Sei sulla pagina 1di 62

A Laboratory Manual for

Refrigeration and Air


Conditioning (2161908)
6th Semester
Mechanical Engineering

DARSHAN INSTITUTE OF ENGINNERING


AND TECHNOLOGY, RAJKOT
Campus: At Hadala, Rajkot-Morbi Highway, Near Water Sump, Rajkot 363650 Phone:
+91-2822-293010 Web: www.dashan.ac.in

1
DARSHAN INSTITUTE OF ENGINNERING
AND TECHNOLOGY, RAJKOT
Certificate

This is to certify that, Mr. / Ms.__________________________


Enroll no.__________________ of Eighth semester Bachelor of
Mechanical Engineering has completed the term work satisfactorily
in Refrigeration and Air conditioning (2161908) for the academic
year 2015 as prescribed in the curriculum.

Place: _________ Enrolment No.:____________


Date: _________ Exam. Seat No.:___________

Subject Teacher Head of the Department

2
DARSHAN INSTITUTE OF ENGINNERING AND
TECHNOLOGY
Department of Mechanical Engineering - 6th Semester
Refrigeration and Air Conditioning (2161908)
List of Experiments
Sr. Starting Date of Assessment
Title Sign Remark
No. Date Completion Marks
To study and calculate
capacity & COP of
1. Vapour Compression
Refrigeration(VCR)
system

To study and calculate


capacity & COP of
Vapour Absorption
2. Refrigeration(VAR)
(Electrolux
Refrigeration) system

Study of Air
Conditioning system
and calculate COP of
3. Air Conditioning
system with the help of
P-H Chart

To carry out Heating


process of fresh air and
find out relevant
4. parameter of air and
also plot the process on
psychrometric chart.

To carry out Cooling


process of fresh air and
find out relevant
5. parameter of air and
also plot the process on
psychrometric chart.

6. To carry out Heating


and humidification
3
process and find out
relevant parameters and
also plot the process on
psychrometric chart

To carry out Cooling


and humidification
process and find out
7. relevant parameters and
also plot the process on
psychrometric chart

To carry out Cooling


and dehumidification
process and find out
8. relevant parameters and
also plot the process on
psychrometric chart

4
5
1. STUDY OF VAPOUR COMPRESSION REFRIGERATION SYSTEM AND
CALCULATE COP OF SYSTEM WITH THE HELP OF P-H CHART

1. Objective:
To Study Refrigeration test rig and to study the vapour compression refrigeration cycle.

2. Aim:
To calculate co-efficient of performance with the help of P-h diagram.

3. Nomenclature:
Nom Column Heading Units Type
Cos Φ Power factor. Given
Cp Specific heat of water kJ/kgoC. Given
(C.O.P.)Rel(b) Relative co-efficient of performance for batch operation Calculated

(C.O.P.)Rel(c) Relative co-efficient of performance for continuous operation Calculated


(C.O.P.)Th Theoretical co-efficient of performance. Calculated
(C.O.P.)Act(b) Actual co-efficient of performance. for batch operation Calculated

(C.O.P.)Act(c) Actual co-efficient of performance for continuous Calculated


Operation
CWAct Actual compression work kJ/kg Calculated
H1 Enthalpy of refrigeration effects at compressor inlet kJ/kg Calculated
H2 Enthalpy of compressor work at compressor outle kJ/kg Calculated
H3 Enthalpy of sub cooling at the outlet of condenser kJ/kg Calculated
H4 Enthalpy of refrigerant inlet of evaporator kJ/kg Calculated
I Ammeter reading Amp. Measured
m(b) Mass of water for batch operation kg/sec. Calculated
m(c) Mass of water for continuous operation kg/sec. Calculated
W Heater Wattage KW Given
P1 Pressure at compressor suction kg/cm2 Measured
P2 Pressure at compressor discharge kg/cm2 Measured
REAct(b) Actual Refrigeration effect for batch operation kJ/sec Calculated
REAct(c) Actual Refrigeration effect for continuous operation kJ/sec Calculated
T1 Temperature at compressor suction C Measured
T2 Temperature at compressor discharge C Measured
T3 Temperature at condenser outlet C Measured
T4 Temperature at evaporator inlet C Measured
T5 Temperature of water inlet for continuous operation C Measured
T6 Temperature of, water in evaporator for batch C Measured
cooling / water outlet for continuous operation
T6i Temperature of water before cooling in batch operation C Measured
T Time sec Measured
V Voltmeter reading Volts Measured
Vwe Volume of water in evaporator for batch cooling Ltrs Measured
6
Vwr Flow rate of water through evaporator for continuous cooling LPH Measured
w Density of water kg/m3 Given

4. Introduction:
Refrigeration may be defined as the process of removing heat from a substance under controlled
conditions. It is used for the manufacture of ice and similar products.
Refrigeration is the branch of science that deals with the process of reducing and maintaining the
temperature of a space or material below the temperature of the surroundings. Heat must be
removed from the body being refrigerated and transferred to another body whose temperature is
below that of the refrigerated body. This is widely used for cooling of storage chambers in which
perishable foods, drinks, and medicines are stored. The refrigeration has also wide applications in
submarine ships, aircrafts.

5. Theory:

Fig. 1.1 Schematic diagram of Vapour Compression Refrigeration System

5.1 Vapour Compression Cycle:


The refrigerant starts at some initial state or condition, passes through a series of processes in a
definite sequence and returns to the initial condition. This series of processes is called a cycle.

7
The Standard Vapour Compression Cycle (SVCC) consists of the following processes:
Process 1-2: Reversible adiabatic compression from the saturated vapour to a super heated
Condition (electrical) input.
Process 2-3: Reversible heat rejection at constant pressure (de-superheating and condensation of
the refrigeration
Process 3-4: Irreversible constant enthalpy expansion from high pressure saturated liquid to a
low- pressure liquid and small amount of vapour.
Process 4-1: Reversible heat absorption at constant pressure from space to be cooled.

Fig. 1.2 Pressure- Enthalpy Diagram

5.2 Standard Vapour Compressor Cycle :


Compressor:
The main function of compressor is to raise the pressure and temperature of the refrigerant by the
compression of the refrigerant vapour and then pump it into the condenser

Condenser:
Condense the vapour refrigerant into the liquid by condenser fan and passes it into the receiver
tank for recirculation.

Capillary Tube:
It expands the liquid refrigerant at high pressure to the liquid refrigerant at low pressure so that a
measured quantity of liquid refrigerant is passed into the evaporator.

Evaporator:
Evaporates the liquid refrigerant by absorbing the heat into vapour refrigerant and sends back into
the compressor.
8
Drier:
A drier is used in between the condenser and expansion device. The main function of the drier is
to absorb the moisture from the liquid refrigerant and filter the dust particles.

Accumulator:
An accumulator is fitted in between the Evaporator and Compressor. It prevents the liquid
refrigerant from entering the compressor.

Co-efficient of Performance:
The coefficient of performance of (C.O.P.) of a refrigerating cycle is defined as the ratio between
net refrigeration (output) and compressor work (input).

RE
C.O.P 
CW
RE  H1  H 4
CW  H2  H1
H1  H 4
C.O.P. 
H 2  H1

6. Description:
The set up demonstrates the basic principal of a refrigeration cycle. The test rig is designed for
the study of Vapour Compression Refrigeration Cycle. The set up consist of voltmeter,
amperemeter, Energymeter, rotameter, heater. Instrumentation is done to measure the temperature
& pressure wherever necessary

7. Utilities Required:
Electricity Supply: Single Phase, 220 V AC, 50Hz, 5-15Amp. Combined socket with earth
connection.
Water Supply @ 2 LPM at 1 Bar.
Floor Drain required.
Floor Area Required: 1.5 m x 1m

8. Experimental Procedure:

8.1 Starting Procedure (For Batch Operation):


1. For batch operation fill known amount of water in the evaporator tank.
2. Put the temperature sensor T6 in the evaporator tank.
3. Note down the reading of temperature T6i.
4. Switch ON the mains power supply.
5. Switch ON the compressor.
6. Wait for 2-3 minutes to switch ‘ON’ the compressor.
7. Open the valves below the pressure gauges.
8. Switch ON the pump for 30 sec after every 10 minutes.
9. After 10 minutes, note the temperature sensors reading.
10. Note down the voltage and current.
11. Note down the time.
12. Note down the reading of pressure gauges.
9
13. Note all the reading after every 10 minute till the temperature of water in evaporator comes
constant.
14. Repeat the experiment for different volume of water.
15. Repeat the experiment by switching ‘ON’ the heater (load condition)

8.2 Starting Procedure (For Continuous Operation):


1. For continuous operation, open the valve and drain the water.
2. Connect pipe evaporator water outlet to drain.
3. Connect water supply to rotameter.
4. Set a flow rate of water with help of valve.
5. Put the temperature sensor T6 at evaporator water outlet.
6. Switch ON the mains power supply.
7. Switch ON the compressor.
8. Wait for 2-3 minutes to switch ‘ON’ the compressor.
9. Open the valves below the pressure gauges.
10. After 10 minutes, note the temperature sensors reading.
11. Note down the voltage and current.
12. Note down the time.
13. Note down the reading of pressure gauges.
14. Note all the reading after every 10 minute till the temperature of water in
evaporator comes constant.
15. Repeat the experiment for different flow rates of water.
16. Repeat the experiment by switching ‘ON’ the heater (load condition).

8.3 Closing Procedure:


1. Switch ‘OFF’ the main supply.
2. Close water supply to rotameter.
3. Open the valve to drain out the water.

9. Observation & Calculations:


9.1.a Data:
Power factor Cos Φ = 0.7
Density of water w = 1000 kg/m3
Specific heat of water Cp = 4.186 kJ/kg oC
Heater Capacity W = …………….KW

9.1.b Observation Table:


T6i = ------------ (oC)
For Batch Operation
10
Sr. t P1 P2 T1 T2 T3 T4 T5 T6 Vwr V I
No min kg/cm2 kg/cm2 o
( C) o
( C) o
( C) o
( C) o
( C) o
( C) (LPH) (Volts) (Amp)

9.1. Calculations:
To Calculate Cop of the System
H1  {(0.04  T1 )  3.548}  P1  0.847  T1  404.174
H 2  {(0.0183 T2 )  3.080}  P2  0.834  T2  413.082
H 3  {(0.005  T3 )  0.225}  P2  1.662  T3  194.441
H1  H 4
C.O.PTh   H3  H4
H 2  H1
(A) For batch operation:
Vwe  w
mb  (kg/sec)
t  1000  60
RE Act  b   mb  C p  (T6i  T6 ) (kJ/sec)
V  I  Cos
CW Act  (kJ/sec)
1000
RE Act b
(C.O.P.) Act b  
CW Act
C.O.PAct  b 
(C.O.P.)Re l  b  
C.O.PTh

9.1.c OBSERVATION TABLE:


T6i = ------------ (oC)
For continuous operation

Sr. t P1 P2 T1 T2 T3 T4 T5 T6 Vwr V I
No min kg/cm2 kg/cm2 o
( C) o
( C) o
( C) o
( C) o
( C) o
( C) (LPH) (Volts) (Amp)

(B) For continuous operation:

11
Vwr  w
mc  (kg/sec)
t  1000  3600

RE Act c   mc  C p  (T5  T6 ) (kJ/sec)


V  I  Cos
CW Act  (kJ/sec)
1000
RE Act c 
(C.O.P.) Act c  
CW Act
C.O.PAct  c 
(C.O.P.)Re l c  
C.O.PTh

10. Precautions & Maintenance Instructions:


1. Never run the apparatus if power supply is less than 180 volts and above 230 volts.
2. Do not start unit, before putting the water in the evaporator.
3. During the observation do note open the evaporator.

11. Troubleshooting:
If electric panel is not showing the input on the mains light, check the main supply.

12. Conclusion

13. References:
12.1 Dossat, Roy J. (2004). Principles of Refrigeration. 4th Ed. ND: Pearson Education Pvt.
Ltd. pp 102-105,118-125
12.2 Jordan, Richard C. & Priester, Gayle B. (1966). Refrigeration & Air Conditioning. 2nd Ed.
ND: Prientice-Hall of India Pvt. Ltd. pp 16-23,423-429.

12
13
2. TO STUDY VAPOUR ABSORPTION REFRIGERATION SYSTEM AND
CALCULATE THE COP.

1. Objective:
To study Electrolux Refrigeration system.

2. Aim:
To determine COP of Vapour absorption refrigeration system.

3. Nomenclature:
Nom Column Heading Units Type
COP Co-efficient of Performance Calculated
o
T1 Temperature of generator C Measured
o
T2 Temperature of condenser C Measured
o
T3 Temperature of evaporator C Measured

4. Introduction:
Electrolux refrigerator is a absorption type refrigeration system. In absorption refrigeration
system the vapour is drawn from the evaporator by absorption into liquid having high affinity
for refrigerant. The refrigerant is expelled from the solution by application of heat and its
temperature is increased. This refrigerant in the vapour form passes to the condenser where
heat is rejected and the refrigerant gets liquefied. This liquid again flows to the evaporator at
reduced pressure and the cycle is completed.

Absorber:
The main function of Absorber is the absorption of the refrigerant vapour by its weak or poor
solution in a suitable absorbent or adsorbent, forming a strong or rich solution.

Condenser:
Condenses the vapour refrigerant into the liquid by condenser fan and passes it into the
receiver tank for recirculation.

Evaporator:
Evaporates the liquid refrigerant by absorbing the heat into vapour refrigerant and sends back
to next run.

5. Theory:
The flow of fluids in the system has been shown in the diagram with different shadings and
the index of these shadings also indicated in diagram. Vertical boiler in which an aqua
solution of ammonia can range itself from distilled water at the bottom of the boiler to strong
ammonia vapour at the surface of liquid.
A water separator which is provided to remove water vapour so that they should not enter the
condenser, get condensed there and pass on to evaporator where chocking might occur due to
its freezing. The water vapour is formed in the boiler as some of the water may evaporate on

14
application of heat to the boiler. The separator is a jacket with liquid ammonia at pressure of
about 14 bar gauge for which the saturation temperature is about 40 ºC

The dehydrate ammonia gas gets condensed to liquid in the condenser and gravitates to ‘U’
tube which acts as seal for a gas to enter the evaporator, or any gas passing from evaporator
to condenser.

Fig. 2.1 Vapour Absorption Type Refrigeration System

In the evaporator, ammonia liquid comes across an atmosphere of hydrogen at about 12-bar
gauge. The plant is charged to a pressure of about 14 bar. Hence due to Dalton’s law of
partial pressure the pressure of ammonia gas should fall to about 2 bar gauge and the
saturation temperature corresponding to about 2 gauge is about –10 ºC. the temperature
surrounding the evaporator is much higher than this. Thus ammonia evaporates and produces
the refrigerating effect, i.e. absorbs the latent heat of vaporization at 2 bar gauge and about–
10 ºC from the space to be refrigerated.

In order to ensure continuous action, hydrogen gas has to be removed from ammonia vapors.
This is done in the absorber where a descending spray of very dilute ammonia liquid moseys
the ascending mixture of ammonia vapour and hydrogen. Ammonia vapour is readily
absorbed with evaluation of heat so that absorber has to be water jacketed or air cooled,
otherwise evaporation may take place in this unit and the absorption may cease.

Heat exchanger (Condenser): liquid heat exchanger is placed in between absorber and the
generator. This weak liquid gets cooled and strong liquid gets heated, thus is economized and
better thermal efficiency obtained. This heat exchanger is counter flow type. The strong
solution from the absorber is preheated on its way to generator or boiler and the dilute
solution on its way to absorber is cooled. This cooling of weak liquid also helps absorption
and reduces the cooling of absorber by external source.

Working:
1. Strong ammonia solution flows from the absorber vessel to the boiler.
2. When the ammonia solution is heated in the boiler, bubbles of ammonia as raises from the
pump.

15
3. The ammonia vapour passes into the condenser.
4. Weak ammonia solution flows into the tube.
5. Air circulating over the fins of the condenser. Cool down the vapour. Condensing it in
liquid ammonia.
6. Liquid ammonia flows through the pipe to the evaporator.
7. The hydrogen in the evaporator lowers the ammonia vapour pressure and makes it
evaporate.
8. This process extracts heat from the evaporator, which in turn extracts heat from the food
storage space. Thereby the temperature inside the refrigeration is lowered.
9. The mixture of hydrogen and ammonia passes from the evaporator to the absorber.
10. Weak ammonia solution is fed from the boiler system.
11. As it turns to the absorber vessel, it absorbs the ammonia from the ammonia/hydrogen
mixture and gets ready for another round in the boiler.

6. Utilities Required:
1. Electricity Supply: Single Phase, 220 VAC, 50 Hz, 5-15 amp socket with earth
connection.
2. Bench Area Required: 1 m x 0.5 m.

7. Experimental Procedure:
1. Ensure that all ON / OFF switches given on the panel are at OFF position.
2. Switch ON the main Supply.
3. Switch ON the refrigerator.
4. Record the temperatures when the steady state is achieved.

8. Observation & Calculation:

8.1 Observation Table:


S. No. T1 (oC) T2 (oC) T3 (oC)

8.2 Calculations:

T 3273 .15   T 1273 .15   T 2273 .15 


COP 
T 1273 .15   T 2273 .15   T 3273 .15 

9. Precaution & Maintenance Instructions:


9.1 Never run the apparatus if power supply is less than 180 volts & above than 230 volts.
9.2 Unnecessary handling of equipment should be avoided.
9.3 Never open the refrigerator during the experiment.

10. Troubleshooting:
16
10.1 If electric panel is not showing the input on the mains light, check the main supply.

11. Conclusion:

12. References:
11.1 Domkundwar, Arora (1995). A Course in Refrigeration & Air Conditioning. 5th Ed. IND:
Dhanpat Rai & CO. (P) Ltd. pp 6.4- 6.5.

17
18
3. STUDY OF AIR CONDITIONING SYSTEM AND CALCULATE COP OF AIR
CONDITIONING SYSTEM WITH THE HELP OF P-H CHART

1. Objective:
To study the vapour compression air conditioning cycle. And calculate the COP of the Air
conditioning cycle.

2. Aim:
To study the Vapour Compression air conditioning cycle
To calculate Co-efficient of performance (COP) by the use of P-H diagram
To measure dry bulb & wet bulb temperature of inlet and outlet air

3. Nomenclature:
Nom Column Heading Units Type

Cos Φ Power Factor Given

Cp Specific heat of water kJ/kgoC. Given


C.O.P.Th Theoretical Co-efficient of performance Calculated
RE Refrigeration Effect kJ/ kg Calculated
CW Compressor Work KJ/Kg Calculated
H1 Enthalpy of refrigeration effects at kJ/ kg Calculated
compressor inlet
H2 Enthalpy of compressor work at compressor kJ/ kg Calculated
outlet
H3 Enthalpy of sub cooling at the outlet of kJ/ kg Calculated
condenser
H4 Enthalpy of refrigerant inlet of evaporator kJ/ kg Calculated
P1 Pressure at compressor suction kg/cm2 Measured
P2 Pressure at compressor discharge kg/cm2 Measured
T1 Temperature at compressor suction C Measured
T2 Temperature at compressor discharge C Measured
T3 Temperature at condenser outlet C Measured
T4 Temperature at evaporator inlet C Measured
Tdi Dry Bulb Temperature of air at inlet of duct C Measured
Twi Wet Bulb Temperature of air at inlet of duct C Measured
Tdo Dry Bulb Temperature of air at outlet of duct C Measured
Two Wet Bulb Temperature of air at outlet of duct C Measured
ρa Density of air Kg/m3 Given
Va Velocity of air flowing through duct m/sec Measured
X1 Humidity at inlet of duct Kg/Kg of dry air Measured
X2 Humidity at outlet of duct Kg/Kg of dry air Measured
X Change in Specific Humidity Kg/Kg of dry air Calculated
19
h1 Enthalpy of air at inlet of duct KJ/Kg of dry air Calculated
h2 Enthalpy of air at outlet of duct KJ/Kg of dry air Calculated
V Voltmeter Reading Volts Measured
I Ampere meter reading Amp. Measured

4. Introduction:
Air conditioning is the simultaneous control of the temperature, humidity, motion and purity
of the atmosphere in a confined space. Air conditioning applies in the heating season as well
as in the cooling season. The Air conditioning has wide applications in submarine ships,
aircrafts and rockets. Air conditioning is associated with the human comfort and controlling
the humidity ratio.

Air conditioning means "preparing the air as per required conditions of temperature, humidity
and velocity. The conditions required are different for different applications, e.g. a small
room requires air at about 24 - 26 °C where humidity control is not so important, or a
building may be air conditioned for supplying air of 24 - 26°C temperature & 50-60 %
relative humidity. Measurement rooms in factories are to be maintained at the temperature of
-20 °C. So depending upon the requirement, the air conditioning system is designed. A
complete air conditioning system has the following jobs.
1. Filtration of air, where it contains dirt or dust particles.
2. Deodorization of air.
3. Cooling of air in summer.
4. Dehumidification of air by cooling coil itself and again heating it, as may be required in
humid areas in summer.
5. Heating of air in winter.
6. Humidifying and heating of air as may be required in winter.
7. Circulating the conditioned air through the space to be air conditioned.

An air conditioning system may be provided with some or all the units required to perform
the above jobs, which is determined by conditioning requirements and cost aspects. A
window type air conditioner provides some filtration and cooling of air. In large buildings,
cooling, heating and humidification systems may be used, along with partial recirculation of
exhaust air. This is done as it will require a huge capacity plant to condition the whole fresh
air entering the space to be conditioned. Thus some air from the exhausted air which is at a
temperature lower than the ambient temperature is mixed with the entering fresh air. Total
recirculation is generally avoided in large installations as the exhausted air contains odors.

The Air Conditioning Test Rig comprises of the following components.


1. A conditioning unit consisting of cooling coil, heaters and humidifier
2. Fan with circulating duct.
3. Control and measurement panel

5. Block Diagram:

20
Fig. 3.1 Line Diagram of Air Conditioning Apparatus
6. Theory:
Air conditioning may be defined as the process of removing heat from a substance under
controlled conditions. It also includes the process of reducing and maintaining the
temperature of a body below the general temperature of its surroundings. This is widely used
for cooling of storage chambers in which perishable foods, drinks, and medicines are stored.
Fig. 4.2 shows the schematic of the unit with complete description.

Condenser

Capillary Compressor
tube

Evaporator
Fig. 3.2 Block Diagram of Standard
Vapour Compression Cycle (SVCC)

COMPRESSOR:
The main function of compressor is to raise the pressure and temperature of the
refrigerant by the compression of the refrigerant vapour and then pump it into the
condenser.

CONDENSER:
21
Condense the high pressure vapour refrigerant into the high pressure liquid by
condenser fan and passes it into the receiver tank for recirculation

CAPILLARY TUBE:
Expands the liquid refrigerant at high pressure to the sub cooled liquid refrigerant at
low pressure so that a measured quantity of liquid refrigerant is passed into the
evaporator.

EVAPORATOR:
Evaporates the sub cooled liquid refrigerant by absorbing the sensible heat into
vapour refrigerant and sends back into the compressor.

VAPOUR COMPRESSION CYCLE:


The refrigerant starts at some initial state or condition, passes through a series of
processes in a definite sequence and returns to the initial condition. This series of
processes is called a cycle.

Fig. 3.3 Standard Vapour Compression Cycle (SVCC)


The Standard Vapour Compressor Cycle (SVCC) consists of the following processes:

 Reversible adiabatic compression from the saturated vapour to a super-heated


condition.

 Reversible heat rejection at constant pressure (sub cooling liquid and


condensation of the refrigerant)

 Irreversible enthalpy expansion from saturated liquid to a low pressure sub


cool liquid.

 Reversible heat addition at constant pressure.

COEFFICIENT OF PERFORMANCE (C.O.P):

22
The coefficient of performance of (C.O.P.) of a refrigerating cycle is defined as the
ratio between net refrigeration (output) and compressor work (input).

RE
C.O.P 
CW

RE  H1  H 4

CW H 2  H1

H1  H 4
C.O.P 
H 2  H1

7. Description:
The air-conditioning test rig unit is required to conduct experiments and demonstrate the
processes of heating, cooling, heating and humidification, cooling and dehumidification,
cooling and humidification of atmospheric air. The unit consists of a compressor. Both
evaporator and the air cooled condenser are mounted on board with separate fans. Air is
sucked from the room and is supplied to the room after conducting the different processes.
The system is provided with voltmeter, ampere meter, digital temperature indicator, air
heater, steam generator. The unit will be fitted with all instrumentation facilities so that
temperature and pressure can be measured at different points in the air-conditioning system.
Steam generator is provided from which steam comes directly to the air inlet of air
conditioning which is required for humidification purpose. Heating coil is provided for
heating of air and cooling coil is provided for cooling and dehumidification of air. Suitable
valves and fittings are fitted in the pipe line of steam. Water level indicator is provided to safe
guard of heater.

8. Utilities Required:
1. Electricity Supply: Single Phase, 220 VAC, 50 Hz, 5-15 Amp. Combined socket with earth
connection.
2. Floor Area Required: 2 m x 1 m

9. Experimental Procedure:

Starting Procedure:
1. Switch ‘ON’ the compressor.
2. Wait for 2-3 minutes for switch ‘ON’ the compressor.
3. Open the valves of pressure gauges.
4. After 10 minutes note down the reading of temperature sensor.
5. Note down the reading of pressure gauges.
6. Note down the reading of inlet and outlet temperature of air.
7. Note down the reading of temperature and pressure after every 10 minutes till the
temperature of outlet of air come constant.

Closing Procedure:
1. Switch off the compressor.

23
2. Switch off the mains power supply.

10. Observation & Calculations:


10.1 Data:
Cos Φ = 0.7
a = 1.21 Kg/m3

10.2 Observation Table:

Va= …………… m/sec

Sr.No. t P1 P2 T1 T2 T3 T4 Tdi Twi Tdo Two V I


min Bar Bar (C) (C) (C) (C) (C) (C) (C) (C)

10.3 Calculations:
To Calculate COP of the System:

H1  (0.011 T1  1.98) P1  (0.652 T1 )  415.723

H 2  (0.011 T2  1.98) P2  (0.652 T2 )  415.723

H 3  1.228 T3  199.93

H1  H 4
C.O.PTh   H3  H4
H 2  H1

V  I  Cos
CW  KJ/sec
1000

To calculate the specific humidity X1 and enthalpy of air h1 at temperature Tdi & Twi.
X 1  __________ (kg/kg of dry air)
h1 = (kJ/kg of dry air) [from psychrometric chart]

To calculate the specific humidity X2 and enthalpy of air h2 at temperature Tdo & Two
X 2  __________ (kg/kg of dry air)
h2 = (kJ/kg of dry air) [from psychrometric chart]

Heat rejected from the air = Change in enthalpy of air = R.E.


R.E. = h1 – h2
= (kJ/kg of dry air)

24
11. Precautions & Maintenance Instructions:
1. Operate the Valves gently.
2. Never run the apparatus if power supply is less than 180 volts and above 230 volts.
3. Duct should be free from dust particles.

12. Troubleshooting:
1. If electric panel is not showing the input on the mains light, check the main supply.
2. If voltmeter showing the voltage given to heater but ampere meter does not, check the
connection of heater in control panel.

13. Conclusion:

14. References:
1. Dossat, Roy J. (2004). Principles of Refrigeration. 4th Ed. ND: Pearson Education
Pvt. Ltd. pp 125-126.
2. Jordan, Richard C. & Priester, Gayle B. (1966). Refrigeration & Air Conditioning. 2nd
Ed. ND: Prientice-Hall of India Pvt. Ltd. pp 444-447,455-466.
3. S.C. Arora, S Domkundwar (1995). A Course In Refrigeration And Air Conditioning.
5th Ed. Dhanpat Rai & Sons pp 16.1-16.24.
4. Psychometric Chart.

25
26
4. TO CARRY OUT THE HEATING PROCESS OF FRESH AIR & FIND OUT
RELEVANT PARAMETERS ON AIR CONDITIONING TEST RIG AND TO
PLOT THE PROCESS ON PSYCHROMETRIC CHART

1. Objective:
To study the heating of air in air conditioning test rig and perform experiment to calculate the
change in relevant parameter of air during heating process.

2. Aim:
To measure dry bulb & wet bulb temperature of inlet and outlet air
Plot the process on Psychrometric chart
Calculate the heat supplied during heating process.

3. Nomenclature:
Nom Column Heading Units Type
Tdi Dry Bulb Temperature of air at inlet of duct C Measured
Twi Wet Bulb Temperature of air at inlet of duct C Measured
Tdo Dry Bulb Temperature of air at outlet of duct C Measured
Two Wet Bulb Temperature of air at outlet of duct C Measured
ρa Density of air Kg/m3 Given
Va Velocity of air flowing through duct m/sec Measured
X1 Humidity at inlet of duct Kg/Kg of dry air Measured
X2 Humidity at outlet of duct Kg/Kg of dry air Measured
X Change in Specific Humidity Kg/Kg of dry air Calculated
h1 Enthalpy of air at inlet of duct KJ/Kg of dry air Calculated
h2 Enthalpy of air at outlet of duct KJ/Kg of dry air Calculated
V Voltmeter Reading Volts Measured
I Ampere meter reading Amp. Measured

4. Introduction:
Air conditioning means "preparing the air as per required conditions of temperature, humidity
and velocity. The conditions required are different for different applications, e.g. a small
room requires air at about 24 - 26 °C where humidity control is not so important, or a
building may be air conditioned for supplying air of 24 - 26°C temperature & 50-60 %
relative humidity. Measurement rooms in factories are to be maintained at the temperature of
-20 °C. So depending upon the requirement, the air conditioning system is designed. A
complete air conditioning system has the following jobs.
1. Filtration of air, where it contains dirt or dust particles.
2. Deodorization of air.
3. Cooling of air in summer.
4. Dehumidification of air by cooling coil itself and again heating it, as may be required in
humid areas in summer.

27
5. Heating of air in winter.
6. Humidifying and heating of air as may be required in winter.
7. Circulating the conditioned air through the space to be air conditioned.

An air conditioning system may be provided with some or all the units required to perform
the above jobs, which is determined by conditioning requirements and cost aspects. A
window type air conditioner provides some filtration and cooling of air. In large buildings,
cooling, heating and humidification systems may be used, along with partial recirculation of
exhaust air. This is done as it will require a huge capacity plant to condition the whole fresh
air entering the space to be conditioned. Thus some air from the exhausted air which is at a
temperature lower than the ambient temperature is mixed with the entering fresh air. Total
recirculation is generally avoided in large installations as the exhausted air contains odors.

The Air Conditioning Test Rig comprises of the following components.


1. A conditioning unit consisting of cooling coil, heaters and humidifier
2. Fan with circulating duct.
3. Control and measurement panel

5. Block Diagram:

Fig. 4.1 Line Diagram of Air Conditioning Apparatus

6. Theory:
The heating of air, without any change in its specific humidity, is known as sensible heating.
Let air at temperature Td1 passes over a heating coil of temperature Td3 as shown in Fig. 5.2.
It may be noted that the temperature of air leaving the heating coil(Td2) will be less than Td3.
The process of sensible heating, on the psychometric chart, is shown by horizontal line 1-2
28
extending from left to right as shown in Fig. 5.2. The point 3 represents the surface
temperature of the heating coil.

The heat absorbed by the air during sensible heating may be obtained from the psychometric
chart by the enthalpy difference (h2-h1) as shown in figure. It may be noted that the specific
humidity during the sensible heating remains constant (i.e. W1 = W2). The dry bulb
temperature from td1 to td2 and relative humidity Φ1 to Φ2
Heat added,
Q = h2 - h1
= Cpa(td2-td1) + Wcps(td2-td1)

Sensible heating of the air is important when the air conditioner is used as the heat pump to
heat the air. In the heat pump the air is heated by passing it over the condenser coil or the
heating coil that carry the high temperature refrigerant. In some cases the heating of air is
also done to suit different industrial and comfort air-conditioning applications where large air
conditioning systems are used.

Fig. 4.2 Sensible Heating Process on Psychrometric chart

In general the sensible heating process is carried out by passing the air over the heating coil.
This coil may be heated by passing the refrigerant, the hot water, the steam or by electric
resistance heating coil. The hot water and steam are used for the industrial applications.

Like the sensible cooling, the sensible heating process is also represented by a straight
horizontal line on the psychrometric chart. The line starts from the initial DB temperature of

29
air and ends at the final temperature extending towards the right (see the figure). The sensible
heating line is also the constant DP temperature line.

7. Description:
The air-conditioning test rig unit is required to conduct experiments and demonstrate the
processes of heating, cooling, heating and humidification, cooling and dehumidification,
cooling and humidification of atmospheric air. The unit consists of a compressor. Both
evaporator and the air cooled condenser are mounted on board with separate fans. Air is
sucked from the room and is supplied to the room after conducting the different processes.
The system is provided with voltmeter, ampere meter, digital temperature indicator, air
heater, steam generator. The unit will be fitted with all instrumentation facilities so that
temperature and pressure can be measured at different points in the air-conditioning system.
Steam generator is provided from which steam comes directly to the air inlet of air
conditioning which is required for humidification purpose. Heating coil is provided for
heating of air and cooling coil is provided for cooling and dehumidification of air. Suitable
valves and fittings are fitted in the pipe line of steam. Water level indicator is provided to safe
guard of heater.
8. Utilities Required:
1. Electricity Supply: Single Phase, 220 VAC, 50 Hz, 5-15 Amp. Combined socket with earth
connection.

2. Floor Area Required: 2 m x 1 m

9. Experimental Procedure:

Starting Procedure:
1. Switch ‘ON’ the main power supply.
2. Switch ‘ON’ the air heater.
3. After 10 minutes note down the temperature of ambient air by rotating sling psychomotor
and also of conditioned air by putting sling psychomotor in front of air duct. Repeat the
experiment till the temperature of outlet of air become constant.

Closing Procedure:
1. Switch OFF the heater.
2. Switch OFF the main power supply.

10. Observation & Calculations:


10.1 Data:
Cos Φ = 0.7
a = 1.21 Kg/m3

10.2 Observation Table:

Va= …………… m/sec

30
Sr.No. t min Tdi (C) Twi (C) Tdo (C) Two (C) V I

10.3 Calculations:

To calculate the specific humidity X1 and enthalpy of air h1 at temperature Tdi & Twi.
X 1  __________ (kg/kg of dry air)
h1 = (kJ/kg of dry air) [from psychrometric chart]

To calculate the specific humidity X2 and enthalpy of air h2 at temperature Tdo & Two
X 2  __________ (kg/kg of dry air)
h2 = (kJ/kg of dry air) [from psychrometric chart]

For Sensible Heating Process X1 = X2

Heat added to the air = Change in enthalpy of air


= h2 – h1
= (kJ/kg of dry air)

11. Precautions & Maintenance Instructions:


4. Operate the Valves gently.
5. Never run the apparatus if power supply is less than 180 volts and above 230 volts.
6. Duct should be free from dust particles.

12. Troubleshooting:
3. If electric panel is not showing the input on the mains light, check the main supply.
4. If voltmeter showing the voltage given to heater but ampere meter does not, check the
connection of heater in control panel.

13. Conclusion:

31
14. References:
5. Dossat, Roy J. (2004). Principles of Refrigeration. 4th Ed. ND: Pearson Education
Pvt. Ltd. pp 125-126.
6. Jordan, Richard C. & Priester, Gayle B. (1966). Refrigeration & Air Conditioning. 2nd
Ed. ND: Prientice-Hall of India Pvt. Ltd. pp 444-447,455-466.
7. S.C. Arora, S Domkundwar (1995). A Course In Refrigeration And Air Conditioning.
5th Ed. Dhanpat Rai & Sons pp 16.1-16.24.
8. Psychometric Chart.

32
33
5. TO CARRY OUT THE COOLING PROCESS OF FRESH AIR & FIND OUT
RELEVANT PARAMETERS ON AIR CONDITIONING TEST RIG AND TO
PLOT THE PROCESS ON PSYCHROMETRIC CHART

1. Objective:
To study the cooling of air in air conditioning test rig and perform experiment to calculate the
change in relevant parameter of air during cooling process.

2. Aim:
To measure dry bulb & wet bulb temperature of inlet and outlet air
Plot the process on Psychrometric chart
Calculate the heat rejected during cooling process.

3. Nomenclature:
Nom Column Heading Units Type
Cos Φ Power Factor Given
Cp Specific heat of water kJ/kgoC. Given
C.O.P.Th Theoretical Co-efficient of performance Calculated
RE Refrigeration Effect kJ/ kg Calculated
CW Compressor Work KJ/Kg Calculated
H1 Enthalpy of refrigeration effects at kJ/ kg Calculated
compressor inlet
H2 Enthalpy of compressor work at compressor kJ/ kg Calculated
outlet
H3 Enthalpy of sub cooling at the outlet of kJ/ kg Calculated
condenser
H4 Enthalpy of refrigerant inlet of evaporator kJ/ kg Calculated
P1 Pressure at compressor suction kg/cm2 Measured
P2 Pressure at compressor discharge kg/cm2 Measured
T1 Temperature at compressor suction C Measured
T2 Temperature at compressor discharge C Measured
T3 Temperature at condenser outlet C Measured
T4 Temperature at evaporator inlet C Measured
Tdi Dry Bulb Temperature of air at inlet of duct C Measured
Twi Wet Bulb Temperature of air at inlet of duct C Measured
Tdo Dry Bulb Temperature of air at outlet of duct C Measured
Two Wet Bulb Temperature of air at outlet of duct C Measured
ρa Density of air Kg/m3 Given
Va Velocity of air flowing through duct m/sec Measured
X1 Humidity at inlet of duct Kg/Kg of dry air Measured
X2 Humidity at outlet of duct Kg/Kg of dry air Measured
X Change in Specific Humidity Kg/Kg of dry air Calculated

34
h1 Enthalpy of air at inlet of duct KJ/Kg of dry air Calculated
h2 Enthalpy of air at outlet of duct KJ/Kg of dry air Calculated
V Voltmeter Reading Volts Measured
I Ampere meter reading Amp. Measured

4. Introduction:
Air conditioning means "preparing the air as per required conditions of temperature, humidity
and velocity. The conditions required are different for different applications, e.g. a small
room requires air at about 24 - 26 °C where humidity control is not so important, or a
building may be air conditioned for supplying air of 24 - 26°C temperature & 50-60 %
relative humidity. Measurement rooms in factories are to be maintained at the temperature of
-20 °C. So depending upon the requirement, the air conditioning system is designed. A
complete air conditioning system has the following jobs.
1. Filtration of air, where it contains dirt or dust particles.
2. Deodorization of air.
3. Cooling of air in summer.
4. Dehumidification of air by cooling coil itself and again heating it, as may be required in
humid areas in summer.
5. Heating of air in winter.
6. Humidifying and heating of air as may be required in winter.
7. Circulating the conditioned air through the space to be air conditioned.

An air conditioning system may be provided with some or all the units required to perform
the above jobs, which is determined by conditioning requirements and cost aspects. A
window type air conditioner provides some filtration and cooling of air. In large buildings,
cooling, heating and humidification systems may be used, along with partial recirculation of
exhaust air. This is done as it will require a huge capacity plant to condition the whole fresh
air entering the space to be conditioned. Thus some air from the exhausted air which is at a
temperature lower than the ambient temperature is mixed with the entering fresh air. Total
recirculation is generally avoided in large installations as the exhausted air contains odors.

The Air Conditioning Test Rig comprises of the following components.


1. A conditioning unit consisting of cooling coil, heaters and humidifier
2. Fan with circulating duct.
3. Control and measurement panel

5. Block Diagram:

35
Fig. 5.1 Line Diagram of Air Conditioning Apparatus

6. Theory:
Cooling of the air is one of the most common psychrometric processes in the air conditioning
systems. The basic function of the air-conditioners is to cool the air absorbed from the room
or the atmosphere, which is at higher temperatures. The sensible cooling of air is the process
in which only the sensible heat of the air is removed so as to reduce its temperature, and there
is no change in the moisture content (kg/kg of dry air) of the air. During sensible cooling
process the dry bulb (DB) temperature and wet bulb (WB) temperature of the air reduces,
while the latent heat of the air, and the dew point (DP) temperature of the air remains
constant. There is overall reduction in the enthalpy of the air.

In the ordinary window or the split air conditioner the cooling of air is carried out by passing
it over the evaporator coil, also called as the cooling coil. The room air or the atmospheric air
passes over this coil carrying the refrigerant at extremely low temperatures, and gets cooled
and passes to the space which is to be maintained at the comfort conditions.

In general the sensible cooling process is carried out by passing the air over the coil. In the
unitary air conditioners these coils are cooled by the refrigerant passing through them and are
called also called evaporator coils. In central air conditioners these coils are cooled by the
chilled water, which is chilled by its passage through the evaporator of the large air
conditioning system. In certain cases the coil is also cooled by the some gas passing inside it.

The sensible cooling process is represented by a straight horizontal line on the psychrometric
chart. The line starts from the initial DB temperature of the air and ends at the final DB
temperature of the air extending towards the left side from high temperature to the low
temperature (see the figure below). The sensible cooling line is also the constant DP

36
temperature line since the moisture content of the air remains constant. The initial and final
points on the psychrometric chart give all the properties of the air.

Fig. 5.2 Sensible Cooling Process on Psychrometric chart

7. Description:
The air-conditioning test rig unit is required to conduct experiments and demonstrate the
processes of heating, cooling, heating and humidification, cooling and dehumidification,
cooling and humidification of atmospheric air. The unit consists of a compressor. Both
evaporator and the air cooled condenser are mounted on board with separate fans. Air is
sucked from the room and is supplied to the room after conducting the different processes.
The system is provided with voltmeter, ampere meter, digital temperature indicator, air
heater, steam generator. The unit will be fitted with all instrumentation facilities so that
temperature and pressure can be measured at different points in the air-conditioning system.
Steam generator is provided from which steam comes directly to the air inlet of air
conditioning which is required for humidification purpose. Heating coil is provided for
heating of air and cooling coil is provided for cooling and dehumidification of air. Suitable
valves and fittings are fitted in the pipe line of steam. Water level indicator is provided to safe
guard of heater.

8. Utilities Required:
1. Electricity Supply: Single Phase, 220 VAC, 50 Hz, 5-15 Amp. Combined socket with earth
connection.

2. Floor Area Required: 2 m x 1 m


37
9. Experimental Procedure:

Starting Procedure:
8. Switch ‘ON’ the compressor.
9. Wait for 2-3 minutes for switch ‘ON’ the compressor.
10. Open the valves of pressure gauges.
11. After 10 minutes note down the reading of temperature sensor.
12. Note down the reading of pressure gauges.
13. Note down the reading of temperature and pressure after every 10 minutes till the
temperature of outlet of air come constant.

Closing Procedure:
3. Switch off the compressor.
4. Switch off the mains power supply.

10. Observation & Calculations:


10.1 Data:
Cos Φ = 0.7
a = 1.21 Kg/m3

10.2 Observation Table:

Va= …………… m/sec


Sr.No. t P1 P2 T1 T2 T3 T4 Tdi Twi Tdo Two V I
min Bar Bar (C) (C) (C) (C) (C) (C) (C) (C)

10.3 Calculations:

To Calculate COP of the System:


H1  (0.011 T1  1.98) P1  (0.652 T1 )  415.723
H 2  (0.011 T2  1.98) P2  (0.652 T2 )  415.723
H 3  1.228 T3  199.93
H1  H 4
C.O.PTh   H3  H4
H 2  H1
V  I  Cos
CW  KJ/sec
1000
To calculate the specific humidity X1 and enthalpy of air H1 at temperature Tdi & Twi.
X 1  __________ (kg/kg of dry air)
H1 = (kJ/kg of dry air) [from psychrometric chart]

38
To calculate the specific humidity X2 and enthalpy of air H2 at temperature Tdo & Two
X 2  __________ (kg/kg of dry air)
H2 = (kJ/kg of dry air) [from psychrometric chart]

For Sensible Cooling Process X1 = X2

Heat rejected from the air = Change in enthalpy of air


R.E. = h1 – h2
= (kJ/kg of dry air)

11. Precautions & Maintenance Instructions:


7. Operate the Valves gently.
8. Never run the apparatus if power supply is less than 180 volts and above 230 volts.
9. Duct should be free from dust particles.

12. Troubleshooting:
5. If electric panel is not showing the input on the mains light, check the main supply.
6. If voltmeter showing the voltage given to heater but ampere meter does not, check the
connection of heater in control panel.

13. Conclusion:

14. References:
9. Dossat, Roy J. (2004). Principles of Refrigeration. 4th Ed. ND: Pearson Education
Pvt. Ltd. pp 125-126.
10. Jordan, Richard C. & Priester, Gayle B. (1966). Refrigeration & Air Conditioning. 2nd
Ed. ND: Prientice-Hall of India Pvt. Ltd. pp 444-447,455-466.
11. S.C. Arora, S Domkundwar (1995). A Course In Refrigeration And Air Conditioning.
5th Ed. Dhanpat Rai & Sons pp 16.1-16.24.
12. Psychometric Chart.

39
40
6. TO CARRY OUT THE HEATING AND HUMIDIFICATION PROCESS OF
FRESH AIR & FIND OUT RELEVANT PARAMETERS ON AIR
CONDITIONING TEST RIG AND TO PLOT THE PROCESS ON
PSYCHROMETRIC CHART

1. Objective:
To study the heating and humidification process of air in air conditioning test rig and perform
experiment to calculate the change in relevant parameter of air during process.

2. Aim:
To measure dry bulb & wet bulb temperature of inlet and outlet air
Plot the process on Psychrometric chart
Calculate the heat supplied during heating process
Calculate the amount of water vapour add during the process

3. Nomenclature:
Nom Column Heading Units Type
Tdi Dry Bulb Temperature of air at inlet of duct C Measured
Twi Wet Bulb Temperature of air at inlet of duct C Measured
Tdo Dry Bulb Temperature of air at outlet of duct C Measured
Two Wet Bulb Temperature of air at outlet of duct C Measured
ρa Density of air Kg/m3 Given
Va Velocity of air flowing through duct m/sec Measured
X1 Humidity at inlet of duct Kg/Kg of dry air Measured
X2 Humidity at outlet of duct Kg/Kg of dry air Measured
X Change in Specific Humidity Kg/Kg of dry air Calculated
h1 Enthalpy of air at inlet of duct KJ/Kg of dry air Calculated
h2 Enthalpy of air at outlet of duct KJ/Kg of dry air Calculated
V Voltmeter Reading Volts Measured
I Ampere meter reading Amp. Measured

4. Introduction:
Air conditioning means "preparing the air as per required conditions of temperature, humidity
and velocity. The conditions required are different for different applications, e.g. a small
room requires air at about 24 - 26 °C where humidity control is not so important, or a
building may be air conditioned for supplying air of 24 - 26°C temperature & 50-60 %
relative humidity. Measurement rooms in factories are to be maintained at the temperature of
-20 °C. So depending upon the requirement, the air conditioning system is designed. A
complete air conditioning system has the following jobs.
1. Filtration of air, where it contains dirt or dust particles.
2. Deodorization of air.
3. Cooling of air in summer.

41
4. Dehumidification of air by cooling coil itself and again heating it, as may be required in
humid areas in summer.
5. Heating of air in winter.
6. Humidifying and heating of air as may be required in winter.
7. Circulating the conditioned air through the space to be air conditioned.

An air conditioning system may be provided with some or all the units required to perform
the above jobs, which is determined by conditioning requirements and cost aspects. A
window type air conditioner provides some filtration and cooling of air. In large buildings,
cooling, heating and humidification systems may be used, along with partial recirculation of
exhaust air. This is done as it will require a huge capacity plant to condition the whole fresh
air entering the space to be conditioned. Thus some air from the exhausted air which is at a
temperature lower than the ambient temperature is mixed with the entering fresh air. Total
recirculation is generally avoided in large installations as the exhausted air contains odors.

The Air Conditioning Test Rig comprises of the following components.


1. A conditioning unit consisting of cooling coil, heaters and humidifier
2. Fan with circulating duct.
3. Control and measurement panel

5. Block Diagram:

Fig. 6.1 Line Diagram of Air Conditioning Apparatus


6. Theory:
In heating and humidification psychrometric process of the air, the dry bulb temperature as
well as the humidity of the air increases. The heating and humidification process is carried
out by passing the air over spray of water, which is maintained at temperature higher than the
dry bulb temperature of air or by mixing air and the steam.
42
When the ordinary air is passed over the spray of water maintained at temperature higher than
the dry bulb temperature of the air, the moisture particles from the spray tend to get
evaporated and get absorbed in the air due to which the moisture content of the air increase.
At the same time, since the temperature of the moisture is greater than the dry bulb
temperature of the air, there is overall increase in its temperature.

During heating and humidification process the dry bulb, wet bulb, and dew point temperature
of the air increases along with its relative humidity. The heating and humidification process is
represented on the psychrometric chart by an angular line that starts from the given value of
the dry bulb temperature and extends upwards towards right (see the Fig. 7.2 below).

Fig. 6.2 Heating and Humidification Process on Psychrometric chart

7. Description:
The air-conditioning test rig unit is required to conduct experiments and demonstrate the
processes of heating, cooling, heating and humidification, cooling and dehumidification,
cooling and humidification of atmospheric air. The unit consists of a compressor. Both
evaporator and the air cooled condenser are mounted on board with separate fans. Air is
sucked from the room and is supplied to the room after conducting the different processes.
The system is provided with voltmeter, ampere meter, digital temperature indicator, air
heater, steam generator. The unit will be fitted with all instrumentation facilities so that
temperature and pressure can be measured at different points in the air-conditioning system.

43
Steam generator is provided from which steam comes directly to the air inlet of air
conditioning which is required for humidification purpose. Heating coil is provided for
heating of air and cooling coil is provided for cooling and dehumidification of air. Suitable
valves and fittings are fitted in the pipe line of steam. Water level indicator is provided to safe
guard of heater.
8. Utilities Required:
1. Electricity Supply: Single Phase, 220 VAC, 50 Hz, 5-15 Amp. Combined socket with earth
connection.

2. Floor Area Required: 2 m x 1 m

9. Experimental Procedure:

Starting Procedure:
4. Switch ‘ON’ the main power supply.
5. Switch ‘ON’ the air heater.
6. Allow steam to pass through the pipe and slowly open the wet steam vent valve to release
wet steam from the pipe.
7. Close the wet steam vent valve.
8. Rotate psychrometer and note down the ambient temperature of air.
9. After 10 minutes note down the temperature of air by putting sling psychrometrer in front
of air duct.
10. Note down the reading of pressure gauges and temperature sensors.
11. Repeat the experiment till the temperature of outlet of air become constant

Closing Procedure:
3. Switch OFF the heater.
4. Stop steam supply by closing the steam valve.
5. Switch OFF the main power supply.

10. Observation & Calculations:


10.1 Data:
Cos Φ = 0.7
a = 1.21 Kg/m3

10.2 Observation Table:

Va= …………… m/sec

Sr.No. t Tdi (C) Twi (C) Tdo (C) Two (C) V I


(min)

44
10.3 Calculations:

To calculate the specific humidity X1 and enthalpy of air h1 at temperature Tdi & Twi.
X 1  __________ (kg/kg of dry air)
h1 = (kJ/kg of dry air) [from psychrometric chart]

To calculate the specific humidity X2 and enthalpy of air h2 at temperature Tdo & Two
X 2  __________ (kg/kg of dry air)
h2 = (kJ/kg of dry air) [from psychrometric chart]

Amount of water vapour added to air = X  X 2  X 1


= (kg/kg of dry air)

Heat added to the air = Change in enthalpy of air


= h2 – h1
= (kJ/kg of dry air)

11. Precautions & Maintenance Instructions:


10. Operate the Valves gently.
11. Never run the apparatus if power supply is less than 180 volts and above 230 volts.
12. Duct should be free from dust particles.

12. Troubleshooting:
7. If electric panel is not showing the input on the mains light, check the main supply.
8. If voltmeter showing the voltage given to heater but ampere meter does not, check the
connection of heater in control panel.

13. Conclusion:

14. References:
13. Dossat, Roy J. (2004). Principles of Refrigeration. 4th Ed. ND: Pearson Education
Pvt. Ltd. pp 125-126.
14. Jordan, Richard C. & Priester, Gayle B. (1966). Refrigeration & Air Conditioning. 2nd
Ed. ND: Prientice-Hall of India Pvt. Ltd. pp 444-447,455-466.

45
15. S.C. Arora, S Domkundwar (1995). A Course In Refrigeration And Air Conditioning.
5th Ed. Dhanpat Rai & Sons pp 16.1-16.24.
16. Psychometric Chart.

46
47
7. TO CARRY OUT THE COOLING AND HUMIDIFICATION PROCESS OF
FRESH AIR & FIND OUT RELEVANT PARAMETERS ON AIR
CONDITIONING TEST RIG AND TO PLOT THE PROCESS ON
PSYCHROMETRIC CHART

1. Objective:
To study the cooling and humidification process of air in air conditioning test rig and perform
experiment to calculate the change in relevant parameter of air during process.

2. Aim:
To measure dry bulb & wet bulb temperature of inlet and outlet air
Plot the process on Psychrometric chart
Calculate the heat rejected during process
Calculate the amount of water vapour add during the process

3. Nomenclature:
Nom Column Heading Units Type
Cos Φ Power Factor Given
Cp Specific heat of water kJ/kgoC. Given
C.O.P.Th Theoretical Co-efficient of performance Calculated
RE Refrigeration Effect kJ/ kg Calculated
CW Compressor Work KJ/Kg Calculated
H1 Enthalpy of refrigeration effects at kJ/ kg Calculated
compressor inlet
H2 Enthalpy of compressor work at compressor kJ/ kg Calculated
outlet
H3 Enthalpy of sub cooling at the outlet of kJ/ kg Calculated
condenser
H4 Enthalpy of refrigerant inlet of evaporator kJ/ kg Calculated
P1 Pressure at compressor suction kg/cm2 Measured
P2 Pressure at compressor discharge kg/cm2 Measured
T1 Temperature at compressor suction C Measured
T2 Temperature at compressor discharge C Measured
T3 Temperature at condenser outlet C Measured
T4 Temperature at evaporator inlet C Measured
Tdi Dry Bulb Temperature of air at inlet of duct C Measured
Twi Wet Bulb Temperature of air at inlet of duct C Measured
Tdo Dry Bulb Temperature of air at outlet of duct C Measured
Two Wet Bulb Temperature of air at outlet of duct C Measured
ρa Density of air Kg/m3 Given
Va Velocity of air flowing through duct m/sec Measured
X1 Humidity at inlet of duct Kg/Kg of dry air Measured

48
X2 Humidity at outlet of duct Kg/Kg of dry air Measured
X Change in Specific Humidity Kg/Kg of dry air Calculated
h1 Enthalpy of air at inlet of duct KJ/Kg of dry air Calculated
h2 Enthalpy of air at outlet of duct KJ/Kg of dry air Calculated
V Voltmeter Reading Volts Measured
I Ampere meter reading Amp. Measured

4. Introduction:
Air conditioning means "preparing the air as per required conditions of temperature, humidity
and velocity. The conditions required are different for different applications, e.g. a small
room requires air at about 24 - 26 °C where humidity control is not so important, or a
building may be air conditioned for supplying air of 24 - 26°C temperature & 50-60 %
relative humidity. Measurement rooms in factories are to be maintained at the temperature of
-20 °C. So depending upon the requirement, the air conditioning system is designed. A
complete air conditioning system has the following jobs.
1. Filtration of air, where it contains dirt or dust particles.
2. Deodorization of air.
3. Cooling of air in summer.
4. Dehumidification of air by cooling coil itself and again heating it, as may be required in
humid areas in summer.
5. Heating of air in winter.
6. Humidifying and heating of air as may be required in winter.
7. Circulating the conditioned air through the space to be air conditioned.

An air conditioning system may be provided with some or all the units required to perform
the above jobs, which is determined by conditioning requirements and cost aspects. A
window type air conditioner provides some filtration and cooling of air. In large buildings,
cooling, heating and humidification systems may be used, along with partial recirculation of
exhaust air. This is done as it will require a huge capacity plant to condition the whole fresh
air entering the space to be conditioned. Thus some air from the exhausted air which is at a
temperature lower than the ambient temperature is mixed with the entering fresh air. Total
recirculation is generally avoided in large installations as the exhausted air contains odors.

The Air Conditioning Test Rig comprises of the following components.


1. A conditioning unit consisting of cooling coil, heaters and humidifier
2. Fan with circulating duct.
3. Control and measurement panel

5. Block Diagram:

49
Fig. 7.1 Line Diagram of Air Conditioning Apparatus

6. Theory:
Cooling and humidification process is one of the most commonly used air conditioning
application for the cooling purposes. In this process the moisture is added to the air by
passing it over the stream or spray of water which is at temperature lower than the dry bulb
temperature of the air. When the ordinary air passes over the stream of water, the particles of
water present within the stream tend to get evaporated by giving up the heat to the stream.
The evaporated water is absorbed by the air so its moisture content, thus the humidity
increases. At the same time, since the temperature of the absorbed moisture is less than the
DB bulb temperature of the air, there is reduction in the overall temperature of the air. Since
the heat is released in the stream or spray of water, its temperature increases.

One of the most popular applications of cooling and humidification is the evaporative cooler,
also called as the desert cooler. The evaporative cooler is the sort of big box inside which is a
small water tank, small water pump and the fan. The water from the tank is circulated by the
pump and is also sprayed inside the box. The fan blows strong currents of air over the water
sprays, thus cooling the air and humidifying it simultaneously. The evaporative cooler is
highly effective cooling devise having very low initial and running cost compared to the
unitary air conditioners. For cooling purposes, the cooling and humidification process can be
used only in dry and hot climates like desert areas, countries like India, China, Africa etc.
This cooling process cannot be used in hot and high humidity climates.

The cooling and humidification process is also used in various industries like textile, where
certain level of temperature and moisture content has to be maintained. In such cases large
quantity of water is sprayed, and large blowers are used to blow the air over the spray of
water.

50
During the cooling and humidification process the dry bulb of the air reduces, its wet bulb
and the dew point temperature increases, while its moisture content and thus the relative
humidity also increases. Also, the sensible heat of the air reduces, while the latent heat of the
air increases resulting in the overall increase in the enthalpy of the air.

Cooling and humidification process is represented by an angular line on the psychrometric


chart starting from the given value of the dry bulb temperature and the relative humidity and
extending upwards toward left.

Fig. 7.2 Cooling and Humidification Process on Psychrometric chart

7. Description:
The air-conditioning test rig unit is required to conduct experiments and demonstrate the
processes of heating, cooling, heating and humidification, cooling and dehumidification,
cooling and humidification of atmospheric air. The unit consists of a compressor. Both
evaporator and the air cooled condenser are mounted on board with separate fans. Air is
sucked from the room and is supplied to the room after conducting the different processes.
The system is provided with voltmeter, ampere meter, digital temperature indicator, air
heater, steam generator. The unit will be fitted with all instrumentation facilities so that
temperature and pressure can be measured at different points in the air-conditioning system.
Steam generator is provided from which steam comes directly to the air inlet of air
conditioning which is required for humidification purpose. Heating coil is provided for
heating of air and cooling coil is provided for cooling and dehumidification of air. Suitable
valves and fittings are fitted in the pipe line of steam. Water level indicator is provided to safe
guard of heater.
51
8. Utilities Required:
1. Electricity Supply: Single Phase, 220 VAC, 50 Hz, 5-15 Amp. Combined socket with earth
connection.

2. Floor Area Required: 2 m x 1 m

9. Experimental Procedure:

Starting Procedure:
12. Switch ‘ON’ the main power supply.
13. Switch ‘ON’ the compressor.
14. Wait for 2-3 minutes for switch ‘ON’ the compressor.
15. Open the valves of pressure gauges.
16. Allow steam to pass through the pipe and slowly open the wet steam vent valve to release
wet steam from the pipe.
17. Close the wet steam vent valve.
18. Rotate psychrometer and note down the ambient temperature of air.
19. After 10 minutes note down the temperature of air by putting sling psychrometrer in front
of air duct.
20. Note down the reading of pressure gauges and temperature sensors.
21. Repeat the experiment till the temperature of outlet of air become constant.

Closing Procedure:
6. Switch OFF the compressor.
7. Stop steam supply by closing the steam valve.
8. Switch OFF the main power supply.

10. Observation & Calculations:


10.1 Data:
Cos Φ = 0.7
a = 1.21 Kg/m3

10.2 Observation Table:

Va= …………… m/sec


52
Sr.No. t P1 P2 T1 T2 T3 T4 Tdi Twi Tdo Two V I
(min) Bar Bar (C) (C) (C) (C) (C) (C) (C) (C)

10.3 Calculations:

To Calculate COP of the System:


H1  (0.011 T1  1.98) P1  (0.652 T1 )  415.723
H 2  (0.011 T2  1.98) P2  (0.652 T2 )  415.723
H 3  1.228 T3  199.93
H1  H 4
C.O.PTh   H3  H4
H 2  H1
V  I  Cos
CW  KJ/sec
1000

To calculate the specific humidity X1 and enthalpy of air h1 at temperature Tdi & Twi.
X 1  __________ (kg/kg of dry air)
h1 = (kJ/kg of dry air) [from psychrometric chart]

To calculate the specific humidity X2 and enthalpy of air h2 at temperature Tdo & Two
X 2  __________ (kg/kg of dry air)
h2 = (kJ/kg of dry air) [from psychrometric chart]

Amount of water vapour added to air = X  X 2  X 1


= (kg/kg of dry air)

Heat rejected from the air = Change in enthalpy of air


R.E. = ∆h
= (kJ/kg of dry air)

11. Precautions & Maintenance Instructions:


13. Operate the Valves gently.
14. Never run the apparatus if power supply is less than 180 volts and above 230 volts.
15. Duct should be free from dust particles.

12. Troubleshooting:
9. If electric panel is not showing the input on the mains light, check the main supply.
10. If voltmeter showing the voltage given to heater but ampere meter does not, check the
connection of heater in control panel.

53
13. Conclusion:

14. References:
17. Dossat, Roy J. (2004). Principles of Refrigeration. 4th Ed. ND: Pearson Education
Pvt. Ltd. pp 125-126.
18. Jordan, Richard C. & Priester, Gayle B. (1966). Refrigeration & Air Conditioning. 2nd
Ed. ND: Prientice-Hall of India Pvt. Ltd. pp 444-447,455-466.
19. S.C. Arora, S Domkundwar (1995). A Course In Refrigeration And Air Conditioning.
5th Ed. Dhanpat Rai & Sons pp 16.1-16.24.
20. Psychometric Chart.

54
55
8. TO CARRY OUT THE COOLING AND DEHUMIDIFICATION PROCESS OF
FRESH AIR & FIND OUT RELEVANT PARAMETERS ON AIR
CONDITIONING TEST RIG AND TO PLOT THE PROCESS ON
PSYCHROMETRIC CHART

1. Objective:
To study the cooling and dehumidification process of air in air conditioning test rig and
perform experiment to calculate the change in relevant parameter of air during process.

2. Aim:
To measure dry bulb & wet bulb temperature of inlet and outlet air
Plot the process on Psychrometric chart
Calculate the heat rejected during process
Calculate the amount of water vapour removed during the process

3. Nomenclature:
Nom Column Heading Units Type
Cos Φ Power Factor Given
Cp Specific heat of water kJ/kgoC. Given
C.O.P.Th Theoretical Co-efficient of performance Calculated
RE Refrigeration Effect kJ/ kg Calculated
CW Compressor Work KJ/Kg Calculated
H1 Enthalpy of refrigeration effects at kJ/ kg Calculated
compressor inlet
H2 Enthalpy of compressor work at compressor kJ/ kg Calculated
outlet
H3 Enthalpy of sub cooling at the outlet of kJ/ kg Calculated
condenser
H4 Enthalpy of refrigerant inlet of evaporator kJ/ kg Calculated
P1 Pressure at compressor suction kg/cm2 Measured
P2 Pressure at compressor discharge kg/cm2 Measured
T1 Temperature at compressor suction C Measured
T2 Temperature at compressor discharge C Measured
T3 Temperature at condenser outlet C Measured
T4 Temperature at evaporator inlet C Measured
Tdi Dry Bulb Temperature of air at inlet of duct C Measured
Twi Wet Bulb Temperature of air at inlet of duct C Measured
Tdo Dry Bulb Temperature of air at outlet of duct C Measured
Two Wet Bulb Temperature of air at outlet of duct C Measured
ρa Density of air Kg/m3 Given
Va Velocity of air flowing through duct m/sec Measured
X1 Humidity at inlet of duct Kg/Kg of dry air Measured

56
X2 Humidity at outlet of duct Kg/Kg of dry air Measured
X Change in Specific Humidity Kg/Kg of dry air Calculated
h1 Enthalpy of air at inlet of duct KJ/Kg of dry air Calculated
h2 Enthalpy of air at outlet of duct KJ/Kg of dry air Calculated
V Voltmeter Reading Volts Measured
I Ampere meter reading Amp. Measured

4. Introduction:
Air conditioning means "preparing the air as per required conditions of temperature, humidity
and velocity. The conditions required are different for different applications, e.g. a small
room requires air at about 24 - 26 °C where humidity control is not so important, or a
building may be air conditioned for supplying air of 24 - 26°C temperature & 50-60 %
relative humidity. Measurement rooms in factories are to be maintained at the temperature of
-20 °C. So depending upon the requirement, the air conditioning system is designed. A
complete air conditioning system has the following jobs.
1. Filtration of air, where it contains dirt or dust particles.
2. Deodorization of air.
3. Cooling of air in summer.
4. Dehumidification of air by cooling coil itself and again heating it, as may be required in
humid areas in summer.
5. Heating of air in winter.
6. Humidifying and heating of air as may be required in winter.
7. Circulating the conditioned air through the space to be air conditioned.

An air conditioning system may be provided with some or all the units required to perform
the above jobs, which is determined by conditioning requirements and cost aspects. A
window type air conditioner provides some filtration and cooling of air. In large buildings,
cooling, heating and humidification systems may be used, along with partial recirculation of
exhaust air. This is done as it will require a huge capacity plant to condition the whole fresh
air entering the space to be conditioned. Thus some air from the exhausted air which is at a
temperature lower than the ambient temperature is mixed with the entering fresh air. Total
recirculation is generally avoided in large installations as the exhausted air contains odors.

The Air Conditioning Test Rig comprises of the following components.


1. A conditioning unit consisting of cooling coil, heaters and humidifier
2. Fan with circulating duct.
3. Control and measurement panel

5. Block Diagram:

57
Fig. 8.1 Line Diagram of Air Conditioning Apparatus

6. Theory:
The process in which the air is cooled sensibly and at the same time the moisture is removed
from it is called as cooling and dehumidification process. Cooling and dehumidification
process is obtained when the air at the given dry bulb and dew point (DP) temperature is
cooled below the dew point temperature.

Let us understand the cooling and dehumidification process in more details. When the air
comes in contact with the cooling coil that is maintained at the temperature below its dew
point temperature, its DB temperature starts reducing. The process of cooling continues and
at some point it reaches the value of dew point temperature of the air. At this point the water
vapor within the air starts getting converted into the dew particles due to which the dew is
formed on the surface of the cooling and the moisture content of the air reduces thereby
reducing its humidity level. Thus when the air is cooled below its dew point temperature,
there is cooling as well as dehumidification of air.

The cooling and dehumidification process is most widely used air conditioning application. It
is used in all types of window, split, packaged and central air conditioning systems for
producing the comfort conditions inside the space to be cooled. In the window and split air
conditioners the evaporator coil or cooling coil is maintained at temperature lower than the
dew point temperature of the room air or the atmospheric air by the cool refrigerant passing
through it. When the room air passes over this coil its DB temperature reduces and at the
same time moisture is also removed since the air is cooled below its DP temperature. The
dew formed on the cooling coil is removed out by small tubing. In the central air conditioning
systems the cooling coil is cooled by the refrigerant or the chilled water. When the room air
passes over this coil, it gets cooled and dehumidified.

58
In the general the cooling and dehumidification process is obtained by passing the air over
coil through which the cool refrigerant, chilled water or cooled gas is passed.

During the cooling and dehumidification process the dry bulb, wet bulb and the dew point
temperature of air reduces. Similarly, the sensible heat and the latent heat of the air also
reduce leading to overall reduction in the enthalpy of the air. The cooling and
dehumidification process is represented by a straight angular line on the psychrometric chart.
The line starts from the given value of the DB temperature and extends downwards towards
left.

Fig. 8.2 Cooling and Dehumidification Process on Psychrometric chart

7. Description:
The air-conditioning test rig unit is required to conduct experiments and demonstrate the
processes of heating, cooling, heating and humidification, cooling and dehumidification,
cooling and humidification of atmospheric air. The unit consists of a compressor. Both
evaporator and the air cooled condenser are mounted on board with separate fans. Air is
sucked from the room and is supplied to the room after conducting the different processes.
The system is provided with voltmeter, ampere meter, digital temperature indicator, air
heater, steam generator. The unit will be fitted with all instrumentation facilities so that
temperature and pressure can be measured at different points in the air-conditioning system.
Steam generator is provided from which steam comes directly to the air inlet of air
conditioning which is required for humidification purpose. Heating coil is provided for
heating of air and cooling coil is provided for cooling and dehumidification of air. Suitable

59
valves and fittings are fitted in the pipe line of steam. Water level indicator is provided to safe
guard of heater.
8. Utilities Required:
1. Electricity Supply: Single Phase, 220 VAC, 50 Hz, 5-15 Amp. Combined socket with earth
connection.

2. Floor Area Required: 2 m x 1 m

9. Experimental Procedure:

Starting Procedure:
22. Close valves below the pressure gauges
23. Open the funnel and air vent valve of steam generator.
24. Fill water in the steam generator upto 3/4th of its capacity by observing the level of water
in level indicator.
25. Switch ‘ON’ the main power supply.
26. Switch ‘ON’ the heater of steam generator and set the temperature of steam with the help
of DTC (100-120 oC). And wait until steam temperature reaches to desired value.
27. Switch ‘ON’ the compressor.
28. Wait for 2-3 minutes for switch ‘ON’ the compressor.
29. Open the valves of pressure gauges.
30. Allow steam to pass through the pipe and slowly open the wet steam vent valve to release
wet steam from the pipe.
31. Close the wet steam vent valve.
32. Switch ‘ON’ the air heater.
33. Rotate psychrometer and note down the ambient temperature of air.
34. After 10 minutes note down the temperature of air by putting sling psychrometrer in front
of air duct.
35. Note down the reading of pressure gauges and temperature sensors.
36. Repeat the experiment till the temperature of outlet of air become constant.

Closing Procedure:
9. Switch OFF the compressor.
10. Stop steam supply by closing the steam valve.
11. Switch OFF the air heater.
12. Switch OFF the main power supply.

10. Observation & Calculations:


10.1 Data:
Cos Φ = 0.7
a = 1.21 Kg/m3

10.2 Observation Table:


60
Va= …………… m/sec
Sr.No. t P1 P2 T1 T2 T3 T4 Tdi Twi Tdo Two V I
(min) Bar Bar (C) (C) (C) (C) (C) (C) (C) (C)

10.3 Calculations:

To Calculate COP of the System:


H1  (0.011 T1  1.98) P1  (0.652 T1 )  415.723
H 2  (0.011 T2  1.98) P2  (0.652 T2 )  415.723
H 3  1.228 T3  199.93
H1  H 4
C.O.PTh   H3  H4
H 2  H1
V  I  Cos
CW  KJ/sec
1000

To calculate the specific humidity X1 and enthalpy of air h1 at temperature Tdi & Twi.
X 1  __________ (kg/kg of dry air)
h1 = (kJ/kg of dry air) [from psychrometric chart]

To calculate the specific humidity X2 and enthalpy of air h2 at temperature Tdo & Two
X 2  __________ (kg/kg of dry air)
h2 = (kJ/kg of dry air) [from psychrometric chart]

Amount of water vapour removed from air = X  X 1  X 2


= (kg/kg of dry air)

Heat rejected from the air = Change in enthalpy of air


= h1 - h2
= (kJ/kg of dry air)

11. Precautions & Maintenance Instructions:


16. Operate the Valves gently.
17. Never run the apparatus if power supply is less than 180 volts and above 230 volts.
18. Duct should be free from dust particles.

12. Troubleshooting:
11. If electric panel is not showing the input on the mains light, check the main supply.
12. If voltmeter showing the voltage given to heater but ampere meter does not, check the
connection of heater in control panel.

61
13. Conclusion:

14. References:
21. Dossat, Roy J. (2004). Principles of Refrigeration. 4th Ed. ND: Pearson Education
Pvt. Ltd. pp 125-126.
22. Jordan, Richard C. & Priester, Gayle B. (1966). Refrigeration & Air Conditioning. 2nd
Ed. ND: Prientice-Hall of India Pvt. Ltd. pp 444-447,455-466.
23. S.C. Arora, S Domkundwar (1995). A Course In Refrigeration And Air Conditioning.
5th Ed. Dhanpat Rai & Sons pp 16.1-16.24.
24. Psychometric Chart.

62

Potrebbero piacerti anche