Fire Alarm Control Panel

V2.1
Fire Alarm Control Panel
 Multi Languages: standard English language, one more additional language configurable
via definition program or USB disk;
 7 inch Touch screen, Graphic user interface design for easy operation, programing via PC
or panel keypad and touch screen;
 Optional Redundancy CPU
 Support up to 6 loops,242 points per loop;
 Support up to 32 ZCP panel, (maximum 640 individual programmable button and 1280
individual LED indicators, max 8 ZCP panels for wall mount cabinet);
 CAN/Fiber Networking, Panel grouping; TCP/IP Networking;
 Remote diagnosis via Ethernet;
 Support USB dongle for securing project database;
 USB port for system configuration and firmware update;
 provides 5 system outputs (Form C contact), Fire, Trouble, Supervisory/F.P.E. and 2x User
defined;
 AUX 24VDC output with totally load no more than 2.5A;
 One user defined input and one NAC output;
 Onboard Repeater circuit output, able to connect up to 64 repeaters;
GST-IFP4M
Fire Alarm Control Panel  Built in onboard printer and provide USB printer interface port for external printer
 Built in protocol to voice alarm system, communicate via onboard RS232 port;
 Built in Bacnet Protocol (Additional License required)
 Wide range power supply 100-240V 50/60Hz;
 Dimension:780mmX516mmX170mm (Wall Mount Type) 2
Fire Alarm Control Panel

Motherboard supports up to 7 slots Programmable Fascia SW & LED

1 – CPU Board
2 ,3 ,4– Single/Dual Loop Card/Extension Card
5 & 6 – Single Loop Card/Extension Card
7 – NAC Card

* Max. 6 loops supported

3
Fire Alarm Control Panel

I/O terminals
Notification Appliance Circuit
Signaling Line Circuit (Power-limited Circuit, Supervised, Class B)
(Power-limited Circuit, Supervised, NAC1 & NAC2 (NAC2/AUX programmed as NAC)
Class A) The end-of-line resistor is 4.7kΩ (Part No. 30107866).
INPUT
(Power-limited Circuit, Refer to Installation and operation Auxiliary Power (NAC2/AUX programmed as AUX)
Unsupervised, Class E) manual for detailed information on (Power-limited Circuit, Supervised, Class B)
Limit to non-monitor use. wiring of addressable devices. The end-of-line resistor is 1kΩ (Part No. 30108576).
End-of-line resistor
Alarm/Supervisory/Trouble Relay and
two programmable relay RL2/RL3 CAN Network
(Unsupervised) EIA-485 (Power-limited
2.0A @ 30VDC (Resistive, Power-limited) No connection Circuit, Class A)

ALARM SUPVR/RL1 TROUBLE RL2 RL3 -1L1O+ -L2O+ -L3O+ -L4O+ -L5O+ -L6O+ -S1O+ -S2O+ -NAC2/AUX+
-L1I+ -L2I+ -L3I+ -L4I+ -L5I+ -L6I+ -S1I+ -S2I+ -NAC1+
+INPUT-
A B

MB-400 Mother Board

- BR-400
BAT Battery Circuit Breaker
KB-400 Keypad Board INPUT + 24VDC / 38Ah
XS4 XS3

OFF
AC Power

OFF
120VAC / 60Hz
PSU-250 220VAC / 50Hz
Power Supply Unit
Ancillary Printer
(5VDC power is Power-limited Circuit.)

4
Fire Alarm Control Panel

MP-400 MCU Mounting Board


MP-401 CPU Card

Specification :
• Single CPU: MP-400*1+MP-401* 1
• Redundancy CPU: MP-400*1+MP-401*2

• Redundancy CPU features:


1. Process equations within and among loops
2. Process usual operations of network (alarm and
fault messages)
3. Provide audio and visual indication of system
fault. (required by EN54)Lit FIRE indicator under
alarm condition.

5
Fire Alarm Control Panel

LC-401 Single Loop Card


LC-402 Dual Loop Card

Specification :
• 242 points per loop
• Support loop power devices
• Provide up to 300mA loop current
• Isolation between loops
• Easy installation, wiring from motherboard

6
Fire Alarm Control Panel

NC-400 NAC Card

Specification :
• Provide 1 NAC Output
• Provide 1 programmable AUX output(NAC or
24V selectable)
• Maximum current: 2.5A (NAC + AUX)

7
Fire Alarm Control Panel

P-9966A CAN Class A network card

Specification :
• Powered by GST-IFP4 mother board
• Interface port : CAN
• Communication distance: 3km every 2 nodes;
• Class A or Class B wiring
• Network capacity: 250 nodes

8
Fire Alarm Control Panel

P-9983 Fibre-Optical network card

Specification :
• Powered by GST-IFP4 mother board
• Interface port : Single mode Fibre-Optical
• Connector Type: LC Type
• Communication distance 20KM between two
nodes.
• Communication Baud rate:11.5kbps
• Network capacity: 250 nodes

9
Fire Alarm Control Panel

P-9956 Configurable RS communication card


Specification :
• Powered by GST-IFP4M mother board
• Interface: configurable RS232/422/485 by
different jumper settings, communication with
the 3rd party equipment

P-9956-Modbus Modbus Card


• ModBus Communication Card for integrating
GST-IFP4M panel into BMS system in
RS232/422/485

10
Fire Alarm Control Panel

Specification :
 Each board include 40 LEDs (Red/Green bicolor)
to display Red, Green and Yellow( Red & Green
both on) Color
 Board addressing range 1 to 32 via on board
DIP switch
 Each LED has individual address, can be
programmed to indicate input signal status
 Description text label easy insert on site,
protected by transparent plastic cover.
P-9981
Zone Display Panel

11
Fire Alarm Control Panel

Specification :
 Each board include 40 LEDs (Red & Yellow)
 Board addressing range 1 to 32 via on board
DIP switch
 Each LED has individual address, can be
programmed to indicate input signal status
 Description text label easy insert on site,
protected by transparent plastic cover.

P-9981F
Zone Display Panel

12
Fire Alarm Control Panel

Specification :
 Each board include 20 keys (non-latching) and
40 LEDs (Red/Green bicolor) to display Red,
Green and Yellow( Red & Green both on) Color
 Board addressing range 1-32 by on board DIP
switch
 Each key and LED has individual address, can
be programmed to active the output modules ,
disable devices and indicate input signal status
P-9982  Description text label easy insert on site,
Zone Display & Control Panel
protected by transparent plastic cover.

13
Fire Alarm Control Panel

Specification :
 Each board include 20 keys (non-latching) and
40 LEDs (Red Yellow color)
 Board addressing range 1-32 by on board DIP
switch
 Each key and LED has individual address, can
be programmed to active the output modules ,
disable devices and indicate input signal status
 Description text label easy insert on site,
P-9982F protected by transparent plastic cover.
Zone Display & Control Panel

14
Fire Alarm Control Panel

• GST-IFP4M Standard Configuration


Model Description Quantity

CA-400-G Enclosure(gray), w/ additional glass door(DR-400) 1


Front panel assembly, w/ fascia, LCD display & control
assembly, keypad board, indicator board and built in micro 1
printer
PSU-250 Power supplier unit 1
MB-400 Mother Board(7 slots) w/ cage 1
MP-400 MCU Mounting Board 1
MP-401 CPU Card 1
NC-400 NAC Card 1
LC-401 Single loop card 0
LC-402 Dual Loop Card 0
P-9966A CAN Class A network card 0
P-9983 Fibre-optical network card 0
P-9956 Configurable RS communication card 0
P-9956-Modbus Modbus card 0
Bacnet License - TCP/IP 0
P-9981 Zone Display panel 0
P-9981F Zone Display panel 0
P-9982 Zone Display and control panel 0
P-9982F Zone Display and control panel 0
USB dongle 0
GST-BAT65-G External battery Enclosure(Gray) 0

15
Fire Alarm Control Panel

• Stand-alone Architecture

16
Fire Alarm Control Panel

• Loop Length under typical loop devices configuration

Configuration 1 Configuration 2 Configuration 3 Configuration 4


No. of smoke detectors 60 80 100 120
No. of heat detectors 8 10 10 15
No. of MCPs 8 10 10 15
No. of input modules 4 4 4 10
No. of output modules 4 4 4 10
No. of loop isolators 2 3 4 5
Total Devices per loop 84 108 128 170
14AWG/2.0mm2 4000m 3300m 2600m 2000m

15AWG/1.65mm2 3500m 2700m 2200m 1700m

16AWG/1.3mm2 3000m 2300m 1900m 1400m

17AWG/1.0mm2 2000m 1500m 1200m 900m

17
Fire Alarm Control Panel

• On Board Repeater circuit, connect up to 64 points


• RS485 – 1000meters

• GSTGMC-up to 8 users
• RS232- 15 meters

18
www.gst.com.cn
Fire Alarm Control Panel

• Panel Networking •Max. 250 panels, pure IFP4M networking

CAN Network Card CAN Network Card CAN Network Card


(P-9966A) (P-9966A) (P-9966A)

Length between panels 3.0Km (max)

CAN Network Card CAN Network Card CAN Network Card


(P-9966A) (P-9966A) (P-9966A)

19
Field Devices
Detector
 Advance digital communication
 Drift compensation, reject false alarm from environment
changing, dust accumulation and component aging.
 Electrically addressed by handheld programmer
 Built-in remote indicator output
 Special LED blink under dirty
 2 levels smoke sensitivities Level 1: 1.23%~2.7% per ft
Level 2: 2.0%~3.89% per ft
 Typical Fixed Alarm Temperature:135℉(57.2℃)
 Magnetic test
 LED blink could be optionally disabled
DI-M9101  Detector store most recent 5 fire alarms and fault alarms, as
Intelligent Combination Heat
Photoelectric Smoke Detector well as total number of alarms.
 IP Rate: IP2X

DB-M01 DC-M9504 C-9314P


Standard Base Isolation Base Remote Indicator
21
Detector

 Advance digital communication


 Drift compensation, reject false alarm from environment
changing, dust accumulation and component aging.
 Electrically addressed by handheld programmer
 Built-in remote indicator output
 Special LED blink under dirty
 Sensitivity Level :1.23%~3.20% per ft
 LED blinking could be optionally disabled
 Magnetic test
DI-M9102  Detector store most recent 5 fire alarms, and fault alarms,
Intelligent Photoelectric
as well as total number of alarms.
Smoke Detector
 IP Rate: IP2X

DB-M01 DC-M9504 C-9314P


Standard Base Isolation Base Remote Indicator
22
Detector

 Advance digital communication


 Rate of rise and fixed temperature, or fixed temperature
programmable
 Action Temperature:135℉(57.2℃)
Response rate of rise:15℉/min (8.3℃/min)
 Electrically addressed by handheld programmer
 Built-in remote indicator output
 LED blink could be optionally disabled
 Magnetic test

DI-M9103  Detector store most recent 5 fire alarms, and fault alarms,
Intelligent Rate of Rise and as well as total number of alarms.
Fixed Temperature Heat
Detector  IP Rate: IP2X

DB-M01 DC-M9504 C-9314P


Standard Base Isolation Base Remote Indicator
23
Manual Call Point

 Semi-flush or Surface mounted


 Standard UL38
 Re-settable (non-breaking glass)
 LED indicator
Type F
3SZM
 Electronically addressed by handheld programmer
 Friendly installation and test
24465
 Optional back box for surface mount
 Ingress Protection Rating: IP 43
 Optional flipping plastic cover (D-92FC)

DI-M9204  Optional weatherproof box(D-92WPB)


Digital Manual Call Point

D-92FC D-92WPB
24
Module

 Din-Rail Mounted or Surface mounted


 Loop Powered
 Low Power consumption
Standby loop current: ≤0.26mA
Active loop current: ≤0.5mA
 Electronically addressed by handheld programmer
 LED status indication for fault or activation
 Programmable N/O or N/C dry contact input
 Cable monitored
Fire Alarm
Equipment
47AU

 Standards:UL864
DI-M9300
Digital Single Input Module
 IP Rate: IP30
 Dimension:78x45.3x28.4mm

25
Module

 Din-Rail Mounted or Surface mounted


 Loop Powered
 Low Power consumption
Standby loop current: ≤0.26mA
Active loop current: ≤0.7mA
 Electronically addressed by handheld programmer
 LED status indication for fault or activation
 N/O or N/C dry contact output (30VDC@2A)
Fire Alarm
Equipment
47AU  Programmable taken 1 address (monitor and control
one equipment) or 2 individual address (monitor and
DI-M9301
control different equipment)
Digital Single Input / Output
Module  IP Rate: IP30
 Dimension: 85.3x78x30.6 mm

26
Module

 Din-Rail Mounted or Surface mounted


 Low Power consumption
Standby loop current: ≤0.15mA
Active loop current: ≤1.5mA
 Isolates faulty part of the loop in case short
circuit
 Auto resume when trouble removed

Fire Alarm
 LED status indicator
Equipment
47AU

 Not occupy loop address


 Maximum 128 pcs per loop
DC-M9503
Loop Isolator  IP Rate: IP30
 Dimension:78x45.3x28.4mm

27
Module

 Din-Rail Mounted or Surface mounted


 Low Power consumption,
Standby loop current: ≤0.26mA
Active loop current: ≤0.5mA
 Maximum Output Load:2A @ 30VDC,0.35PF
 Electronically addressed by handheld programmer
 LED status indication for fault or activation
 Provide 24V output with cable monitoring ( external
Fire Alarm
Equipment
47AU
24V input needed)
 Relay capacity: 30VDC 2A / 125VAC 0.5A
DI-M9305
Digital Single Riser  IP Rate: IP30
Output Module  Dimension: 85.3x78x30.6 mm

28
Module

 Din-Rail Mounted or Surface mounted


 Low Power consumption
Standby loop current: ≤0.23mA
Active loop current: ≤0.25mA
Standby external 24V input current: ≤10mA
Active external 24V input current : ≤60mA
 Interface with conventional fire devices

Fire Alarm
 24VDC required
Equipment
47AU

 Cable monitored
DI-M9319  Electronically addressed by handheld programmer
Digital Zone Monitor Module
 LED status indication for fault or alarm condition
 Provide on board NO/NC dry contact relay output , auto to
triggered by input circuit alarm signal
 IP Rate: IP30
 Dimension: 85.3x78x30.6 mm
29
Sounder & Sounder Strobe

 Build in field-configurable switch for selecting


the desired candela (15,30,75 and 110cd)
output.
 High sounder level output 97.3-101.4dB @24V
in 10 feet/3.05m
 Enhanced synchronization circuit to comply
with the latest requirements of UL 1971
Signaling Devices for the Hearing Impaired.
 Synchronized operation requires a separately
DC-M9413W
installed synchronization control module or
Wall Mount Sounder Strobe (White)
compatible panel NAC circuit.
DC-M9413R
Wall Mount Sounder Strobe (Red)  Default settings 1 flash per second (fps)
 Wire size 12 to 18 AWG (0.75 to 2.50mm)

30
Sounder & Sounder Strobe

 Operating Voltage: Regulated 16 to 33 VDC, 16 to 33


VFWR
 Alarm Current: 40mA at 24VDC
 Built in field configuration jumper option to select
temporal or steady , High or low dB sounder output
 Sounder Level output @24VDC in 10 feet/3.05m
Temporal Mode :Low 79.4 High 84.4dB
Continuous Mode :Low 83.5 High 88.6dB

DC-M9414W
Wall Mount Sounder (White)

DC-M9414R
Wall Mount Sounder (Red)

31
Sounder & Sounder Strobe

 Build in field-configurable switch for selecting


the desired candela (15,30,75 and 110cd)
output.
 Enhanced synchronization circuit to comply
with the latest requirements of UL 1971
Signaling Devices for the Hearing Impaired.
 Synchronized operation requires a separately
installed synchronization control module or
compatible panel NAC circuit.
DC-M9415W
 Default settings 1 flash per second (fps)
Wall Mount Strobe (White)
 Wire size 12 to 18 AWG (0.75 to 2.50mm)
DC-M9415R
Wall Mount Strobe (Red)

32
Sounder & Sounder Strobe

 Build in field-configurable switch for selecting


the desired candela (15,30,75 and 90cd)
output.
 High sounder level output 88.8-93.6dB @24V
in 10 feet/3.05m
 Enhanced synchronization circuit to comply
with the latest requirements of UL 1971
Signaling Devices for the Hearing Impaired.
 Synchronized operation requires a separately
installed synchronization control module or
DC-M9416W
Ceiling Mount Sounder Strobe (White) compatible panel NAC circuit.
 Default settings 1 flash per second (fps)
DC-M9416R
Ceiling Mount Sounder Strobe (Red)  Wire size 12 to 18 AWG (0.75 to 2.50mm)

33
Sounder & Sounder Strobe

 Provides precision synchronization signal to


control GST UL listed strobes and horns.
 Only one module is required for each
notification appliance circuit.
 Operating voltage :16 to 33 VDC; 16-33 VFWR
 Output rating :3 A max. Actual value limited by
system NAC and power outputs
 Resistance between two Flash appliances: 20
Ω max.
DC-M9410  Wire size :12 to 18 AWG (0.75 to 2.50 mm²)
Signal Synchronization Module

34
Conventional Devices

 Drift compensation, reject false alarm from environment changing,


dust accumulation and component aging.
 Built-in remote indicator output
 Special LED blink to indicate detector dirty condition
 2 levels smoke sensitivities programmable, complies with UL268.
Heat part complies with UL521.
 Sensitivity Range: Level 1: 1.23%~2.7% per ft
Level 2: 2.0%~3.89% per ft
 Typical Alarm Temperature: 135℉(57.2℃)
 LED blink could be optionally disabled
DC-M9101  Magnetic test
Conventional Combination
Heat Photoelectric Smoke  IP Rate: IP2X
Detector

DB-M01 C-9314P
Standard Base Remote Indicator 35
Conventional Devices

 Drift compensation, reject false alarm from environment


changing, dust accumulation and component aging.
 Built-in remote indicator output
 Special LED blinking to indicate detector dirty condition
 Sensitivity Range 1.23%~3.20% per ft
 LED blink could be optionally disabled
 Magnetic test
 Complying with UL268.
 IP Rate: IP2X
DC-M9102
Conventional Photoelectric
Smoke Detector

DB-M01 C-9314P
Standard Base Remote Indicator 36
Conventional Devices

 Built-in remote indicator output


 LED blink could be optionally disabled
 Magnetic test
 Sensitivity: Action Temperature :135℉(57.2℃)
Response rate of rise:15℉/min (8.3℃/min)
 Complying with UL 521.
 IP Rate: IP2X

DC-M9103
Conventional Rate of Rise
and Fixed Temperature Heat
Detector

DB-M01 C-9314P
Standard Base Remote Indicator 37
Conventional Devices

 Semi-flush or Surface mounted


 Re-settable (non-breaking glass)
 LED indicator
 Friendly installation and test
 Optional back box for surface mount
 Comply with Standard: UL38.
 IP Rate: IP43

DC-M9204
Digital manual Call Point

38
Voice Alarm System
GST Voice Alarm System

 True Multiplex multi Channel Audio integrated Fire Phone


 Integrated 2 Channel Digital Message repeater
 Live Microphone Page to any zone
 Fast RS-485 Communication Protocol
 Built in Standard Alarm and Alert Signals, up to 4 Minute Message
Capacity, Optional customized voice message
 Multi options of DP configurations. 25W, 50W or 100W amplifier and
GST-MP
Single or Dual channels
Master Panel
 System capacity: up to 256 Distributed Panels, maximum 8 Class A or 4
Class B speaker and 8 fire phone circuits per DP
UL Listed  Communication distance: 4000ft(1.2km),#16AWG,(1.3 mm2),Between
#S9079
panels and 50000ft (15km) in the overall system.
 Communicate with GST fire alarm panel via RS232 port

GST-DP
Distributor Panel

40
GST Voice Alarm System

• FA & VA System Wiring Diagram

GST-DP

RS232

GST-IFP4M GST-MP

GST-DP
41
Q&A