Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
SUMMER TRAININGREPORT ON
UTTEER PRADESH POWER TRANSMISSION CORPORATIONLIMITED
132/33KV SUBSTATION, MANAURE
ALLAHABAD
A
Summer training Report Submitted in Partial
Fulfillment of the Requirement For
The Award of Degree of
Bachelor of Technology
In
Electrical & Electronics Engineering
By
Alok Tiwari
UN. R.N. - 1201021011
UNDAR GUIDANCE: -
Mr.-FULCHAND (S.D.O)
Mr. - SHUDHANSU SUCSENA (J.E)
(1)
CERTIFICATE
Alok Tiwari
(2)
ACKNOWLEDGEMENT
NOW I WOULD LIKE TO THINK THE PEOPLE WHO GUIDED ME AND HAVE
BEEN A CONSTANT SOURCE OF INSPIRATION THROUGH THE TRAINER OF MY
TRAINING.
Alok Tiwari
(3)
INDEX :-
• INTRODUCTION …………………………………..(05)
• ISOLATOR ………………………………………….(05)
• INSULATOR ………………………………………...(06)
• TRANSFORMER ……………………………………(06)
• TYPE OF SUBSTATIONS……………………………(18)
• CHARACTRISTICS OF SUBSTATIONS…………….(20)
• DISIGNE OF SUBSTATIONS………………………...(21)
• EARTHING MATERIAL……………………………..(23)
• APPLICATIONS OF PLCC……………………………(26)
(4)
Introduction
India has been divided into five regions for power system planning
and operation. These regions are the Northern region, Western region, Eastern
region and North-eastern region. Provide means of connection and disconnection of
engine with rest of power train without shock and smoothly.
Provide a varied leverage between the engine and the drive wheels
Provide means to transfer power in opposite direction. Present almost 70% of the
population is enjoying the fruits of electricity.
The present day electricity power system is AC i.e. electric power is
generated, transmitted and distributed in the form of alternating current. The electric
power is produced at the power station, whicare located at favorable place,
generally quite away from the consumers.
ISOLATOR:-
Mainly the isolator is connected after the circuit breaker .The circuit
breaker is trip due to the fault, or when suddenly a heavy current is flows, it means
that the current will not flow after the breaker, but small amount of current is flows
inner circuit.
For making this current total zero the isolator is open and isolator is connected to
ground so all inner current will grounded. This is the main work of isolator and
other equipments are saved.
(5)
INSULATOR:-
The insulator serves two purposes. They support the conductor (bus
bar) and confine the current to the conductor. The most commonly used material for
the manufacturer of insulator is porcelain
But the most wild use of insulator is to insulate the support or tower
from the electric current .These are several type of insulators (e.g. pin type,
suspension type , post insulator ,shackle insulator etc.) and their use in the substation
will depend upon the service requirement .For example post insulator is used for bus
bars can directly bolted to the cap.
TRANSFORMER
A transformer is an electrical device that transfers energy between two
or more circuits through electromagnetic induction.
Types of Transformers:-
1. Step Up Transformer
2. Step Down Transformer
3. Power Transformer
4. Distribution Transformer
Ideal Transformer:-
Its primary and secondary winding resistances are negligible.
Its leakage flux and leakage inductance are zero. There are no losses due
to resistance, hysteresis and eddy currents. The efficiency is 100 percent.
In case of ideal transformer Np*Ip = Ns*Is
(6)
PROTECTION OF TRANFORMER:-
CONSERVATOR -
• The conservator has got a capacity between minimum and maximum oil
level equal to 10% of the total oil in transformer.
• The conservator is provided with magnetic oil level gauge on one of the end
covers which has a low oil level alarm. The ideal indicates empty 1/4, 30.c, ¾
and full oil level.
RADIATOR:-
Owing the transport limitation and considering possible transient damages.
Large transformers are provided with detachable radiators with radiator value.
(7)
At the time of dispatch these radiators are detach and sent
separately keeping the valve in position on tank flange. The valve blanking plate is too
removed only when the radiators is ready for mounting on flanges. On removal of blanking
plate a small quantity of oil which may have collected between valves and blanking plate will
seep out.
The radiator section is made of 1mm thick cold rolled carbon steel sheets. The
distance between each section is 50mm. The number of section per radiators and the
number of radiators per transformer will depend upon cooling requirement of that
transformer.
BUCHHOLZ RELAY:-
The device comprises with the cast iron housing containing the
hinged floats, one in upper part and other in lower part . Each float is fitted with
mercury switches, leads of which are connected to terminal box for external
connection
(8)
The transformer is fitted with double float buchholz
relay.
• It is fitted in the feed pipe from conservator to tank and it is provided with
two sets of mercury contacts.
• An arrow in cast on the housing to indicate the direction of conservator.
The operation of buchholz relay should be tested before installing by
injecting air at the lowest cock.
• It is connected to the protection circuit to give an early alarm in case of gas
collection and to disconnection of transformer from supply in case the sever
fault inside the transformer.
(9)
AIR BLAST COOLING-
It is similar to natural cooling with an addition that continuous blast of
filtered cooled air is forced through the core and winding for better cooling. A fan
produces the blast.
Water Co Forced Oil with Circulating oiling
In this type of system heat exchanger is used for cooling the
transformer. This system is used for large rating of power transformer.
EQUIPMENT OF SUB-STATION
WAVE TRAP :-
Wave trap unit is inserted between bus bar and connection of coupling
capacitor to the line. It is parrel tuned circuit comprising L and C. It has low
impedance to 50 Hz and high impedance to carrier frequencies. Thus coupling
capacitor allows carrier frequencies signals to enter the carrier equipment, but
does not allows 50Hz power frequency current to enter the carrier equipment
(10)
LIGHTING ARRESTER:-
CURRENT TRANSFORMER
A current transformer (CT) is used for measurement of alternating
electric currents. Current transformers, together with voltage (or potential)
transformers (VT or PT), are known as instrument transformers. When current in
a circuit is too high to apply directly to measuring instruments, a current
transformer produces a reduced current accurately proportional to the current in the
circuit, which can be conveniently connected to measuring and recording
instruments.
(11)
Current transformers are commonly used in metering and
protective relays in the electrical power industry. They are commonly used in
metering and protective relaying in the electrical power industry. The current
transformer safely isolates measurement and control circuitry from high voltage
typically present on the circuit being measured. The CT acts as constant current
series device with an apparent power burden a fraction of that of high voltage primary
circuit.
Common secondary's are 1 or 5 amperes . For example; a 400:1 CT
would provide an output current of 1 ampere when the primary was passing 400
amperes. Current transformers used in metering equipment for three-phase 400-
ampere electricity supply
The alternating current in the primary produces an alternating
magnetic field in the core, which then induces an alternating current in the
secondary winding circuit. An essential objective of current transformer design is
to ensure the primary and secondary circuits are efficiently coupled, so the
secondary current is linearly proportional to the primary curren
(12)
POTENTIAL TRANSFORMER:-
(13)
CIRCUIT BREAKER
Circuit breaker is mechanical device which is so designed by which
circuit normal current fault position will be on and off .They are used for high
capacity. A circuit breaker can make or break a circuit either manually or
automatically under all condition viz. no load and short circuit condition.
(14)
CONTROL PANNEL :-
This is the main part of the substation. We plant it outside the
switchyard. All the equipment which is installing inside the switchyard is connected
to the control panel by a underground cable. These cables are connected to the
measuring devices like as voltmeter and ammeter of high rating.
(15)
BATTERY ROOM:-
This is the room, which consist DC batteries. There are 55 DC
cell of 2 Volt each. These cells are connected in series, so it will give total of 110V.
This 110V DC Supply is used for operating the control panel, when the AC supply is
off. This 110V DC voltage is also supplied to circuit breakers for operating; this
supply is used when AC is off. We use this supply as a secondary supply. It means
that this DC voltage is used when the AC is interrupted.
(16)
SINGLE LINE DIAGRAM MANAURI;-
(17)
TYPES OF SUBSTATION;-
Transformer substation
Switch substation
3 .Power factor correction substation
Frequency change substation
Converting substation
Industrial substation
substation
Outdoor substation
Underground substation
Pole mounted Indoor substation
TRANSFORMER SUBSTATION;-
Transformer substation-
STEP UP SUBSTATION-
The generation voltage is steeped up to high voltage to affect
economy in transmission of electric power. These are generally located in
the power houses and are of outdoor type.
(19)
PRIMARY GRID SUBSTATION-
Here, electric power is received by primary substation which reduces
the voltage level to 11KV for secondary transmission. The primary grid
substation is generally of outdoor type.
SECONDARY SUBSTATIONS-
At a secondary substation, the voltage is further steeped down to
11KV. The 11KV lines runs along the important road of the city. The
secondary substations are also of outdoor type.
DISTRIBUTION SUBSTATION-
These substations are located near the consumer’s localities and step
down to 400V, 3-phase, 4-wire for supplying to the consumers. The voltage
between any two phases is 400V & between any phase and neutral it is
230V.
CHARACTERISTICS of SUBSTATION
Each circuit is protected by its own circuit breaker and hence plant
outage does not necessarily result in loss of supply.
A fault on the feeder or transformer circuit breaker causes loss of the transformer
and feeder circuit, one of which may be restored after isolating the faulty circuit
breaker.
(20)
A fault on the bus section circuit breaker causes complete
shutdown of the substation. All circuits may be restored after isolating the faulty
circuit breaker. Maintenance of a feeder or transformer circuit breaker involves
loss of the circuit Introduction of bypass isolators between bus bar and circuit
isolator allows circuit breaker maintenance facilities without loss of that circuit.
Touch Voltage:
This is the difference in potential between the surface potential and the
potential at earthedequipment whilst a man is standing and touching the earthed
structure.
(21)
Step Voltage:
Mesh Voltage:
This is the maximum touch voltage that is developed in the mesh of the
earthing grid.
Calculations for earth impedances, touch and step potentials are based on
site measurements of ground resistivity and system fault levels. A grid layout with
particular conductors is then analyzed to determine the effective substation
earthing resistance, from which the earthing voltage is calculated.
In practice, it is normal to take the highest fault level for substation earth
grid calculation purposes. Additionally, it is necessary to ensure a sufficient margin
such that expansion of the system is catered for.
To determine the earth resistivity, probe tests are carried out on the site.
These tests are best performed in dry weather such that conservative resistivity
readings are obtained.
(22)
Earthing Materials
Conductors:
Bare copper conductor is usually used for the substation earthing grid. The
copper bars themselves usually have a cross-sectional area of 95 square
millimeters, and they are laid at a shallow depthof 0.25-0.5m, in 3-7m squares. In
addition to the buried potential earth grid, a separate above ground earthing ring is
usually provided, to which all metallic substation plant is bonded.
Connections:
Connections to the grid and other earthing joints should not be soldered
because the heat generated during fault conditions could cause a soldered joint to
fail. Joints are usually bolted.
Earthing Rods:
The earthing grid must be supplemented by earthing rods to assist in the dissipation
of earth faultcurrents and further reduce the overall substation earthing resistance.
These rods are usually made ofsolid copper, or copper clad steel.
The switchyard fence earthing practices are possible and are used by
different utilities. These are:
(23)
Extend the substation earth grid 0.5m-1.5m beyond the fence perimeter. The fence
is thenbonded to the grid at regular intervals.
Place the fence beyond the perimeter of the switchyard earthing grid
and bond the fence to its own earthing rod system. This earthing rod system is not
coupled to the main substation earthing grid.
The most suitable material for the conductor system is copper or aluminums.
Steel may be used but has limitations of poor conductivity and high susceptibility
to corrosion.
In an effort to make the conductor ideal, three different types have been
utilized, and these include: Flat surfaced Conductors, Stranded Conductors, and
Tubular Conductors.
(24)
POWER LINE CARRIER COMMUNICATION
Introduction:
As we have available very reliable physical paths viz. the power lines, which
interconnected, hence power line carrier communication is found to be most
economical and reliable for electricity boards.
(25)
APPLICATIONS:
1. Telephony
2. Teleprotection
4. Telemetry
5.Teleprinting
PRINCIPLE OF PLCC:
All type of information is modulated on carried wave at frequency 50Hz to
500 KHz. The modulated HF carrier fed into the power line conductor at the
sending end and filtered out again at the respective stations. Long earlier system
double side band amplitude modulation was more common but the present
amplitude modulated system.
Since high voltage power lines are designed to carry large quantities of
energy on the high voltage and the communication system at low voltage, they
cannot be directly connected to high voltage lines. Suitably designed coupling
equipments have therefore to be employed which will permit the injection of high
frequency carrier signal without undue loss and with absolute protection of
communication equipments or operating personal from high voltage hazard.
(26)
The coupling equipment essentially comprises the following:-
Wave trap is connected in series with power line between the point of
connection of coupling capacitor and S/S. Wave trap offers negligible impedance
to HF carrier. Wave trap stands electromechanically and thermally for short circuit
current in the event of fault on the line. On the basis of blocking frequency bank,
the wave trap can be following type:
I. ALL WAVE
II. SINGAL FREQUENCY
III. DOUBLE FREQUENC
IV. BROAD BAND
Coupling capacitor:
The modulated carrier is let into power line through coupling capacitor
specially designed to with stand line voltage under all weather condition. The
upper end of the coupling capacitor is connected directly to the line and the lower
end is connected to the ground through a carrier frequency chock coil or drain coil.
Thus coupling capacitor forms the link between the PLCC equipment and power
line. The coupling capacitor used in UPSEB is 2200pf capacitance.
The coupling capacitor are designed for outdoor use and hence to withstand
normal atmospheric phenomenon such as temperature & humidity changes, rain,
snow, anticipated wind load, nominal wire tension etc. at full rated voltage.
(27)
In some case capacitive voltage transformers (CVT) used as a source of line
voltage for metering and protection as also used coupling capacitor for PLCC.
This is connected across the primary of the coupling filter i.e. one end is
connected to the bottom of the coupling capacitor and other end is earthed. This is
provided to protect the coupling filter against line surges. An air gap is provided,
where voltage of the order of 1.8 to 2KV as observed across due to lighting etc. on
line.
Coupling of Filter:
The coupling filter is inserted between the low voltage terminal of the
coupling capacitor and the carrier frequency connection of the carrier terminal.
Some time an earth switch is also provided with this unit. This unit mainly
performs two functions; firstly it isolates the connection of equipment from the
power line. Secondly it serves to match characteristic impedance of the power line
to that of the H.F. cable to connection equipments.
H.F. Cable:
H.F. cable normally used to connect the coupling filter to another coupling
terminal. The cable is insulated to withstand the test voltage of 4KV. The
impedance of this H.F. cable is so as to match with the output of the PLCC
terminal and secondary impedance of coupling filter.
(28)
TYPES OF COUPLING:
The following three types of coupling are being used in UPSEB depending on the
requirement:
Internal coupling
COUPLING LOSSES:
Composite loss
Tapping loss
cable loss
Additional loss
(29)
OVERVIEW OF TRANSMISSION SYSTEM OF UTTAR PRADESH;-
(30)