Sei sulla pagina 1di 21

Fire resistance

Owen Brooker
BEng CEng MICE MIStructE MCS
Technical Director

© 2019 Modulus Structural Engineering Ltd 1

Indicative Design Process


Step Task Standard
1 Determine design life EN 1990
2 Assess actions EN 1991 (Parts 1 to 10)
3 Assess load arrangements EN 1992-1-1
4 Assess combinations of actions EN 1990
5 Assess durability EN 1992-1-1(BS 8500?)
6 Assess fire resistance EN 1992-1-2
7 Determine cover EN 1992-1-1
8 Analyse structure EN 1992-1-1
9 ULS checks EN 1992-1-1
10 SLS checks EN 1992-1-1
11 Detailing EN 1992-1-1

© 2019 Modulus Structural Engineering Ltd 2
Simplified methods

Eurocode 2 has three design approaches for fire resistance:


• Tabular - covers the vast majority of cases
• Advanced – best left to fire engineering specialists
• Simplified – to be used if possible when tables are out of
scope or when a small enhancement is required.
The following flow chart gives will guide the decision making
process.

© 2019 Modulus Structural Engineering Ltd 3

Decision making process

© 2019 Modulus Structural Engineering Ltd 4
Actions in a fire scenario

© 2019 Modulus Structural Engineering Ltd 5

Using EN 1991-1-2

Use the accidental combination, Exp (6.11):


Gk,j + Ad + 2,1 Qk,1 + 2,i Qk,I

2,1 is the Recommended Value

© 2019 Modulus Structural Engineering Ltd 6
“Simplified” method for
determine actions during fire
Ed,fi = ηfi Ed
where:
Ed = design value of actions at normal temperature
η fi = reduction factor for actions in fire situation
= 0.7 conservatively
Where combination 6.10 has been used for normal
temperature design:
G k   fi Q k ,1
fi 
 G G k   Q Q k ,1
ψfi = ψ2,1 is the Recommended Value

© 2019 Modulus Structural Engineering Ltd 7

Tabular method

© 2019 Modulus Structural Engineering Ltd 8
Fire resistance

Tables are provided in section 5.

Axis distance, a, to centre of bar

a = c + m/2 + l

a Axis
Distance

© 2019 Modulus Structural Engineering Ltd 9

Fire resistance - tables

• Suitable for standard fire exposure up to 4 hrs.


• Empirical - but confirmed by experience and
theoretical evaluation of tests
• Based on NWC with siliceous aggregates
• For calcareous or lightweight aggregates
minimum dimension may be reduced by 10%
• Deemed to cover shear, torsion or anchorage
• No further checks are required for spalling up to
an axis distance of 70 mm
• For HSC (> C50/60) the minimum cross section
dimension should be increased

© 2019 Modulus Structural Engineering Ltd 10
Columns – Method A

© 2019 Modulus Structural Engineering Ltd 11

Method A - conditions

The restrictions on the use of Method A are:


• The effective length of the braced column in the fire
condition, l0,fi should be ≤ 3 m
• The first order eccentricity under fire conditions should
satisfy the limit:
e = M0Ed,fi / NEd,fi ≤ emax
where
M0Ed,fi = first order design moment
NEd,fi = axial force under fire conditions
emax = 0.15h (or 0.15b for circular sections)
• Reinforcement outside of laps should satisfy: As ≤ 0.04Ac

© 2019 Modulus Structural Engineering Ltd 12
Columns – Method B

© 2019 Modulus Structural Engineering Ltd 13

Method B - conditions

The restrictions on the use of Method B are:


• The slenderness of the column under fire conditions should
be λfi = l0,fi / i ≤ 30 where i is the minimum radius of inertia.
• The first order eccentricity under fire conditions should
satisfy the limit:
e = M0Ed,fi / N0Ed,fi ≤ emax
where
emax = 100 mm
e/b ≤ 0.25
b = minimum column dimension
The load level at normal temperature conditions,
n = N0Ed,fi / [0.7(Ac fcd + As fyd)].

© 2019 Modulus Structural Engineering Ltd 14
Walls

© 2019 Modulus Structural Engineering Ltd 15

Beams

© 2019 Modulus Structural Engineering Ltd 16
Slabs
Solid Ribbed

Notes omitted
© 2019 Modulus Structural Engineering Ltd 17

Simplified methods

© 2019 Modulus Structural Engineering Ltd 18
Annex B.3 – Braced columns

• The method described in Annex B.3 is the basis for Table


5.2b (Method B)
• Table 5.2b has a limit on slenderness and load eccentricity
(Method A. Table 5.2a has an even lower limit)
• The method is complex and therefore tables have been
provided in Annex C

© 2019 Modulus Structural Engineering Ltd 19

Extract of Annex C table

© 2019 Modulus Structural Engineering Ltd 20
Unbraced columns?

PD 6687-1 notes:
• at the discretion of the designer, the methods given in BS
EN 1992-1–2:2004 for columns may be used for the initial
design of unbraced structures.
• In critical cases the chosen column sizes should be verified
using Annex B.
• Historically BS 8110 (Parts 1 and 2), did not make any
distinction between braced and unbraced construction in
fire design
• The column sizes in BS EN 1992-1-2:2004 generally exceed
those that were used in BS 8110 (Parts 1 and 2)
• However, more care should be adopted where the column is
the primary means of structural stability

© 2019 Modulus Structural Engineering Ltd 21

Simplified methods for slabs and


beams
• Annex E contains a simplified design method
• It is an extension of the tabular method
• No reduction in section size is permitted
• Axis distances may be reduced
• The verification is MEd,fi ≤ MRd,fi
Where
MEd,fi = Moment under fire conditions
MRd,fi = Moment of resistance under fire conditions

© 2019 Modulus Structural Engineering Ltd 22
Design resistance – simply supp.

The design resistance under fire loading is determined :


MRd,fi = (γs / γs,fi ) ks(θ) MEd (As,prov /As,req )
where
γs = partial material factor for steel at ambient
γs,fi = partial material factor for steel under fire conditions
ks(θ) = strength reduction applied to steel for a given
temperature (θ) under the required fire resistance
(Use temperature profiles in Annex A)
MEd = design moment for ambient design
As,prov = cross-sectional area of tension reinforcement
provided
As,req = cross-sectional area of tension reinforcement
required
• The ratio As,prov/As,req should not be taken greater than 1.3
• As simplification, ks(θ) may be determined from figure on
next slide
© 2019 Modulus Structural Engineering Ltd 23

© 2019 Modulus Structural Engineering Ltd 24
Design resistance - continuous

• Moment can be redistributed from span to supports


provided:
• there is sufficient reinforcement over the support
• this reinforcement is suitably curtailed to accommodate
the bending moment envelope.
• The mid-span moment resistance = MRd,fi (from above)
• The ‘free’ bending moment for the fire situation is then
determined and ‘fitted’ to the moment of resistance of the
span:
• MRd,fi,Support = (γs / γs,fi ) MEd (As,prov /As,req ) (d – a)/d
Where
d = effective depth of the section
a = required average bottom axis distance for tabular
method
• As,prov /As,req should not be taken greater than 1.3
© 2019 Modulus Structural Engineering Ltd 25

500 °c Isotherm method

• Concrete at a temperature above 500°C is neglected.


• Concrete at or below 500°C is assumed to retain its full,
ambient temperature strength
• The section must meet the minimum cross-sectional width
Fire resistance R60 R90 R120 R180 R240
Minimum width of cross‐section (mm) 90 120 160 200 280
• A reduced section size (bfi dfi) is used where the concrete
retains its original properties
• Temperature profiles for a number of typical member types
and cross-sections are given in Annex A
• The rounded corners of the residual section reflect the real
profile of the isotherm and may be approximated to a
rectangle

© 2019 Modulus Structural Engineering Ltd 26
Example temperature profile

© 2019 Modulus Structural Engineering Ltd 27

Reduced cross-section

© 2019 Modulus Structural Engineering Ltd 28
500 °C Isotherm method

• The temperature of each reinforcing bar is found using


temperature profiles
• The reduced strength of the reinforcement due to
temperature may be determined in accordance with Figure
4.2
• The reinforcement may fall outside of the residual cross-
section. In such cases, these bars may still be counted when
determining the section capacity.

© 2019 Modulus Structural Engineering Ltd 29

Decrease in strength of
reinforcement

© 2019 Modulus Structural Engineering Ltd 30
Bending resistance

bfi = width of reduced cross-section


dfi = effective depth of the reduced cross-section
z = lever arm between the tension reinforcement and
concrete
z’ = lever arm between the tension and compression rebar
As = area of tension reinforcement
As1 = part of tension reinforcement in equilibrium with the
concrete compression block
As2 = part of tension reinforcement in equilibrium with the
compression reinforcement

© 2019 Modulus Structural Engineering Ltd 31

As’ = area of compression reinforcement


fcd,fi(20) = design value of compression strength concrete in
the fire situation at normal temperature
= fck/γc,fi = fck
fsd,fi(θm) = design value of the tension reinforcement strength
in the fire situation at mean temperature θm in that
layer
fscd,fi(θm) = design value of the compression reinforcement
strength in the fire situation at mean temperature
θm in that layer
Fs = total force in compression reinforcement in the
fire situation

© 2019 Modulus Structural Engineering Ltd 32
Bending resistance calculation

The bending moment calculation is illustrated as follows:


Mu = Mu1 + Mu2
Mu1= As1 fsd,fi(θm)z
Mu2=As2 fscd,fi(θm)z’
Where
As = total tension reinforcement area
fsd,fi = design tensile strength of reinforcement
fscd,fi = design strength for compressive reinforcement
bfi = width of the fire exposed cross-section
dfi = efficient height of the fire exposed cross-section

© 2019 Modulus Structural Engineering Ltd 33

500 °c Isotherm method

© 2019 Modulus Structural Engineering Ltd 34
Zone method

• More accurate than 500 °c Isotherm method


• More laborious than 500 °c Isotherm method
• Determine fire damaged zone, az
• Divide the section into a number of parallel zones
• Determine the temperature profile
• Calculate the resistance of each zone
• Sum the resistances to give overall resistance

© 2019 Modulus Structural Engineering Ltd 35

Reduced section

© 2019 Modulus Structural Engineering Ltd 36
Width, w, to use

w, is assessed as:
• The thickness of a slab,
• The thickness of a one sided exposed wall or column,
• Half the thickness of the web of a beam,
• Half the thickness of a two sided exposed wall or column or
• Half the smallest dimension of a four sided exposed column.

© 2019 Modulus Structural Engineering Ltd 37

Determining az

© 2019 Modulus Structural Engineering Ltd 38
Division into zones

© 2019 Modulus Structural Engineering Ltd 39

Determine strength reduction


coefficient

© 2019 Modulus Structural Engineering Ltd 40
Shear and torsion

• For the tabular method no checks beyond those carried out


for ambient design are required
• Annex D can be used for other cases
• For typical sections, shear failure due to fire loading is
uncommon
• A reasonable approach is to use a reduced cross-section due
to fire and apply the principles of Part 1-1
• Where shear reinforcement is not provided, resistance must
be reduced to account for temperature effects by a factor of
kct (θ)
• Where links are provided, including for torsion, the strength
of the links are reduced due to the temperature effects and
the section resistance then determined based on the
reduced section
© 2019 Modulus Structural Engineering Ltd 41

Reduction in concrete strength


for concrete with no shear
reinforcement

© 2019 Modulus Structural Engineering Ltd 42

Potrebbero piacerti anche