Sei sulla pagina 1di 32

VITOTRES 343

Compact heating centre


for energy−efficient houses

Technical guide
Vitotec technical guide folder, register5
File in:

Vitotres343

Compact device for energy−efficient houses with

H Controlled domestic ventilation with heat recovery

H Exhaust air heat pump with 1.5kW rated output for


DHW loading and central heating

H DHW cylinder with 250litres capacity

H Prepared for utilising solar energy

58222821 GB5/2004
Contents

Contents Page

1 Basic principles 1.1 The energy−efficient house . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3


1.2 Requirements of an energy−efficient house . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Requirements regarding the energy centre of an energy−efficient house . . . . . . . . . . . 4

2 Product information 2.1 Function description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


2.2 Benefits at a glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Alternative use in buildings without energy−efficient standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3 Specification 3.1 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7


3.2 Vitotres dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Dimensions  outside air filter box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Dimensions  connection panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.5 Dimensions  electrical junction box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4 General planning information 4.1 Location and installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10


H Installation room requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
H Ventilation system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
H Primary and secondary connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
H Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
H Operating tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2 Sizing the ground energy exchanger (GEE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3 Solar panel connection and calculating the diaphragm expansion vessel . . . . . . . . . . 15
H Design and effect of the diaphragm expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
H Calculating the diaphragm expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.4 Installation of an auxiliary heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.5 System type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
H Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
H System design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
H Required equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

5 Air distribution system 5.1 Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21


H Calculating the basic air change or the average air change volume . . . . . . . . . . . . . . . . . 21
H Average air change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
H Ventilation air/exhaust air and overflow areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
H Air volume flow segregation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
H Air volume flow and heating load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.2 Air routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
H Routing air into rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
H Routing air inside rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
H Air extraction from kitchens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
H Silencer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
H Pipework insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.3 Vitotres connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.4 Pressure drop and flow velocities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
H Pressure drop of different pipeworksystems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
H Flow velocity  volume flow diagram of different pipeworksystems . . . . . . . . . . . . . . . . 29
H Ventilator curves  ventilation module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
H Pressure drop diagram  outside air filter box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

6 Appendix 6.1 Form for designing air volume flow patterns for Vitotres343 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.2 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5822282 GB

2 VITOTRES 343
1.1The energy−efficient house

1.1The energy−efficient house


Development of heating demand subject to building standard
(detached house, 3 to 4occupants, 150m2 floor area, A/V=0.84)

240 Over the past few years, major progress


has been made in reducing heating
demand. For example, in existing
200 housing, the annual heating demand for a
50
detached house exceeds
200kWh/(m2·p.a.). Similar new buildings
160 constructed in accordance with the Heat
Loss Order (WSchV) 1995 [Germany], only
require approx. 100kWh/(m2·p.a.).
Heat demand in kWh (m2·a)

Although there is no legal formula for


120 50 low−energy houses (LEH), it can be
160 assumed that a detached low−energy
40 house in accordance with the EnEV
80 [Germany] has a heat demand lower than
35
70kWh/(m2·p.a.), and a multi−occupancy
80 low−energy house a heat demand lower
25
40 50 than 55kWh/(m2·p.a.). For
210 130 90 35 70 5 40 energy−efficient houses, the specific
10
heating demand reaches a maximum of
15 15 15 15 15
15kWh/(m2·p.a.).
A B C D E Energy−efficient houses are the logical
development of the low−energy building
method. With this building method,
transmission and ventilation heat losses
A Building stock J Heat recovery proportion are reduced to the extent that the heating
B Buildings from 1984 J Ventilation heat loss demand is largely covered by solar
C Buildings from 1995 (losses through air changes) irradiation as well as by internal heat
D Low energy house (LEH) J Transmission heat loss sources such as, for example, the waste
E Energy−efficient house (losses through building envelope) heat from domestic equipment.
J DHW heat demand The heating load in energy−efficient
houses at approx. 10W/m2 is so low that
the required residual heat (maximum
average daytime heating load) can be
provided by backing up the heating of the
ventilation air for a regulated domestic
ventilation system. This prepares the
ground for the use of the compact
Vitotres343. This makes the use of static
heating surfaces completely superfluous.
This application requires a high thermal
quality in the entire building envelope,
including its windows. Correspondingly
high surface temperatures ensure
comfort, even when no compensating
heating surfaces are installed near
windows or outside walls. A small
radiator in the bathroom can provide
increased comfort.
Along with the thermal insulation and the
absence of thermal bridges, the airtight
nature of the building envelope is vital to
the perfect function of the energy−efficient
house. Only if infiltration and expulsion
through leaks are generally minimised
can the regulated ventilation with heat
recovery function properly, the heating
load be kept low and the occupant’s
comfort be assured. The regulated
domestic ventilation of an energy efficient
house is essential for maintaining
excellent air quality in the living space.
DHW heating represents a substantial
5822282 GB

proportion of the energy demand in an


energy−efficient house. Subject to
consumption, it can represent up to 60%
of its total energy demand.

VITOTRES 343 3
1.2Requirements of an energy−efficient house
1.3Requirements regarding the energy centre of an energy−efficient house

1.2Requirements of an energy−efficient house


The energy−efficient house standard is a H Orienting the main window areas south We recommend you implement design
vital basis for the efficient use of compact makes the maintenance of characteristic and sizing in accordance with the
heating centres, such as Vitotres. values easier, but is not an essential planning document of the PHPP*2 .
The following structural conditions must requirement (for example, if the outline
be maintained to achieve the planning restrictions make this
energy−efficient house standard: impossible, etc.). Allow for the option of
H Heating energy demand providing shade, to prevent the building
<15kWh/(m2·p.a.)*1 from being overheated in summer.
H Max. required heating load<10 W2 *1
 H Air tightness n50<0.6/h
m 
H Heat transfer coefficientU of the This means that, with an over or under
 building envelope pressure inside the building of 50Pa,
U<0.15W/(m2·K), free of thermal less than 0.6 times the heated building
bridges air volume can ingress or be expelled.
 window This is checked using the Blowerdoor
U<0.80W/(m2·K), in its installed test.
state <0.85W/(m2·K)

1.3Requirements regarding the energy centre of an energy−efficient house

The PHI Darmstadt*3 has defined the H the sound pressure level of the H the internal and external leak rate of the
following requirements for the energy ventilation equipment must be equipment must be below 3 % 

centre of an energy−efficient house: below 35dB(A) H the volume flow of the equipment must
H the heat recovery of the regulated H for living spaces, a sound pressure level be balanced
domestic ventilation system must of 25dB(A) and in domestic offices of H the equipment must provide the DHW
exceed 75 %
 30dB(A) must be ensured using convenience to DIN4753
H the heat recovery and the ventilation air commercially available silencers H the ventilation equipment must provide
backup heating must be frost protected H the power consumption of the the low standby losses of the building
H the ventilation air temperature must not ventilation system must be below (<5W/K)
be hotter than 52ºC to prevent dust 0.45W/(m3/h) Vitotres meets or performs better than
being disturbed H the equipment must be able to create these requirements.
air changes of 0.7 times the room
volume

5822282 GB

*1Values relate to calculations in accordance with DIN277 (living space calculationII.BV)


*2Energy−efficient house engineering pack. Source: www.passiv.de
*3PassivhausInstitut, Rheinstr.44/46, D64283Darmstadt

4 VITOTRES 343
2.1Function description

2.1Function description
Vitotres offers controlled ventilation with To safeguard the minimum volume flow,
heat recovery and includes a heat pump the heat pump provides additional
for heating a DHW cylinder and the outside air terminalL.
building. The heating energy gained by the heat
pump will besubject to demand
Fresh outside airA is supplied via an routed either to ventilation bankC or to
external air filter(F 7) and a supply line.
 DHW cylinderH, until the respective set
After entry into the ventilation module, temperatures have been reached. A
this ventilation air is pre−heated by multi−stage electric heater is provided as
countercurrent heat exchangerB. Then, second heat source to ensure high DHW
subject to the selected set temperature, convenience. It is controlled subject to
the ventilation air is routed across load. Vitotres is equipped with connection
ventilation air bankC, through which hot for solar panelsK to enable the
heating water or cold water flows. Fresh utilisation of solar energy. All relevant
ventilation airD is routed through the control functions and Solar Divicon are
channel system and distributed into the already integrated into Vitotres.
various living spaces. Exhaust airE is The control operates according to
extracted via a channel system from the differential temperature and can be
areas where steam and odours are utilised for DHW heating and for indirect
created (bathroom, WC, kitchen) and ventilation air backup heating.
routed to the ventilation module. This
exhausted air is cleaned by a filter(G 4)


inside the equipment. Heat is transferred


to the ventilation air via countercurrent
heat exchangerB. Some of the residual
energy from the cooled exhaust air is
utilised by evaporatorF of a heat pump,
which yields up to 1.5kW heating energy
from this process.

This severely cooled−down exhaust air is


expelled from the building via expelled
air channelG. The volume flow balance
ensures a constant ventilation and
exhaust volume flow, independent of the
prevailing static pressure.

B
A E
L C

G D
F
H
5822282 GB

VITOTRES 343 5
2.2Benefits at a glance
2.3Alternative use in buildings without energy−efficient standard

2.2Benefits at a glance

H Tower system for ventilation, heat and H Reversible heat pump operation for H Prepared for integration into a solar
solar utilisation on a footprint of only cooling function (1kW). heating system. Hydraulic connections,
600×670mm, fully assembled and SolarDivicon and control unit are
wired. H Integral connection for hydraulic already integrated.
heating system (bathroom radiators).
H Ventilation with heat recovery, heat H Specification:
availability level higher than 80 %.
 H Air supply filter at the inlet aperture and Performance factor
exhaust air filter inside the equipment. (heating operation)>4
H Exhaust heat pump with 1.5kW output. Sound level<35dB (A)

Maximum temperatures: Heat pump H Connection of ventilation channels Air volume flow 70  250m3/h.
 

65ºC, heating element 70ºC. without thermal bridges.

H Integral electric heating rod with H Energy−saving DC fans.


three−stage operation as backup heating
for DHW and ventilation air
(2, 4, 6kW).

2.3Alternative use in buildings without energy−efficient standard


Vitotres may also be integrated into A further decisive benefit is the option of The combination of Vitotres and
buildings which do not comply with the active cooling of the ambient air conventional heat source ensures a
energy−efficient house standard. In such (up to 1kW). comfortable atmosphere and
cases, Vitotres provides the regulated With this form of application, the bulk of simultaneous heating of DHW under the
building ventilation. The advantage heating demand of the building will be most favourable operational and cost
offered by Vitotres compared to provided by a separate heat source (e.g. a conditions.
conventional ventilations sytems (for gas fired wall mounted boiler*1 or a heat
example Vitovent300) lies in the pump) and a separate heat distribution
additional utilisation of the exhaust air system. That heat source would operate
energy for heating DHW and ventilation separately from Vitotres and could, for
air. In addition, solar panels can also be example, be installed in the attic.
easily connected.

*1Observe the limitations on page11.

5822282 GB

6 VITOTRES 343
3.1Specification

3.1Specification
Complete equipment
Length mm 677
Width mm 600
Height (excl. fan) mm 2 095


Height when tilted


H Boiler on a pallet mm 2 395


H Boiler alone mm 2 085




Weight (empty) kg 250


Rated voltage 3/N/PE 400V~/50Hz
Fuse (slow) A 3×16
Protection IP 20
IP20
Maximum output
H hydraulic kW 7.3
H via air (at a ventilation air volume flow of 210m3/h, ventilation air temp. 50ºC, room temp. 20ºC) kW 2.3
Process medium fill volume litres 20
Max. system pressure heating circuit/solar circuit bar 3.5
Response pressure of the safety valve on the primary side bar 4
Max. flow temperature  auxiliary heating circuit ºC 65
Minimum volume flow  auxiliary heating circuit l/h 700
Pressure drop of the auxiliary heating circuit at minimum volume flow mbar 175
Residual height  solar circuit mbar 180
Heat recovery/ventilation module
Sound pressure level (1m in front of the equipment) dB (A)
 35
Air volume flow m3/h 70 to 250
Max. ventilation air compression at 250m3/h (without filter) Pa 250
Max. exhaust air compression at 250m3/h Pa 100
DC fan  expelled air W 100
DC fan  outside air W 100
Heat availability level of the heat recovery % >80 

Pressure drop  outside air filter box at 250m3/h Pa 40


Max. permiss. pressure drop  outside air supply to the heat pump at 150m3/h Pa 50
Max. ventilation air temperature (adjustable) ºC 52
Min. cooling temperature (adjustable) ºC 18
Heat pump module
Lower application limit ºC 15
Max. flow temperature ºC 65
Rated output kW 1.5
Performance factor at L 2/W 35ºC
  2.6
Performance factor at L 7/W 35ºC
  2.8
Refrigerant fill/volume kg R134A/0.9
Max. cooling output kW 1
Auxiliary heating element  electric (stepped) kW 2/4/6
DHW cylinder
Capacity litres 250
Continuous DHW output l/h 200
DHW performance factorNL 1.5
Max. draw−off volume at the stated DHW performance factorNL litres/min 16.8
and DHW heating from 10 to 45ºC
Max. system pressure bar 10
Max. DHW temperature ºC 65
Cylinder protection External current anode
Connections
Outside air/ventilation air/expelled air/exhaust air ∅mm 160
Outside air supply to the heat pump ∅mm 125
Flow/return  auxiliary heating circuit Multiconnect system sleeve
DN20
Flow/return  solar circuit Multiconnect system sleeve
DN20
Cold water R (fem.) ¾"
Domestic hot water R (fem.) ¾"
DHW circulation R (fem.) ¾"
Drain (overflow) DN 32
5822282 GB

VITOTRES 343 7
3.2Vitotres dimensions

3.2Vitotres dimensions

160
A A
AW AW 116
111
102
62
51
45
B

40
WW

106
Z

160
KW
HR
HV
2084
2213

RL
2026

2095

VL

137
72 FO AW
B

122
292
427
512

KOA ZU
100.5

AU
E AB
600 677 112
487

Key to symbols
AB Exhaust air KOA Condensate drain A Quick−acting air vent valve with
AU Outside air (flexible hose) flexible connection line
AW Outside air to heat pump KW Cold water B Hydraulic connections
E Drain (inside equipment, see page19) RL Solar return
FO Expelled air VL Solar flow
HR Heating return WW Hot water
HV Heating flow Z DHW circulation
ZU Ventilation air
5822282 GB

8 VITOTRES 343
3.3Dimensions  outside air filter box
3.4Dimensions  connection panel
3.5Dimensions  electrical junction box

3.3Dimensions  outside air filter box

72 650 54 340 Material: EPP in black


Material thickness: 50mm
Thermal
conductivity: 0.042W/(m · K)
 

Filter type: Slide−in filter as


pocket filter

340
210
ClassF 7 (pollen filter)


3.4Dimensions  connection panel


375 HR Heating return Note
HV Heating flow All connection brackets can be rotated on
KW Cold water the connection panel to make the on−site
VL RL Solar return pipe connections easier.
RL VL Solar flow All connections R¾"fem. thread
HR
WW Hot water
250

HV Z DHW circulation
WW
Z
KW

280

*1
55

*1Illustration without connecting bracket.

3.5Dimensions  electrical junction box


The electrical junction box is already
connected to Vitotres343 with a
1m long cable.
5822282 GB

VITOTRES 343 9
4.1Location and installation conditions

4.1Location and installation conditions


Installation room requirements

Clearances Pressure points H Required room height min. 2 400mm




View from above (2 500mm recommended).




Maintain a space of 1 000mm depth in




front of the equipment for operating


and service purposes.
min. 15 mm
57 mm H Total weight incl. DHW filling: 500kg.

H Each pressure point (with an area of


64 mm
3 215mm2 each) is loaded with 125kg.


502 mm
¨Observe the permissible floor load.

H This equipment is suitable for


installation, for example, in place of a
min. 5 A min. 5 422 mm kitchen unit.
mm mm
min. 20 min. 20 H The installation room must be dry and
mm mm safe from the risk of frost.
89 mm
H Permissible ambient temperatures
B  during operation
A Clearance min. 1 000mm
 max. +35ºC
B Partition joint with edge insulation min. +2ºC
strip as part of the floor construction  during storage and transport
max. +60ºC
min. 25ºC

5822282 GB

10 VITOTRES 343
4.1Location and installation conditions

Ventilation system

¨Safety instruction H Never locate the outside air inlet H Thermally insulate any parts of the air
This equipment must not be operated immediately above ground level (to distribution system which are routed
with open flue boilers and/or an VDI6022 at 3m height). To prevent through unheated areas, with
unenclosed, open flue combustion facility ingress of humidity (driving rain, vapour−tight material.
(e.g. open fireplace). turbulent snowfall) and icing up of the
inlet grille, it would be advantageous to H In case of installation inside the
Doors to the boiler room(s) must be locate the inlet underneath a roof thermally insulated building envelope
airtight and must be kept closed. overhang or similar. Expelled air should (temperature inside the installation
freely blow away and not be directed location approx. room temperature):
Note against building structures/parts. To Carefully thermally insulate the outside
Do not interconnect extractor fans and prevent a "short circuit" between the and exhaust air lines with suitable
dryers with waste air expulsion into the fresh air and the expelled air connector material (vapour−tight) (to prevent
pipework of the ventilation equipment. (problem: transfer of odours between condensation and saturation of the
Design cooker hoods and extractors as expelled and outside air), position these thermal insulation). Install this
recirculating or expulsion extractors. in separate locations with a different equipment as near to the thermal
Extractors which expel air to the outside, orientation of inlet and exhaust insulated building envelope to keep
must be equipped with their own outside aperture. these pipe sections as short as possible.
air supply. Thermal losses through these pipe
H Filter the outside air via the filter box sections lead to a significant reduction
H The design and implementation of the supplied with filterF 7 (see ventilation
 of efficiency. Therefore, size the thermal
ventilation system must meet the equipment pack); exhaust air filterG 4 is
 insulation not only in accordance with
criteria for energy−efficient houses. integrated in the equipment. the prevention of dew, but with a
minimum thickness of 100mm.
H Observe the location of the air H We recommend the use of filters in all
connectors (see equipment top view on exhaust air apertures. These are, for In case of installation outside the
page8) and sizing (see page7). example, offered as pre−filters upstream thermally insulated building envelope
of the exhaust air valves, and may be (installation room free from the risk of
H For the outside air supply of the heat simply changed by the user (remove frost):
pump, we recommend the use of a cover grille). Exhaust apertures in Thermally insulate the ventilation air
ground energy exchanger (see page14). kitchens must be equipped with a and exhaust air lines up to the point
Size the ground energy exchanger for a grease filter. We recommend the use of where they penetrate through the
volume flow of 150m3/h. A filterG 4 will
 filters made from stainless steel wool building envelope (at least 100mm).
be sufficient, if a ground energy (grease condensation). Note the Thermal losses from these pipe
exchanger is connected to the resulting pressure drop. The exhaust air sections significantly reduce the
additional outside air terminal. Provide filters also must be replaced or cleaned efficiency; therefore keep them as short
a filterF 7 for reasons of hygiene, if a
 regularly. as possible. For that reason, install the
ground energy exchanger should be equipment as near to the thermal
used upstream of the outside air H Install silencers for ventilation and building envelope as possible.
channel which is routed via the heat exhaust air immediately upstream or
exchanger. The pressure drop in the downstream of the equipment. Select H Arrange the ventilation air outlets (wide
ground energy exchanger may be a an insert silencer which brings the angle nozzle or plate valve) so that
max. of 50Pa. sound level inside the living space draughts and short circuit flow patterns
lower than 25dB(A) or in domestic in the living space are prevented. We
H When using a ground energy exchanger offices lower than 30dB(A). Set recommend the installation of wide
for outside air and outside air supply of telephony silencers between rooms to angle nozzles (arranged approx.
the heat pump, install a motor−driven limit sound transmission between 150mm below the ceiling), since users
damper downstream of the tee piece different rooms. will not block these with furniture.
and upstream of the fan for the outside
air supply of the heat pump. H Subject to the location of the inlet and H Design the channel network as short as
For information regarding the sizing of outlet apertures for outside and exhaust possible, using the smallest number of
the ground energy exchanger, air, install silencers to protect the duct/channel profiles (low pressure
see page7. outside against noise pollution. This drop, easy cleaning).
may be appropriate, if walkways
(arcades, development paths, etc.) are H The overall pressure drop of the air
located near the in/outlet apertures. channel network must not exceed
100Pa either for the ventilation air or
H Route equipment lines flexibly inside a the exhaust air.
flexible pipe to provide an anti−vibration
separation. H Size the air channel network for a
maximum volume (required air volume
H Do not let lines sag, to prevent the to deliver the maximum heating load at
accumulation of condensate. 14ºC outside temperature and 20ºC
room temperature).
5822282 GB

H Heating load or heat demand are


calculated per room to EN12831.

VITOTRES 343 11
4.1Location and installation conditions

Primary and secondary connections

H The water connections are located at


B the r.h. top of the equipment (see top
view of the equipment on page8).

E H Only fill TyfocorGLS or LS (frost


protection down to 28ºC) into the
internal hydraulic circuit and into the
optional auxiliary heating circuit.
Never dilute the process medium with
water.

H When operating Vitotres without


external hydraulic circuits (auxiliary
heating circuit, solar panel), adjust the
diaphragm expansion vessel inlet
pressure to 1.5bar and the system
pressure to 1.7bar.
A
H Design the auxiliary heating circuit as
single pipe circuit or install an overflow
valve (minimum circulation volume
700litres/h).
C
H Equip the auxiliary heating circuit on
site with a circulation pump (with check
F valve), with a diaphragm expansion
vessel and a Tyfocorresistant air vent
valve.

C H If, in addition to the auxiliary heating


circuit, a solar circuit is connected,
install a common diaphragm expansion
vessel, which must be sized in
accordance with the details on page16.

H Never use zinc−plated/galvanised pipes


D for the auxiliary heating circuit and the
solar circuit.

H Permissible primary system operating


A Vitotres dimensions D Position (centre pipe) of the on−site pressure (Vitotres with auxiliary heating
B Installation location of the connection drain connection DN32 for condensate circuit and/or solar circuit): 3.5bar.
panel with a wall clearance of 15mm
C Possible position (centre pipe) of the E Possible installation location of the H The solar circuit pump is integrated into
on−site drain connection DN32 for electrical junction box (permanently Vitotres.
condensate with a wall clearance of connected to Vitotres)
y45mm F Top edge  finished floor H Equip the DHW circulation pipe with a
circulation pump and a check valve.

H Provide anti−scalding protection for


DHW temperatures >60ºC.
For connecting the secondary side, observe DIN1988 and DIN4753.
H A safety valve with visible outlet of the
K blow−off line (to DIN1988) on the DHW
B side, and a shut−off and drain valve are
A integrated in the equipment.
C
H A safety valve is installed into the
F G H L H K primary and secondary side of the
equipment.
D E H G M N
H A common drain with siphon for the
safety valve on the secondary side and
G Drain valve for condensate from the heat exchanger
A Hot water H Shut−off valve has been integrated into the equipment.
B DHW circulation pump K Cold water For this drain line, provide a connection
C Spring−loaded check valve L Drinking water filter DN32 to the domestic waste water
5822282 GB

D Hydraulic connection array of Vitotres M Pressure reducer system.


(top view) N Non−return valve/pipe separator
E Flow regulating valve
F Pressure gauge connection

12 VITOTRES 343
4.1Location and installation conditions

Electrical connections

H All external electrical connections of the H Make the mains power supply H Control the motor for the damper of the
equipment (including sensor leads) are connection as permanently installed ground energy exchanger (optional) via
terminated in the separate junction box. cable 5×2.5mm2 (e.g. typeNYM), and an on−site relay (24V/25mA, with a
The junction box is factory−equipped protect it with a breaker of 3×16A protective diode in accordance with the
with a permanent electrical connection (minimum contact separation 3mm). details provided by the relay
to Vitotres in the form of a cable manufacturer).
approx. 1 m long. H As sensor leads we recommend the use Do not install the relay inside the
of a screened cable (e.g. JY(St)Y, Vitotres junction box. Maximum length
H The junction box may be installed at a 2×0.8mm2, max. length 10m). Room of the connecting cable between the
height of 2 to 2.5m up to 0.3 or 0.4m temperature sensor leads should be junction box and the relay 500mm.
adjacent to the equipment (see chased into the wall.
page12). All on−site power supply H The electric heater in Vitotres may be
cables and sensor leads must be Note switched OFF by an external zero volt
terminated inside this box. Never route LV cables immediately next contact (N/C) to be installed on site. The
When installing the equipment in to 230/400 V cables. contact must be suitable for 230V~, and
corners or niches, ensure the easy meet the VDE guidelines (or local
accessibility of the junction box for For cable runs>10m use a larger regulations).
maintenance work. cross−section or terminate several cores
together.
H Never secure the junction box on the
Vitotres casing. Install the junction box H Observe the following requirements for
so that the cable entries are located at the installation location of the room
the bottom of the casing. temperature sensor:
 in the overflow range (see page23) on
H Route the following cables/leads to the an internal wall, approx. 1.5m from
junction box: the floor
 Mains power supply  not near windows and doors
 Room temperature sensor  not near heat sources (direct sunlight,
 Pump of the auxiliary heating circuit fireplace, TV set, etc.)
(if installed)  install the room temperature sensor
 DHW circulation pump on a flush box.
(if installed)
 External shutdown of the electric
heater
(if installed)
 Collector temperature sensor
(if installed)
 Relay for controlling the damper in
the outside air supply of the heat
pump.

Operating tips

H Never disconnect the equipment for H Note H Change the air filter twice annually.
longer periods from the mains supply This equipment is not suitable for A severely contaminated filter and all
or at the mains isolator, otherwise: screed drying. other faults are reported in the control
 there will be no frost protection unit display.
 the DHW cylinder will not be When using this equipment for drying
protected against corrosion (the the building (during the first year of H If the system is operated in exhaust
power supply of the external current use), expect a higher level of mode only during summer, hygiene
anode will be interrupted) condensation and more severe filter dictates a change of the outside air filter
 the house will not receive its basic contamination than normal. Ensure the before bringing the system fully into
ventilation. condensate drains off properly during use again.
that phase; for this, regularly check the
When heating, ventilation or DHW drain connection and the Vitotres
heating are not required for a longer condensate drain.
period of time (e.g. during a holiday),
we recommend you activate the holiday
program. At this setting, the basic
ventilation of the house, frost
5822282 GB

protection and corrosion protection of


the DHW cylinder are ensured.

VITOTRES 343 13
4.2Sizing the ground energy exchanger

4.2Sizing the ground energy exchanger (GEE)


Requirements of the ground energy exchanger

Pipe diameter (recommendation) DN200 We recommend the use of a ground


energy exchanger for supplying the
Required length (guide valve) Approx. 0.2m per m3 transported air volume
outside air to the heat pump. This
(transported air volume  ventilation equipment
ensures that the Vitotres heat pump
and heat pump max. 300m3/h, heat pump only
receives a supply of frost−free air even at
max. 150m3/h)
outside temperatures below zero, which
Required length with a frost−free Min. 0.3m per m3 air volume (subject to type of enables the heat pump to operate with a
inlet soil, see diagram below) correspondingly good performance
Max. permissible pressure drop Up to 50Pa factor.
To protect the ground energy exchanger
Material Pipes made from PVC, PE, clay or concrete
against contamination, install a
Installation depth Approx. 0.2m below frost limit (1.2 to 1.5m depth) ventilation air filter classG 4 at the air


Outside air inlet Min. 1.2m above ground level inlet aperture. Ensure the entry into the
Installation fall 2 % to the lowest point of the condensate drain

building is implemented free from
thermal bridges and airtight.
If, as shown in the installation example, a
dewatering system (draining elementC)
is used, then the ground energy
exchanger should not be installed in an
Minimum outlet temperature depending on type of soil (result from an annual simulation) area influenced by groundwater.
Length of the ground energy exchanger 0.3m/m3 air volume, depth of installation 1.2m Furthermore, the routing and dewatering
and pipe diameter DN200) method shown in the installation
example is only then appropriate, if the
Min. outlet temperature in °C

4
ground energy exchanger is only
3 connected to the outside air supply of the
heat pump. If the fresh air routed into the
2
building also should be preheated by the
1 ground energy exchanger, dewater the
0 ground energy exchanger via a siphon
(hygiene, prevention of radon being
−1 introduced from the ground). In this case,
−2 install a filterF 7 in front of the inlet.


To save excavation costs, we recommend


−3 the installation of the ground channel in
Sand Coarse Chalky Sand Sand Sand Loamy Loam
the wider excavation of the building. The
dry pebbly rich stone soil damp soil
ground pipework must be absolutely sound (butt
welding or welding sleeves).
Type of soil

Installation example

Cut−away Top view

A
F

B min. 1,500 mm F
E

C
5822282 GB

A Inlet aperture D Observe 2 % fall


 F For supplying outside air to the heat
B Filter (G 4 or F 7, see text)   E Cleaning aperture pump in Vitotres
C Draining element (use only for the
outside air supply to the heat pump)

14 VITOTRES 343
4.3Solar panel connection and calculating the diaphragm expansion vessel

4.3Solar panel connection and calculating the diaphragm expansion vessel


A maximum of 5m2 Vitosol100 flat Connect a suitably sized diaphragm To achieve the required flow capacity, it is
collectors or 3m2 Vitosol200/250/300 expansion vessel to the pipework to be necessary to calculate the pressure drop
tube collectors can be connected to installed. If an auxiliary heating circuit is of the pipework including the collector
Vitotres343.*1 connected to Vitotres, include that in your area. A residual head of 180mbar is
Provide pipework from the collector area calculations too. available.
to the Vitotres connection panel on site. A safety valve, a solar circuit pump and
Vitotres is fully prepared for the the relevant control functions are already With regard to implementation,
connection of the solar circuit. Provide integrated into Vitotres. calculation and limits of application, the
thermal insulation for the pipework in a technical guide, the datasheet, the service
material which is capable of withstanding instructions and the installation
temperatures up to 185ºC. This also instructions of the relevant solar heating
applies to the use of fixing clamps. systems as amended apply.

*1Themaximum collector area mentioned in the Vitosol technical guide, which relates to the volume of the DHW cylinder, does not
apply to Vitotres343. These values can be exceeded, as Vitotres offers several redundant temperature sensors. The use of an
additional high limit safety cut−out is also no required.

Design and effect of the diaphragm expansion vessel

A diaphragm expansion vessel is a closed To safely prevent steam being created To ensure that no process medium can
expansion vessel whose gas chamber during the operating phase, collectors escape from the safety valve, the
(nitrogen filling) is separated from the must indicate a pressure of at least expansion vessel must be sufficiently
liquid chamber (process medium) by a 1.5bar in their cold state. The inlet large to accommodate the content of the
diaphragm and whose inlet pressure is pressure of the expansion vessel will then collector when steam forms (stagnation).
subject to the system head. be 0.1×higher than static headh. In hot To protect the diaphragm against
conditions, the system pressure rises by unacceptably high temperatures
Note approx. 1 to 2bar. Maximum shutdown (generally x70 ºC), we recommend the
The inlet pressure must be adjusted as temperature figures: installation of a stratification cylinder
follows: 1.5bar+0.1×static head. H Vitosol100, (mostly required for systems installed
The water seal should be 0.01 to types/w2.5: 211ºC under the roof). A generally applicable
0.02×liquid content of the complete type5DI: 185ºC formula for calculating the required
system, but no less than three litres. H Vitosol200: 300ºC, container size cannot be provided.
H Vitosol250: 286ºC, However, the cylinder volume should be
H Vitosol300: 150ºC. at least 50 % of the system volume.


A A A

D E

B C C

As delivered condition Solar heating system Under maximum pressure


(3bar inlet pressure) filled, without heat effect with the highest process
medium temperature

A Process medium
B Nitrogen filling
C Nitrogen buffer
D Safety water seal (min. 3litres)
E Safety water seal
5822282 GB

VITOTRES 343 15
4.3Solar panel connection and calculating the diaphragm expansion vessel

Specification of the solar expansion vessels (see Vitosol accessory)

a Table for calculating Cu pipe content


Pipe dimension litres/m ml/m
15×1mm 0.14 140
18×1mm 0.20 200
22×1mm 0.30 300
b

Contents Operating ∅a b Connection Weight


litres pressure mm mm R kg
bar
18 10 280 370 ¾" 7,5
25 10 280 490 ¾" 9,1
40 10 354 520 ¾" 15,0

Calculating the diaphragm expansion vessel

The nominal capacity of the expansion Calculation example


vessel is calculated according to the System comprising:
equation 1Vitosol100, type5DI with 4.2litres
 (V v ) V 2 ) z @ V k) @ (p e ) 1)
VN= p e * p st Total liquid capacity of the system:
VA=22litres
Whereby Static head: h=4m
VN = nominal capacity of the diaphragm Permissible final pressure: pe=3.6bar(ü)
expansion vessel (MAG) in litres (Safety valve blow off pressure: 4bar)
Vv = Safety water seal (here  (V v ) V 2 ) z @ V k) @ (p e ) 1)
process medium) in litres VN= p e * p st
Vv=VA·(0.01 ... 0.02) in litres
(min. 3litres)
VA = Liquid content of the entire Vv = VA·0.015
system = 0.33litres, selected 3litres
V2 = Increase in volume when the system (see l.h. column)
heats up V2 = VA·b
V2 = VA·b = 2.86litres
b = Expansion quotient (b=0.13 pst = 1.5bar+0.1·4
for Viessmann process = 1.9bar
medium from 20 to 120ºC)
 (3 ) 2.86 ) 1 @ 4.2) @ (3.6 ) 1)
pe = Permissible end pressure in bar(ü) VN =
3.6 * 1.9
pe = psi0.1·psi
psi = safety valve blow off pressure = 27.22litres
pst = Nitrogen inlet pressure of DEV
in bar(ü) The next largest expansion vessel,
pst = 1.5bar+0.1 bmar ·h[m] i.e. 40litres, should be chosen.
h = Static head of the system in m
Difference in height between
the Vitotres pressure gauge
and the highest point of the
solar heating system
z = Number of collectors
Vk = Collector capacity in litres
5822282 GB

16 VITOTRES 343
4.4Installation of an auxiliary heating circuit

4.4Installation of an auxiliary heating circuit


An additional hydraulic heating circuit Design temperatures: Note
can be connected to Vitotres. Underfloor There is no ventilation air heating, when
heating system 45ºC (max. 60ºC) the auxiliary heating circuit is operated.
The use of an additional radiator may be Radiator
sensible for two reasons: to increase the heating system 55ºC (max. 70ºC) Design the auxiliary heating circuit as
comfort and the room temperature in a single pipe heating circuit or with
bathroom or for supplying additional Both design temperatures ensure overflow valve (minimum circulating
heat, which cannot be supplied via the operation with the integral heat pump. Up volume 700litres/h), and fill with
ventilation air. Increasing the ventilation to 7.5kW output can be achieved via the TyfocorGLS or LS.
air flow beyond that which is sensible hydraulic heating circuit. Of that, 6kW is Equip the auxiliary heating circuit on site
from a hygiene point of view (30m3/h per provided by the electric heater. with a Tyfocorresistant circulation pump
person) is not recommended, otherwise (with check valve), with a diaphragm
the relative humidity in the ventilated expansion vessel and a Tyfocorresistant
areas would drop too low. air vent valve.

A constant, adjustable flow temperature Provide a suitably sized common


can be provided for the flow of the diaphragm expansion vessel (see
auxiliary heating circuit. The heating page15) when simultaneously
periods can be selected at random on the connecting solar panels.
Vitotres control unit.
5822282 GB

VITOTRES 343 17
4.5System versions

4.5System type
Functions

Note
The figure on page19 complements the function description.

Ventilation If, at very low outside temperatures, the Solar heating system
output of heat pump7 is insufficient,
The Vitotres compact device offers a then electric heaterqQ can be started The equipment is prepared for
central domestic ventilation system manually or automatically. connection of a solar heating system for
with heat recovery1 in accordance with DHW heating. Apart from installing solar
energy−efficient house criteria. panelsqR, only an expansion vesselqT
The heat recovery is bypassed when and a collector temperature sensorqZ
temperatures inside the house are too DHW heating must be connected.
high (summer bypass2). The control is
implemented according to the difference The DHW heating through heat pump7 The solar heating system will be
between the selected set temperature and has priority over central heating. Heating regulated via a two−point controller
the actual temperature measured at room demand is signalled via 3cylinder integrated into the control unit, which
temperature sensor3 in the lead room. temperature sensorsqW and the control compares the collector temperature with
This lead room should be approximately unit, which regulates heat pump7 via the temperature at lower cylinder
representative of the average three−way valve9 to load DHW temperature sensorqW.
temperature of the living unit. It is cylinderqE. The heat pump raises the
therefore measured in the core of the flow temperature to the value required for
building, generally in a hallway, see DHW heating.
page23). Arrange the room temperature Auxiliary heating circuit
sensor so that it is free from interference. In case of higher demand, the DHW is
Avoid direct solar irradiation onto the backed up by electric heaterqQ. A hydraulic heating circuitqU (e.g. for a
room temperature sensor. Erroneous The control unit switches the heating flow bathroom radiator) can be connected.
control patterns may also be caused by via three−way valve9 to ventilation This heating circuit is unsuitable for
the room temperature sensor being bankqP,if the actual value measured at providing the basic home temperature.
heated by heating surfaces (e.g. through cylinder temperature sensorsqW is higher For a selectable period (e. g. 30minutes in


a bathroom wall). than the set value selected at the control the morning), heat pump7 provides the
unit. Where a high DHW demand is flow temperature set at the control unit.
anticipated, install an instantaneous On−site heating circuit pumpqI is started
water heaterwI for DHW into the DHW by the control unit.
Ground energy exchanger line downstream of Vitotres during the The external heating circuit is filled with
system installation. In that case, the DHW TyfocorGLS or LS process medium and
A ground energy exchanger (GEE) can be backup by electric heaterqQ is is protected by the internal safety valve
installed on the outside air side of the suppressed by the control unit. with 4bar.
ventilation equipment.
A ground energy exchanger for frost
protection is not required. The equipment
is fitted with internal frost protection. Cooling operation Electric radiator
Provide a filterG 4wO for outside air


supply 4 to the heat pump. We The ventilation air6 of the ventilation If no external heating circuit is connected,
recommend the use of a ground energy equipment can be cooled by the heat the control unit time switch, which
exchanger5. pump7. This is controlled by the controls the auxiliary heating circuit relay,
difference between the selected set can be used to control a contactor/mains
temperature and the actual temperature switch of another heat source (electric
measured by the room temperature radiator).
Central heating sensor3.
Ensure the component surface is free ¨Safety instruction
The compact device heats the house by from condensation. The externally connected electric radiator
heating ventilation air6. For this, heat must be thermostatically controlled and
pump7 is used, which utilises the protected in its own right.
residual energy in expelled air8 Vitotres provides no monitoring of this
downstream of heat recovery1. external device.
Three−way valve9 diverts the heat
pump to ventilation air bankqP to provide


central heating.
The requirement for central heating is
triggered by the difference between the
selected set room temperature and the
actual room temperature measured by
5822282 GB

room temperature sensor3 in the lead


room.

18 VITOTRES 343
4.5System versions

System design

3 qZ
qR wI

*1
qT

*1
qT

wU qU wT qI
qO
wZ

wO 5 wP

wR wE
4 8 wQ wW
6 ZU AB AU AW FO HV HR RL VL WW Z KW

G4

2
7

HR AB Exhaust air
9 AU Outside air
qP qQ AW Outside air supply to the
100%
HV heat pump
WW E Drain
qW FO Expelled air
qE VL HR Heating return
Z HV Heating flow
qW
KW Cold water
qW RL Solar return
RL VL Solar flow
WW Hot water
Z DHW circulation
KW/E Vitotres 343 ZU Ventilation air
Air routing

*1Alternatively in the solar circuit or auxiliary heating circuit.

1 Heat recovery 7 Air heat pump qW Cylinder temperature sensors


2 Summer bypass 8 Expelled air qE DHW cylinder
3 Room temperature sensor 9 Three−way valve
4 Outside air supply to the heat pump qP Ventilation air bank PositionsqR to wU are explained on
5 Ground energy exchanger qQ Electric heater page20.
6 Ventilation air
5822282 GB

VITOTRES 343 19
4.5System versions

Required equipment

Item Description Number Part no.


Vitotres343 1 Z002366
3 Room temperature sensor 1 Standard delivery
wR Outside air filterF 7
 1 Standard delivery

Accessories
5 Ground energy exchanger 1 on−site
qT Diaphragm expansion vessel (only required for the options solar circuit and auxiliary 1 See Vitoset price list
heating circuit; only required once if both options are utilised)
wP Connection panel 1 7159985
wO Outside air filterG 4
 1 on−site

Accessory for DHW circulation option


qO DHW circulation pump 1 See Vitoset price list
wE DHW circulation extension 1 7169387

Accessory for solar circuit option


qR Solar panels
up to 5m2 Vitosol100 or up to 3m2 Vitosol200/250/300 according to See Vitotec price list
requirements
qZ Collector temperature sensor 1 7814617
wW Solar circuit extension 1 7169386

Accessory for auxiliary heating circuit option


qU Universal radiator or underfloor heating system according to See Vitoset price list
requirements
qI Heating circuit pump 1 See Vitotec price list
wQ Heating circuit extension 1 7169385
wT Check valve 1 See Vitoset price list
wZ Room thermostat 1 See Vitoset price list
wU Overflow valve 1 on−site

5822282 GB

20 VITOTRES 343
5.1Sizing

5.1Sizing
The following sizing information applies
exclusively to energy−efficient houses.

We recommend you let a design engineer


size the air distribution system. For this,
short paths within the air distribution
system and even room flow rates are
desirable. Possible higher thermal losses
of individual rooms must be taken into
consideration in the final planning stages
and should be compensated through
matching volume flow patterns.

Calculating the basic air change or the average air change volume

This is calculated via the fresh air supply The distribution of the exhaust air volume The air volume hygienically necessary
demand of occupants (30m3/h per flow to the rooms from which air is (30m3/h per person) is applied as sizing
person). The ventilation flow should be exhausted is generally derived from the criterion for the overall volume flow and
distributed across all rooms, so that two following table. not the air volume required for delivering
occupants can occupy a normal room for In many cases, the exhaust air volume heat. If the latter is higher than the
a longer period and with good air quality, can be reduced if the exhaust air former, the additional output must be
whilst internal doors are shut and no condition results in substantially greater provided by static heating surfaces,
additional ventilation via windows is values than the ventilation air condition. otherwise there will be a risk of the
required. This applies particularly to For example, the volume flow from a ambient air becoming too dry. However, it
domestic offices and bedrooms. As first room, from which air is extracted can be would be sensible to slightly match the
rule of thumb, 40m3/h can be applied. reduced provided the air change rate in volume flow in individual rooms in the
Since generally, not all rooms are that room is higher than 2h1 (empirical final planning stage, to compensate for
simultaneously occupied by two value). The balance must be maintained possibly higher thermal losses in
occupants, the air volume in less for the whole living unit. Consequently individual rooms.
occupied zones may possibly be reduced the exhausted air volume must be
to the minimum air change rate. increased in the reverse case (ventilation
The minimum air change rate is 0.3h1 air condition greater than the exhaust air
independent of the occupancy (expulsion condition), making the ventilation and
of noxious matter and odours). exhaust air flow equal.

Room Essential minimum air rate for the ventilation equipment


in 24 hour operation
[m3/h]
Kitchen 60
Kitchenette 40
Bath (WC poss.) 20
WC 20

Calculation example

Given:
Detached house with 4occupants
Exhaust air areas: kitchen, bathroom, shower, WC

Fresh air requirement Exhaust air requirement


Number of occupants 4 Kitchen 40
Fresh air requirement per person 30 Bath 40
[m3/h] Shower 20
WC 20
Total fresh air requirement [m3/h] 120 Total exhaust air requirement 120
[m3/h]
5822282 GB

Result: Adjust Vitotres to a basic air change of 120m3/h.

VITOTRES 343 21
5.1Sizing

Average air change


Apart from day ventilation, Vitotres can The average air change results from the
also be adjusted for other operating average value of the air volume flow
stages (party or night ventilation). For supplied during the day, divided by the
this, ensure that the average air change volume of the building to be ventilated.
will not drop below 0.3.

Calculation example
Given: Building volume 338m3/h, basic Vitotres air changes adjusted to 120m3/h.

Operating mode Factor relative Air volume Air change Case1 Case2
t standard
to t d d fl
flow Daily Air volume Daily Air volume
operation runtime flow runtime flow
[m3/h] [1/h] [h] [m3/24h] [h] [m3/24h]
Party ventilation (maximum) 1.33 160 0.47 0 0 4 640
Day ventilation (basic air change) 1.00 120 0.35 24 2880 0 0
Night ventilation (reduced) 0.67 80 0.24 0 0 20 1600
Air volume 120 Air volume 93
flow [m3/h] flow [m3/h]
Average air 0.35 Average air 0.28
change [1/h] change [1/h]

Result: In case of predominantly reduced operation (case2), the required average air change of 0.3 cannot be achieved.

5822282 GB

22 VITOTRES 343
5.1Sizing

Ventilation air, exhaust air and overflow area


After determining the volume flow for The following are part of the ventilation The following are part of the overflow
basic ventilation, calculate the air change section, e.g. section, e.g.
rates for the individual ventilation air and H Living rooms H Hallways
exhaust air areas. For this purpose, the H Bedrooms H Stairwells
accommodation or utility unit to be H Children’s rooms
ventilated is segregated into ventilation H Dining rooms
air and exhaust air sections. Generally, all
rooms should be ventilated either via The following are part of the exhaust air
ventilation air or exhaust air (except section, e.g.
overflow areas). This also applies to H Kitchen
smaller or box rooms. For this, usually a H Bathrooms
small aperture in the air channel is H WC
sufficient. H Domestic offices

Ground floor Attic

Ventilation air section Exhaust air section Overflow area


5822282 GB

VITOTRES 343 23
5.1Sizing

Air volume flow segregation


The air volume flow is distributed to the For example, for rooms frequently For the regular exhaust air volume flow
individual rooms based on the ventilation occupied by two persons (e. g. living
 for windowless rooms to DIN19466, see
air volume hygienically necessary room), an air volume flow of 40m3/h the table below.
(number of occupants×30m3/h). is applied. For rooms predominantly To enable odours to be removed quickly,
If this results in an air change rate of less occupied by only one person (e.g. child’s a volume flow of 40  60m3/h is
 

than 0.3h1, apply a ventilation air room), an air volume flow of 20m3/h is recommended for kitchens.
volume flow >(building volume×0.3h1). applied.
In that case, the air volume flow will be The remainder of the calculated
distributed to individual rooms subject to ventilation air flow is then distributed to
the number of occupants who generally the other ventilated rooms.
stay in those rooms.

Room Air volume flow for rooms without windows to DIN19466 for a runtime of y12h/d
[m3/h]
Kitchenconstant ventilation (basic ventilation) 40
Bath (WC poss.) 40
WC 20

Example:
Residential building with 4occupants

Ventilation areas

Ventilation areas Floor area [m2] Volume [m3] Ventilation air volume flow [m3/h]
Living room 48.8 122 40
Bedroom 16.8 42 40
Nursery1 23.2 58 20
Nursery2 18.4 46 20

Total ventilation areas 107.2 268 120

Exhaust air areas

Exhaust air areas Floor area [m2] Volume [m3] Exhaust air volume flow [m3/h] Air change [1/h]
Kitchen 16.4 41 40 0.98
Shower 3.6 9 20 2.22
WC (EG) 4.4 11 20 1.82
Bath 7.2 18 40 2.22

Total exhaust air areas 31.6 79 120

If
Ventilationairvolumeflowrequired for hygiene
air change rate of the entire building=
 Totalventilatedairvolume ) totalexhaustairvolume

then for this example, we have

 4occupants @ 30m 3ńh


air change rate of the entire building= =0.351/h
 268m 3 ) 79m 3

Therefore, the air change rate for the entire building is substantially higher than the required minimum air change rate of 0.31/h.
5822282 GB

24 VITOTRES 343
5.1Sizing

Air volume flow and heating load


Guide values for the heating output of Vitotres343 at various ventilation air temperatures and 20ºC room temperature

250 The ventilation air volume flow calculated


A B C D E F in the previous chapter can, subject to the
selected ventilation air temperature,
cover only a certain heating load. Where
200 a generally higher heating load is
required, the equipment will increase the
volume flow up to the value selected for
party ventilation (max. 250m3/h).
150 The adjacent diagram shows the
dependency of the transported heating
output on the volume flow and the
ventilation air temperature.
The heat pump can, subject to the outside
100
air temperature, provide a heating
Volume flow in m3/h

output*1 of up to 1 500W; any higher




requirement will be covered by starting


the internal electric heater. Check for each
50 room, where values approach the
available limits, whether the specific
room heat requirements can be covered
by the selected volume flow. Where that
0 is not the case, increase the volume flow
0 500 1000 1500 2000 2500 3000 or the ventilation air temperature,
Heating output in W alternatively cover the heat demand by
G H means of an additional heat source.

*1Operating point:
Outside air 7ºC, ventilation air 50ºC.

A Ventilation air temperature 30ºC G Heating output provided by the


B Ventilation air temperature 35ºC heat pump
C Ventilation air temperature 40ºC H Heating output provided by the
D Ventilation air temperature 45ºC electrical heater
E Ventilation air temperature 50ºC
F Ventilation air temperature 55ºC

Calculating the heating output

Heating output[W]=Ventilation volume flow[m3/h]·(ventilation air temperature[ºC]room temperature[ºC])·0.34


5822282 GB

VITOTRES 343 25
5.2Air routing

5.2Air routing
Routing air into rooms

Running pipework with suspended ceilings (section)

E The air is distributed by Vitotres to the


living space (ventilation air) or from the
wet areas to the ventilation and extraction
device (exhaust air) via an air distribution
150 mm system with flat channels or circular
D*2 tubes together with matching tees,
B silencers, cleaning and air apertures.
*1 *2 C
A To prevent flow noise development and
pressure drops, observe the following:
H Symmetrical pipework design
F F H Short runs, few bends
H The ventilation pipework takes priority
over the heating, domestic hot water
and drainage network to avoid
complicated pipe runs
H Select a sufficiently large pipe diameter
H Construct the central rising and falling
*1Use wide angle nozzles for this installation location. lines with circular pipe DN160 to
*2Alternative installation options for exhaust air apertures. reduce the pressure drop.

A Overflow area J Ventilation air Pipe material


B Suspended ceiling J Exhaust air H Utilise smooth pipes (folded spiral
C Ventilation air seam)
D Exhaust air H Smooth pipes prevent dust
E Ceiling accumulation and unnecessary
F Door pressure drop
H The pipe material should be corrosion
resistant, non−hygroscopic and
non−combustible.

Connect all pipe joints using plug−in


connectors and make these connections
airtight with cold sealing tape.

Routing air inside rooms

Create a physical air interconnection for


150 mm the air flow from the ventilation air into
the exhaust air areas. A gap of 15mm
height above the entire door width is
sufficient for a volume flow up to 40m3/h.
As rule of thumb, the pressure drop
should not exceed 1Pa. This corresponds
to a flow velocity in the unobstructed
cross−section of less than 1m/s. Where
internal doors are sealed well, noise
attenuated overflow apertures can be
built into the internal wall or into the door
(on−site).
We recommend the use of wide angle
nozzles.
5822282 GB

26 VITOTRES 343
5.2Air routing

Air extraction from kitchens

Because of greasy vapours and


contamination it cannot be recommended
that cooker hoods are connected to the
exhaust air duct. Cooker hoods are
min. 2 m
designed for substantially larger volume
flows (approx. 500m3/h).
Route the exhaust air from cooker hoods
outdoors or utilise recirculating cooker
hoods with grease filters to prevent
energy losses.
When using cooker hoods, take suitable
steps to provide a separate ventilation air
supply into the kitchen to prevent the
creation of negative pressure. Never
extract the kitchen air to Vitotres
immediately next to the cooker hood.

Silencer

Location Installation recommended Installation required


Outside air supply to the ventilation module ×
Outside air supply to the heat pump ×
Expelled air ×
Central ventilation air ×
Ventilation air  living room ×
child’s room ×
V domestic office ×
bedroom ×
Exhaust air − bathroom ×
WC ×
kitchen ×
utility room ×
Central exhaust air ×

Pipework insulation

For optimum operation of the Vitotres In all cases, thermally insulate outside air Insulate carefully and in accordance with
with heat recovery, thermal losses from and expelled air pipes/ducts (min. 20mm) current standard practice. Seal all butt
the pipework must be kept to a minimum. against condensation and provide an joints with adhesive, isolate all ceiling
Insulate ventilation and exhaust air pipes external vapour barrier. and wall outlets by using insulating strips
in unheated areas (min. 50mm). For heated areas, we recommend a and avoid gaps.
thermal insulation of at least 50mm.
Keep pipework lengths from the Suitable installation material could be, for
equipment to the wall outlet through the example Armaflex.
insulated building envelope as short as
possible (for this, see also section4.1).
5822282 GB

VITOTRES 343 27
5.3Vitotres connection
5.4Pressure drop and flow velocities

5.3Vitotres connection
C B Connect the air distribution system of the Please note
building in accordance with local To prevent flow noise, use only rigid
conditions, either pipes as 90 º bends.


H with smooth and rigid 90º bends to the


connector.
Make the connection to the existing air
distribution systems with a flexible pipe
of at least 100mmlength
B (anti−vibration).
C
A or

H with a flexible pipe of at least. 100mm


length (anti−vibration) to the connector.
Make the connection to the existing air
distribution system with smooth and
rigid 90º bends.

A Connector (standard delivery)


B 90º pipe bend DN160
C Flexible pipe DN160
(flexible channel or pipe)

5.4Pressure drop and flow velocities


Pressure drop of different pipework systems

10 A Pipework (flat)100, flexible


B B Pipework (flat)150, flexible
9 C Pipework (round) DN160
D Pipework (flat) 150, rigid
8
E Pipework (circular) DN100
7

6
D
5
Resistance R in Pa/m

4 C
3

2
E
1
A
0
20 30 40 90 150 225
Air volume flow in m3/h
5822282 GB

28 VITOTRES 343
5.4Pressure drop and flow velocities

Flow velocity  volume flow diagram of different pipework systems

7 A Pipework (flat) 100


B Pipework (circular) DN100
D
6 C Pipework (round) DN125
D Pipework (flat) 150
E Pipework (circular) DN160
5

4
B
E
Flow velocity in m/sec.

3 A

1 C

0
20 40 60 90 150 225
Air volume flow in m3/h

Ventilator curves  ventilation module


700

600

500

400
A Ventilation air (without filter)
Pressure drop in Pa

300 B Exhaust air


B A
200

100

0
0 50 100 150 200 250 300 350 400 450 500
Volume flow in m3/h

Pressure drop diagram  outside air filter box (with outside air inlet aperture)
100

80
Pressure drop in Pa

60

40

20

0
5822282 GB

0 50 100 150 200 250 300


Volume flow in m3/h

VITOTRES 343 29
6.1Form for designing air volume flow patterns for Vitotres343

6.1Form for designing air volume flow patterns for Vitotres343


Project:

Project:

Ventilation areas

Ventilation area Volume flow guide value*1 Number Ventilation air volume flow
[m3/h] [m3/h]
Living room
Bedroom
Dining room
Study
Child’s room1
Child’s room2

Total ventilation areas


*1With 1person occupying the room: 20m 3/h, for 2occupants: 40m 3/h.
See also page24.

Exhaust air areas

Exhaust air area Volume flow guide value*2 Number Exhaust air volume flow,
[m3/h] calculated
[m3/h]
Kitchen
Bath (WC poss.)
WC
Utility room

Total exhaust air areas


*2See page24.
5822282 GB

30 VITOTRES 343
6.2Glossary

6.2Glossary
Air change Ground energy exchanger (GEE) Standard mode
A measure for the air changes which A pipework system laid underground to See basic air change
identifies how often air in a building is utilise energy or cold stored in the
completely changed every hour. ground to precondition outside air Ventilation air
channelled to the ventilation equipment. The total air volume flowing into a room.
Basic air change
Air change required to maintain hygienic Heat recovery Ventilation air valve
conditions and ambient air quality for Steps required for reusing the thermal See ventilation air aperture
normal activities of occupants. energy of air being extracted from a
room. Ventilation aperture
Blower door test The heat which would otherwise be lost Aperture through which ventilation air is
Procedure for testing the air tightness of through the exhaust air is recovered and supplied to a room.
buildings. added to the ventilation air intake.
Ventilation heat loss
Energy−efficient house Outside air That proportion of the annual heat
Houses with a heating energy All air drawn in from the outside. demand attributable to the heating of the
requirement <15kWh/(m2·a) and a air changed within the building.
necessary heating load <10W/m2. Overflow area
No ventilation and exhaust air apertures Volume flow balance
Exhaust air are installed in the overflow area. (physically correct: mass flow balance)
Air extracted from the room by the The air flows across this area from Automatic fan influence, which constantly
ventilation system. ventilation areas into exhaust air areas. maintains the ventilation air and exhaust
air balance.
Exhaust aperture Party mode
See exhaust valve The air changes required for maintaining
hygienic conditions and the quality of
Exhaust valve ambient air with high occupancy rates or
Aperture through which exhaust air is high air contamination (e.g. through
removed from the room. smoking).

Expelled air Reduced mode


Air expelled to the outside. Air change required to maintain hygienic
and ambient air quality for low levels of
Filters activities of occupants or during their
Separation of contamination from air absence.
streams.
5822282 GB

VITOTRES 343 31
Printed on environmentally friendly,
chlorine−free bleached paper

Subject to technical modifications.

Viessmann Werke GmbH&Co


D35107 Allendorf
Tel: +49 6452 700
Fax: +49 6452 702780
www.viessmann.de

Viessmann Limited
Hortonwood 30, Telford
5822282 GB

Shropshire, TF1 7YP, GB


Tel: +44 1952 675000
Fax: +44 1952 675040
E−mail: info−uk@viessmann.com

32 VITOTRES 343

Potrebbero piacerti anche