VEPL/RAMPS/D&RLA

TAN DELTA TEST REPORT FOR


POWER TRANSFORMER
DATE : 11/06/2019

CUSTOMER : M/s. KALPATARU POWER TRANSMISSION LTD Page No: 02


PROJECT : 220/33 KV GIS S/S HVPNL

1 .Equipment details:
Make : IMP POWERS LTD
Volts at No Load HV : 220KV
Volts at No Load LV : 33KV
Year of MFG : 2017/18
Frequency : 50 Hz
Vector Group : YNyn0
Serial No : PT-8079
2. Using Equipment Details
Make : Megger
Range : 0-12Kv
Serial No : 19781015
Calibration Due Date : 23-08-2019
3. Atmospheric temperature: 45˚C

TESTED BY VOLTECH WITNESS BY KPTL WITNESS BY IMP WITNESS BY HVPNL


POWER LTD
NAME BHARATH RAJ.C

DESIGNATION DIAGNOSTIC ENGINEER

SIGNATURE & DATE


VEPL/RAMPS/D&RLA
TAN DELTA TEST REPORT FOR
POWER TRANSFORMER
DATE : 11/06/2019

CUSTOMER : M/s. KALPATARU POWER TRANSMISSION LTD Page No: 02


PROJECT : 220/33 KV GIS S/S HVPNL

Tan delta test for HV BUSHING:

Applied Measured Capacitance Tan Delta Power


Serial No Mode
Voltage (kV) Current(mA) (Pf) (%) (mW)
2 0.257377 409.593 0.203129 0.001046
R PH
UST 5 0.642927 409.51 0.202114 0.006495
(37997010830)
10 1.28833 409.89 0.203462 0.026223
2 0.260185 414.123 0.223279 0.001162
Y PH
UST 5 0.64931 414.03 0.22297 0.007228
(37997010735)
10 1.30047 414.435 0.222284 0.028884
2 0.250243 399.546 0.203714 0.001016
B PH
UST 5 0.625882 399.449 0.203797 0.006361
(37997010857)
10 1.25538 399.808 0.205768 0.025803

COMMENTS:

According to the IEEE standard of C57.12.90-1980, Permissible limit of dissipation factor is


<0.7%

TESTED BY VOLTECH WITNESS BY KPTL WITNESS BY IMP WITNESS BY HVPNL


POWER LTD
NAME BHARATH RAJ.C

DESIGNATION DIAGNOSTIC ENGINEER

SIGNATURE & DATE


VEPL/RAMPS/D&RLA
TAN DELTA TEST REPORT FOR
POWER TRANSFORMER
DATE : 11/06/2019

CUSTOMER : M/s. KALPATARU POWER TRANSMISSION LTD Page No: 02


PROJECT : 220/33 KV GIS S/S HVPNL

Tan delta test for (HV-LV) WINDING

Applied Measured Capacitance Tan Delta Power


Winding Mode
Voltage (kV) Current(mA) (Pf) (%) (mW)
2 3.67173 5840.53 0.263335 0.019337
(HV)-(LV) UST 5 9.12756 5839.51 0.262257 0.119031
10 18.3157 5833.87 0.261452 0.477959
2 2.63297 4204.82 1.59213 0.08346
(HV)-(E) GSTg 5 6.59906 4204 1.5945 0.525076
10 13.1833 4198.9 1.58871 2.09055
2 6.29011 10048.7 0.818828 0.102532
(HV)-(LV+E) GST 5 15.6782 10028.9 0.817023 0.636787
10 31.5143 10035.5 0.81814 2.57439

COMMENTS:

According to the IEEE standard of C57.12.90-1980, Permissible limit of dissipation factor is <0.7%

Correction Factor (K) : 1.75 for 45˚C

REMARKS :

Dissipation Factor value for HV-LV Winding exceeds the limit.

TESTED BY VOLTECH WITNESS BY KPTL WITNESS BY IMP WITNESS BY HVPNL


POWER LTD
NAME BHARATH RAJ.C

DESIGNATION DIAGNOSTIC ENGINEER

SIGNATURE & DATE


VEPL/RAMPS/D&RLA
TAN DELTA TEST REPORT FOR
POWER TRANSFORMER
DATE : 11/06/2019

CUSTOMER : M/s. KALPATARU POWER TRANSMISSION LTD Page No: 02


PROJECT : 220/33 KV GIS S/S HVPNL

Tan delta test for (LV-HV) WINDING:

Applied Measured Capacitance Tan Delta Power


Winding Mode
Voltage (kV) Current(mA) (Pf) (%) (mW)
2 3.65462 5839.7 0.262772 0.019119
(LV)-(HV) UST 5 9.15156 5839.21 0.262676 0.119845
10 18.2939 5831.55 0.253288 0.462473
2 9.04376 14420.8 0.345662 0.062334
(LV)-(E) GSTg 5 22.5596 14393.2 0.339185 0.381451
10 45.1842 14402.7 0.339369 1.52998
2 12.7199 20225.9 0.316316 0.080473
(LV)-(HV+E) GST 5 31.7457 20227.3 0.317079 0.502482
10 63.3454 20241.1 0.315604 1.9905

COMMENTS:

According to the IEEE standard of C57.12.90-1980, Permissible limit of dissipation factor is <0.7%

TESTED BY VOLTECH WITNESS BY KPTL WITNESS BY IMP WITNESS BY HVPNL


POWER LTD
NAME BHARATH RAJ.C

DESIGNATION DIAGNOSTIC ENGINEER

SIGNATURE & DATE