SIRIUS 3RM1 Hybrid Motor Starter

A simple and efficient product range for small motors

Page 1 February 2014 Siemens Industry


3RM1 Hybrid Compact Starters in 22.5mm width
What is a Hybrid Starter?

 The 3RM1 motor starters combine the benefits of


semiconductor technology and relay technology.
This combination is known as hybrid technology.

 The inrush current of motorized loads is conducted


briefly via the semiconductors.
 Advantage: The relay contacts are protected from the
inrush current. Reduced maintenance and longer
service life is achieved thanks to reduced wear and tear.

 The continuous current is conducted via relay contacts.


 Advantage: Relay contacts cause less thermal losses than
semiconductors and consumes less energy.

 Switch-off is implemented again via the semiconductor.


 Advantage: The relay contacts are only slightly burdened by arcs.
This results in increased service life.

Page 2 February 2014 Siemens Industry


SIRIUS 3RM1 Motor Starter
Now with safety functionality!

3RM10 3RM12 3RM11 3RM13

Direct starter Reversing starter Direct starter Reversing starter

Failsafe SIL 3
Motor overload protection ATEX motor overload protection

3 current ranges → (0.1-0.5 A / 0.4-2 A / 1.6-6.1 A)


2 control voltages → (DC 24 V / AC 110 … 230 V, DC 110 V)
2 terminal types → (screw connection, push-in, mixed terminals)

Page 3 Siemens Industry


4 Functions in one small device!

The 3RM1 Failsafe motor starter

Motor starter 3RM1 Failsafe

Direct / Reversing starters

With Safety functionality


Suitable for safety applications
up to SIL 3 / PL e / Cat. 4

With overload protection


ATEX certified up to SIL 2

Page 4 February 2014 Siemens Industry


Hybrid Compact Starters 3RM1
Group Installation

 Higher density in the panel – benefit


 Use UL489 CB or fuses for short circuit
protection
 Two types of Infeed Systems
3RM19 Comb Busbar for Mains UL489 MSP
 16A UL max rating or fuse required for UL
 2, 3 or 5 starter options
 Screw versions only in standard or safety

3ZY1 Device Connectors for Control 16A max per infeed

 For use with 3RM1 and 3SK1 Safety Relays


 Buses safety control across the starter group
in case of 3SK1 with 3RM11 / 3RM13.
 Buses coil control in the case of
3RM10 / 3RM12 only.
 No mixing of standard and safety starters in one
system. Separate systems should be used in this
case.
Page 5 February 2014 Siemens Industry
SIRIUS 3RM1 Motor Starter
Technical details

Clockwise-/counter-
Control supply voltage,
clockwise rotation, Reset
signal output
Response
Standard mounting rail
fixture

LED indicator
Device, Failure, State,
Rotary encoding switch Reset mode
Setting motor current

Button Main circuit, 3 phase infeed


TEST / RESET / RESET MODE

Main circuit,
3 phase load

Page 6 Siemens Industry


Hybrid Compact Starters 3RM1
Key Features

Or both in one starter

Page 7 February 2014 Siemens Industry


Hybrid Compact Starters 3RM1
Expanded Portfolio – NEW mixed terminal versions

• Maximum flexibility for wiring


labor savings
• Order with -3xxxx to get
spring loaded terminals on
control side and screw
terminals on power side of the
starter
• Allows for quicker termination
of all control circuits with
push-in technology for solid
core or stranded with ferrules
• Allows for use of power infeed
busbar system which is only
available with screw versions

Page 8 February 2014 Siemens Industry


SIRIUS 3RM1 Motor Starters
Connection method – details

Control circuit Main circuit

Max. 2.5 mm², Max. 4 mm²,


Screw terminals

(14 AWG) (12 AWG)


terminals – push-in

Max. 1.5 mm², Max. 4 mm²,


Spring-type

technology

(16 AWG) (12 AWG)


1 conductor!
2 conductors in
twin/duo
end sleeve

Tool Conductor

Page 9 Siemens Industry


Hybrid Compact Starters 3RM1
Value Prop - Significant Space Savings

- 64% - 82% - 86%

Page 10 February 2014 Siemens Industry


Hybrid Compact Starters 3RM1
Value Prop – Energy Efficient

Hybrid controls
The SIRIUS 3RM1 motor starter combines
the benefits of semiconductor and relay
controls. This makes it especially:
 Low intrinsic power losses
 Hybrid technology
 Switching with semiconductors
 Control with relay contacts
 Solid-state overload relays
 Reduced temperature rise in the cabinet
 Smaller air-conditioning required

76%
The motor starter is especially suitable for
high switching frequencies.

Economical Compared to 3-piece motor starters

Page 11 Siemens Industry


Hybrid Compact Starters 3RM1
Value Prop - Energy Efficiency

Low losses thanks to hybrid technology and electronic current measurement

 By combining the functions and technology (and much more) of hybrid


technology for switching and controlling the current of the main current paths.
and a solid-state overload relay in a single device, contact resistances
(switching points, cable transitions, etc.) are reduced to a minimum.

-76% -73% -37%

8.1 8.1 8.3


Standard
starter, contactor
Power loss [W]

5.2 and overload relay


3RM1
compact starter
1.9 2.2

1 2 6.1 [A]
Motor current

Page 12 February 2014 Siemens Industry


Hybrid Compact Starters 3RM1 in 22.5mm width

Device connectors further


reduce wiring time by
allowing for the bussing of
the 24V control for the coil.

For every 5 starters, four do


not require connection, saving
~18 minutes of wiring time for
the group shown (2 min each)

Very simple system with plug


and play characteristics.

Page 13 February 2014 Siemens Industry


SIRIUS 3RM1 Motor Starter
Same form factor as the 3SK1 Safety Relay

Page 14 Siemens Industry


SIRIUS 3RM1 Motor Starter
One System for evaluating, detecting and reacting

First time!! One system for evaluating, detecting and


reacting!!
 Easy handling
 No safety wiring
 Easy project planning
 Saves money and time

3SK13RM1 3RM1 3RM1 3RM1

In combination with 3SK1 …

… 100% Saving of Safety control wiring of the


actuating elements and therefore less time and less
potential for wiring errors

Page 15 Siemens Industry


New Safety Versions
– all other characteristics stay the same

Brief description of 3RM11 and 3RM13 Failsafe Starters


 Width: 22.5 mm
 Direct-on-line or reversing starter
 Safety-related shutdown (SIL 3 / PLe / Cat4)
 Motor overload protection (ATEX SIL 2)
 Overload trip class: Class 10
 Group installation possible
 Short-circuit current rating with J type fuses up to 100 kA
 3 versions to 6.1A (3HP)
 (0.1 to 0.5 A; 0.4 to 2 A; 1.6 to 6.1 A)
 Rated operating voltage: 500 V
 Control supply voltage:
24 V DC or 110 to 230 V AC 50/60 Hz, 110 V DC

Page 16 February 2014 Siemens Industry


SIRIUS 3RM1 Motor Starter
Specific features of the Failsafe version

3RM1 Failsafe switches off the motor


in case of an emergency!
 Safe switching with the 3RM1 is possible via the control voltage
or via the inputs for the 24 VDC-Version
-> The 3RM1 switches 3-phases.

3RM1 Failsafe is self-monitoring!


 The 3RM1 Failsafe monitors its safety-function:
-> In case of an error (e.g. welded relay contact) the 3RM1
doesn’t start the motor and signals a fault.
-> the Fault signaling output is not part of the safety function
-> to ensure the safety functionality the minimum current (phase
loss) is monitored even during the start-up routine

Page 17 Siemens Industry


SIRIUS 3RM1 Motor Starter
Group Assembly with Device Connector

Assembly with Standard 3RM10 / 3RM12 Assembly with Failsafe 3RM11 / 3RM13

• One infeed of 24 VDC supplies five motor • Assembly:


starters
• Each device connector group consists of 5
• 2 possibilities for group assembly: motor starters at the most, and the group
ends with a termination connector
• Each device connector group consists
of 5 motor starters at the most, and the • Each group of 5 is supplied individually with 24 VDC
group ends with a termination connector (A1) via a safe output
• All motor starters are connected in one • Safe switching via control voltage supply of the
device connector group, the last motor
Geräteverbinder whole group
starter is connected via termination
Abschlussverbinder
connector

Safe Safe Safe


output output output
L+
L- L-

Device connector
Termination connector

Page 18 Siemens Industry


SIRIUS 3RM1 Motor Starter
Safe switching of groups of 3RM1 motor starters

• The safety relay can supply up to five L+


L-
motor starter with 24 VDC
With Safety relay 3SK1

• The 3SK1 disconnects the control voltage 3SK1 3SK1 3RM1 3RM1 3RM1 3RM1 3RM1

supply in case of hazards, so the whole


group is safely shut down.
• More than 5 motor starters:
• Additional motor starter groups can be
connected and safely switched off via
wiring on the safe outputs of the 3SK1
System
Device connector
Termination connector

L-
With any FDQ

• For safe switching of groups of 5, the control voltage supply A1 (L+) of


the first motor starter gets connected with a safe output FDQ
• Depending on the type of the FDQs and the wiring it is sufficient to
switch off via A1, otherwise A2 needs to be switched off as well. See
system manual for details.

Page 19 Siemens Industry


Motor Starter SIRIUS 3RM1 Assembly guideline
Motor loads, ambient temperature 40°C

3RM1001/1002 or 3RM1201 / 1202


3RM1101/1102 or 3RM1301 / 1302
Ie_AC53 ≤ 4.6 A

No limitations until 4.6 A1) 3RM1007 or 3RM1207

setting or higher 3RM1107 or 3RM1307

a a a > Minimum distance = 22.5 mm


The 3RM19 Comb Infeed and 3ZY1 Device
Connectors are both suited for this spacing
requirement

From 4.6 A single blank spacing

1) only possible when motor starters next to the 7A device will carry max 2 A.
In all other cases refer to the derating table in the product manual (next slide).
Page 20 Siemens Industry
Motor Starter SIRIUS 3RM1
Mounting and Derating Data

a a

A = 22.5mm clearance

Page 21 Siemens Industry


SIRIUS 3RM1 Motor Starters
Technical details – sample circuit diagram (control circuit)

Direct-on-line
Direktstarter starter
DC 24 24 V DC
V mit with switch operation
Schalterbetrieb
DC 24 V
L+
L-
Control voltage

Ein
Start Fern-Reset
Reset

Control inputs
L1 L2 L3 A1 A2 IN 1 IN 3 95

Start Reset

Error Error signaling


3RM1 contacts

Out 96 98

T1 T2 T3 Signaling output

Page 22 Siemens Industry


SIRIUS 3RM1 Motor Starters
Technical details – sample circuit diagram (control circuit)

24 V DC failsafe reversing starter


with control system

Control supply voltage

Control inputs, safety-


related shutdown is
performed via IN1, IN2

Page 23 Siemens Industry


SIRIUS 3RM1 Motor Starters
Technical details – safety-related shutdown
Version Us 24 V DC Version Us 110 V DC, 110 to 230 V AC

 Safety shutdown to SIL3 / PL e  Safety shutdown to SIL3 /


Cat.4 PL e Cat.4
Removal of the
control voltage

 Shutdown by removing the 24 V  Shutdown by removing the voltage


DC on A1 Us on A1, IN1, IN2

 It is not necessary to shut down A2 if  It is not necessary to shut down A2 if


shutdown is achieved by means of shutdown is achieved by means of wiring
wiring that is resistant to cross circuit that is resistant to cross circuit or short-
or short-circuit to P. circuit to P.

 Safety shutdown to SIL3 / PL e


Cat.4
Removal of the
control signals

 Shutdown by removing the Shutdown via the control signals


control signals on IN1, IN2
IN1, IN2 is not possible for the
 It is not necessary to shut down M1, 110-230V version.
M2 if shutdown is achieved by means
of wiring that is resistant to cross
circuit or short-circuit to P.

Page 24 Siemens Industry


SIRIUS 3RM1 Motor Starter
Technical details – control voltage

Motor starter 3RM1


 A1, A2 control voltage
 95,96,98 Fault signaling output
 IN1 Direct starter
 IN1, IN2 reversing starter

Standard 3RM10 / 3RM12 Failsafe 3RM11 / 3RM13

24 V DC: 24 V DC:

• IN3 remote reset • M1, M2 ground for inputs IN1


and IN2
• OUT: feedback „motor run“

110 V DC, 110 – 230 V AC:


• IN3 remote reset 110 – 230 V AC / 110 V DC:

Page 25 Siemens Industry


Safe Switching with 3RM1

3RM1 motor starters can be


used in safety circuits.
Safe switching can be
realized, for example, with a
safety PLC, 3TK28 or 3SK1
safety relay and power
contactors.
The following examples
describe possible
configurations that
correspond to the various
safety levels.

Page 26 February 2014 Siemens Industry


Safe Shutdown via Control Supply Voltage up to
SIL 3 or PL e

In the case of safe shutdown via the control supply voltage, the control supply voltage is disconnected from a
motor starter, at which point safe shutdown of the load is started. Groups of up to five motor starters can be
set up using the optional 3ZY1212 device connectors. In this case, the control supply voltage is disconnected
from just one of the motor starters, at which point the remaining motor starters of the group also shut down
safely
Page 27 Siemens Industry
Safe Shutdown via Control Inputs up to SIL 3 or
PL e

The 3RM11 motor starter (direct-on-line starter) has the safe control input IN1. The
3RM13 motor starter (reversing starter) by contrast has two control inputs, IN1 and
IN2, for specifying the direction of rotation. Operational switching as well as safe
shutdown can be carried out via these inputs.
Page 28 Siemens Industry
Safe Shutdown in Conjunction with 3SK1 Safety
Relays to SIL 3 or PL e

The SIRIUS 3SK1 safety relays and the SIRIUS 3RM1 motor starters can be
connected up using the 3ZY1212 device connectors without any further wiring. Up to
five motor starters can be operated together with one safety relay on one device
connector group. The motor starters are supplied with control supply voltage from the
safety relay via the device connector. The advantage of this solution is that up to five
motor starters can be safely shut down with minimum wiring.
Page 29 Siemens Industry
Safe Shutdown of Several Motor Starter Groups
up to SIL 3 or PL e

If more than five motor starters are used, these can be placed on device connectors
in groups of five. Safe shutdown of the individual groups takes place in the same
way as the examples shown above.
Page 30 Siemens Industry
Safe Shutdown of Several Motor Starter Groups
up to SIL 3 or PL e (cont.)

Page 31 Siemens Industry


Standard 3RM1 Safe Switching up to SIL 1 or PL c

The 3RM1 motor starter has no effect or


influence on the safety function of the
application. For this reason, the 3RM1 motor
starter is not taken into consideration in the
safety application, either in the positive or
negative sense, and thus does not have to be
included in the calculation for normative proof.

If achievement of SIL 1 according to IEC 62061 or PL c according to ISO 13849-1is required, the series
connection of an additional contactor with the 3RM1 motor starter, in conjunction with a safety relay suitable
for this (e.g. 3SK1111), is necessary, along with monitoring of the contactor's auxiliary contacts.
Page 32 Siemens Industry
Standard 3RM1 Safe Switching up to SIL 2 or PL d

While the enabling circuits of the safety relay are closed, the undervoltage release is supplied with voltage. When the EMERGENCY STOP
is actuated, the power contactor switches off immediately. The voltage at the time-delayed outputs 37/38 and 47/48 is retained for the set
time. After expiration of this time, the undervoltage release will continue to be supplied with voltage via the power contactor's auxiliary
contact, which is now closed again. Only in the case of a fault in which the contactor does not switch off and the auxiliary contact thus
remains open does the undervoltage release switch off after expiration of the set time according to the switching time of the contactor.

Page 33 Siemens Industry


Standard 3RM1 Safe Switching up to SIL 3 or PL e

Safe switching up to SIL 3 according to IEC 62061 and PL e according to ISO 13849-
1 requires the use of two redundant contactors and monitoring of the auxiliary
contacts of both contactors. Two-channel monitoring of the EMERGENCY STOP is
also required here.
Page 34 Siemens Industry
Standard 3RM1 Safe Switching of a Group of
Motor Starters up to SIL3 or PL e

Safe switching of a group of motor starters up to SIL 3 according to IEC 62061 or PL e according to ISO 13849-
1 is implemented in the same way as for an individual motor starter. The power contactors must be dimensioned
accordingly. The 3ZY1 device connector enables up to five motor starters to be connected to each other. In this
case, the control supply voltage only has to be connected to the first motor starter and is then distributed to the
downstream motor starters via the device connectors.

Page 35 Siemens Industry


Application Manual - SIRIUS Safety Integrated

Contents:
Includes the 3RM1 Failsafe motor starters:

• Wiring diagrams in combination with


3SK1, MSS or PLC

• Advantages and disadvantages of safe


shutdown methods

• Safe shutdown of more than 5 motor


starters

Page 36 Siemens Industry


Thank you!!

For more information:


www.usa.siemens.com/3RM1

Page 37 February 2014 Siemens Industry