 G1
S 29 365 24 1200 1150 980 395 750 850 990 2120 400 300 340 340 G1
G = Weight
B = The static pressures are below the admisible valves.
Amount of air, fan capacity and supply air opening see page 3.2.
Screw compressors
SD 6 - SD 29:
Connections and
spacing, super silenced
mounted on
compressed air
refrigeration drier
1 Electrical connection
2 Compressed air outlet
3 Exhaust air
4 Distance to wall
5 Distance to wall in case of straight compressed
air outlet
6 Distance to wall in case of angular compressed
air outlet
7 Safety clearance according to VDE 0100
section 729
8 Mounting with wall brackets only with angular m
compressed air outlet
9 Operation side
10 Servicing side
11 Supply air
12 Condensate
13 Mains supply
super silenced
G B Dimension
[kg] [N/cm²] a b c d e f g h i j k m
SD 16 210 13 875 1215 1040 470 580 680 1960 325 250 190 280 G 1/ 2
SD 18 220 14 875 1215 1040 470 580 680 1960 325 250 190 280 G 1/ 2
SD 10 250 16 943 1265 1090 585 700 730 2060 350 300 255 G 1/ 2
SD 15 260 17 943 1265 1090 585 700 730 2060 350 300 255 G 1/ 2
SD 20 400 26 1227 1495 1325 750 850 990 2480 400 300 170 340 G 3/ 4
SD 24 425 27 1227 1495 1325 750 850 990 2480 400 300 170 340 G1
SD 29 425 27 1227 1495 1325 750 850 990 2480 400 300 170 340 G1
G = Weight
B = The static pressures are below the admisible valves.
Amount of air, fan capacity and supply air opening see page 3.2.
Screw compressors
S 6 - S 29:
Connections and
spacing, silenced
and super silenced
with compressed air
container
1 Electrical connection
2 Compressed air outlet
3 Exhaust air
4 Distance to wall
5 Distance to wall in case of straight compressed
air outlet
6 Distance to wall in case of angular compressed
air outlet
7 Safety clearance according to VDE 0100
section 729
8 Mounting with wall brackets only with angular
compressed air outlet
9 Operation side
10 Servicing side
11 Supply air
12 Condensate
13 Mains supply
G B Dimension
Ltr. kg [N/cm²] a b c d e f g h i j k l m n o p q
S 16/150 150 245 11 1550 1170 950 400 285 G 1/2 500 570 773 ø 19 400 2100 325 250 280 690 380
S 16/250 250 285 11 1650 1270 1120 500 370 G 1/2 600 670 773 ø 19 410 2200 325 250 280 690 380
S 16/350 350 310 14 1850 1300 1150 550 380 G 3/4 600 670 773 ø 19 540 2230 325 250 280 690 380
S 16/500 500 350 18 1920 1360 1210 600 405 G1 600 670 1100 ø 24 455 2290 325 250 280 690 380
S 18/250 250 295 12 1650 1270 1120 500 370 G 1/2 600 670 773 ø 19 410 2200 325 250 280 690 380
S 18/350 350 320 14 1850 1300 1150 550 380 G 3/4 600 670 773 ø 19 540 2230 325 250 280 690 380
S 18/500 500 360 19 1920 1360 1210 600 405 G1 600 670 1100 ø 24 455 2290 325 250 280 690 380
S 10/250 250 325 13 1650 1320 1170 500 370 G 1/2 600 670 773 ø 19 410 2300 350 300 320 790 440
S 10/350 350 350 16 1850 1350 1200 550 380 G 3/4 600 670 773 ø 19 540 2330 350 300 320 790 440
S 10/500 500 390 20 1920 1410 1260 600 405 G1 600 670 1100 ø 24 455 2390 350 300 320 790 440
S 10/750 750 460 24 2000 1560 1470 750 480 G 11/4 600 730 1100 ø 24 495 2540 350 300 320 790 440
S 15/350 350 360 16 1850 1350 1200 550 380 G 3/4 600 670 773 ø 19 540 2330 350 300 320 790 440
S 15/500 500 400 21 1920 1410 1260 600 405 G1 600 670 1100 ø 24 455 2390 350 300 320 790 440
S 15/750 750 470 25 2000 1560 1470 750 480 G 11/4 600 730 1100 ø 24 495 2540 350 300 320 790 440
S 20/750 750 600 32 2000 2000 1790 750 480 G 11/4 600 730 1100 ø 24 495 2930 400 300 340 980 560
S 24/750 750 615 33 2000 2000 1790 750 480 G 11/4 600 730 1100 ø 24 495 2930 400 300 340 980 560
S 29/750 750 615 33 2000 2000 1790 750 480 G 11/4 600 730 1100 ø 24 495 2930 400 300 340 980 560
G = Weight B = The static pressures are below the admisible valves.
Amount of air, fan capacity and supply air opening see page 3.2.
Screw compressors
SDM 6 - SDM 15:
Connections and
spacing, silenced
and super silenced
with container and
diaphragm drier
1 Electrical connection
2 Compressed air outlet
3 Exhaust air
4 Distance to wall
5 Distance to wall in case of straight compressed
air outlet
6 Distance to wall in case of angular compressed
air outlet
7 Safety clearance according to VDE 0100
section 729
8 Mounting with wall brackets only with angular
compressed air outlet
9 Operation side
10 Servicing side
11 Supply air
12 Condensate
13 Mains supply
G B Dimension
l [kg] [N/cm²] a b c d e f g h i j k l m n o p q r
SDM 6/150 150 265 12 1550 1170 950 1100 1320 400 285 G 1/2 500 570 773 ø 19 400 2100 325 250 280 800
SDM 6/250 250 305 12 1650 1270 1120 1270 1420 500 370 G 1/2 600 670 773 ø 19 410 2200 325 250 280 800
SDM 6/350 350 330 15 1850 1300 1150 1300 1450 550 380 G 3/4 600 670 773 ø 19 540 2230 325 250 280 800
SDM 6/500 500 370 19 1920 1360 1210 1360 1510 600 405 G1 600 670 1100 ø 24 455 2290 325 250 280 800
SDM 8/250 250 315 13 1650 1270 1120 1270 1420 500 370 G 1/2 600 670 773 ø 19 410 2200 325 250 280 800
SDM 8/350 350 340 15 1850 1300 1150 1300 1450 550 380 G 3/4 600 670 773 ø 19 540 2230 325 250 280 800
SDM 8/500 500 380 20 1920 1360 1210 1360 1510 600 405 G1 600 670 1100 ø 24 455 2290 325 250 280 800
SDM 10/250 250 345 14 1650 1320 1170 1370 1520 500 370 G 1/2 600 670 773 ø 19 410 2300 350 300 320 840
SDM 10/350 350 370 17 1850 1350 1200 1400 1550 550 380 G 3/4 600 670 773 ø 19 540 2330 350 300 320 840
SDM 10/500 500 410 21 1920 1410 1260 1460 1610 600 405 G1 600 670 1100 ø 24 455 2390 350 300 320 840
SDM 10/750 750 480 25 2000 1560 1470 1670 1760 750 480 G 11/4 600 730 1100 ø 24 495 2540 350 300 320 840
SDM 15/350 350 380 17 1850 1350 1200 1400 1550 550 380 G 3/4 600 670 773 ø 19 540 2330 350 300 320 840
SDM 15/500 500 420 22 1920 1410 1260 1460 1610 600 405 G1 600 670 1100 ø 24 455 2390 350 300 320 840
SDM 15/750 750 490 26 2000 1560 1470 1670 1760 750 480 G 11/4 600 730 1100 ø 24 495 2540 350 300 320 840
G = Weight B = The static pressures are below the admisible valves.
Amount of air, fan capacity and supply air opening see page 3.2.
Screw compressors
SD 6 - SD 29:
Connections and
spacing, silenced
and super silenced
with container and
built-on compressed air
refrigeration drier
1 Electrical connection
2 Compressed air outlet
3 Exhaust air
4 Distance to wall
5 Distance to wall in case of straight compressed
air outlet
6 Distance to wall in case of angular compressed
air outlet
7 Safety clearance according to VDE 0100
section 729
8 Mounting with wall brackets only with angular
compressed air outlet
9 Operation side
10 Servicing side
11 Supply air
12 Condensate
13 Mains supply
G B Dimension
Ltr. [kg] [N/cm²] a b c d e f g h i j k l m n o p q r
SD 6/250 250 335 13 1650 1490 1120 1120 1640 500 370 G 1/2 670 773 ø 19 320 2200 325 250 280 690 380
SD 6/350 350 360 16 1850 1520 1150 1150 1670 550 380 G 1/2 670 773 ø 19 450 2230 325 250 280 690 380
SD 6/500 500 400 21 1920 1580 1210 1210 1730 600 405 G 1/2 670 1100 ø 24 365 2290 325 250 280 690 380
SD 8/250 250 345 13 1650 1490 1120 1120 1640 500 370 G 1/2 670 773 ø 19 320 2200 325 250 280 690 380
SD 8/350 350 370 16 1850 1520 1150 1150 1670 550 380 G 1/2 670 773 ø 19 450 2230 325 250 280 690 380
SD 8/500 500 410 21 1920 1580 1210 1210 1730 600 405 G 1/2 670 1100 ø 24 365 2290 325 250 280 690 380
SD 10/350 350 400 18 1850 1520 1200 1230 1720 550 380 G1/2, G1 670 773 ø 19 450 2330 350 300 320 790 440
SD 10/500 500 440 26 1920 1580 1260 1290 1780 600 405 G1/2, G1 670 1100 ø 24 365 2390 350 300 320 790 440
SD 10/750 750 510 27 2000 1730 1470 1500 1930 750 480 G1/2, G1 730 1100 ø 24 405 2540 350 300 320 790 440
SD 15/350 350 410 18 1850 1520 1200 1230 1720 550 380 G1 670 773 ø 19 450 2330 350 300 320 790 440
SD 15/500 500 450 23 1920 1580 1260 1290 1780 600 405 G1 670 1100 ø 24 365 2390 350 300 320 790 440
SD 15/750 750 520 27 2000 1730 1470 1500 1930 750 480 G1 730 1100 ø 24 405 2540 350 300 320 790 440
SD 20/750 750 670 35 2000 1850 1790 1790 2000 750 480 G1 730 1100 ø 24 750 2930 400 300 340 980 560
SD 24/750 750 695 36 2000 1850 1790 1790 2000 750 480 G1 730 1100 ø 24 750 2930 400 300 340 980 560
SD 29/750 750 695 36 2000 1850 1790 1790 2000 750 480 G1 730 1100 ø 24 750 2930 400 300 340 980 560
G = Weight
B = The static pressures are below the admisible valves.
Amount of air, fan capacity and supply air opening see page 3.2.
Screw compressors
Duplex unit
S 6 - S 15:
1 Electrical connection
2 Compressed air outlet
3 Exhaust air
4 Distance to wall
5 Distance to wall in case of straight compressed
air outlet
6 Distance to wall in case of angular compressed
air outlet
7 Safety clearance according to VDE 0100
section 729
8 Mounting with wall brackets only with angular
compressed air outlet
9 Operation side
10 Servicing side
11 Supply air
12 Condensate
13 Mains supply
G B Dimension
l [kg] [N/cm²] a b c d e f g h i j k l m n o p q
S 6/500 500 579 30 2180 1350 1170 600 405 G1 600 670 1100 ø 24 455 2290 325 250 280 690 380
S 8/500 500 599 32 2180 1350 1170 600 405 G1 600 670 100 ø 24 455 2290 325 250 280 690 380
S 10/750 750 745 39 2270 1550 1370 750 480 G 11/4 600 730 1100 ø 24 495 2540 350 300 320 790 440
1
S 15/750 750 765 40 2270 1550 1370 750 480 G 1 /4 600 730 1100 ø 24 495 2540 350 300 320 790 440
G = Weight
B = The static pressures are below the admisible valves.
Amount of air, fan capacity and supply air opening see page 3.2.
Installation conditions – Protect compressed air receivers against damage through mechanical
for compressed air effects (e.g. falling objects).
receivers – Operate the compressed air receiver and its equipment from a safe
location.
– Adhere to safety areas and safety clearances.
– Ensure that the compressed air receiver stands securely. It must not shift
or tilt due to external forces. This also includes the additional weight dur-
ing a pressure test!
– Ensure that the compressed air receiver is easily accessible from all sides
(for recurring tests).
– Ensure that the factory label is clearly visible.
– Ensure that compressed air receivers are adequatly protected against
corrosion.
Installation surface A level industrial floor without foundation is adequate for the installation of the
compressor. No special fastening elements are required.
Fire protection The following applies to rooms in which compressors with oil injection cool-
ing are to be installed:
– For compressors with motor ratings exceeding 40 kW, ensure that the
compressor room is equipped with special fire protection.
– Install compressors with motor ratings exceeding 100 kW in a separate
fire protected room.
Sound protection Only install compressors in workrooms if the sound pressure level of
their measuring surfaces does not exceed 85 dB(A).
Admissible The compressor room must be clean, dry, cool and free of dust.
environmental
influences Admissible ambient temperatures
Maximum ambient temperature (for air cooling): + 40°C
Minimum ambient temperature: + 5°C
ATTENTION!
Nonobservance of the admissible ambient temperature may lead to the
following problems:
– The compressor will switch off when the admissible final compres-
sion temperature is exceeded or gone below.
– Pipe lines and valves will freeze up at low temperatures.
– Damage due to reduced lubricating ability of the compressor oil.
Ventilation If the following instructions are not observed, the admissible final
compression temperature may be exceeded.
In this case, the compressor will switch off automatically.
Attention!
Arrange the compressor intake openings or ducts such, that dangerous
admixtures (e.g. explosive or chemically unstable materials) cannot be
drawn in.
Ventilators
Ensure that the heated exhaust air is not aken in again.
If necessary, the heated air must be extracted by ventilators.
To ensure perfect cooling even at higher temperatures in the summer, the
ventilators must be designed as follows:
– The ventilator capacity must be rated approx. 10 - 15% higher than the
sum of the cooling air quantity required for all machines operated in the
room (VDMA Code of Practice sheet 4363 “Ventilation of compressor
rooms”).
– For free-standing installation, the cooling air requirement specified in the
table corresponds to the required ventilator capacity.
Cooling air requirement Please refer to the following table for the cooling air requirement and size of
the supply air openings for your compressor. Ensure that flaps and weather
protection grids have the necessary free cross section. We generally recom-
mend contacting a specialist company for performing the duct construction
work and planning.
Table 1: Cooling air requirement, required opening and duct cross sections.
* The cooling air requirement was based on a 4° C temperature difference between the ambient
temperature and the outside temperature.
Ventilation possibilities
A B
C D
Condensate The air taken in contains water in form of vapour, which turns into conden-
disposal sation during compression.
ATTENTION!
The condensate contains oil. Never lead it into the public sewage system
without prior treatment.
Strictly observe the effluent disposal laws of your local authorities.
Oil-water separator
The BOGE-ÖWAMAT separates the oil from the condensate.
The cleaned water may be fed directly into the public sewage system.
The oil is collected in a separate container. Dispose of the oil according to
environmental regulations.
If, due to special operating conditions, the oil should emulsify, use an emul-
sion cracking plant.
General BOGE screw compressor units are supplied ready for connection. Only the
work described in the following paragraphs needs to be carried out during
the installation.
ATTENTION!
Only have the installation work carried out by appropriately trained persons
or specialists.
Connecting the – Connect the compressor to the compressed air network or a compressed
compressor to the air receiver.
compressed air network For this, use a BOGE high pressure hose.
Acess protection
device Fig. 3.1:
Remove warm air hood
ATTENTION!
To avoid damage to the cooler, support the screw connection at the cooler outlet
using a spanner.
2
Q Electrical connection
R Compressed air connection
Fig. 3.2:
Connecting the compressor
ATTENTION!
Do not loosen or change the sealed nuts for setting the spring tension.
1
1
Checking the oil level BOGE compressors are supplied with a complete oil filling.
Prior to commissioning/start up, check the oil level as described in chapter
6.3 and page 6.9.
Main switch
According to accident prevention regulation VBG 5, §12, the customer is
responsible to provide the following safety measures:
Compressor plants having a drive motor larger than 3 kW and current
intensities larger than 16 amperes must be equipped with a lockable main
switch (DIN VDE 0660, ...0105) and series fuses.
Please refer to the technical data (chapter 2.1) for the design and fuse rating.
Rated voltage
The data of your mains (operating voltage, control voltage, type of current,
frequency, ...) must coincide with the data on the type plate on the switch
cabinet.
In the event of deviations, please contact the BOGE service or your supplier.
Never omit a single safety step! Otherwise, you will risk injuries due to
restarting, electric shock or self-releasing parts.
WARNING!
When the automatic restart (AWAL) is activated, the compressor will auto-
matically restart following a power failure.
Prerequisite: the mains pressure is lower than the switch-on pressure set on
the operating pressure switch.
Checking ATTENTION!
the rotational Always check the rotational direction of the drive motor prior to commission-
direction ing/initial start up.
Even brief operation in the wrong direction of rotation (more than approx.
5 seconds) may cause total destruction of the air end!
Ensure that the rotational direction coincides with the rotational direction
arrow on the air end.
– Switch on the main switch.
– Switch the compressor on and immediately off again to check the rota-
tional direction.
Opening the stop valves Open ball valve 1 on the compressor delivery.
Commissioning Following an extended stoppage of more than 2 months, fill a small amount
following extended of oil in the suction controller prior to starting the compressor.
stoppages
ATTENTION!
Only fill the suction controller with the grade of oil used to operate the com-
pressor.
Never mix different oil grades and brands.
General BOGE screw compressors are equipped with the modern ARS control sys-
tem concept (Autotronic, Ratiotronic, Supertronic).
One of these control systems will be built into your compressor, depending
on the desired equipment and the monitoring functions.
ARS is an integrated control and monitoring concept, having two objectives:
– Energy savings and thus reduction of ongoing costs
– Prolonging the service life of the compressor due to wear which is as low
as possible
All programmed data is stored in a memory module (EEPROM), which can
be written on electrically and deleted.
Thus the stored information is even available following a power failure.
Micro-controller The BOGE ARS control system concept dynamically adapts to the respec-
tive operating conditions. A micro-controller assumes the following three
tasks:
1. Dynamic full load/idling control system
The micro-controller continuously determines the current consumption
trend of the plant. It automatically adjusts to alterations in the compressed
air requirement as this varies throughout the day.
2. Automatic selection of the most economical operating mode
The micro-controller calculates the optimum operating mode from the
current operating state and a programmed ideal value, also taking into
account the constant compressor system data (e.g. delivery quantity,
receiver volume, motor switching cycles) as well as the current variables
(e.g. compressed air consumption, supply and non-supply times, pressure
increase and decrease speed).
In order to save operating costs, it always strives for the most economical
intermittent operation.
3. Automatic optimization of the motor switching cycles
The micro-controller calculates the optimum number of motor switching
cycles. This protects the drive motor and prolongs the service life of the
plant.
Modular design All ARS control systems comprise of standard components which can be
purchased separately. They are also easy to retrofit. In this manner, the
control systems can be optimally adapted to individual customer wishes.
Rapid replaceability of the controls in the event of failures increases the
availability of the compressor. This eliminates time consuming and costly
trouble shooting by specialists.
Emergency
STOP button
Access protection
device
Field: Supply
Symbol exploration pressure gauge
Emergency
STOP button
Access protection
device
Field: Supply
Symbol exploration pressure gauge
Supply pressure gauge Constant The supply pressure is the pressure at the com-
display of the pressor delivery behind the minimum pressure
supply pressure check valve.
Access protection Warm air hood and switch cabinet cover from one
device part. To gain access to the switch cabinet, remove
the entire hood.
– Unscrew the access protection device
– Lift and remove the hood.
NOTE:
The access protection device has
no electrical function!
Flow chart Orientation during – Through the numbers specified in the flow chart,
malfunction or you will be able to determine at a glance, to
maintenance work which component part a malfunction message
(Autotronic and Ratiotronic) or maintenance
message (Ratiotronic) refers.
INFO button Select information – Keep INFO key pressed down for approx. 2 sec-
to be displayed onds. The display will change to the selected
information.
Four different information texts may be invoked:
Press Info key once: Total operating hours.
Press Info key twice: Idle operating hours
Press Info key 3 times: Version number of the
control system
Press Info key 4 times: Lamp test
Press Info key 5 times: Final compression tem-
perature
Autotronic
Total operating hours Display of – Keep the INFO key pressed down for approx.
total operating 2 seconds.
hours The display changes from the final compression
°C temperature to the total operating duration. (The
dot to the right of the middle digit is displayed.)
Idle hours Display of idle – Press the INFO key in the „Total operating
hours duration“ display mode.
The display will change to the idle running
duration.
x 100
(The dot next to the RH digit is displayed.)
Operating fault Display of the – If a fault occurs in one of the monitored compo-
malfunctioning nents, the control system will react as follows:
component – The compressor is switched off immediately.
– The left digit flahes.
The fault is displayed.
3 digit seven segment dis- Significance of the Q Correct code entered (programming mode
play decimal points „PM“)
°C R Operating hours
S Idling hours
R+S Automatic restart is programmed (AWAL)
QRS
Ratiotronic
Continuous operation – The dot on the right next to the LH digit is dis-
played.
– The compressor operates between the indi-
°C vidual supply stages in idling operation
(continuous operation).
Intermittent operation – The dot on the right next to the 2nd digit from
the left is displayed.
– The compressor switches off between the indi-
vidual supply stages (intermittent operation).
Total operating hours Display of the total – Keep the INFO key pressed down for approx.
operating duration 2 seconds.
The display changes from the final compression
temperature to the total operating hours.
(The dot on the right next to the 3rd digit from
the right is displayed.)
Idle hours Display of the idle – Press the INFO key in the „Total operating
running duration hours“ display mode.
The display changes to the idle hours.
(The dot on the right next to the 2nd digit from
the right is displayed.)
Operating fault Display of the – If a fault occurs in one of the monitored compo-
malfunctioning nents, the control system will react as follows:
component – The compressor is switched off immediately.
– The digit of the malfunctioning component
flashes on the left in the display.
(1) Final compression temperature
(2) Drive motor
Options:
(4) Rotational direction/ V-belt tear/system depres-
surization
(5) Pressure limitation / safety pressure switch
(9) System pressure build-up
– All other displays will be cancelled.
– Please refer to the section "Faults" for causes
and measures to rectify the faults.
General On the basis of the current operating data, the control system calculates the
optimum operating mode and selects it automatically.
The parameters can be set.
The parameters are divided into two groups, in order to prevent accidentally
altering the preset parameter values.
The operator may alter the parameter values directly in the operating level.
Altering the parameter values in the service level may lead to damage to
the compressor. Therefore, the service level is protected by a code number.
These parameters can only be accessed by BOGE service technicians.
ATTENTION!
Never alter the value of a parameter if you are not aware of its precise signifi-
cance! Otherwise this could result in a completely false regulating behaviour
of the control system!
Never experiment with the settings of the parameter values!
If in doubt, call the BOGE Service.
– Press the INFO and OFF buttons simultaneously for approx. 5 seconds.
+ The control sytem changes to the programming mode.
The value set for the first parameter appears in the display.
01 Total hours
02 Idle hours
03 Code entry ... 000 bis 999
04 Compressor type 1 0 = piston / 1= screw
05 Star/delta switch-over time 6 6 8 3 to 15 seconds
06 After-run time 30 30 30 30 to 999 seconds
07 Motor switching cycles per hour 10 30 25 1 to 60
08 Automatic restart (AWAL) 0 0 = no / 1 = yes
Restart delay with
09 0 30 30 0 to 360 seconds
AWAL
Anti-switch-on timer active after
10 0 30 30 0 to 360 seconds
switch-off
11 Max. final compression temperature 100 90 to 130 °C
12 Min. final compression temperature -10 –20 to +10 °C
Percentual intermittent operation
13 100 0 to 100 percent
proportion
Anti swtich-on timer active in
14 0 0 = no / 1= yes
intermittent operation
Display of final compression 1 1= Celsius
15
temperature 2=Fahrenheit
Maintenance intervals / motor
16 0 0 to 300 (x 100 h)
set point value
Maintenance intervals / motor
17 0 –99 to 300 (x 100 h)
actual value (remaining time)
Maintenance requirement /
18 0 1 = yes
acknowledge motor
Maintenance intervals / compressor
19 0 0 to 300 (x 100 h)
set point value
Maintenance intervals / compressor
20 0 –99 to 300 (x 100 h)
actual value (remaining time)
Maintenance requirement /
21 0 1 = yes
acknowledge compressor
Maintenance requirement =
22 0 1= Malfunction
Warning / malfunction
1)
Valve depends on type of machine
WARNING!
Attach a warning plate to the compressor in a clearly visible position when
the automatic restart following a voltage loss (AWAL) is activated!
– When AWAL is programmed by BOGE, the plate will be attached at the
factory.
– If you program AWAL yourself, please order the adhesive plate ID.No.
59604300 from BOGE and attach it clearly visible on your compressor.
01 Total hours
02 Idle hours
03 Code input ... 000 to 999
04 Do not change parameter
05 Do not change parameter
06 Do not change parameter
07 Do not change parameter
08 Do not change parameter
09 Do not change parameter
10 Do not change parameter
0 = fault only
Collective message relay
11 1 = Fault + Warning
Fault / Warning / Service
2 = fault+warning+service
1)
Machine-related values
WARNING!
Attach a warning plate to the compressor in a clearly visible position when
the automatic restart following a voltage loss (AWAL) is activated!
– When AWAL is programmed by BOGE, the plate will be attached at the
factory.
– If you program AWAL yourself, please order the adhesive plate ID.No.
59604300 from BOGE and attach it clearly visible on your compressor.
0 = Multi-input warning
1 = Operational
16 Transistor output function 0 2 = Load operation
3 = Idling operation
4 = Remote control active
Anti switch-on timer active
17 0 0= NO / 1= YES
in intermittent operation
Display of the final compression 0 = Degrees Fahrenheit
18 1
temperature 1=Degrees Celsius
0 = ART in seconds
19 Display of after-run time (ART) 0
1= ART in minutes
Delay for feedback /
20 60 0 to 360 seconds
ventilation
Maintenance intervals / motor
21 0 0 to 30,000 (h)
set point value
Maintenance intervals / motor
22 0 – 99 to 30,000 (h)
actual value (remaining time)
Maintenance requirement /
23 0 1 = YES
acknowledge motor
Maintenenance intervals /
24 0 0 to 30,000 (h)
compressor set point value
Maintenance intervals / compressor
25 0 – 99 to 30,000 (h)
actual value (remaining time)
Maintenance requirement /
26 0 1 = YES
acknowlede compressor
Maintenance requirement =
27 0 1 = Malfunction
Warning / malfunction
1)
Valve depends on type of machine
WARNING!
Attach a warning plate to the compressor in a clearly visible position when
the automatic restart following a voltage loss (AWAL) is activated!
– When AWAL is programmed by BOGE, the plate will be attached at the
factory.
– If you program AWAL yourself, please order the adhesive plate ID.No.
59604300 from BOGE and attach it clearly visible on your compressor.
Variable parameters in You can alter the following parameters without entering a code:
the operator level
Parameter 05, star/delta switch-over time
The start-up time of the motor is adapted to the operating conditions by
means of the star/delta switch-over time.
The star delta switch-over time is the time span between the point in time
when the motor is switched on and the time when the drive motor reaches
its rated speed. During this time, the motor is operated in a star connection,
to avoid high start-up currents and overload of the electrical network.
Once this switch-over time has elapsed, the motor is switched to delta con-
nection.
If the drive motor requires a longer start-up time due to undervoltage or inad-
equate temperatures, the control system switches over to delta connection
too early and high peak current will occur.
Extend the star/delta switch-over time if the drive motor switches to
delta operation before reaching its rated speed.
General The tables on the following pages give information on the possible causes of
operating faults and measures for their rectification.
ATTENTION!
Ensure that any work required to rectify faults is only carried out by trained
personnel or specialists.
Ensure that components which have a safety function are only set, repaired
or exchanged by BOGE Service!
Automatic monitoring All data is stored in a memory module (EEPROM), which can be electrically
of the control systems written on and deleted.
If a fault occurs while the data stored in the EEPROM is being read, the
control system will react as follows:
– The compressor is switched off.
– The following fault message appears in the display.
Oil in suction filter Minimum pressure non- Check the minimum pressure check valve and
return valve is leaking replace, if necessary
Suction controller is leaking Check the suction controller and replace,
if necessary
Excessive oil Drain line is blocked Dismantle and clean drain line
consumption Defective oil separator Check oil separator and replace, if necessary
element
Excessive oil filling Drain off oil
Safety valve blows Operating pressure switch Set operating pressure to the maximum permissible
has been misadjusted pressure of the screw compressor
Defective safety valve Replace safety valve
System pressure does Venting valve does not open Check venting valve and replace, if necessary
not decrease when
switching off Check valve is leaking Check the check valve and replace, if necessary
Compressed air Malfunction of the con- Check the compressed air purification component
0 treatment
(option)
nected purification compo-
nent
and overcome malfundtion.
Note:
In the standard configuration, the message (0) does
not result in the compressor being switched off.
System pressure Air relief valve does not Check air relief valve and replace, if necessary
9 build-up
(option)
close
Suction controller does not Check suction controller and replace, if necessary
open
Leakage in system Check system, overcome leaks
ATTENTION!
Ensure that maintenance work is ony carried out by specialists or appro-
priately trained person.
– Prior to starting any maintenance work, always stop the compressor as
described in these operating instructions prior to removing any cladding
or safety devices. Refit the cladding or safety devices immediately upon
completion of the maintenance work.
– Only use original spare parts, compressor oils and operating materials
released by BOGE for the maintenance work.
– When the automatic restart (AWAL) is activated, the compressor will
start automatically following a voltage loss.
Prerequisite: The line pressure is lower than the switch-on pressure set
on the operating pressure switch.
Maintenance through Have BOGE service check your compressor every 3000 operating hours or
BOGE service annually.
Maintenance agreement
Enter into a maintenance agreement with BOGE.
BOGE service will carry out the proper maintenance on your compres-
sor at regular intervals.This guarantees maximum safety and realiability
of your compressed air supply.
Clean
compressed
air/oil cooler
externally
Top up oil in
the suction
controller Change
after an oil filter
extended
down time
Check V-belts
Change oil
separator
Change
supply oil filter
Maintenance intervals The maintenance intervals specified in the table are based on average oper-
ating and ambient conditions.
Extreme conditions may require shorter maintenance intervals.
Note down any maintenance work in the table on the last page.
This will facilitate trouble shooting for Boge service.
1. Oil change
Change the oil after the first 500 operating hours!
Retighten the electrical connections.
Retighten the electrical connection in the switch cabinet after the first 50
operating hours.
– Only use BOGE compressor oil Longlife S 46. The specified maintenance
intervals are based exclusively on this special oil!
Longlife S 46 can only be purchased from BOGE retailers.
– Never mix different oil types and brands.
The additives may be incompatible. It may lead to foam formation,
premature ageing or loss of lubricating ability.
Disposal of ATTENTION!
used The handling and disposal of mineral oils is subject to legal regulations.
operating It is an offense not to ensure correct and safe disposal of old oil!
material Please instruct one of the known service companies to dispose of used
operating materials or deliver them to an authorized disposal point.
Lubricating the drive As a rule, the bearings of the drive motors are provided with a maintenance
motor bearings free permanent lubrication.
The drive motor of some series are equipped with a post-lubricating unit.
These motors can be easily recognised by the two grease nipples on the
upper side of the housing. In addition, plates on the compressor indicate the
type of motor lubrication.
Drive motors with Under normal operating conditions (coolant temperature max. 40°C,
permanent lubrication continous operation) the bearings are maintenance free for the service
life.
Lubrication of bearings:
Mains frequency Operating hours
50 10,000
60 18,000
ATTENTION!
Have BOGE service dismantle and regrease the bearings once the specified
service life has expired!
The BOGE GM drive system automatically adjusts the V-belt to the correct
V-belt tension in any operating mode.
Thus maintenance of the V-belt drive is limited to the above mentioned work.
Changing Vee-belts:
– Open the noise suppression hood and remove the hot air hood
(refer to page 3.14).
– Screw up setting nut Q.
The two collars in the spring must butt together.
– Remove the slackened belts from the pulley.
– Fit new Vee-belts.
– Screw down the setting nut Q again as far as possible. The Vee-belts are
automatically correctly tensioned by the BOGE-GM drive system.
– Refit noise suppression hood and hot air hood.
S8 10 46 98
S8 13 46 98
S 10 8 66 105
S 10 10 66 105
S 10 13 66 105
S 15 8 77 105
blue 1
S 15 10 77 105
S 15 13 77 105
S 24 10 89 108
S 24 13 89 108
S 29 8 98 99
S 29 10 98 99
S 29 13 98 99
blue 1
The setting values given in the table are fixed by the manufacturer and must
not be changed. Slight deviations are allowed and and are compensated by
the GM drive system.
The current settings are shown on a sticker on the GM drive system.
On special versions the settings on the sticker may differ from the standard
values.
ATTENTION!
Always use the same oil type when topping up.
Never mix different oil types and brands.
ATTENTION!
Do not use tools to screw in the new oil filter! You might damage the oil filter
or its sealing ring.
A hand tight seating of the oil filter is sufficient.
– Reattach warm air hood.
– Open ball valve at the compressed air outlet.
– Switch on the compressor and heat up to operating temperature.
– Subsequently, check the oil filter for leaks once again and tighten by hand,
if necessary.
Changing the oil Change: – When warning message „8“ appears on the control
separator system display (only for Ratiotronic).
– After 3000 operating hours,
however, no later than after one year.
If the prescribed maintenance intervals are not observed, the oil sepa-
rators might become blocked. In this case, the differential pressure will
increase until the safety valve blows.
ATTENTION!
Do not use tools to screw in the new oil separators! You might damage the
oil separators or their sealing rings.
A hand tight seating of the oil separators is sufficient.
– Open ball valve at the compressed air outlet.
– Switch on the compressor and heat up to operating temperature.
– Check the oil filter for leaks once again.
Fig. 6.6:
Changing the oil separators
The service life of the oil, the oil filter and oil separators is reduced under the
following conditions:
– When the compressor is operated at extreme ambient temperatures.
– When the intake air is extremely soiled.
ATTENTION!
Always fill with the same oil type as previously used. Never mix different oil
types and brands.
The oil circuit must be flushed prior to changing the oil type (see page 6.13).
Flushing the oil circuit Flushing the oil circuit with clean oil becomes necessary:
– when the oil is excessively soiled.
– prior to changing the oil type.
ATTENTION!
To flush out the oil circuit, only use oil of the same type to that which is to be
used later.
– Drain off old oil completely (see page 6.13).
– Leave old oil filter and oil separator in the compressor.
– Fill oil/compressed air receiver with clean oil up to approx. one third of the
total capacity.
– Close oil filling socket.
– Let compressor run for approx. 10 minutes.
– Drain off flushing oil and dispose of it properly.
– Change oil filter and oil separator cartridges (see page 6.10 and 6.11).
– Fill up with oil to the specified level (see page 6.9).
Fig. 6.10:
Flushing the oil circuit
ATTENTION!
Do not use any sharp objects for cleaning! These could damage the cooling
unit!
– Blow down the dirt with compressed air Q in the opposite direction to the
normal cooling air flow. Vacuum out the dirt using an industrial vacuum
cleaner (see Fig. 6.11).
– Reattach warm air hood.
ATTENTION!
Never set operating pressure switch higher than the admissible final com-
pression pressure (see type plate).
CAUTION: Voltage!
The operating pressure switch may only be set by an electrician! Live con-
tacts may be exposed on the pressure switch, implying the danger of injury
resulting from an electrical shock!
ATTENTION!
The ball valve at the compressor outlet must remain open during setting
work.
The operating pressure switch must only be adjusted while under pressure!
– Open the sound insulation hood (only for super silenced version).
– The operating pressure switch is located at the rear of the switch cabinet.
It is marked with „S4“.
– Remove the housing of the operating pressure switch after releasing the
1
two fastening screws.
– Set the switch-on or switch-off pressure on handwheel Q:
Increase switch-off pressure: Turn handwheel clockwise
Reduce switch-off pressure: Turn handwheel counterclockwise
Increase switch-on pressure: Press handwheel down and turn clockwise
Reduce switch-on pressure: Press handwheel down and turn
counterclockwise
– Refasten housing of operating pressure switch.
– Close the sound insulation hood.
Always set the proportional controller higher than the upper switching
point of the operating pressure switch (Pmax)!
– Type
– Year of manufacture
– Machine number
Air IN Air IN
Page 7.2
Date Operating Line System Tempe- Intake Oil- Oil- Oil Cooling Motor Com- Remarks
hours pressure pressure rature filter filter level separator unit mainte- pressed
Appendix
* R = Cleaning ** K = Check
W = Change W = Change
Date Operating Line System Tempe- Intake Oil- Oil- Oil Cooling Motor Com- Remarks
hours pressure pressure rature filter filter level separator unit mainte- pressed
Appendix
Fließ.pm6.5 - 01/2001 - GB
7.2
* R = Cleaning ** K = Check
W = Change W = Change
Page 7.3