Sei sulla pagina 1di 8

We are ready: IEC 62271-200

The new switchgear standard

Power Transmission and Distribution


Standards for all

Switchgear are important nodal points


in modern power distribution. Corre-
spondingly important is their reliable
functioning, a clearly defined switch-
ing behavior according to specified
parameters as well as the protection of
personnel and protection against oper-
ational interruptions when an overload
occurs.

The International Electrotechnical


Commission (IEC) has taken up the
task of developing the required speci-
fications, their worldwide standard-
ization and further development. The
same applies to IEC 62271-200 – the
new standard for medium-voltage
switchgear.

As one of the first manufacturers,


Siemens has implemented these
requirements and already offers the
complete product range of air-insu-
lated and gas-insulated switchgear
today, type-tested according to
IEC 62271-200.

IEC 62271-200
IEC 62271-2
IEC 62271-200
2
Retrospective

IEC 60298 – for four decades this abbre- Criterion 1:


viation was the decisive factor for the type Doors and covers must not open.
testing of metal-enclosed switchgear. In Criterion 2:
the meantime there are tens of thousands Parts of the switchgear must not fly off.
of switchgear panels of the primary and Criterion 3:
secondary distribution level based on this Holes must not develop in the external
standard in use – certified according to parts of the enclosure.
the mandatory part of the standard and, Criterion 4:
if required, according to optional tests. Vertical indicators must not ignite.
The passing of the following tests was Criterion 5:
obligatory in order to identify switchgear as Horizontal indicators must not ignite.
type-tested: Criterion 6:
Earth connections must remain effective.
Dielectric test to verify the insulation
level of the switchgear (tests with rated In order to guarantee safe access to the
lightning impulse withstand voltage and individual switchgear components, e.g.the
rated short-duration power frequency incoming cable, without isolating the busbar,
withstand voltage with the specified the IEC 60298 standard differentiates bet-
values depending on the respective rated ween three types of compartmentalization
voltage). that serve exclusively as protection against
electric shock.
Temperature rise tests to verify the
current carrying capacity with rated normal Metal-clad switchgear: Division of the
currents. switchgear panel into four compartments
(busbar compartment, switching-device
Peak and short-time withstand current compartment, connection compartment
tests to verify the dynamic and thermal and low-voltage compartment); partitions
current carrying capacity of the main and between the compartments made of sheet
earth circuits; the tests are performed with steel, front plate made of sheet steel or
rated peak short-circuit current or rated insulating material.
short-circuit making current or rated short-
time current or rated short-circuit breaking Compartmented switchgear: Division of
current. the switchgear panel same as for metal-clad
switchgear, but with the partitions between
Switching capacity test to verify the the individual compartments made of insu-
making/breaking capacity of the installed lating material.
switchgear.
Cubicle-type switchgear: All other types
Mechanical function test to verify the of construction that do not meet the above
mechanical functions and interlocks. features of the metal-clad or compartmented
designs.
Degree of protection tests to verify the
protection against electric shock and foreign In this context, access to the then common
objects. minimum-oil-content circuit-breakers for
maintenance work without longer opera-
Pressure and strength tests to verify tional interruptions was of prime importance
the gas tightness and pressure resistance for because of the limited number of operating
gas-filled switchgear. cycles. Therefore, with switchgear in metal-

00 There is also the possibility of voluntarily


certifying switchgear for resistance to inter-
nal arc faults and for personal protection.

Manufacturers and operators can select the


clad or compartmented design, the busbar
in the busbar compartment and the incom-
ing cable in the connection compartment
could remain in operation. With a cubicle-
type design, the incoming cable had to be
isolated, but the busbar itself could remain
criteria which are relevant to them from the in operation.
following six criteria and have them tested.

3
New specifications –
new challenges
Overview of IEC 62271-200

Although the old IEC 60298 standard Four key features are of special note with 4. Stricter internal arc classification
was very helpful, in time it was super- the new IEC 62271-200 standard: Significantly stricter changes have also
seded by the technological progress. been implemented here. The energy flow
Above all, the appearance of mainte- 1. Changed dielectric requirements direction of the arc supply, the maximum
nance-free vacuum circuit-breakers, According to IEC 60298, two disruptive number of permissible panels with the
with operating cycles far exceeding discharges were permitted in a series of test in the end panel and the dependency
the normal number, made frequent 15 voltage impulses for the test with rated of the ceiling height on the respective
access to this circuit-breaker no longer lightning impulse withstand voltage. Ac- panel height have been redefined. In
of prime importance. cording to the new standard, the series addition, the five following new criteria
must be extended by another five voltage must always be completely fulfilled (no
The vacuum arc-quenching principle impulses if a disruptive discharge has oc- exceptions are permitted):
is technologically so superior to other curred during the first 15 impulses. This can
arc-quenching principles that the lead to a maximum of 25 voltage impulses, 1) Covers and doors remain closed.
circuit-breaker can be fixed-mounted whereas the maximum number of permis- Limited deformations are accepted.
again. This resulted in the first-time sible disruptive discharges is still two. 2) No fragmentation of the enclosure,
use of gas insulation with the impor- no projection of small parts above
tant features of climatic independence, 2. Increased demands on the circuit- 60 g weight.
compactness and maintenance-free breaker and earthing switch 3) No holes in the accessible sides up
design. However, both technologies – In contrast to the previous standard, the to a height of 2 meters.
the vacuum arc-quenching principle switching capacity test of both switching 4) Horizontal and vertical indicators do not
and gas insulation – were not ade- devices is no longer carried out as a pure ignite due to the effect of hot gases.
quately taken into account in the exist- device test. Instead, it is now mandatory 5) The enclosure remains connected to
ing standard. to carry out the test in the corresponding its earthing parts.
switchgear panel. The switching capacity
Therefore, at the end of the nine- may get a negative influence from the For the internal arc classification of
ties, the responsible IEC committees different arrangement of the switchgear substations with and without control
decided on the reformulation of the with contact arms, moving contacts, aisle, the testing of the substation with
switchgear standard, which finally conductor bars, etc. installed switchgear is mandatory in the
came into effect as IEC 62271-200 in new IEC 62271-202 standard. The clas-
November 2003. At the same time the For this reason, the test duties T100s and sification of the substation is only valid
old IEC 60298 standard was withdrawn T100a from the IEC 62271-100 standard in combination with the switchgear used
without any transition period. are stipulated for the test of the circuit- for the test. The classification cannot be
breaker inside the switchgear panel. transferred to a combination with an-
other switchgear type as each switchgear
3. New partition classification behaves differently in the case of an in-
The new partition classes PM (partitions ternal arc (pressure relief equipment with
metallic = partitions and shutters made different cross-sections and pickup pres-
of metal) or PI (partitions nonmetallic = sures, different arcing conditions because
partitions and shutters made of insulat- of different conductor geometries).
ing material) now apply with respect to
the protection against electric shock dur-
ing access to the individual components.
The assignment is no longer according
to the constructional description (metal-
clad, compartmented or cubicle-type
design), but according to operator-related
criteria (Tables 1 and 2).

4
Table 1

Loss of service When an accessible compartment of Constructional design


continuity category the switchgear is opened: …

LSC 1 … then the busbar and therefore No partitions within the panel, no
the complete switchgear must be panel partition walls to adjacent
isolated. panels.

Overview of the characteristic values


LSC 2 LSC 2A … then the incoming cable must be Panel partition walls and isolating
isolated. The busbar and the adjacent distance with compartmentaliza- The IAC classification describes a success-
switchgear panels can remain in tion to the busbar. ful test. It results from the definition of
operation. the degree of accessibility, the possibili-
ties of arrangement inside a room, as
well as the test current and test time
LSC 2B … then the incoming cable, the Panel partition walls and isolating (Table 3).
busbar and the adjacent switchgear distance with compartmentaliza-
panels can remain in operation. tion to the busbar and to the cable.
Medium-voltage switchgear in the pri-
mary and secondary distribution level is
generally classified with degree of acces-
sibility A. This means they are intended
for use in rooms that are only accessible
Table 2
to authorized personnel (closed electrical
Type of accessibility Access features service locations).
to a compartment
Switchgear that is accessible by general
public has the degree of accessibility B
Interlock-based Opening for normal operation and Access is controlled by the (distance of indicators = 100 mm) and
maintenance, e.g. fuse replacement. construction of the switchgear, polemounted switchgear has the degree
i.e. integrated interlocks prevent
impermissible opening.
of accessibility C (indicators below a
tower in an area of 3 x 3 m).

Consequences for operators


Procedure-based Opening for normal operation and Access control via a suitable pro- With the new IEC 62271-200 standard,
maintenance, e.g. fuse replacement. cedure (work instruction of the the following conditions must be satisfied
operator) combined with a locking
device (lock). by the switchgear operators:

Already existing switchgear can still be


operated in accordance with IEC 60298.
Tool-based Opening not for normal operation or Access only with tool for opening,
maintenance, e.g. cable testing. special access procedure
However, new switchgear must fulfill the
(instruction of the operator). IEC 62271-200 standard in order to avoid
any resulting legal disadvantages. A situ-
ation which has a number of advantages.
For example, the comparison and evalu-
Nonaccessible Opening not possible / not intended for operator, ation of switchgear features is now more
opening can destroy the compartment. transparent. But also from an economic
This applies generally to the gas-filled compartments of gas-insulated point of view, they are an investment in
switchgear. As the switchgear is maintenance-free and climate-indepen-
the future.
dent, access is neither required nor possible.

Table 3

The notation IAC A FLR, I and t contains the abbreviations for the following values:

IAC Internal Arc Classification

Distance between the indicators 300 mm, i.e. installation in rooms with access for
A
authorized personnel, closed electrical service location

FLR Access from the front (F), from the sides (L = lateral) and from the rear (R)

I Test current = rated short-circuit breaking current (in kA)

t Internal arc duration (in seconds)

5
Air- and gas-insulated switchgear
from Siemens in accordance with
IEC 62271-200
We are ready – to make you ready as well

With intensive development work and Ready for the future – with Siemens
comprehensive tests, Siemens has al- With the fulfillment of the new IEC 62271-
ready implemented the performance 200 standard, all our switchgear types
features requested by IEC 62271-200 at represent the latest state of development
an early stage. As one of the first man- in technology, safety and reliability.
ufacturers, we offer the entire product
range of air- and gas-insulated switch- Without exception, Siemens switchgear
gear for medium-voltage applications fulfills the internal arc classification as vital
in primary and secondary distribution proof of the personal safety. Our switch-
systems today – type-tested according gear therefore also meets the require-
to the new IEC 62271-200 standard. ments of CAPIEL – the European associa-
tion of national switchgear manufacturer
A greater margin for your safety associations: “This is now a type test and
Not only that: the more stringent require- not anymore subject of agreement be-
ments of the dielectric type tests have tween manufacturer and user.”
been implemented without exception.
An investment in the switchgear technol-
All switching capacity tests for the various ogy made by Siemens is a profitable invest-
circuit-breakers and earthing switches ment in the future.
were performed in installed condition,
i.e. inside the switchgear panel with the With the successfully verified internal arc
associated arrangement of the conducting classification, IAC A FLR up to 50 kA and
path, contacts, etc. This means for you as one second arc duration, our switchgear
the operator: One hundred percent cer- offers maximum possible personal protec-
tainty that this combination of switchgear tion. Our type-tested series also entirely
and switchgear panel functions reliably. fulfill the specifications of IEC 62271-200
in all aspects. In addition, they guarantee
All switchgear series were also tested for the highest possible degree of operational
the internal arc classification in accordance reliability and therefore an extremely low
with the new standard. The maximum failure rate.
permissible number of test objects (gener-
ally two or three panels) as well as the
changed direction of energy flow of the arc
supply significantly increased the demands
on the switchgear panels. All switchgear
certified in accordance with IEC 62271-
200 satisfies all five criteria required for
the internal arc test without exception.

Siemens medium-voltage switchgear


therefore corresponds to the IAC A FLR
classification for short-circuit currents up
to 50 kA (depending on the system type)
and short-circuit times up to one second.

6
Overview of Siemens switchgear

Distribution Insula- Design Loss of service Partition Internal arc classifi- Switchgear Busbar system Voltage Short-circuit Rated current, Rated current,
level tion continuity class cation* type (kV) current (kA) busbar (A) feeder (A)
1s 3s

Primary Gas- Extendable LSC 2B (panels PM IAC A FLR 31,5 kA, 1s NXPLUS C Single 15,0 31,5 31,5 2500 2500
insulated without HV HRC fuses)
LSC 2A (panels with 24,0 25,0 25,0 2500 2000
HV HRC fuses)

LSC 2B (panels PM IAC A FLR 25 kA, 1 s NXPLUS C Double 24,0 25,0 25,0 2500 1250
without HV HRC fuses)
LSC 2A (panels with
HV HRC fuses)

LSC 2B PM IAC A FLR 31,5 kA, 1 s NXPLUS Single 40,5 31,5 31,5 2500 2500
LSC 2B PM IAC A FLR 31,5 kA, 1 s NXPLUS Double 36,0 31,5 31,5 2500 2500
LSC 2B PM IAC A FL 40 kA, 1 s 8DA10 Single 40,5 40,0 40,0 4000 2500
LSC 2B PM IAC A FL 40 kA, 1 s 8DB10 Double 40,5 40,0 40,0 4000 2500
Air- Extendable LSC 2B PM IAC A FLR 40 kA, 1 s NXAIR Single 12,0 40,0 40,0 3150 3150
insulated
LSC 2B PM IAC A FLR 40 kA, 1 s NXAIR Double 12,0 40,0 40,0 3150 3150
LSC 2B PM IAC A FLR 25 kA, 1 s NXAIR M Single 24,0 25,0 25,0 2500 2500
LSC 2B PM IAC A FLR 25 kA, 1 s NXAIR M Double 24,0 25,0 25,0 2500 2500
LSC 2B PM IAC A FLR 50 kA, 1 s NXAIR P Single 15,0 50,0 50,0 4000 4000
LSC 2B PM IAC A FLR 50 kA, 1 s NXAIR P Double 15,0 50,0 50,0 4000 4000
LSC 2B PM IAC A FLR 31,5 kA, 1 s SIMOPRIME Single 17,5 31,5 31,5 3150 3150
LSC 2A PM IAC A FLR 25 kA, 1 s 8BT1 Single 24,0 25,0 25,0 2000 2000
LSC 2B PM IAC A FL 31,5 kA, 1 s 8BT2 Single 36,0 31,5 31,5 2500 2500
LSC 1 PM IAC A FL 16 kA, 1 s 8BT3 Single 36,0 16,0 16,0 1250 1250
Secondary Gas- Non- LSC 2B (panels PM IAC A FL 21 kA, 1 s 8DJ10 Single 17,5 25,0 20,0 630 630
insulated extendable without HV HRC fuses)
LSC 2A (panels with 24,0 20,0 20,0 630 630
HV HRC fuses)

LSC 2B (panels PM IAC A FL 21 kA, 1 s 8DJ20 Single 17,5 25,0 20,0 630 630
without HV HRC fuses)
LSC 2A (panels with 24,0 20,0 20,0 630 630
HV HRC fuses)

Extendable LSC 2B (panels PM IAC A FLR 21 kA, 1 s 8DH10 Single 17,5 25,0 20,0 1250 630
without HV HRC fuses)
LSC 2A (panels with 24,0 20,0 20,0 1250 630
HV HRC fuses)

Air- Extendable LSC 2B (panels PM IAC A FLR 20 kA, 1 s SIMOSEC Single 17,5 25,0 20,0 1250 1250
insulated without HV HRC fuses)
LSC 2A (panels with 24,0 20,0 20,0 1250 1250
HV HRC fuses)

* Maximum possible IAC classification


Siemens AG For questions on power transmission and Subject to change without prior notice
Power Transmission and Distribution distribution, please contact our Customer Order no. E50001-U229-A282-X-7600
Printed in Germany
Medium Voltage Division Support Center, 24 hours a day.
Dispo 30403
Mozartstr. 31 c Tel.: +49 180 / 524 70 00 GB 06612 101976 08064.
91052 Erlangen Fax: +49 180 / 524 24 71
Germany (Subject to charge: e.g. 12 ct/min)
E-mail: support.energy@siemens.com
www.siemens.com/energy www.siemens.com/energy-support

The information in this document contains general descriptions of the technical features, which may not always be available.
An obligation to provide the respective performance feature shall exist only if expressly agreed in the terms of contract.

Potrebbero piacerti anche