Sei sulla pagina 1di 1

GENERAL NOTES

1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE


PROVISION OF THE LATEST APPROVED EDITION OF THE PHILIPPINE
ELECTRICAL CODE, THE LAW AND ORDINANCES OF THE LOCAL CODE
ENFORCING AUTHORITIES AND REQUIREMENTS OF
THE LOCAL POWER AND TELEPHONE COMPANY.
2. SERVICE ENTRANCE TO THE PROJECT SHALL BE 400V,
LOAD SCHEDULE AND DESIGN COMPUTATION
THREE PHASE, 4 WIRE PLUS GROUND WIRE AND 230V
FOR SINGLE PHASE LINE TO NEUTRAL AND 60 HERTZ.
3. TYPE OF WIRING INSTALLATION SHALL BE DONE IN
INTERMEDIATE METAL CONDUIT FOR SERVICE SINGLE LINE DIAGRAM
ENTRANCE AND IMC TO ALL BRANCH CIRCUIT WIRING.
4. UNLESS OTHERWISE SPECIFIED ON THE PLAN MINIMUM SIZE
200AT,3P,ACB
5. ALL ELECTRICAL EQUIPMENT TO BE USED SHALL BE EQUIPPED in NEMA 3R ENCL. TO
WITH PROPER AND ADEQUATE GROUNDING SYSTEM.
EMERGENCY
6. EACH FLUORESCENT LAMP WILL HAVE HIGH POWER
SUPPLY
FACTOR BALLAST AND GE LAMP HOLDERS.
7. CONVENIENCE OUTLETS SHALL BE RATED 15 AMPERES, 200AT,3P,ACB
in NEMA 3R ENCL. TO
220 VOLTS DUPLEX TYPE.
8. SWITCHED FOR LIGHTING WILL BE RATED 15 AMPERES, NORMAL
230 VOLTS AND QUIET MATIC TYPE. M SUPPLY
9. OUTLET FOR SPECIAL PURPOSE WILL HAVE A RATING OF
30/230 AMPERE VOLTS. M
10. ALL SPARE CIRCUITS SHALL HAVE A BOX 10CM IN SIZE AND
MOUNTED IMMEDIATELY ABOVE DROPPED CEILING WITH

11. OUTLET BOXES SHALL BE GAUGE 16mm PRESSED STEEL 200AT,3P MTS
GALVANIZED AS FOLLOWS: ACB TYPE
A. LIGHT OUTLET 5cm DEEP BY 10cM OCTAGONAL BOX
FOR ONE OR TWO RACEWAYS ENTRIES.
B. CONTROL SWITCHES 6cm DEEP UTILITY BOX
FOR ONE OR TWO SWITCHES ON A TRAP. GROUND
C. CONVENIENCE OUTLET 6cm DEEP UTILITY BOX
FOR ONE OR TWO RACEWAY ENTRIES.
PANEL MDP
D. SPECIAL PURPOSE OUTLET 3.5cm DEEP BY
10cm SQUARE BOX WITH ONE.

12. MOUNTING HEADS:

1. LIGHTING CONTROL SWITCHES 1.50m ABOVE FINISH FLOOR LINE PANEL PP

2. CONVENIENCE OUTLET 0.30m ABOVE FINISH FLOOR LINE

3. SPECIAL PURPOSE OUTLE 1.60m ABOVE FLOOR LINE OR AS LOAD SCHEDULE AND DESIGN COMPUTATION
DIRECT BY THE FIELD CONDITIONS.

13. ALL ELECTRICAL MATERIALS TO BE USED SHALL BE


BRAND NEW AND APPROVED TYPE FOR
BOTH LOCATION AND PURPOSES. MALL/BLDG
14. ALL ELECTRICAL WORKS HEREIN SHALL BE UNDER THE PROVISION
DIRECT SUPERVISION OF A DULY LICENSED PROFESSIONAL VERIFY
ELECTRICAL ENGINEER, REGISTERED ENGINEER,
OR A REGISTERED MASTER ELECTRICIAN.
EXACT AT SITE

OTHER NOTES
1. USE MICA TUBE (6 INCHES ) FOR LIGHTING
FIXTURES AND OUTLET
TERMINATION IS REQUIRED.
2. USE OF FLEXIBLE METAL CONDUIT (1 METER MAX)
FOR HARD TO REACH AREAS.
3. PROVIDE (600 X 600MM) MANHOLE NEAR THE
SPLICING BOX.
4. PROVIDE INDIVIDUAL HANGERS AND SUPPORTS
WITH MINIMUM DISTANCE OF 1.5M (DOUBLE -COAT
W/ RUST-PROTECTIVE PAINT)
5. STRICTLY NO G.I. WIRES FOR SUPPORTS.
6. USE GFCI OUTLET FOR WET AREAS GROUND
7. USE INDUSTRIAL TYPE CIRCUIT BREAKERS (SQ.D.
OR G.E.)
8. DOUBLE CHECK THE RATING OF MOTORS/FCU'S
ON THE SITE OR LOAD SCHEDULE.
9. SEE MECHANICAL PLAN FOR THE EXACT LOACTION
OF MOTOR AND ACCU CONDENSER.

RA 9266 " The Architecture Act of 2004 " PROJECT & LOCATION: OWNER: DESIGNED BY: SHEET CONTENT: SHEET NO:

Sec 33: Ownership of Plans, Specification and other Contract Documents.


DRAWN BY: GENERAL NOTES

E-2
Drawings and specifications and other contract documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and documents of the Architect, wether the PROPOSED INTERIOR RENOVATION EBCHIZZ FOOD SERVICE SCHEDULE OF LOADS AND
object for which they are made is executed or not. It shall be unlawful for any person to duplicate or to
make copies of said documents for use in the repitition of and for other projects or buildings, wether CHECKED BY: DESIGN COMPUTATION
executed partly or in whole , without the written consent of architect or author of said documents. EBC (EVERTHING BUT CHEESE) BENIGNO ROCO
REVISION NO:
# 324 GENEVIVE, 3RD FLOOR SM MANILA