WIND LOAD ANALYSIS
Occupancy Category of the building = IV; Base from the table above.
2. DETERMINE BASIC WIND SPEED, V, for the applicable category.
The location of the building is located at Dinagat Islands (Caraga Region). As the
occupancy category of the structure is categorized as IV, and base on the map above (figure 207A.5-1A)
the basic wind speed is;
V = 300km/h
3. DETERMINE WIND LOAD PARAMETERS:
Kd = 0.85
b1. Base on the site location above;
d1 > 790 m
d2 < 180 m
Therefore the structure is categorize to *exposure D*.
Note:
* Surface roughness D: Flat, unobstructed areas and water surfaces. This category
includes smooth mud flats, salt flats and unbroken ice.
Kzt = 1.0
c. Determine the gust effect factor (G);
Frequency determination
- Checking the limitations of approximate Natural Frequency
13.03(3.00+4.75)
= = 13.03 m
(3.00+4.75)
17.3.(00+4.75)
= = 10.75 m
(3.00+4.75)
na = 43.5/h0.9
Use;
G = 0.85
Accordingly, the code requires that a determination be made of the amount of openings
in the envelope to assess enclosure classification (enclosed, partially, enclosed, or opening).
“Openings” are specially defined in the version of the code as “apertures or holes in the building
envelope which allow air to flow through the building envelope and which are designed as “open”
during winds”. (NSCP 2015, Section 207A.10)
If a building by definition complies with both the “open” and “partially enclosed”
definitions, it shall be classified as an “open” building. A building that does not comply with either the
“open” or “partially enclosed” definitions shall be classified as an “enclosed” building. (NSCP 2015,
207A.10.4)
Checking for enclosure classification
For building partially enclosed condition;
1. Ao > 1.01Aoi
Ao = 8.7332 m2
Aoi = 6.7116 m2
Since,
8.7332 m2 < 1.01(6.7116 m2)
GCpi = ±0.18
Table 207A.11-1
Kz = 0.98
Kh = 1.038
For sideward:
hm = 4.75 m
he = 3.00
zm = 3.00 m
by Interpolation :
Kz = 0.98
Kh = 1.038
qz = 3.7559
qh = 3.546
Given that (for sideward);
Kzt = 1.0
Kz = 0.98
Kh = 1.038
Kd = 0.85
V = 300km/h
We get values for sideward;
qz = 3.7559
qh = 3.546
SPECIFICATION
based on NSCP 2015
Occupancy Category IV
Basic Windspeed (V)
300
(km./h)
Windload Parameter
Exposure Category Kd
Wind Directionality
0.85
Factor (Kd)
Topographic Facor
(Kzt)
K1 = 0
K2 = 0
K3 = 0
KZT = 1
Enclosure
Classification
Ao = 8.7332 m2 Enclosed
condition 1 (fail)
condition 2 (check)
Aoi = 6.7116 m2
Ag = 40.97 m2
Agi = 58.52 m2
Internal Pressure For enclosed 0.18
Coefficient GCpi building -0.18
WINDWARD SIDEWARD
Kz 0.98 0.98
Velocity pressure
exposure coefficient Kh 1.038 1.038
Eave height (z ) in m. 3
WINDWARD SIDEWARD
Velocity Pressure qz 3.7559 3.7559
KPa qh 3.546 3.546
h (m.) 4.75 L/B = 1.327875484
B (m.) 13.02833 h/L = 0.274566474
L (m.) 17.3 Ѳ = 20
External Pressure
Coefficient
External Pressure
Coefficient
ALONG FRAME 4
Windward wall Pz (KPa) Leeward wall Pz (KPa)
Z
qz with - with -
(Height) KZ with + GCpi with + GCpi
(KPa) GCpi GCpi
in m.
4.75 1.038 3.54600 1.77300 1.52478 -1.93434 -0.65778
3 1.03 3.72695 1.86348 0.33543 -0.67085 0.67085
0 1.03 3.72695 1.86348 0.33543 -0.67085 0.67085
Pressure
Computation
ALONG FRAME E
Windward wall Pz (KPa) Leeward wall Pz (KPa)
Z
qz with - with -
(Height) KZ with + GCpi with + GCpi
(KPa) GCpi GCpi
in m.
4.75 1.038 3.54600 1.77300 1.52478 -1.93434 -0.65778
3 1.03 3.72695 1.86348 0.33543 -0.67085 0.67085
0 1.03 3.72695 1.86348 0.33543 -0.67085 0.67085
wo L2 502.21 (3.35)2
MX = = = 704.51 N.m
8 8
wo L2 39.14 (3.35)2
MY = = = 54.91 N.m
8 8
SECTION MODULUS:
SX = MX/0.66Fy
SX = 704.51 (10)3/0.66(345) = 3094.03 mm3
Sy = My/0.75Fy
SY = 54.91 (10)3/0.75(345) = 212.21 mm3
TRY C4 x 54:
fbX = MX/SX = 704.51 (10)3/ 31627= 22.28 MPa
fbY = MY/SY = 212.21 (10)3/4588.4 = 46.25 MPa
CHECKING FOR ADEQUACY:
fbx fby
+ ≤1.0
0.66Fy 0.75Fy
WR =√WN 2 +WT 2
R1 = 6.15 kN
R2 = 5.10 kN
w = 3.09 kN/m
w L2 (3.02) (1.01)2
M= =
8 8
M = 0.385 kN.m
MX 0.385(10)6
fb = = = 61.90 MPa Use for adequacy:
SX 2(3110)
fa Cm fb
+ f ≤ 1.0
F 14.33 (10)3 Fa [1- a ] Fb
Fe '
fa = = = 14.83 MPa
A (2)(483) fa
Cm = 1 – 0.40
Fe ′
KL 1(1004.86) 12π2 E
= = 143.55 Fe ' = KL 2
r 7 23 ( )
r
Therefore, use:
F a > 𝐟𝐚 Ok! Safe! 50 x 50 x 5 mm EQUAL LEG
ANGLE BAR (2 pieces)
DESIGN OF KING POST
K = 1.0 12π2 E
Use Fa = KL 2
23 ( )
Length = 2.78 m r
KL 2780
= = 397.14 Fa > fa Ok! Safe!
r 7
2 π2 E 2 π2 (200,000)
Cc = √ =√
Fy 345
Therefore, use:
Cc =106.97
50 x 50 x 5 mm EQUAL LEG
ANGLE BAR (2 pieces)
DESIGN OF BEAM
DATA CONSTANTS: Steel Cover from center of the bar = 60 mm
LIMITED SECTION:
b= 250 mm
h= 350 mm
d= 290 mm
Ceiling Weight
=0.1708 kPa
Partition Weight
=0.15(1.5)(21.6)
PW = 4.86 kN/m
Beam Weight=0.25(0.35)(23.6)
BW = 2.065 kN/m
TOTAL DEAD LOAD = 7.494 kN/m
U = 1.2(DL) + 1.6(LL)
U = 1.2(7.494) + 1.6(2.4975)
U = 12.99 kN/m
2R = 12.99(3.35)
R = 21.76 kN
12.99(3.352 )
MU = 8
MU = 12.22 kN.m
0.85fc' β600
ρmax =0.75( )
fy (600+fy )
ρ = 0.01603
fy
ω=ρ
f'c
414
ω = 0.01603 = 0.31602
21
Rn = 0.65
0.85f'c 2 𝑅𝑛
ρ= [1-√1 − 0.85(f'c ) ]
𝐹𝑦
ρ = 0.0016
1.4 1.4
ρmin = = = 0.00338 - USE THIS
𝐹𝑦 414
Use 10 mm Φ bar
Asfs
S= ; v'= vactual -vallowable
v'b
fc ′ = 21 MPa
fy = 414 MPa
PU = 108.6 kN
Pu = ∅Pn
pg = 0.039
Ast = 0.039(300)2
Using 16 mm Φ bars
4(3510)
N= = 17.46
π(16)2
S = 16 x db = 16(16) = 256 mm
Therefore:
fy – 414 MPa
fc’ – 21 MPa
Clear Cover – 75 mm
DL = 30.92 kN
LL = 26.78 kN
qe = 117.92 kPa
Dimension:
DL+LL 30.92+26.78
L2 = =
qe 117.92
Pu = 1.2DL + 1.6LL
Vu =qu x (450)(450-d)
Vu = 0.05552 (450)(450-d)
1
Vc = 𝜆√f'cbw d
6
1
Vc = (1)√21 (1200)d
6
Vc = 916.52 d
Vu = ∅Vc
d = 13.98 mm
bo = 4(300 + d)
1
Vc = √f'cbo d
3
1
Vc = √21 [4(300 + d)]d
3
Vu = ∅Vc
1
0.05552[12002 – (300 + d)2]=0.85 x √2[4(300 + d)]d
3
d = 44.60 mm
h = 250 mm
d = 250 – 75
deffective = 175 mm
Mu = qu * bw * x2/2
Mu = 98.21(1.2)(0.45)2/2
Mu = 6.75 kN.m.
Mu = ΦRnbd2
Rn = 0.3607
0.85f'c 2Rn
ρ= [1-√1- ]
fy 0.85f' c
0.85(21) 2(0.3607)
ρ= [1-√1- ]
414 0.85(21)
ρ= 0.00088
1.4 1.4
ρmin = = =0.0034 ← use this
fy 414
As = ρbwd
Using 20 mm Φ bar:
4(714)
N= = 2.27 say 3 bars
π(20)2
Ld fyΨe Ψs Ψtλ
=
db 1.1λ√f'c (C+Ktr )
d b
C+Ktr 75+0
= = 4.69>2.5
db 16
C+Ktr
Use = 2.5
db
Ld 414(1.3)(1)(1)(1)
= = 42.71
db 1.1(1)√21(2.5)
Ld = 1200/2 – 150 – 75
THEREFORE: