Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
KARNATAKA
UNDER THE GUIDENCE OF: SATHISKUMAR K, MAHESH KUMAR AND SANTHOSH NAIK
5/21/2014
Voltage specifica on:
1) What is HT?
Answer: HT is high tension its range is 11Kilo volts to 33KV.
Transformer:
4) What is transformer? State its func ons?
Answer: transformer is sta c device it transforms the voltage from primary to secondary
without changing the frequency. It works on the principle of Faraday’s Law of
Electromagne c induc on.
Breather is fi ed to top of the conservator tank through a pipe. Temperature of transformer oil
raise as winding temperature raises at the same me air in the transformer also expands, when
temperature of the winding reduces, Oil temperature also reduces and air in the transformer
depresses, this expansion is called breathing.
When atmospheric air come in to transformer through breather, moisture contents in the air
observed by the silica gel in the breather for maintaining the insula ng property of the
Transformer oil. By observing the moisture contents in the air it slowly loses its blue colour and
turn in to white.
13) What is good condi on colour and bad condi on colour of silica gel?
Answer: silica gel is blue in good condi on and pink colour in bad condi on.
Top float is used for alarm circuit and bo om float used for tripping the breaker in case of
service faults. Or
It is a protec on relay of the transformer. This relay operates on the excessive forma on of the
oil vapors or gas inside the transformer tank due to any internal fault of the transformer. It is
fi ed between the tank and conservator.
When a heavy internal fault like short circuit, earth leakage or failure of insula on occurs in the
system, it rapidly increases the temperature of the oil.
Due to this to abnormal increase of temperature, the oil expands quickly and rushes firstly to the
conservator through the relay. On the way it trip the tripping coil of Bucholz relay, thus the
transformer is saved from possible damage. Bucholz relay: This is a transformer sta c device. It has
two switches or relay such as Alarm switch and Trip switch.
Buchholz relay defined as Iden fica on and significance of gas the nature of the fault could be
judge with the help of gas collected in bucholz relay.
Colour iden fica on of gas:
It is used up to 33KV, the fixed and moving contacts housed in the vacuum contacts to
quench the arc produced when the opening and closing of contacts. VCB is used for low
currents and high voltage side.
22) What is the procedure followed during transformer oil filtra on?
Answer: Check oil level in transformer, Check & remove silica gel and replace if required,
Check HV test before and a er oil filtra on.
26) What are the safety relays and alarms provided for Transformer?
Answer: Over current relay, Earth fault relay, Bucholz alarm, Bucholz trip, Winding temperature
alarm, winding temperature trip, Tripping relay.
27) What are the safety measures in transformer?
Answer: Oil level, Oil temperature, Winding temperature, Winding tap posi on, Silica gel
colour, Bucholz relay, Input & Output voltage & current.
28) What is the acceptable current for human?
Answer: Human acceptable current is 30 milli Amps.
29) What is meter cubical? What is it using?
Answer: Meter cubical is a energy meter it consist of C.T & P.T It is moun ng the load of
KW,KVA,PF,MD,VOLTS, etc and it is used to measure the energy consumed by the consumer.
30) In star connec on: the phase current and line current will be same, but the line voltage is
equal to √3 mes of phase voltage.
31) In delta connec on: the phase voltage and line voltage will be same, but the line current is
equal to √3 mes of phase current.
32) OT = Oil Temperature Acceptable range as = 65°C to 80° C in maximum range Alarm starts at
85°C.
33) WT = winding Temperature Acceptable range as = 65°C to 85°C in maximum range, Alarm
starts at 90°C.
DG set(Diesel Generator) :
46) What type of ba ery to be used for DG Star ng? State its func on?
Answer: Lead acid cell ba ery to be used for DG Star ng, It is used to supply the 24V DC
supply to the self starter.
47) What are the Earthing’s required for commissioning the DG?
Ans- Four Earth pits required for commissioning of DG.
Two earth pits required for the body earth and both are interlinked together.
Another two earth pits required for the neutral and both are interlinked together.
48) If AVR fails in Dg sets what will be the effect?
Ans- If AVR fails in generator the output voltage of the generator will have more
fluctua ons, that means the output voltage is increased and decreased. Which affects the
speed of DG?
2. Engine :
Answer: Radiator, Radiator pump, Exhaust pipe, Turbo charger, Air filter, Crank sha , Piston,
Starter, Governor, Fuel tank, & fuel pump.
3. Alternator :
Answer: Stator, Armature, Rotor, Magne c field.
DG Maintenance:
Types of check
a) A- check =Everyday
b) B- check =Every six months or 250 hours
c) C- check =Every year or 1500 hours
A- Check
a) Oil level
b) Fuel level
c) Water level in radiator
d) Ba ery voltage & terminal voltage more than 26 volts for (range of 24v)
e) Tension of drive belts.
f) Dis lled water level in ba eries.
g) Check all fuel connec ons for leakages and damages.
h) Check all panel meters are working
i) Cleaning of DG Set.
B-Check
Protec ons:
Engine side
a) Low lube oil pressure
b) High water temperature
c) Ba ery voltage
d) Low fuel alarm
e) Thermosta c opera on and trip relay
Alternator side
a) Earth fault relay
b) Earth leakage relay
c) AVR Relay
d) Over current relay
e) Under and Over voltage relay
DG parallel opera on:
Engine Oil = SAE = 15W = 40W
12V Ba ery = 6 No Cell.
1 Cell—2 VOLT Charging voltage =13 or 13.5
Ba ery- Series Connec on
Dis lled water check =Hydrometer
Specifica on =1.2 or 1.24
a) Voltage level
b) Phase Sequence
c) Frequency
Synchroniza on notes
When mains are healthy, then both the D.G. Sets remain in the standby mode.
• When mains fail, Line Voltage Monitor (L.V.M.) senses it. Star ng pulses are given to the Master
D.G. Set. (Master D.G. Set is automa cally selected by program.)
• A er sa sfactory star ng of the D.G. Set 1, voltage is sensed by Generator Voltage Monitor
(G.V.M.). If voltage is healthy, then closing signal is given to D.G.1 breaker and it is closed.
• Giving corresponding pulses from the Synchronizing Panel can then automa cally start load.
• The load is then sensed by KW transducer in the panel & con nuously monitored by
Programmable Logic Controller (P.L.C.)
• Engine & Alternator parameters are also con nuously monitored by P.L.C. in the Panel. In case of
any fault (e.g. Low Lube Oil Pressure, High Cooling Water Temperature etc.), breaker is tripped &
engine is stopped.
• If the load reaches & crosses 80 % of the rated capacity of the D.G. 1, then star ng pulses are
given to the second D.G. set from P.L.C.
• When D.G.2 starts, then again G.V.M. checks the voltage, and if voltage is healthy, then breaker 2
is closed.
• A er closing of the second breaker, Auto load sharing func on starts sharing the load between
the two D.G. Sets. The percentage of sharing is directly propor onal to their individual capaci es.
• Since sharing is propor onal to their respec ve capaci es, even D.G. sets of different capaci es
can be synchronized successfully.
• D.G. sets con nue to run in Synchroniza on un l the load is above 80 % of any one D.G. set.
• When load comes down below 80 % of any one D.G. set, then the automa c signal is given to that
D.G. & then it starts taking the full load.
• A er transferring the total load to one D.G. (on which 80 % load is to be connected), the breaker
of the second D.G.is opened. Now one D.G. is taking the load, which is less than 80 % of its rated
capacity.
• The programmed is repeated automa cally for any varia on of the load.
• When mains are resumed, then load is transferred to the mains & both the D.G. sets are stopped
a er their cooling period.
• For stable opera on even for sudden varia ons in the load, programmed mers in PLC are used,
which take ac on only a er stabiliza on of the load.
• The total Automa c opera on has a manual override. In manual mode, the total opera on can
be performed manually.
• Auto load shedding facility can be incorporated by suitable programming of PLC. With this facility,
various loads can be brought in or switched off at par cular me or for various intervals.
• With the same logic, 3, 4 or 5 sets of equal or different capaci es can be synchronized with Auto
load sharing facility.
• the total program is based on load in KW. Hence the actual sharing, star ng, stopping & transfers
are actual load dependent & not on any other unrealis c parameter like voltage, current. Etc.
• Changing of scheme becomes very easy because of changes are made through so ware only.
There is no changing of wires, adding of components like relays, contactors, which is very me
consuming, cumbersome & requiring addi onal space.
• Along with KW sharing, KVAR sharing & PF sharing is very accurate, because of PLC programming.
There is no possibility of any unequal sharing as regards KW, KVAR & PF.
• For any type of load addi on or reduc on, manual interven on as regards D.G. set opera on is
not required. However, in case of emergency manual override is possible.
• Special programmers using Real Time Clock (RTC) are possible. With this facility, along with KW
dependent programs; day, date & me dependent programmers are possible.
• Because of KW dependent load sharing, op mum u liza on of D.G. sets are possible. This
increases D.G. sets efficiency & saves lot of fuel.
• D. G. sets are always tried to run with 80 % to 90 % load factor, where we get maximum efficiency
of D.G. sets. This is easily possible with our system.
• Because of PLC opera on, hardware like relays, contactors, wiring etc is reduced dras cally. This
reduces fault points & increases the MTBF of the system.
• If any changes are required to be made in future, then there is no need of addi onal hardware
like relays, contactors etc. There is also no need to make new wiring or changes in the wiring. All the
changes / modifica ons can be easily made through so ware only.
Due to unbalanced loading of the phases you will get neutral current. I hope you know this. When
the voltages and currents of supply system are balanced the neutral current will be zero and the
voltage between the neutral to the earth (ground) will be zero too. but in prac ce there will always
be some amount of unbalance in the phases due to this current will be available in neutral and
further to this there will be voltage between the earth to neutral. The neutral to ground voltage can
also occur in case there is any leakage from one of the phases to the neutral connec on line.
Further to the above there could be induced voltages due to harmonics.
With above I think you got idea how to avoid it too. Normally the allowed neutral to earth voltage
maximum in India is 5 Volts.
Power Factor: Cosine angle between current and voltage is called Power Factor.
Advantages:
a) Improved efficiency of the equipment
b) Less Line losses
c) Voltage regula on
d) Reduced KVA demand.
Off online UPS:
AC Transfer Switch
Ba ery
normal mode
Bypass mode
On line UPS:
AC Transfer Switch
Ba ery
Normal mode Off Line UPS
Backup mode
7) What are the main parts of UPS? Explain the func ons of each stage?
Ans-The main parts of UPS are Rec fier, Inverter, Sta c Switch, and Sta c by pass switch,
Main by Pass switch & Ba ery.
Rec fier: This is a unidirec onal device which converts AC to DC and it is used to charge
ba eries.
Inverter: This device is used to convert the DC into AC and it is used as output supply of UPS
through sta c switch.
Sta c Switch: This is used to trip the circuit if any fault is occurred.
Sta c by-pass switch- At normal working condi on the main supply goes through this sta c
by-pass switch.
Main by-pass switch: If any maintenance work is to be done the sta c by pass switch is
turned ON and main supply goes through this main by-pass switch.
Ba ery- Ba ery is used to give the supply to the UPS when the raw power is failed.
1. To reduce the pressure of the liquid from the condenser pressure to evaporator pressure.
2. To keep the evaporator fully ac ve and,
3. To modulate the flow of liquid to the evaporator according to the load requirements of the
evaporator so as to prevent flood back of liquid refrigerant to the evaporator.
4. Power Element with a feeler / sensor Bulb. (The power element is charged with a refrigerant.
For air-condi oning jobs the same refrigerant as the system is used.)
5. Valve seats and needle. And ,
6. Super heat adjustment spring
7.
8. The opera on of valve i.e., the closing and opening of the valve is controlled by three basic
forces / pressure.
9. Pressure in the power element acts to open valve, i.e.,., to move the valve needle away from its
seat
10. The evaporator pressure acts on the bo om side of the diaphragm of the power element
tending to close the valve and,
11. The pressure of the super heat spring also assist in the closing ac on.
12. Therefore, if the power element pressure is greater than the combine pressure of evaporator
pressure plus super heat spring pressure the valve will open.
13.
17. R11 - trichloro fluoro methane CCL3 F ( its uses for flushing purpose )
18. R12 - Dichloro-difluoro-methane CCL2 F2 ( mostly uses for mobile A/c , and for domes c and
commercial refrigerator systems)
19. R22 - Mono chloro difluoro Methane CH CL F2 ( extensively uses at Air-condi oning systems)
20. R717 - Ammonia NH3 ( highly toxic gas )
21. R502 - it’s a 48.8% mixture of R22 and 51.2% of R115 gas ( extensively uses at highly low
temperature control purpose)
22. R115 - chloropentafluoroethane.
23.
1. Operation & Maintenance :
Daily check - leak detec on, loose connec on in electrical installa on, abnormal sound,
vibra on, sensi ve component, voltage and ampere are in proper regulariza on, control on
desired temperature and pressures (i.e., HP / LP / OP), mechanical and electrical controllers,
records maintenance.
Weekly Check - Along with above ac vity, filter cleaning, drain water flow check, V-belt
condi on, and prepara on of weekly report.
Quarterly Maintenance - Along with above , carry-out pressure test, service CW- pumps, check
condi on of expansion tank, fill clean oil or glycerin to the sensor wells, clean magne c
contactors, apply grease to the all hand operated mechanical valve glands / motor bearings,
checking of earth points to the all related equipment and prepara on of quarterly maintenance
report.
Annual Maintenance - A er carrying out all the above men oned ac vi es, clean make up
water tank, flush out chilled water (if contaminated) and refilled the clean water in it, check the
condi on of air-filters and replace for damaged ones, check the VCD / diffuser for both supply
and return air ducts, check the air leaks and fresh air vent posi on.
General Information:
1. Leak detection: a) Soap solu on method, b) Electronic leak detector method, c) Halide torch
method.
2. About refrigerant :
3. It’s colourless
4. It’s almost odourless
5. It’s non toxic
6. It’s non corrosive
7. It’s non flammable
8. It’s non irrita ng
9. It’s safe gas
10. It’s mixes well with oil
11. It has low boiling point
12. It has low freezing point
Epabx / Definite
3. Communica on 18 / 68.5 22 / 72 40% to 52%
Room
Refrigerant cycle:
In compressor: input refrigerant is in Low pressure, low temperature in the form of vapours &
output refrigerant is high pressure, high temperature in the form of gas.
In condenser: input refrigerant is high pressure, high temperature in the form of gas & output
refrigerant is high pressure, high temperature in the form of liquid.
In expansion valve: input refrigerant is high pressure, high temperature in the form of liquid &
output refrigerant is low pressure, low temperature in the form of liquid.
In Evaporator: input refrigerant is low pressure, low temperature in the form of liquid & output
refrigerant is low pressure, low temperature in the form of vapour
Expansion
valve
Condenser Evaporator
Compressor
The basic working of air condi oner is based on the Refrigerant cycle.
GENERAL:
What are the safety seals?
(OR) Safety seals are provided in all electrical equipments to protect from any changes made
by unauthorized person.
What are the documents to be maintained as per ISO standard in an so ware company?
Ans:
1. Standard opera ng procedure for all the equipments/ installa ons.
2. History card for all the equipments/ installa ons.
3. Complete asset list of the facility.
4. 5s( Five S) policy.
5. Escala on matrix.
6. Periodical preven ve maintenance schedule.
7. Incident reports and etc
8. Document related to vendor review mee ng.
What are the applicable ISO policies for a so ware company?
Ans:
1. ISO-9000 for Quality.
2. ISO-1400 1 for Environmental management system.
3. ISO-18000 for Safety.
What are the indoor and outdoor plants used in so ware company?
Ans: Indoor plants: Kind palms, Xanada, Aglinomino, Mus c these plants are kept in air
condi oning otherwise it will feather out.
Out door: Fitus, Spchessaera these plants either kept indoor or outdoor on rota on
basis.
What are the safety controls provided in the Li s/Elevator?
Ans: ARD it is called as Automa c Rescue Device. It is integrated in the li opera on
whenever both DG and EB fails to take the load, ARD will ac vate and brings down the li to
the nearest floor with ba ery backup.
Speaker phone/ Intercom, Emergency light and Cau on board.
What are the ac vi es to be performed in property management?
Ans:
1. Should be aware of distribu on of electrical bill to all the mul tenants of the
building.
What is the different kinds of belts used in the air condi oning?
Ans: A-16, A-31, B-32 etc.
What is the func on of the Actuator?
Ans: It automa cally regulates the chilled water to the set temperature at the thermostat.
Why chilled water inlet is given in the bo om of the AHU unit?
Ans: This is to control the air pockets in the chilled water line. If chilled water line is given at
the top of the AHU, flow of chilled water will increase due to gravita on resul ng in
forma on of air pockets in between the chilled water lines.
What is the difference between the Air condi oning and Refrigera on?
Ans: Refrigera on: It is a science of producing and maintain temperature below that of the
surrounding atmosphere. This means removing of heat from the substance to be cooled.
Air Condi oning: It is defined as a process which cools (or heats), cleans, circulates and
freshens air and controls its moisture contents simultaneously.
What is the func on of AHU?
Ans: It transforms heat load from the office floor to the chilled water with fresh air addi on
What is the func on of the filters in the AHU?
Ans: It filters the return air in the AHU room.
What is the Air condi oning required for the 1000 cubic feet space?
Ans: One ton of AC with 400 CFM of air through. 1KW= 860 Lcal/hr, 1 ton =3040 Kcal/hr or
12,000 BTU.
Which is the instrument used to measure the CFM?
Ans: Anemometer.
What are the steps to be taken for the power conserva on?
Ans: Switching ON ligh ng as per need basis, Switching ON AHU’s as per need basis,
Maintaining PF approximately 0.98, if not achieved increase the capacitor bank.
Why compressor in a AC unit will set to start a er three minutes when ever power
interrup on in the line?
Ans: Compressor is set to start a er three minutes when ever there is power interrup on
because Freon is in the form of vapour stage in the condenser coil, if it is allowed to cool it
will change into liquid form. So that compressor will get sufficient gas to func on effec vely.
Other wise compressor draws more current due to starva on of gas, Low pressure valve will
tend to trip the compressor.
What is the permissible distance to install outdoor unit of the Split unit?
Ans: Five meters.
Name the types of comfort AC’s with its func ons and applica ons?
Ans:
1. Split AC’s :Evaporator coil and blower in the indoor unit and compressor, condenser
with cooling fan in the outdoor unit.
2. Package AC’s: Evaporator coil, blower fan and compressor in the indoor unit and
condenser coil and cooling fan in the out door unit.
3. Window AC’s : All the parts are integrated in one unit with double end sha motor.
One end of the sha is mounted with blower fan for evaporator coil whereas the
other end of the sha is for cooling fan for condenser coil.
4. Precession AC’s: This units are used in the cri cal areas like Server rooms and Hub
room. Normally air through from the floor, it can be adjusted up to 18 deg. Whether
compensator is incorporated in the system to ac vate heaters, incase of rela ve
humidity (RH) crosses its upper limits.
ELECTRICAL:
Current: The flow of electrons through a conductor is called current.
Resistance: It opposes the flow of electrons. Current is inversely propor onal to the voltage.
What is the approved PF at which you can run your electrical systems without having
penal es imposed?
Ans: 0.98
What are the stages of laisioning(commissioning) work of of KSPCB & Electrical Inspectorate?
Ans: KSPCB
1. Every year we have to obtain consent for water and air a er submi ng required fees
and requisite documents.
2. Proper discharging of waste water a er proper treatment.
3. Disposal of waste lube oil of DG sets to the KSPCB authorized agencies.
Electrical Inspectorate
1. Every year electrical inspector inspect our facility with prior informa on.
2. He will inspect the installa on and rise NCR if any.
3. We have to set right the non conformi es and get it cer fied from the class I
electrical contractor.
4. We have to obtain renewal from electrical inspectorate a er paying required fees
along with the required documents like calibra on cer ficates of ACB’s, VCB’s,
Electrical instruments, Earth pits recondi oning and etc,.
What is the required illumina on level at the work sta on?
Ans: 360 -400 Lux
What is the approximate power consump on in the IT Company?
Ans: Air condi oning 4%, UPS 4% & other (ligh ng, desktop & u li es) 1%
What is the difference between MCB & MCCB?
Ans: MCB is miniature circuit breaker where thermal protec on for tripping
MCCB is moulded case circuit breaker with protec on of OIC & SIC relays
Which is the instrument used to measure rela ve humidity?
Ans: Hygrometer.
What is the difference between MCB & Isolator?
Ans: MCB is a circuit breaker with protec on upto 60 Amps, where as Isolator is switch
for more that 60 amps without any protec on.
What are the scope of ac vi es in BMS room?
Ans: Access control, CCTV, Fire alarm, UPS audio alarm, AC control (BTU meter), Li
integrated, Fire alarm integrated.
It is used for high current and low voltage capaci es. And ACB’s are found in the low
tension side only.
Range 400A to 6300A
Prats: Shunt coil, Tripping coil, Universal motor AC or DC, Arc hunt(D-ion plates), Slide
contactor, Pole assembly, Auxiliary contact, Closing coil.
Abbreva ons
1. CT – current transformer.
2. AS- Ammeter selector Switch.
3. VS- Voltemeter Selector switch.
4. CBCT- Core Balance Current Transformer.
5. ELR- Earth Leakage Relay.
6. FM- Fuel maintain.
7. LOP- Low Lube Oil Pressure.
8. LDB- Ligh ng Distribu ons Board
9. PDB- Power Distribu ons Board.
10. VCB- Vacuum Circuit Breaker
11. RMU- Ring Master Unit.
12. MPCP- Motor Protec on Circuit Breaker
13. PLC- Program Logic Control
14. LED- Light Emi ng Diode
15. AMF- Auto Main Failure
16. MA- milli amps
17. UPS- Uninterrup ble Power Supply
18. AVR- Auto Voltage Regulator
19. MES- Mul Pulse Electronics Switch Gear
20. L&T- Larsen and Turbo Limited
21. MCC- Motor Control Center
22. KPA- Kilo Pascal
23. PSIG- Pound Square Inch Gauge
Why starter ad choke required for flourcent tube?
Ans: Choke: It gives high voltage for star ng the lamp( 1000V while starter open), it gives low
uniform voltage while running the lamp.
Starter: Starter has two metal strips as electrodes it completes in series circuit of tube,
choke at given supply fast then it open immediately and interrupt the current in the circuit
and their induced high voltage surge of 1000V to start the tube.
PVC Cable in Sqmm Current ra ng in Amps PVC Cable in Sqmm Current ra ng in Amps
0.5 4 95 210
0.75 7 120 235
1 11 150 295
1.5 14 185 330
2.5 19 240 400
4 26 300 475
6 33 400 550
10 45 500 635
16 60 630 725
25 75 800 840
35 95 1000 950
50 125 70 170
FIRE ALARM:
1. What is fire?
Fire is a chemical reac ons of two element normally fuel and oxygen at igni on
temperature of the fuel.
a. Foam type,
b. Dry Chemical Powder,
c. Co2 Type.
LIFTS:
What is a Li ?
Ans: Li is a machine which li s the weight ( Equipment, material and persons) from one
floor to another florr.
What are the important safety measures to be considered when there is opera on?
Ans: For li opera ng get permission le er from li manufacturer/agency and electrical
inspector, display these le er in li . Check emergency switch, door, telephone working
condi on.
What is li car?
Ans: It is a chamber like mini room having li opera ng switches, light and fresh air fan that
is move floor to floor is called li car.
In case of li struck in between what is your ac on?
Ans: Switch OFF li power supply, Remove the people from li car by using manual door
open key, Call vendor for Li service.
What is the equipment associated with this system? Explain the func on of equipment.
Ans: Li control panel with VFD, it controls the li opera ng.
Motor with gearbox assembled, li run smoothly.
Li break – to control the speed when li need to stop and hold the li in posi on.
Li car- to travel very safely to floor to floor.
High mechanical strength spring- this spring will avoid to direct hit to the ground in
case of li car falling down.
Rope and counter weight- it holds the li car and help for the movement and to
balance the car weight.
PPC- Programmable Power Control
PT- Poten al Transformer
PVC- Poly Vinly Chloride
RCC- Reinforced Cement Concrete
RCCB- Residual Current Circuit Breaker
RMS- Root Mean Square
RMU- Ring Main Unit
RO- Reverse Osmosis
RPM- Revolu on Per Minute
RTCC- Remote Tap Changeover Control
SCR- Silicon Controlled Rec fier
SLD- Single Line Diagram
SP- Single Pole
SPM- Suspended Par cular Ma er
ST- Super Tension
STP- Sewage Treatment Plant
SWG- Standard Wire Gauge
TP- Triple Pole
TPN- Triple Pole with Neutral
UGC- Under Ground Cable
UJT- Unit Junc on Transistor
UPS- Uninterrup ble Power Supply
V- Voltage
VCB- Vacuum Circuit Breaker
VESDA-Very Early Smoke Detector Alarm system
VFD- Variable Frequency Drive
WT- Winding Temperature/Water Temperature
WTP- Water Treatment Plant
XLPE- Cross linked poly ethylene
Air condi on Abbrevia on
AC- Air Condi on
AHU- Air Handling Unit
AFT- An Freezing Thermostat
BTU- Bri sh Thermal Unit
CFC- Cloro Fluro Carbon
CFM- Cubic Feet per Minute
CHWT- Chilled Water Temperature
Electrical Abbrevia on
CT = Current Transformer
PT =Poten al Transformer
PF = Power Factor
TR = Tone of Refrigera on
ICTP = Iron
NE = NEUTRAL EARTHING
BE = BODY EARTHING
DE = DEDICATED EARTHING
EE =EQUIPMENT EARTHING
SE = SYSTEM EARTHING
CURRENT = AMPS
VOLTAGE = VOLTS
POWER = WATTS
Transformers:
Transformer parts:
1) Primary Winding
2) Secondary winding
3) Bucholz relay
4) Tap changer
5) Breather relay
6) Conservator
7) Cooling tubes
Primary winding is the input voltage side.(11kV), The output voltage side is Secondary
winding(400V).
Bucholz relay: This is a transformer sta c device. It has two switches or relay such as Alarm
switch and Trip switch.
Buchholz relay defined as Iden fica on and significance of gas the nature of the fault could
be judge with the help of gas collected in bucholz relay.
Colour iden fica on of gas :
Fuse NO OFF
TP
Fuse No OFF
ON OFF
Fuse NO T1 NO T2 NC
Aux Contact
T M NC NC
Star Delta
When On push bu on is pressed then the main contactor and the star contactor are
closed at a me and then a er some me (specified me which is set by Manufacturer)
the star contactor will open and delta contactor will close then the motor is in delta
mode of opera on.
Main contact K1
Star Contact K2
Delta Contact
K3
Basics of Electricity:
1. Con nuous flow of electrons in a conductor is called Electric current.
2. Current(I) is given by I= V/R.
3. The electric pressure, which circulates electric current in an electrical circuit is called
Electro mo ve force(EMF)
4. The sources of EMF are chemicals and solar cells.
5. The capacity of a charged body to do the work is called Electric poten al.
6. Unit of poten al is Volt.
7. The difference in electric pressure between any two of an electrical circuit points is
called poten al difference.
8. Unit of poten al difference is Volt.
9. The resistance is the opposi on offered by a material to the flow of current through
it.
10. The resistance offered between two opposite faces of unit cube is called as specific
resistance.
11. Resistance of a conductor is given by R=V/I
12. Magic triangle gives I=V/R; V=IR; R=V/T;
13. Ohms law is applicable for both DC and AC circuits & for simple circuits.
14. The total (effec ve) resistance of a series circuit is given by R= R1+R2+...+Rn.
15. The total (effec ve) resistance of a parallel circuit is given by 1/R=1/R1+1/R2+...1/Rn.
16. The algebraic sum of all the currents mee ng at a junc on of an electrical network is
zero.
17. In any closed circuit of an electrical network algebraic sum of all emf sources and
poten al drops taken with proper signs is equal to zero.
18. KVL states that incoming currents is equal to outgoing currents.
19. The total amount of work done during a certain period of me is called Energy.
20. Unit of energy is joule.
21. Electrical power is given by: electrical power= Electrical energy/ me.
22. Ohms law is true only at constant temperature.
23. The total resistance of series circuit is the sum of all the individual resistances
connected in series fashion.
24. Reciprocal of effec ve resistance is equal to sum of reciprocal of individual resistance
connected in parallel.
25. Ohms law does not hold good in case of semi conductors and electrolytes.
26. Electricity at rest is known as sta c electricity.
27. Electricity in mo on is known as dynamic electricity.
28. SI units of specific resistance is Ohm.
29. Current always flow from higher poten al to lower poten al.
30. Prac cal unit of electrical energy is Kwh.
31. If a poten al of A is 20V and B is 12V then poten al difference of A & B is 20-12= 8V.
32. Specific resistance of a conductor is inversely propor onal to area of cross sec on.
33. Unit of electric power is Kilowa .
34. The resistance of resistor which takes 5A when connected to 110V supply is R=V/I
=110/5=22ohms
35. The resistance of conductor of 1 sqmm in cross sec on and 20 m long is 0.346ohm
then the specific resistance is given by R=ρl/A therefore ρ=RA/l=(0.3468*1*10^-6)/2.
36. Unit of EMF is volts.
37. One ampere is the amount of current which flows through a circuit when on
coulomb of charge per second is transferred through a point in the circuit.
38. Rela on between power and energy is E=PT.
39. Electron flows from nega ve terminal to posi ve terminal but conven onal current is
always assumed to flow from posi ve terminal to nega ve terminal of ba ery or
source.
40. If a body is capable of sending charges to earth, the body is said to be at posi ve
poten al.
41. If a body is capable of reac ng charges from the earth when connected to it is called
nega ve poten al.
42. Unit of resistance is ohms
43. Provided temperature is kept constant, the ohms law states that the current flowing
through conductor is
a) directly propor onal to voltage applied at the ends of the conductor.
b) inversely propor onal to resistance of the conductor.
44. When circuit elements (resistance) are connected end to end as to form a chain
cons tutes series circuit.
45. If a circuit takes a current of 58 Amps at 100 V, supplied to limit the current to 2 amps.
The resistance to be added in series with circuit is 30 Ohm
46. If 10 amp is to be circulated through circuit of 100 ohm resistance the voltage to
applied is V= IR=10*100=1000V
47. The ra o of power output to power input is called efficiency.
48. In series circuit the voltage across each resistance is different.
49. In parallel circuit the current across each resistance is different
50. Electrical power is given by P=E^2/R.
Kirchoff’s voltage law states that the algebraic sum of all the branch voltages is equal to zero.
Electrical Formulas
P= V*I
This informa on page provides formulas and documenta on to take certain electrical values
and convert them into other electrical values. The formulas below are known and used
universally in the Generator Industry but you can use them for computer, network, telecom
and powered equipment
E X L X PF E X I X 1.73 X PF
kW X 1000 kW X 1000
IXE I X E X 1.73
Actual Wa s Actual Wa s
POWER FACTOR (PF)
IXE I X 1.73 X E
I v E X PF I X E X 1.73 X PF
kW X 1000 kW X 1000
AMPERES (when kW is
E X PF E X 1.73 X PF
known)
I = current in amperes
E = voltage in volts
W = wa s
kW = power in kilowa s
HP = horsepower
Background
The Formulas
To Find Wa s
We have a appliance with a nameplate shows 2.5 amps. Given a normal 120 Volt, 60 hz
power source and the ampere reading from equipment, make the following calcula on:
POWER (WATTS) = 120 * 2.5 ANSWER: 300 WATTS
1. SINGLE PHASE
2. TWO-PHASE
Given: We have a Sun server with an amp ra ng of 4.7 and requiring a 208-240 power source.
We'll use 220 volts for our calcula ons.
KILOVOLT-AMPERES (kVA) = VOLTS x AMPERES x 2
1000
220 x 4.7 x 2 = 2068 2068 / 1000 = 2.068 kVA
3. THREE-PHASE
Given: We have a large appliance with nameplate data of 50-amp 208 VAC receptacle. For
this calcula on, we will use 21 amps. Do not calculate the value of the plug or receptacle.
Use the value on nameplate.
KILOVOLT-AMPERES (kVA) = VOLTS x AMPERES x 1.73
1000
208 x 20.5 x 1.73 = 7,376.72 7,376.72 / 1000 = 7.377 kVA
To Find Kilowa s
Finding Kilowa s is a bit more complicated in that the formula includes a value for the
"power factor". The power factor is a nebulous but required value that is different for each
electrical device. It involves the efficiency in the use of the electricity supplied to the system.
This factor can vary widely from 60% to 95% and is never published on the equipment
nameplate and further, is not o en supplied with product informa on. For purposes of these
calcula ons, we use a power factor of .85. Most generators have a power factor of .80.
Whatever the number, it places a slight inaccuracy into the numbers. Its OK and it gets us
very close for the work you need to do.
1. SINGLE PHASE
2. TWO-PHASE
Given: We have a larger appliance with a running amp ra ng of 4.7 and requiring a 208-240
power source. We'll use 220 volts for our calcula ons.
KILOVOLT-AMPERES (kVA) = VOLTS x AMPERES x POWER FACTOR x 2
1000
220 x 4.7 x 2 = 2068 2068 x .85 = 1757.8 1757.8 / 1000 = 1.76 kW
3. THREE-PHASE
Given: We have a very large appliance that shows a requirement for a 50-amp 208 VAC
receptacle. For this calcula on, we will use 21 amps. Do not calculate the value of the plug or
receptacle. Use the value on nameplate.
KILOVOLT-AMPERES (kVA) = VOLTS x AMPERES x POWER FACTOR x 1.73
1000
208x20.5x1.73 = 7,376.72 7,376.72 * .85 = 6,720.21 6,720.21/1000=6.27 kW
The only difference between kW and kVA is the power factor. Once again, the power factor,
unless known, is an approxima on. For purposes of our calcula ons, we use a power factor
of .80 which most generators use. The kVA value is always higher than the value for kW.
kW To kVA kW / .80 = SAME VALUE EXPRESSED IN kVA
kVA To kW kVA * .80 = SAME VALUE EXPRESSED IN kW
To Find BTUs From Electrical Values
The above is a generally known value for conver ng electrical values to BTUs. Many
manufacturers publish kW, kVA and BTU in their equipment specifica ons.