Sei sulla pagina 1di 1

OPERATING INSTRUCTIONS SAFETY SUMMARY connections are correct. 1) Snubber Part No.: APRC - 01.

All safety related codification, symbols and instructions 3.Use lugged terminals to meet M3 screws and ensure that 2) MOV Part No.: AP-MOV - 03.
800XU that appear in this operating instruction manual must be the screws are tightened . Note: Use snubber as shown above to increase the life
strictly observed to ensure operator as well as equipment of internal relay.
safety. The instruction manual is meant for personnel DIP SWITCH SETTINGS FOR SELECTION OF
involved in wiring, installation, operation and routine
TERMINAL CONNECTIONS
DELAY MODES
A1 ( + ) 15 25
maintenance of the equipment. SWITCH SETTINGS
If the equipment related above safety measures are not
A2 ( - ) 16 18 26 28 1 2 SCALE 3 4 TIME RANGE
practiced, the manufacturer does not have any liability for
human or equipment safety. SUPPLY: A1 (+), A2 (-)
1 SEC
A1 25
! CAUTION: Read complete instructions prior to 15 26 AC: 50 / 60Hz
installation and operation of the unit. 3 MIN
SPECIFICATIONS ! CAUTION: Risk of electric shock.
CONTACT 10 HRS
SUPPLY VOLTAGE MAINTENANCE 16 28
5A,250V AC/
24V DC, RESISTIVE
20 to 240 VAC (AC@50 or 60Hz),12 to 240VDC 1. The power supply should be switched off before 18 A2 30 HRS
ON DELAY INTERVAL
INPUT removing the equipment for cleaning. Ensure that no POWER
Control contact. parts are charged. RELAY
t t

OUTPUT CONTACT 2. Clean the equipment with a clean, soft cloth. Do not use t = Set time
2 C/O (DPDT) any organic cleaning agent .
RELAY RATING TERMINAL DESCRIPTION
DIR 5 MODE
5A @ 230 VAC/24 VDC, resistive. INSTALLATION GUIDELINES A1 L ( + ) T I M E R S U P P LY
DELAY MODES CAUTION: A2 N ( - ) T I M E R S U P P LY ON DELAY
On delay / Interval modes 15 COM
TIME RANGES 1. The equipment is built-in type with Class II construction RELAY INTERVAL
16 NC
and is protected by reinforced insulation. Terminals are a CONTACT 1
1 / 3 / 10 / 30 18 NO
Sec. / min / hr part of the front panel and are protected by means of finger 25 COM RELAY
ACCURACY guard. Finger guards are not to be removed during wiring, 26 NC CONTACT 2
Setting: ± 5% of full scale. 28
Repeat: ±0.5% or 50 msec whichever is greater. installation, operation or maintenance. NO

POWER CONSUMPTION 2. Conductors must not come in contact with the internal TYPICAL LOAD CONNECTIONS
2 VA max. circuitry of the equipment as it may lead to a safety hazard.
LED INDICATION 1. For load current less than 0.5A MODES OF OPERATION
3. Circuit breaker or main switch should be installed
Power ON. 230VAC
between power source and supply terminals to facilitate L N Fig1. On Delay:
Relay ON.
RESET : On interruption of power. power ON/OFF function. This installation must be in a Supply
RESET TIME convenient position normally accessible to the operator. A1 25
(L) (COM2) Voltage
Less than 100 msec. CAUTION: 15 26
(COM1) (NC2)
SIZE (IN MM) 1.! The equipment should not be installed in the
22.5 (W) x 75 (H) x 101 (D). Snubber
N/O Contact
HOUSING environmental conditions other than those mentioned in this L
O
NC Contact
Flame retardant engineering plastic. manual. C
A t
MOUNTING 2. Fuse Protection: The equipment does not have a built-in R
D
16 28
1
DIN rail mounting. fuse. A fuse of rating 275 VAC/1Amp is recommended. (NC1) (NO2) t = set time delay
Screw mounting. 18 A2
EMC Installation Guidelines: (NO1) (N) Fig 2. Interval Delay:
TEMPERATURE
o
Operating: 0 C to 50 C.
o 1. Use proper input power cables with shortest connections Supply
o o
Storage: 0 C to 50 C. and twisted type. Voltage
HUMIDITY 2. Layout of connecting cables shall be away from any 2. For bigger loads, use interposing relay/contactor
Up to 95% RH. internal emf source.
WEIGHT 230VAC
Mechanical Installation Guidelines: L N N/O Contact
115 grams. NC Contact
1. The equipment uses a clamp for T type DIN rail only.
t
2. Ensure that the rail clamp is correctly fitted. A1 25
(L) (COM2)

PANEL DIMENSIONS 3. Slide the equipment using appropriate tools and holding 15 26
(COM1) (NC2)
t = set time delay
the unit from the front side, slide it over the fixed rail.
m

11.5mm
m

22.5mm
80

101mm LOAD 1
4.

WIRING GUIDELINES (Specifications subject to change as development is a


A2

CONTACTOR
NO continuous process)
CAUTION: COM
A1 Selec Controls Pvt. Ltd.
R
1.! The power should be turned off while wiring and (Formerly Selectron Process Controls Pvt. Ltd.)
61.0mm

8 9
16 28
10

7 10
6 75 35 75
(NC1) (NO2)
mm mm
5
4
3 0
mm
maintenance to prevent the risk of electric shock. Do not C R Tel:91-22-28476443, Fax:91-22-28471733,
18 A2
0

2 1
ON

touch the terminals when power is ON.


Snubber (NO1) (N) Website: www.selec.com
E- mail: sales@selec.com
2. Wiring shall be done strictly according to the terminal
Document name: Operating/0711/800XU/ Version 1 OP218-V01 Page 1 of 1
85mm Mounting holes layout with shortest connections. Confirm that all the