Zn Fe Cu Al Pb Cl TH PO4 SO4
Recommendation Rekomendasi
BASE ON CALTEX DELO XLC ANTIFREEZE PRODUCT DATA SHEET SPESIFICATION,ALL TESTS ARE ACCEPTABLE. CONTINUE BERDASARKAN DARI PRODUCT DATA SHEET SPESIFIKASI COOLANT CALTEX DELO XLC ANTIFREEZE, SEMUA PENGUJIAN
COOLANT USE WITH CORRECT MIX OF XLC-WATER BASE ON PRODUCT DATA SHEET. DALAM RENTANG YANG DIBOLEHKAN. TERUSKAN PENGGUNAAN COOLANT DENGAN CAMPURAN TEPAT DARI COOLANT
XLC-AIR BERDASARKAN PRODUCT DATA SHEET.
Glycol Nitrite
100 1200
1000
80
800
60
600
40
400
20
200
0 0
11/5/2018 8/21/2019 11/5/2018 8/21/2019
B19H22C032 Page 1 of 2
PT. Trakindo Utama S•O•S Fluids Analysis Laboratory
Scheduled Oil Sampling Report
Jl. Jendral Sudirman No.848, Balikpapan 76114, Indonesia
Tel. +62 542 762810, Call Center 1500 228
Glossaries
ELC = Extended Life Coolant Elements Zn = Zinc PO4 = Phosphate EC = Electrical Conductivity
DEAC = Diesel Engine Antifreeze Coolant Fe = Iron ppm = Parts Per Million MoO4 = Molybdate DL = Dilution Level
SCA = Supplemental Coolant Additives Cu= Copper SO4 = Sulfate TH = Total Hardness CL = Chloride
Notice : This analysis provided is indicative of conditions based upon sample infomation received and the quality of sample supplied. Recommendations are provided as a guide only. Any decision relating to repair of
components is entirely at the descretion of the customer.
Glycol 45 - 55 % 40-50 % MoO4 >300 ppm Cu <3 ppm Iron (No precipitate) <5 ppm
pH 7.5 - 9.5 8.5 - 10.5 PO4 * <4500 ppm Al <3 ppm Iron (With precipitate) <15 ppm
Nitrite 250 - 2000 1000 - 2600 SO4 <600 ppm Cl <80 ppm
Electrical Conductivity < 6000 µS/cm < 6000 µS/cm Zn <15 ppm Total Hardness <170 ppm
* CATERPILLAR DEAC AND ELC CONTAIN NO PHOSPHATES. OTHER BRAND MAY CONTAIN PHOSPHATES.
** THIS CHARTS ARE FOR GENERAL USE ONLY, AND DO NOT INDICATE DEFINITE LIMITS OF WEAR METALS FOR ANY SPECIFIC MAKE OR MODEL.
TABEL INI HANYA DIGUNAKAN UNTUK ANALISIS SECARA UMUM DAN TIDAK MENGINDIKASIKAN SUATU BATASAN UNTUK MODEL DAN MEREK TERTENTU
KINDLY ADVISED YOU TO CONTACT US PRIOR 7 DAYS AFTER REPORT RELEASE SHOULD YOU NEED FURTHER DISCUSSION ABOUT THIS SAMPLE.
DISARANKAN AGAR DISKUSI LEBIH LANJUT MENGENAI SAMPLE INI HARUS DILAKUKAN SEBELUM 7 HARI DARI TANGGAL LAPORAN DI TERBITKAN
Cycle Time
Interpretation Process
Mukhlisin
TU Branch to Forwarded
Manager S∙O∙S Laboratory