Effects of Generator’s Under-Excited Operation on Power


System Low-Frequency Oscillation
By Qian Xu, Zhifei Chen & Hailong Zhang
Nanjing Normal University
Abstract- In this paper, the wavelet method is applied to identify the time-varying frequency and damping
ratio based on the PMU recorded data during Pingwei generator’s under-excited operation. The relation of
oscillation frequency and damping ratio with the variation of reactive power is then attained. Furtherly, the
damping torque is used to analyze the reason for easily oscillation during generator’s leading phase
operation with an OMIB system. The effects of tie-line’s reactive power on inter-area oscillation damping
have also been studied and results of the 4-machine 2-area system are used to verify the conclusions.

Keywords: the degree of generator’s under-excited operation; low-frequency oscillation; wavelet


transform; frequency; damping ratio.
GJRE-F Classification: FOR Code: 090699

EffectsofGeneratorsUnderExcitedOperationonPowerSystemLowFrequencyOscillation

Strictly as per the compliance and regulations of:

© 2017. Qian Xu, Zhifei Chen & Hailong Zhang. This is a research/review paper, distributed under the terms of the Creative
Commons Attribution-Noncommercial 3.0 Unported License http://creativecommons.org/licenses/by-nc/3.0/), permitting all non
commercial use, distribution, and reproduction in any medium, provided the original work is properly cited.
Effects of Generator’s Under-Excited Operation
on Power System Low-Frequency Oscillation
Qian Xu α, Zhifei Chen σ & Hailong Zhang ρ

Abstract- In this paper, the wavelet method is applied to Analyses The Effects Of Generator’s Under-
identify the time-varying frequency and damping ratio based Excitation Operation On Voltage And Reactive Power;
on the PMU recorded data during Pingwei generator’s under- Reference [7] Analyses The Effects Of Generator’s
excited operation. The relation of oscillation frequency and
Under-Excitation Operation On Power System Transient
damping ratio with the variation of reactive power is then
Stability; Reference [8] Offers A Set Of Effective On-Line

2017
attained. Furtherly, the damping torque is used to analyze the
reason for easily oscillation during generator’s leading phase Monitoring System Of The Leading Phase Of Generator.

Year
operation with an OMIB system. The effects of tie-line’s Reference [9] Analyses Effects Of Different Generator
reactive power on inter-area oscillation damping have also Excitation Modes On Generator’s Under-Excitation
been studied and results of the 4-machine 2-area system are Operator Stability, And Proposes The Improvement On 1
used to verify the conclusions. Phase Lead Stability Of Generators For A Nonlinear
Keywords: the degree of generator’s under-excited Excitation Control System.

Global Journal of Researches in Engineering ( F ) Volume XVII Issue VI Version I


operation; low-frequency oscillation; wavelet transform; Study on effects of generator’s under-excited
frequency; damping ratio. operation on static stability of the electric power system
was calculating the static stability reserve coefficient at
I. Introduction some degree of generator’s under-excited operation

W
ith the continuous expansion of the scale of which couldn’t present the effects of time-varying
power grids and the establishment of UHV reactive power on oscillation frequency and damping
along with long-distance power transmission ratio. The wavelet method is applied in this paper to
network,the problem of higher voltage of power identify the time-varying oscillation frequency and
system in valley period becomes important increasingly. damping ratio based on the PMU recorded data during
Research shows that generator’s under-excited Pingwei generator’s under-excited operation, and the
operation has been applied gradually as a means for relation of oscillation frequency and damping ratio with
adjusting voltage because of its special excellences, the variation of reactive power has been attained;
including simple executive, security, economy, adjust Furthermore, the damping torque is used to analyze the
continuously, etc. effect on low-frequency oscillation damping during
Generator’s under-excited operation belongs to generator’s leading phase operation with an OMIB
the normal low-excitation synchronous operation state. system. The effects of tie-line’s reactive power on inter-
Generator’s capability of absorbing the capacitive area oscillation damping have also been studied.
reactive power, namely the degree of generator’s under-
II. PINGWEI GENERATOR’S LOW-FREQUENCY
excited operation is restricted by many factors such as
stator end fever, the decrease of bus voltage of auxiliary OSCILLATION ACCIDENTS
power system, steady-state stability limit, transient a) Pingwei Generator’s Low-frequency Oscillation
stability limit, etc. Therefore, generator’s capability of the Accidents
leading phase operation should be determined With two 720MVA transformers, Generator1, 2
scientifically during generator’s leading phase operation. of Pingwei generator are upgraded to 500 kV. They are
Only in this way can power system be ensured to connected to the main grid of Shandong province
operate safety under the leading phase mode. through the 500kV transmission line. The connection
Reference [2-4] analyses on leading phase operation between Pingwei generators and the system is shown in
capacity of huge hydro generator and turbo generator; Fig.1.
Reference [5] analyses the influence of generator’s und To Anhui province
Manuscript received “Date here here” Excitation On 500kV major grid
Yuan Village power plant
Stability Of Zhejiang Power System; Reference [6]
Pingwei power plant

Author α σ: Jiangsu Sumec Engineering Technology Co. Ltd. To Anhui province


e-mails: 1196440651@qq.com, zhl_chosenone@163.com 500kV major grid

Author ρ: Nanjing Normal University. e-mail: 61204@njnu.edu.cn


Figure 1: The diagram of Pingwei generators

© 2017 Global Journals Inc. (US)


Effects of Generator’s Under-Excited Operation on Power System Low-Frequency Oscillation

PMU recorded data such as active power, Fig.2 (b-d) shows that during the period when
reactive power; terminal voltage magnitude, the internal generator’s under-excited operation varies into lagging
voltage and power angle of generators are shown in phase operation again after 10s, the internal and
Fig.2. terminal voltage of generators decrease continuously,
while the power angle increases continuously. After that,
Active power
Reactive power
there comes another low-frequency oscillation accident.
Based on the active power oscillation trajectory of
Active power/MW;Reactive power/Mvar

generator during 4-14s in Fig.2 (a), the continuous


wavelet transform method is applied to identify the time-
varying oscillation frequency and damping ratio. The
results are shown in Fig.3.
1.5

1.45
1.4
2017

Time /s
1.35

Frequency/Hz
(a) active power and reactive power of generator 1.3
Year

1.25
11.9
Phase A 1.2
11.8
Phase B 1.15
2 11.7 Phase C
Terminal voltage/kV

1.1
11.6
1.05
11.5
Global Journal of Researches in Engineering ( F ) Volume XVII Issue VI Version I

1
11.4 0 5 10 15 20 25 30 35 40
Time /s
11.3

11.2

11.1
(a) Identified frequency
11
16

10.9 12
0 5 10 15 20 25 30 35 40
Time /s
8

Damping ratio/%
(b) terminal voltage magnitude of generator 4

0
11.9

11.8 -4

11.7 -8
Internal potential/kV

11.6
-12
11.5
-16
11.4
4 5 6 7 8 9 10 11 12 13 14
11.3 Time /s

11.2

11.1
(b) Identified damping ratio
Figure 3: Identified frequency and damping ratio based
11

10.9
0 5 10 15 20
Time /s
25 30 35 40
on wavelet method
(c) internal voltage of generator Because of the ending effect, wavelet method
65 has little influence on identified frequency error and has
much influence on identified damping error. According
60
to the method of area elimination of ending effect in
reference [12], the effective damping ratio area can be
Power angle/。

55
seen in the solid line of Fig.3 (b).
50 From Fig.3, during generator’s under-excited
operation varies into lagging phase operation, with the
45
increase of reactive power, the frequency of the low
40 frequency oscillation increases and the oscillation
0 5 10 15 20 25 30 35 40
Time /s damping increases from a negative to a positive
(d) power angle of generators accordingly. Therefore the system has turn to a system
of small signal stability.
Figure 2: PMU data of oscillation accidents
b) Damping Torque During Oscillation
Fig.2 (a) shows that during Pingwei generator’s To make it simple, the impact of generator’s
leading phase operation, the increasing amplitude under-excited operation on oscillation damping torque is
oscillation accident of generators happens at 6s. With studied on an OMIB system.From Reference [13],
the increase of reactive power of generators, the electromagnetic torques variation ∆Te consists of two
vibration of the system decays to steady-state
operation. parts: ∆Te1 and ∆Te 2 . ∆Te1 is synchronizing torque

© 2017 Global Journals Inc. (US)


Effects of Generator’s Under-Excited Operation on Power System Low-Frequency Oscillation

equals with k1∆δ ; ∆Te 2 includes two parts namely respectively. ∆δ represents the increment of
generators’ power angle. p represents differential
synchronizing torque ∆Ts ∆δ and damping torque
operator, p = jh .
∆TD ( jh∆δ ) . Where, ∆Ts and ∆TD are additional
synchronizing torque and damping torque coefficients

∆Te = ∆Te1 + ∆Te 2 = k1∆δ + ∆Ts ∆δ + ∆TD ( jh∆δ ) (1)

Suppose that the excitation system During the period of generator’s under-excited
kA operation varies into lagging phase operation, the
Ge ( s ) = is in one-order inertia. Where, k A and internal and terminal voltages of generators decrease
1 + TA s
continuously, while power angle increases continuously.
TA are the gain and inertial time constant of the With power angle increasing gradually, k5 decreases by

2017
excitation system respectively. According to reference
degrees. When k5 <0, the damping torque ∆TD < 0 ,
[13], ∆Ts and ∆TD are shown as follows:

Year
then increasing amplitude oscillation accident of
− k 2 k5 k A generators occurs. That’s the reason for easily oscillated
∆Ts = (2)
during generator’s leading phase operation. 3
1 k3 + k6 k A − Td′0TA h 2
III. PINGWEI GENERATOR’S LOW-FREQUENCY

Global Journal of Researches in Engineering ( F ) Volume XVII Issue VI Version I


k2 k5 k A (TA k3 + Td′0 ) OSCILLATION ACCIDENTS THE EFFECTS OF TIE-
∆TD = (3)
(1 k3 + k6 k A − Td′0TAh2 )
2
LINE’S REACTIVE POWER ON INTER-AREA
Where, OSCILLATION DAMPING
Eq′U xd′ − xq Take the 4-machine 2-area system shown in
=k1 cos δ + U 2 cos ( 2δ ) (4) Fig.4 as an example. Its network and generators
xd′ ∑ xd′ ∑ xq ∑ possess the same parameters as those in reference
[14]. In the case of two-axis generator model with power
k2 = U sin δ xd′ ∑ (5) system stabilizer and constant impedance load model,
the total active power load and total reactive power are
k3 = xd′ ∑ xd ∑ (6) 2734MW and 200MVar respectively.
1 5 6 10 11 3

U td 0  xq x′ 
7 8 9
G1 G3

k5 U cos δ − d sin δ  (7)


U t 0  xq ∑ xd′ ∑  G2 G4


L7 L9
C1 C2
2 4

area 1 area2

U tq 0 xe Figure 4: A two-area system


k6 = (8)
U t 0 xd′ ∑
According to the results of power flow, the total
xd′ = xd′ + xe (9) power of tie-line 8-9 is S%
8−9 , where

S%
=8−9 390.3 − j15.9 MVA,namely the active power
xq ∑= xq + xe (10) from bus 8 to bus 9 is 390.3MW and the reactive power
from bus 8 to bus 9 is -15.9Mvar. By the use of the small
Where Eq′ ,δ ,xd′ ,xq ,xd′ ∑ ,xq ∑ ,Td′0 are sub- signal analysis tool (SSAT), inter-area oscillation mode
transient voltage, power angle, direct-axis sub-transient of the system is the oscillation between generating units
reactance, quadrature-axis reactance, direct-axis sub- G1, G2 and generating units G3, G4. The oscillation
transient time constant of generators respectively; frequency of the mode is 0.7032Hz and damping ratio is
U t 0 ,U tq 0 ,U td 0 are terminal voltage of generators, 1.55%.

quadrature-axis and direct-axis component of terminal While active power from bus 8 to bus 9 is a
voltage of generators respectively, the suffix 0 means constant, the reactive load of bus 7 and 9 varies. The
change of inter-area oscillation damping with variation of
initial values; U is terminal voltage of infinite bus; xe is
the tie-line’s reactive power is simulated and studied.
Transformer and total line reactance between
generators and infinite bus.

© 2017 Global Journals Inc. (US)


Effects of Generator’s Under-Excited Operation on Power System Low-Frequency Oscillation

1.75
4. Wei YAN, Jun CHEN, Quanrong SHENG.
1.7

1.65
“Discussion on large non-salient pole generator
phase-advancement operation,” Automation of

Damping ratio/%
1.6

1.55
Electric Power Systems, 2007, 31(2): 94-97.
1.5
5. Yuji CHEN. “The influence of generator under-
1.45
excitation on stability of Zhejiang power system,”
1.4
Zhejiang University, April 2004.
1.35 6. Tao WANG, Dashan ZHOU, Zhi DU, et al. “Effects of
-100 -80 -60 -40 -20
Time /s
0 20 40 60 80
generator in leading power factor operation under
light flow on voltage and reactive power,” Hubei
Figure 5: The change of inter-area oscillation damping Power, 2001, 25(1): 1-3.
with variation of the tie-line’s reactive power 7. Lian YAN, Jiayu HUANG, Xiaochuan LUO.
Fig.5 shows that oscillation damping is higher “Transient stability study of east China power
with the tie-line’s positive reactive power’s increase, and system during light load,” Power System
2017

vice versa. When tie-line’s reactive power is negative, Technology, 1996, 20(10): 5-7.
Year

which is in the reverse direction of active power, will give 8. Jiayan SHI, Yuansu SHI, Xiaomin ZHAO, et al. “The
rise to inter-area oscillation negative damping/poor new method of determining the capability of leading
4 damping. phase of generator and realizing the online
As generating units of area 1 and area 2 are monitoring. Proceedings of the CESS,” 2006,
26(11): 139-143.
Global Journal of Researches in Engineering ( F ) Volume XVII Issue VI Version I

coherent, therefore generating units of area 1 and area 2


can be aggregated into an equivalent, and bus 7 and 9 9. Xuesong ZHOU, Youjie MA, Qiang LU, et al.
can be regarded as near zones of the equivalent. The “Experimental study on phase lead stability of a
original system is equivalent to a 2-machine system. So generator for a nonlinear excitation control system,”
when tie-line’s reactive power is in the reverse direction Journal of Tsinghua University (Sci & Tech) , 1996,
of active power, it can bear a resemblance to 36(9): 9-13.
generator’s under-excited operation. The increase of 10. Zhengfeng WANG, Shengsong LIU. “Analysis of low
negative reactive power is not conducive to the damping frequency oscillation of Anhui 500kV network,”
of the system. Relay, 2002, 30(10): 41-43.
11. Pengfei ZHANG, Yusheng XUE, Qiping ZHANG.
IV. Conclusion “Power system time-varying oscillation analysis with
The wavelet method is applied in this paper to wavelet ridge algorithm. Automation of Electric
identify the time-varying frequency and damping based Power Systems,” 2004, 28(16): 32-35,66. .
on the PMU recorded data during Pingwei generator’s 12. Kijewski T, Kareem A. “Wavelet transforms for
under-excited operation, and the relation of oscillation system identification in civil engineering,”
frequency and damping ratio with the variation of Computer-aided civil and infrastructure engineering.
reactive power has been attained; Furthermore, the 2003, 18: 339-355.
damping torque is used to analyze the reason for easily 13. Daqiang. MA “Power system mechanical-electrical
oscillated during generator’s leading phase operation. transient course,” Hydraulic and Electric Power
When the active power is constant, the effects Press, Beijing, 1988.
of tie-line’s reactive power on inter-area oscillation 14. Powertech Labs Inc. SSAT user manual. April 2004,
damping have also been studied in this paper. When tie- Canada.
line’s reactive power is in the reverse direction of active 15. Yusheng XUE. “Quantitative study of general motion
power, it can give rise to negative damping/poor stability and an example of power system stability,”
damping, which causes inter-area oscillation of power Nanjing: Jiangsu Science and Technology Press,
system. 1999.

References Références Referencias


1. Kekela J, Firestone L. “Under-excited operation of
generators,”. IEEE Trans on PAS. 1964, 83(8): 811-
817.
2. Ming WANG. “Analysis on leading phase operation
capacity of 1000MW hydro-generator,”. Harbin
University of Science and Technology, March 2010.
3. Wanqin XIANG. “The analysis and research for the
character of large turbo-generator in leading phase
operation,” North China Electric Power University,
Dec. 2005.