Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
2015.3
AHU KIT 1
1. Precautions
2. Installation information
3. Attached fittings
4. Installation method and dimension
5. Material and size of the piping
6. Electrical wiring
7. Application control
8. Trouble shooting
1. Precautions
Be sure to be in conformity with the local, national and international laws and regulations
Read “PRECAUTIONS” carefully before installation
The following precautions include important safety items. Observe them and never forget.
Keep this manual with the owner’s manual in a handy place for future reference.
Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel
The safety precautions listed here are divided into two categories. In either case, important safety information is
listed which must be read carefully.
Warning: Failure to observe a warning may result in death.
Caution: Failure to observe a caution may result in injury or damage to the equipment
After completing the installation, make sure that the unit operates properly during the start-up operation. Please
instruct the customer on how to operate the unit and keep it maintained. Also, inform customers that they should store
this installation manual along with the owner's manual for future reference
Warning:
Be sure only trained and qualified service personnel to install, repair or service the equipment.
Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other
damage to the equipment.
Install according to this installation instructions strictly.
If installation is defective, it will cause water leakage, electric shocks, fire.
When installing the unit in a small room, take measures against to keep refrigerant concentration from
exceeding allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen
deficiency.
Use the attached accessories parts and specified parts for installation.
Otherwise, it will cause the set to fall, water leakage, and electrical shock fire.
Install at a strong and firm location which is able to withstand the set’s weight.
If the strength is not enough or installation is not properly done, the set will drop to cause injury.
The appliance must be installed 2.5m above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits must be disconnected.
The appliance must be positioned so that the plug is accessible.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow
For electrical work, follow the local national wiring standard, regulation and this installation instructions. An
independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in electrical work, it will cause electrical shock fire
Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the
terminal.
If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
Wiring routing must be properly arranged so that control board cover is fixed properly.
Caution:
Ground the air conditioner
Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire. Incomplete grounding
may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks.
Connect the outdoor unit wires, then connect the indoor unit wires
You are not allow to connect the air conditioner with the power source until wiring and piping the air conditioner is done.
While following the instructions in this installation manual, install drain piping in order to ensure proper
drainage and insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from
televisions or radios in order to prevent image interference or noise
Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children or infirm persons without supervision.
Young children should be supervised to ensure that they do not play with the appliance
Don't install the air conditioner in the following locations :
1. Outdoor occasions
2. There is petrolatum existing
3. There is salty air surrounding (near the coast)
4. There is caustic gas (the sulfide, for example) existing in the air (near a hot spring)
5. The Volt vibrates violently (in the factories)
6. In buses or cabinets.
3. Attached fittings
Please check whether the following fittings are of full scope. If there are some spare fittings, please restore them
carefully.
NAME SHAPE QUANTITY FUNCTION
1. Installation & owner’s manual / 1 /
2. Wire controller
1 Wired controller
3. Wire controller
1 /
1 Receive signal
5. Screw ST3.96×25
Secure the
8
installation board
7. Temp. sensor
10HP AHU kit temp.
sensor is double of
3
5HP AUH kit temp.
sensor
Note:
1. The controller box cannot installation in outdoor occasions, if inevitable, it must increase rainproof precautions,
specific methods please contact the local dealer or technical support engineer.
2. As hanging installation please use Screw ST3.9x25 for installation.
3. As hanging installation, the box should be vertical, and the box cannot be installed horizontally.
4. Please refer to the foregoing, make sure the laying direction of the refrigerant pipe and the connecting place of the
connecting wire.
All the pictures in this manual are for explanation purpose only. They may be slightly different from the control box you
purchased (depend on model).The actual shape shall prevail
6. Electrical Wiring
Caution:
1. The air conditioner should use separate power supply with rated voltage
2. The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of
the indoor and outdoor unit.
3. The wiring work should be done by qualified persons according to circuit drawing.
4. The fixed connecting lines must equip with at least 3mm electric shock spacing.
5. A leakage protector should be installed according to the local electrical standard.
6. Be sure to locate the power wiring and the signal wirings well to avoid cross-disturbance and their contact with
connecting pipe or stop value body. Generally, do not twist two wiring together unless the joint is soldered well and
covered with insulator tape.
7. Do not turn on the power until the electrical wiring have been done correctly.
6.1 The specification of power
The specification of power as the follow display figure, if the capacity is too small will lead to overheat of the wiring,
and cause burning of the machine accident
Table 6-1
Model AHU-5P/AHU-10P
Phase Single-phase
Power 220-240V~50Hz
Voltage and Frequency
208-230V~60Hz
Indoor unit power wiring(mm2) 4.0(<50 m)
Indoor/outdoor connecting wiring(mm2)
0.75
weak electric signal
Caution:
The air-gap notch in the circuit breaker is used for insulating the flexible conductor, so that must respond to the related
national wire requests to connect to the fixed circuit
Fig 6.1
Fig 6.2
The connecting terminals of the water level switch W1 and W2 are connected by default, when connect the indoor unit
with water pump please remove the connecting wire and connect to the water level switch.
Caution:
1. AHU-5P, AHU-10P are applied one main control panel, the temperature sensor T1, T2 and T2B must connect to the
main control panel before first powered on;
2. T1 is indoor temperature sensor, install to the air inlet of the indoor unit;
3. T2 is indoor evaporator intermediate temperature sensor, install to the intermediate of temperature evaporator;
4. T2B is indoor evaporator outlet sensor, install to the outlet of the evaporator
6.4 Indoor and outdoor unit wiring figure
5 2
REMO_CTRL
1 4
wire
CN26
TRANS OUT
4
CN7
Controller LOW
6 5
SW1
CN16
EXV
EXV1
5 1 4
RD MEDIUM
N L MH
BK
6 5
WH
1 4
10
PUMP
HIGH
CN8
10
Duct display
6 5
Receive and display light board
CN23
2
ALARM
HEAT
CN1
CN4
Water switch
2
3 4
CN18
SW3
OFF 1 2
CN5
Wire control
CN27
ON
2 5
1 2 3 4 5 6 7 8
2
SW2
SW8
OFF 1 2
N
ON
N
OFF
ON
4
RD BL
P E Q
CN17 CN28
CN3
CN12
CN15
L
T2B
CN9
TX1
TX2
TX3
3
L N 3
T1
T2
3
temperature
sensor
Outlet
Ambient
sensor
PT3
PT2
PT1
Middle
RD BL
2
BL BL
RD BL 2 3 2 2
RD BK WH RD BK BR BL RD WH BK WH WH BK BK
2
YE/GN
P1 N1 P2 N2 BK BK
POWER FAN PUMP ALARM COMMUNICATION Water switch REMO_CTRL
wire
10
Controller
Receive and display light board
BL
2
10
N N
2
CN1 CN8 N L MH CN7
10
CN3 CN5 ALARM PUMP CN3 CN2 CN1
TRANS OUT
RD
L
POWER
CN6 CN10
L N
TRANS_IN
SW3 CN4 CN4
CN9 SW2
BL
ON SW1
RD
TX1 ON
HEAT
BL
OFF 1 2 3 4 5 6 7 8
Ambient CN12 OFF 1 2 3 4
temperature TX2 CN5
BL
N
sensor CN15
TX3
PT1
CN18
RD
T1 CN6
PT2 Water switch
5
T2
BK
CN7
FAN
PT3 CN23 CN16
Middle
sensor
T2B SW8 CN27 Duct display EXV CN26
CN8
WH
Outlet ON Wire control REMO_CTRL
CN17 CN28
sensor
10
PE Q
CN10
3
EXV 2
2
3
5
3
2
P1 N1
P2
RD BK BR BL
2
N2
P1 N1 P2 N2
4
PUMP ALARM
N N
CN5 CN1 CN8 N L MH CN7
CN3 ALARM PUMP
TRANS OUT
L CN6 CN10 TRANS_IN
SW3 CN4
CN9 SW2 ON
TX1 HEAT
ON SW1
OFF 1 2 3 4 5 6 7 8
CN12 OFF 1 2 3 4
Ambient TX2
temperature CN15
1
sensor TX3
PT1
T1 CN18
3
PT2 Water switch
2
T2
BK
CN16
RD
CN23
WH
PT3
Middle
sensor
T2B Duct display EXV CN26
SW8 CN27 REMO_CTRL
Outlet CN17 CN28 ON Wire control
sensor
OFF 1 2
5
PE Q
5
2
EXV1
NOTE:Two pieces of electronic control board for all set to 5 HP, that is to SW1 dial 9:
P QE
3
23
2
BK
RD
6
1
6
1
6
1
BK
RD RD WHWHBK BK WH WH BK BK BK BK
Water_SW REMO_CTRL
RD
LOW
HIGH
4
4
5
5
5
2
2
BL
3
2
4
4
2
AHU KIT
Function specification
SW1——Cooling capacity setting, set the cooling capacity of this machine (Table. 7-1)
Table 7-1
SW1 Toggle switch For setting cooling capacity
Code Setting cooling capacity
0 2200W(0.8HP)
1 2800W(1.0HP)
Caution: 2 3600W(1.3HP)
The horsepower has been set before 3 4500W(1.6HP)
leaving the factory; anyone can’t 4 5600W(2.0HP)
modify it expect the maintenance 5 7100W(2.5HP)
person. 6 8000W(3.0HP)
7 9000W(3.2HP)
8 11200W(4.0HP)
9 16000W(5.0HP)
ON
SW3 Automatic Addressing mode and (Factory default)
OFF
4
NO.4
ON
Test mode (to allow clear address)
OFF
4
ON 15℃ ON 20℃
Factory
OFF default OFF
5 6 5 6
ON 24℃ ON 26℃
OFF OFF
5 6 5 6
Table 7-4
Heating stop the fan time to choose set
SW2 NO.7&8 Time selection SW2 NO.7&8 Time selection
ON Factory
4 Minute ON 8 Minute
ON 12 Minute ON 16 Minute
OFF OFF
7 8 7 8
ON Factory 6 ℃
ON 2 ℃
OFF default OFF
3 4 3 4
ON 4 ℃
ON 8 ℃
OFF OFF
3 4 3 4
ON ON
OFF OFF
1 1
ON No power-down memory
OFF
1
NOTE: The electronic control board set to 5HP, which is to SW1 dial 9:
Factory default
SW1 SW3
SW2 SW8
ON ON ON
OFF 1 2 3 4 5 6 7 8 OFF 1 2 3 4 OFF 1 2
8. Troubleshooting
8.1 Display with Fault
Definitions of malfunction Contents appearing
The first time to switch on and there is no address FE
Errors of phase sequence or fault of losing phase E0
Communication failure of indoor and outdoor unit E1
T1 sensor fault E2
T2 sensor fault E3
T2B sensor fault E4
Malfunction of outdoor unit E5
Testing fault of zero-crossing signal E6
EEPROM malfunction E7
Wind testing fault of PG electric motor E8
Communication fault of wire controller E9
Alarming fault of water level switch EE
Model conflict EF