■OCGH   Caluculation for the capacity of Japanese SPA machines

1.  Circulation filtration System
1. 1  Water Volume of Indoor Bath and Outdoor Bath
Water Volume of Indoor Bath (Vi): 10.8m2 x 0.3m(H) + 9.45m2 x 0.3m(H) = 6.08 [m3]
Water Volume of Outdoor Bath (Vo): 8.4m2 x 0.3m(H) + 6.75m2 x 0.3m(H) = 4.55 [m3]

1. 2  Capacity of Sand Filter and Filter Pump
Number of Passage (Nb): 3 [times/h]
Filter Passage Velocity: 40 [m/h]

Capacity of Sand Filter for Indoor Bath: Nb × Vi = 3 × 6.08  = 18.2 [m3/h]   ≒ 304 [L/min]


Capacity of Sand Filter for Outdoor Bath: Nb × Vi = 3 × 4.55  = 13.6 [m3/h]   ≒ 228 [L/min]

Capacity of  Filter Pump for Indoor Bath : 304 [L/min] Automatically Alternate


Capacity of  Filter Pump for Outdoor Bath : 228 [L/min] Automatically Alternate

1. 3  Capacity of Heat Pump ■Legend

① Heating Load Calculation v: Air Vellocity at the surface of Bath ⇒ 0.5 [m/s] (Indoor)   /  3.0 [m/s] (Outdoor)

(a) Heat Loss by evaporation from the water surface of bath Pw: Saturated vapor pressure of saturated air temperature which is equal to water temperature

Indoor:qe = (0.114・v + 0.134)(Pw‐Pa)Asi・0.2778・r =        6,663.2 [W] ⇒ 7.37 [kPa]

Outdoor:qe = (0.061・v+0.125)(Pw‐Pa)Aso・0.2778・r  =        9,452.9 [W] Pa: Vapor pressure of air  ⇒ 2.535 [kPa] (Indoor)    / 1.901 [kPa] (Outdoor)

(b) Heat Loss by heat transfer at the water surface of bath Asi: Bath surface Area (Indoor Bath) ⇒ 10.8 [m2]

 Indoor:qt = Va(tw‐ta)Asi =        1,458.0 [W] Aso: Bath surface Area (Outdoor Bath) ⇒ 8.4 [m2]

 Outdoor:qt = Va(tw‐ta)Aso =        4,410.0 [W] r: Latent heat of vaporiza on of Saturated vapor which is equal to water temperature   ⇒ 2404.9 [kJ/kg]

(c) Heat Loss by heat transfer at wall and floor of bath Va: Heat transfer rate at the surface of water   ⇒   9 [W/(m2・℃)](Indoor)   /   35 [W/(m2・℃)](Outdoor)

 Indoor:qs = Kw(tw‐ta)Aw = 286.2 [W] tw: Bath Water Temperature ⇒ 40 [℃]

 Outdoor:qs = Kw(tw‐ta)Aw = 231.3 [W] ta: Air Temperature in Bathroom  ⇒ 25 [℃]

(d) Heat Loss by pipe, valve and machine:qs = qp1 + qp2 qp1 = 0.41*(tw‐ta)*L tc: Cold Water Temperature ⇒ 23 [℃]

 Indoor:qp1 + qp2 =         2,706.7 [W] qp2 = 0.3(qe+qt+qs) Kw: Thermal transmittance of wall and floor of bath ⇒ 1.0 [W/(m2・℃)]

 Outdoor:qp1 + qp2 =        4,412.8 [W] Aw: Wall and Floor Area of Bath ⇒ 13.26 [m2]

(e) Heat Loss by people L: Pipe Length ⇒ 30 [m]

 Indoor:qh = 0.1(qe+qt+qs)  = 840.7 [W] <Subtotal Load> <Total Load>


 Outdoor:qh = 0.1(qe+qt+qs)  =        1,409.4 [W] Indoor:     11,954.9 [W]
    31,871.3 [W]
Outdoor:     19,916.4 [W]

② Capacity of Heat Pump: Total Load × 1.1  =          35,058 [W] ⇒ 36.0 [kW] (shared by Indoor and Outdoor)

1. 4  Capacity of Heat Exchanger
Capacity of Heat Excenger for Indoor Bath:             36.0 [kW] ×     11,954.9 /     31,871.3 =           13.50 [kW] ⇒              14.0 [kW]
Capacity of Heat Excenger for Outdoor Bath:             36.0 [kW] ×     19,916.4 /     31,871.3 =           22.50 [kW] ⇒              23.0 [kW]

1. 5  Capacity of Bath Heating Primary Pump
0.86 × Total Load / 60 / Δt  ≒ 101 [ltr/min] ⇒ 101 [ltr/min] Automatically Alternate

ΔT: Temperature difference between going and returning water ⇒ 5 [℃] (45℃ - 40℃)

Page 1 of 2
2.  Makeup Water & Shower System
2. 1  Heating Load and Capacity of Heat Pump
① Hot Water Consumption (60℃)
(a) Shower
Nos. of Shower: 8
Hot water Consumption by shower: 15 [L/(min・1 shower)] 1,800 [L/h]
Simultaneous Usage Factor: 0.25

(b) Make‐up Water for Bath Overflow      2,823.75 [L/h]


Daily Maximum Number of Bathing People: Nos. of Locker(=15) × 6.5 = 97.5 [person]
Hourly Maximum Number of Bathing People: 97.5 [person]  ×   15% = 14.6 [person/h] Indoor: 586 [L/h]
Makeup Water Volume: 14.6 [person/h]  ×  70[L/person] =           1,024 [L/h] Outdoor: 438 [L/h]

Regarding the above, the rate of Hot Water: 46 [%] ※ (60℃ × A% + 23℃ × (100 ‐ A)%) ÷ 100 = 40℃


⇒ A ≒ 46.0 [%]

Hot Water Consumption:           2,824 [L/h]× 46 [%] ≒           1,299 [L/h]

Total Load:           1,299 [L/h]  × (th ‐ tc) × 4186 / (3.6 × 10^6) = 55.9 [kW]

② Capacity of Heat Pump: Total Load × 1.1 = 61.5 [kW] ⇒ 62.0 [kW] (shared by Indoor and Outdoor)

2. 2  Capacity of Hot Water Tank
① for Indoor Bath
Actual Capacity:              586 [L/h]  + 1,800 [L/h]    =        2,385.6 [L/h] ⇒        2,385.6 [L/h] × 46.0 [%] ≒        1,097.4 [L/h]
       1,097.4 [L/h] × 0.8 = 877.9 [L]
          877.9 [L] × 1.4 =         1,229.1 [L] ⇒           1,300 [L]

② for Outdoor Bath
Actual Capacity:              438 [L/h] ⇒            438.1 [L/h] × 46.0 [%] ≒           201.5 [L/h]
          201.5 [L/h] × 0.8 = 161.2 [L]
          161.2 [L] × 1.4 =            225.7 [L] ⇒              300 [L]

 Capacity of Hot Water Tank: ① + ② =           1,600 [L]

2. 3  Capacity of Hot Water Primary Pump
0.86 × (Total Load + Ht) / 60 / Δt  ≒ 176.6 [ltr/min] ⇒ 177.0 [ltr/min] Automatically Alternate

ΔT: Temperature difference between going and returning water ⇒ 5 [℃] 


Ht: Heat Loss by pipe ⇒ 0.20 [W/(m・℃)]    × (60[℃] - 25[℃])    × 20 [m] ≒ 140 [W] 

2. 4  Capacity of Hot Water Return Pump
① for Indoor Bath
Heat Loss of PPR(PN20) pipe w/insulation: 0.20 [W/(m・℃)]
Pipe Length: 40 [m]
Temperature difference between hot water and air: 35 [℃] ※ 60℃(Hot Water) - 25℃(Air)

Ht: Heat Loss by pipe ⇒ 0.20 [W/(m・℃)]    × 35[℃]    × 50 [m] ≒ 350 [W] 


ΔT: Temperature difference between going and returning water ⇒ 5 [℃] 

0.86 ×  Ht / 60 / Δt  ≒ 1.0 [ltr/min] ⇒ 2.0 [ltr/min] Automatically Alternate

② for Outdoor Bath
Heat Loss of PPR(PN20) pipe w/insulation: 0.20 [W/(m・℃)]
Pipe Length: 40 [m]
Temperature difference between hot water and air: 35 [℃] ※ 60℃(Hot Water) - 25℃(Air)

Ht: Heat Loss by pipe ⇒ 0.20 [W/(m・℃)]    × 35[℃]    × 50 [m] ≒ 350 [W] 


ΔT: Temperature difference between going and returning water ⇒ 5 [℃] 

0.86 ×  Ht / 60 / Δt  ≒ 1.0 [ltr/min] ⇒ 2.0 [ltr/min] Automatically Alternate

2. 5  Capacity of Line Pump & Panel Water Tank (Water Supply)
① Line Pump
    2,823.75 [L/h] ⇒             47.1 [L/min]  ⇒     48 [L/min] 
※According to 2.1

② Panel Water Tank
The necessary capacity shall be for 30 minutes  operation of Line Pump.
    48 [L/min]   × 30 [min]   = 1440 [L] ⇒ 1.44 [m3]

Size of Panel Water Tank: 1.0m × 1.0m × 2.0m(H)  (Effective Capacity:1.6[m3])

Page 2 of 2