Effects of Generator’s Under-Excited Operation
on Power System Low-Frequency Oscillation
Qian Xu α, Zhifei Chen σ & Hailong Zhang ρ
Abstract- In this paper, the wavelet method is applied to Analyses The Effects Of Generator’s Under-
identify the time-varying frequency and damping ratio based Excitation Operation On Voltage And Reactive Power;
on the PMU recorded data during Pingwei generator’s under- Reference [7] Analyses The Effects Of Generator’s
excited operation. The relation of oscillation frequency and
Under-Excitation Operation On Power System Transient
damping ratio with the variation of reactive power is then
Stability; Reference [8] Offers A Set Of Effective On-Line
2017
attained. Furtherly, the damping torque is used to analyze the
reason for easily oscillation during generator’s leading phase Monitoring System Of The Leading Phase Of Generator.
Year
operation with an OMIB system. The effects of tie-line’s Reference [9] Analyses Effects Of Different Generator
reactive power on inter-area oscillation damping have also Excitation Modes On Generator’s Under-Excitation
been studied and results of the 4-machine 2-area system are Operator Stability, And Proposes The Improvement On 1
used to verify the conclusions. Phase Lead Stability Of Generators For A Nonlinear
Keywords: the degree of generator’s under-excited Excitation Control System.
W
ith the continuous expansion of the scale of which couldn’t present the effects of time-varying
power grids and the establishment of UHV reactive power on oscillation frequency and damping
along with long-distance power transmission ratio. The wavelet method is applied in this paper to
network,the problem of higher voltage of power identify the time-varying oscillation frequency and
system in valley period becomes important increasingly. damping ratio based on the PMU recorded data during
Research shows that generator’s under-excited Pingwei generator’s under-excited operation, and the
operation has been applied gradually as a means for relation of oscillation frequency and damping ratio with
adjusting voltage because of its special excellences, the variation of reactive power has been attained;
including simple executive, security, economy, adjust Furthermore, the damping torque is used to analyze the
continuously, etc. effect on low-frequency oscillation damping during
Generator’s under-excited operation belongs to generator’s leading phase operation with an OMIB
the normal low-excitation synchronous operation state. system. The effects of tie-line’s reactive power on inter-
Generator’s capability of absorbing the capacitive area oscillation damping have also been studied.
reactive power, namely the degree of generator’s under-
II. PINGWEI GENERATOR’S LOW-FREQUENCY
excited operation is restricted by many factors such as
stator end fever, the decrease of bus voltage of auxiliary OSCILLATION ACCIDENTS
power system, steady-state stability limit, transient a) Pingwei Generator’s Low-frequency Oscillation
stability limit, etc. Therefore, generator’s capability of the Accidents
leading phase operation should be determined With two 720MVA transformers, Generator1, 2
scientifically during generator’s leading phase operation. of Pingwei generator are upgraded to 500 kV. They are
Only in this way can power system be ensured to connected to the main grid of Shandong province
operate safety under the leading phase mode. through the 500kV transmission line. The connection
Reference [2-4] analyses on leading phase operation between Pingwei generators and the system is shown in
capacity of huge hydro generator and turbo generator; Fig.1.
Reference [5] analyses the influence of generator’s und To Anhui province
Manuscript received “Date here here” Excitation On 500kV major grid
Yuan Village power plant
Stability Of Zhejiang Power System; Reference [6]
Pingwei power plant
PMU recorded data such as active power, Fig.2 (b-d) shows that during the period when
reactive power; terminal voltage magnitude, the internal generator’s under-excited operation varies into lagging
voltage and power angle of generators are shown in phase operation again after 10s, the internal and
Fig.2. terminal voltage of generators decrease continuously,
while the power angle increases continuously. After that,
Active power
Reactive power
there comes another low-frequency oscillation accident.
Based on the active power oscillation trajectory of
Active power/MW;Reactive power/Mvar
1.45
1.4
2017
Time /s
1.35
Frequency/Hz
(a) active power and reactive power of generator 1.3
Year
1.25
11.9
Phase A 1.2
11.8
Phase B 1.15
2 11.7 Phase C
Terminal voltage/kV
1.1
11.6
1.05
11.5
Global Journal of Researches in Engineering ( F ) Volume XVII Issue VI Version I
1
11.4 0 5 10 15 20 25 30 35 40
Time /s
11.3
11.2
11.1
(a) Identified frequency
11
16
10.9 12
0 5 10 15 20 25 30 35 40
Time /s
8
Damping ratio/%
(b) terminal voltage magnitude of generator 4
0
11.9
11.8 -4
11.7 -8
Internal potential/kV
11.6
-12
11.5
-16
11.4
4 5 6 7 8 9 10 11 12 13 14
11.3 Time /s
11.2
11.1
(b) Identified damping ratio
Figure 3: Identified frequency and damping ratio based
11
10.9
0 5 10 15 20
Time /s
25 30 35 40
on wavelet method
(c) internal voltage of generator Because of the ending effect, wavelet method
65 has little influence on identified frequency error and has
much influence on identified damping error. According
60
to the method of area elimination of ending effect in
reference [12], the effective damping ratio area can be
Power angle/。
55
seen in the solid line of Fig.3 (b).
50 From Fig.3, during generator’s under-excited
operation varies into lagging phase operation, with the
45
increase of reactive power, the frequency of the low
40 frequency oscillation increases and the oscillation
0 5 10 15 20 25 30 35 40
Time /s damping increases from a negative to a positive
(d) power angle of generators accordingly. Therefore the system has turn to a system
of small signal stability.
Figure 2: PMU data of oscillation accidents
b) Damping Torque During Oscillation
Fig.2 (a) shows that during Pingwei generator’s To make it simple, the impact of generator’s
leading phase operation, the increasing amplitude under-excited operation on oscillation damping torque is
oscillation accident of generators happens at 6s. With studied on an OMIB system.From Reference [13],
the increase of reactive power of generators, the electromagnetic torques variation ∆Te consists of two
vibration of the system decays to steady-state
operation. parts: ∆Te1 and ∆Te 2 . ∆Te1 is synchronizing torque
equals with k1∆δ ; ∆Te 2 includes two parts namely respectively. ∆δ represents the increment of
generators’ power angle. p represents differential
synchronizing torque ∆Ts ∆δ and damping torque
operator, p = jh .
∆TD ( jh∆δ ) . Where, ∆Ts and ∆TD are additional
synchronizing torque and damping torque coefficients
Suppose that the excitation system During the period of generator’s under-excited
kA operation varies into lagging phase operation, the
Ge ( s ) = is in one-order inertia. Where, k A and internal and terminal voltages of generators decrease
1 + TA s
continuously, while power angle increases continuously.
TA are the gain and inertial time constant of the With power angle increasing gradually, k5 decreases by
2017
excitation system respectively. According to reference
degrees. When k5 <0, the damping torque ∆TD < 0 ,
[13], ∆Ts and ∆TD are shown as follows:
Year
then increasing amplitude oscillation accident of
− k 2 k5 k A generators occurs. That’s the reason for easily oscillated
∆Ts = (2)
during generator’s leading phase operation. 3
1 k3 + k6 k A − Td′0TA h 2
III. PINGWEI GENERATOR’S LOW-FREQUENCY
U td 0 xq x′
7 8 9
G1 G3
L7 L9
C1 C2
2 4
area 1 area2
quadrature-axis and direct-axis component of terminal While active power from bus 8 to bus 9 is a
voltage of generators respectively, the suffix 0 means constant, the reactive load of bus 7 and 9 varies. The
change of inter-area oscillation damping with variation of
initial values; U is terminal voltage of infinite bus; xe is
the tie-line’s reactive power is simulated and studied.
Transformer and total line reactance between
generators and infinite bus.
1.75
4. Wei YAN, Jun CHEN, Quanrong SHENG.
1.7
1.65
“Discussion on large non-salient pole generator
phase-advancement operation,” Automation of
Damping ratio/%
1.6
1.55
Electric Power Systems, 2007, 31(2): 94-97.
1.5
5. Yuji CHEN. “The influence of generator under-
1.45
excitation on stability of Zhejiang power system,”
1.4
Zhejiang University, April 2004.
1.35 6. Tao WANG, Dashan ZHOU, Zhi DU, et al. “Effects of
-100 -80 -60 -40 -20
Time /s
0 20 40 60 80
generator in leading power factor operation under
light flow on voltage and reactive power,” Hubei
Figure 5: The change of inter-area oscillation damping Power, 2001, 25(1): 1-3.
with variation of the tie-line’s reactive power 7. Lian YAN, Jiayu HUANG, Xiaochuan LUO.
Fig.5 shows that oscillation damping is higher “Transient stability study of east China power
with the tie-line’s positive reactive power’s increase, and system during light load,” Power System
2017
vice versa. When tie-line’s reactive power is negative, Technology, 1996, 20(10): 5-7.
Year
which is in the reverse direction of active power, will give 8. Jiayan SHI, Yuansu SHI, Xiaomin ZHAO, et al. “The
rise to inter-area oscillation negative damping/poor new method of determining the capability of leading
4 damping. phase of generator and realizing the online
As generating units of area 1 and area 2 are monitoring. Proceedings of the CESS,” 2006,
26(11): 139-143.