HVAC SUMMARY

TENDER ANALYSIS - 3

Subject : TENDER ANALYSIS - 3 FOR TAJ GATE WAY

Dear Sir,

S.no DESCRIPTION TRANE CARRIER


Supplying, installing, testing and
commissioning of 340 TR SCREW WATER
CHILLING UNITS. Imported portion of
1 Indicate for all chillers
above chillers portMumbai,
CIF (Delhi, charges , port
Chennai).
handling charges, other local duties, loading,
transportation/insurance upto site, octroi
1.1 charges and all other taxes and incidentals
complete till delivered at site.
Receiving at site above imported equipment,
unloading, storing, handling hoisting, installing
in position, effecting connections, anchoring,
grouting testing and commissioning above
equipment including supplying & installing
all necessary indigenous accessories as required
to complete the installation.
1.2
Supply, installation, testing and commissioning
of Factory manufactured micro-processor based
1.3 Chiller system Manager
GRAND TOTAL 0 0

L-1 L-2

Regards,

Taamaesek Engineering Consortium


KIRLOSKAR

L-3
BILL OF QUANTITIES – WATER COOLED SCREW CHILLERS

TRANE
S.No Description UNIT QTY RATE AMOUNT

EQUIPMENT (IMPORTED).PRICES TO BE QUOTED ON THE


A.
BASIS OF CUSTOMER AVAILING EPCG BENEFIT

Supplying, installing, testing and commissioning of 340 TR


SCREW WATER CHILLING UNITS each complete with multiple
screw compressor, motor, starter, water cooled condenser, factory
insulated chiller, flow switch at chiller and condenser, vibration
isolators, integral refrigerant piping and wiring, accessories as
1
required and called for, automatic and safety controls mounted in
central console panel and all mounted on a steel frame complete
as per specifications. Motor shall be suitable for 415±10% 50
cycles, 3 phase AC supply. Numbers indicated includes one No. as
50 % standby.
Chiller Water IN - 54°F
Chilled Water OUT - 44°F
Fouling Factor for Evaporator - 0.0005 FPS
Fouling Factor for Condenser - 0.001FPS
Chiller Water flow - 816 USGPM
Condenser Water flow - 1020 USGPM
Condenser Water IN - 90°F
Condenser Water OUT - 100°F
Capacity at above conditions - 340 TR each
Noise Level
Max Noise Level - 74 dbA at 1 Mtr distance (provide acoustic
jacket for compressors/evaporator if required)
IKW/TR not exceeding 0.65 KW/TR
Refrigerant R-134a

Supply imported portion of above chillers CIF (Delhi, Mumbai,


1.1 Nos.
Chennai). 3 4560000 13680000

Indicate for all chillers port charges , port handling charges, other
local duties, loading, transportation/insurance upto site, octroi
1.2 Nos.
charges and all other taxes and incidentals complete till delivered
at site. 3

Receiving at site above imported equipment, unloading, storing, 525000


handling hoisting, installing in position, effecting connections,
anchoring, grouting testing and commissioning above equipment Nos.
including supplying & installing all necessary indigenous
accessories as required to complete the installation.
3

Supply, installation, testing and commissioning of Factory


1.3 Nos.
manufactured micro-processor based Chiller system Manager 1 600000 600000

1.4 Supply of Jbus for the Third Party BMS Integration Nos 3

TOTAL 14805000

CARRIER
Note: The Quoted Prices are Exclusive of local taxes and duties that are applicable

For Item No: 1.1 Customs duty at the rate of 29% shall be extra
For Item No: 1.2 Service Tax @ 12.36% shall be extra
For Item No: 1.3 & 1.4 VAT @ 12.5% Shall be extra
KIRLOSKAR
Note: The prices are exclusive of Central Excise Duty, Sales Tax/VAT and Octroiduty/Entry tax.
Additional charges for factory witness test for one load point (100%,at only) shall be rs.75000/-

TRANE
Note: The Chiller Price includes R134a&oil, Insulation of Cold parts, under / over voltage protection, closed transition Wye-delta starter, communicatio
flow switch, isolation pads and commissioning
Additional charges for factory witness test for one Chiller@ (100%,75%,50%,25%) four point tests as per standard factory test will be USD 19,0
Exclusions:
Custom duties / Port Clearance / Delivery to site
Any rigging, carting or handling
Erection / installation of Chillers
Charges for stand by labour

OPERATION AND MAINTENANCE CONTRACT

Sl.No. Operation All-Inclusive Operation All-Inclusive


contract maintenance contract maintenance
TRANE CARRIER
1 FIRST YEAR FROM DATE OF HANDOVER 1050000 1080000 PART OF DLP

2 SECOND YEAR FROM DATE OF HANDOVER 1102500 1245000 1005000


INCLUDING 1435000
3 THIRD YEAR FROM DATE OF HANDOVER 1157625 DLP 1055000

4 FOURTH YEAR FROM DATE OF HANDOVER 1215506 1652000 1110000

5 FIFTH YEAR FROM DATE OF HANDOVER 1276281 1900000 1170000

TOTAL FOR FIVE YEARS 5801912 7312000 4340000

TRANE
Note: Service Tax Extra @ 12.36%

CARRIER
Note: AMC Charges quoted are exclusive of local Taxes that are applicable
Service Tax Extra @ 12.36%
HILLERS

CARRIER KIRLOSKAR
RATE AMOUNT RATE AMOUNT

3060000 9180000 4333333 12999999.999

175000 525000

135000 405000 300000 900000

230000 230000 350000 350000

75000 225000

10565000 14249999.999
e-delta starter, communication card

factory test will be USD 19,000/-

Operation All-Inclusive
contract maintenance
KIRLOSKAR

Not Quote
HVAC COMPARISON

250
RUPEES IN LAKHS

200

150

100

50

0
VOLTAS STERLING ETA TRAC
VENDORS

A Installation, Testing and Commisioning of equipment (Imported) - Owner supplied at site free of cost B Supply, installation, Testing and Commissioning of equipment (Indegenous)

C Condenser and Chilled Water Piping D Air Distribution

E Toilet Exhaust System - Guest Room Toilets F Thermal Insulation


HVAC SUMMARY

TENDER ANALYSIS - 3

Subject : TENDER ANALYSIS - 3 FOR TAJ GATE WAY

Dear Sir,

Based on the discussions on 03.05.08 we are submitting hereby the Tender analysisfor
Air conditioning accessories. Our consists of the following

S.no DESCRIPTION VOLTAS STERLING ETA TRAC


Installation, Testing and
Commisioning of equipment
(Imported) - Owner supplied at site
A free of cost 933,490 1,033,319 1,688,662 2,530,366
Supply, installation, Testing and
Commissioning of equipment
B (Indegenous) 12,643,670 12,669,954 21,566,941 17,869,928
C Condenser and Chilled Water Piping 8,540,740 7,194,834 9,575,827 9,885,639
D Air Distribution 6,248,080 7,802,996 9,635,119 11,267,858
Toilet Exhaust System - Guest Room
E Toilets 715,000 1,101,540 968,520 4,585,645
F Thermal Insulation 5,419,020 5,185,464 6,890,057 8,898,659
GRAND TOTAL 34,500,000 34,988,107 50,325,126 55,038,095

L-1 L-2 L-3 L-4

Regards,

Taamaesek Engineering Consortium


S.noDESCRIPTION VOLTAS STERLING ETA TRAC
A Installation, Testing and Commisi 9 10 16.88662 25.30366
B Supply, installation, Testing an 13 13 215.66941 178.69928
C Condenser and Chilled Water Pip 9 7 95.75827 98.85639
D Air Distribution 6 8 96.35119 112.67858
E Toilet Exhaust System - Guest Ro 7 11 9.68520 45.85645
F Thermal Insulation 54 52 68.90057 88.98659
IMPORTED ITEMS

SL.
DESCRIPTION QTY UNIT
NO

2 CHILLED WATER VERTICAL INLINE PUMPS

2.1 Secondary chilled water pumps for Guest room areas

Water flow rate =516 GPM


Head =100 Ft. of water
Motor HP =25
Quantity indicated includes one standby. Nos. 3

2.2 Secondary chilled water pumps for Common Areas

Water flow rate =886 GPM


Head =100 Ft. of water
Motor HP =40
Quantity indicated includes one standby. Nos. 2

3 VARIABLE SPEED PUMPING SYSTEM

3.1 3 Nos x 25 HP Set 1


3.2 2 Nos x 40 HP Set 1

4 CONDENSER VERTICAL INLINE PUMPS

4.1 Condenser water pumps

Water flow rate = 1020 USGPM


Head = 80 Ft. of water
Motor HP = 40
Quantity indicated includes one standby. Nos. 3

4.2 CHILLED WATER PRIMARY PUMPS

Water flow rate = 816USGPM


Head = 40 Ft. of water
Motor HP = 20
Quantity indicated includes one standby. Nos. 3

5 FAN COIL UNITS

5.1 2.43 TR / 1441 CFM Hi-speed / 1082 CFM Med speed Nos. 4
5.2 2.29 TR / 1188 CFM Hi-speed / 900 CFM Med speed Nos. 15
5.3 1.93 TR / 905 CFM Hi-speed / 682 CFM Med speed Nos. 143
5.4 1.77 TR / 753 CFM Hi-speed / 565 CFM Med speed Nos. 19
5.5 1.44 TR / 612 CFM Hi-speed / 462 CFM Med speed Nos. 31
5.6 1.15 TR / 436 CFM Hi-speed / 312 CFM Med speed Nos. 12

B SUPPLY,INSTALLATION, TESTING AND COMMISIONING OF


EQUIPMENT (INDEGENOUS)
1 Receiving of INDUCED DRAFT COOLING TOWERS (to be
installed on Terrace 24mtrs above from Ground Level-
supplied by owner)at site, unloading, storing, handling
hoisting, installing in position, effecting connections, anchoring,
grouting testing and commissioning including supplying &
installing of all necessary indigenous accessories as required
to complete the installation.

1.1 Induced draft FRP Cooling tower for screw chillers (340 TR)
plant each having flow rate of 1020 GPM @ 90-100 ° F.
Quantity indicated includes one standby. Nos 3

2 TWO WAY VALVES The actuator shall be provided with


interface cards to receive 0-10V or 4-20 mA signal from
Building Automation System. The valve shall be suitable for
following pipe sizes :
Honeywell V5011 series or equivalent –
upto 50 mm Honeywell V5211 series or
equivalent –65mm and 80 mm Honeywell V5088 series
or equivalent –100mm to 150 mm

2.2 80 mm dia for AHUs No. 2


2.3 65 mm dia for AHUs No. 7
2.4 50 mm dia for AHUs Nos. 8
2.5 40 mm dia for AHUs Nos. 4
2.6 32 mm dia for AHUs Nos. 11
2.7 25 mm dia for AHUs Nos. 4

3 COOLING THERMOSTAT
3.1 Modulating digital cooling thermostats Honeywell T6571B1007 Nos 224
or equivalent complete with 3-speed fan control, and with
energy saving mode to enable switching to higher set point on
command from key tag.
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
A INSTALLATION, TESTING AND COMMISIONING OF EQUIPMENT
(IMPORTED) -OWNER SUPPLIED AT SITE FREE OF COST

1 Receiving of WATER COOLED SCREW


CHILLER(340TR,9000Kgs(Approximate weight),to be installed at
Basement 2 Level-supplied by owner) at site, unloading, storing,
handling hoisting, installing in position, effecting connections, anchoring,
grouting testing and commissioning including supplying & installing
all necessary indigenous accessories as required to complete the
installation.
Nos. 3 100,000 300,000 94870 284,610 113792 341,376
0
2 Receiving of VERTICAL INLINE PUMPS(supplied by owner) at site,
unloading, storing, handling hoisting, installing in position, effecting
connections, anchoring, grouting testing and commissioning including
supplying & installing all necessary indigenous accessories as required
to complete the installation. 0
0
2.1 Secondary chilled water pumps for Guest room areas 0
0
Water flow rate =516 GPM 0
Head =100 Ft. of water 0
Motor HP =25 0
Quantity indicated includes one standby. Nos. 3 18,000 54,000 6320 18,960 24067 72,201
0 0
2.2 Secondary chilled water pumps for Common Areas 0 0
0 0
Water flow rate =886 GPM 0 0
Head =100 Ft. of water 0 0
Motor HP =40 0 0
Quantity indicated includes one standby. Nos. 2 18,000 36,000 6320 12,640 24067 48,134
0
3 Receiving of VARIABLE SPEED PUMPING SYSTEM(supplied by
owner) at site, unloading, storing, installing in position, effecting
connections, testing and commissioning including supplying &
installing all necessary indigenous accessories as required to complete
the installation.
0
Installation of AFD, Pump controllers & sensor transmitter. 0
0
3.1 3 Nos x 25 HP Set 1 10,000 10,000 6320 6,320 3880 3,880
3.2 2 Nos x 40 HP Set 1 10,000 10,000 6320 6,320 3880 3,880
0
4 Receiving of VERTICAL INLINE PUMPS(supplied by owner) at site,
unloading, storing, handling hoisting, installing in position, effecting
connections, anchoring, grouting testing and commissioning including
supplying & installing all necessary indigenous accessories as required
to complete the installation. 0
0
4.1 Condenser water pumps 0
0
Water flow rate = 1020 USGPM 0
Head = 80 Ft. of water 0
Motor HP = 40 0
Quantity indicated includes one standby. Nos. 3 18,000 54,000 6320 18,960 19029 57,087

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.1
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
0
4.2 Primary chilled water pumps 0
0
Water flow rate = 816USGPM 0
Head = 40 Ft. of water 0
Motor HP = 20 0
Quantity indicated includes one standby. Nos. 3 18,000 54,000 6320 18,960 24067 72,201
0
0
5 Receiving of FAN COIL UNITS(supplied by owner) of at site, unloading,
storing, handling hoisting, installing in position, effecting connections,
anchoring, grouting testing and commissioning including supplying &
installing all necessary indigenous accessories as required to complete
the installation. 0
Horizontal unit with cabinet (Ceiling Hung) 0
0
5.1 2.43 TR / 1441 CFM Hi-speed / 1082 CFM Med speed Nos. 4 4,000 16,000 2530 10,120 1940 7,760
5.2 2.29 TR / 1188 CFM Hi-speed / 900 CFM Med speed Nos. 15 4,000 60,000 2530 37,950 1940 29,100
5.3 1.93 TR / 905 CFM Hi-speed / 682 CFM Med speed Nos. 143 4,000 572,000 2530 361,790 1940 277,420
5.4 1.77 TR / 753 CFM Hi-speed / 565 CFM Med speed Nos. 19 4,000 76,000 2530 48,070 1940 36,860
5.5 1.44 TR / 612 CFM Hi-speed / 462 CFM Med speed Nos. 31 4,000 124,000 2530 78,430 1940 60,140
5.6 1.15 TR / 436 CFM Hi-speed / 312 CFM Med speed Nos. 12 4,000 48,000 2530 30,360 1940 23,280

SUB TOTAL COST 1,414,000 933,490 1,033,319

B SUPPLY,INSTALLATION, TESTING AND COMMISIONING OF


EQUIPMENT (INDEGENOUS)
1 Receiving of INDUCED DRAFT COOLING TOWERS (to be installed
on Terrace 24mtrs above from Ground Level-supplied by owner)at
site, unloading, storing, handling hoisting, installing in position, effecting
connections, anchoring, grouting testing and commissioning including
supplying & installing of all necessary indigenous accessories as
required to complete the installation.

1.1 Induced draft FRP Cooling tower for screw chillers (340 TR) plant each
having flow rate of 1020 GPM @ 90-100 ° F.
Quantity indicated includes one standby. Nos 3 80,000 240,000 63250 189,750 112016 336,048
0
2 Supply, installation, testing and commissioning of TWO WAY VALVES
with modulating actuators in chilled water line at each air handling units /
Fan coil units. The valves shall have required shut off capability because
of high pressure differentials encountered in variable flow system. The
valves & actuators for AHU’s shall be compatible with Building
Automation System. The actuator shall be provided with interface cards
to receive 0-10V or 4-20 mA signal from Building Automation System.
The valve shall be suitable for following pipe sizes :
Honeywell V5011 series or
equivalent –upto 50 mm Honeywell V5211 series or
equivalent –65mm and 80 mm Honeywell V5088 series or
equivalent –100mm to 150 mm
0
PRICES TO BE QUOTED ON THE BASIS OF CUSTOMER AVAILING
EPCG BENEFIT 0
2.1 100 mm dia for AHUs No. R.O 1650 2667
2.2 80 mm dia for AHUs No. 2 1,400 2,800 1340 2,680 1253 2,506
2.3 65 mm dia for AHUs No. 7 1,310 9,170 1320 9,240 1056 7,392
2.4 50 mm dia for AHUs Nos. 8 1,200 9,600 1100 8,800 858 6,864
2.5 40 mm dia for AHUs Nos. 4 1,200 4,800 1050 4,200 726 2,904
2.6 32 mm dia for AHUs Nos. 11 750 8,250 930 10,230 626 6,886
2.7 25 mm dia for AHUs Nos. 4 580 2,320 850 3,400 529 2,116
0 509

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.2
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
3 Receiving of COOLING THERMOSTAT at site , installation, testing and
commissioning for various fan coil units as described in specifications.
0
0
3.1 Modulating digital cooling thermostats Honeywell T6571B1007 or Nos 224 1,647 368,928
equivalent complete with 3-speed fan control, and with energy saving
mode to enable switching to higher set point on command from key tag.
630 141,120 189 42,336
0 0
4 Supply, installation, testing and commissioning of wall mounted return Nos 12 3,200 38,400
air temperature thermostat for controlling 2 way chilled water control
valves fitted to various air handling units. Honeywell -T2798 or
equivalent 2220 26,640 5116 61,392
0 0
5 Supply, installation, testing and commissioning of duct mounted supply
air temperature thermostat for controlling 2 way chilled water control
valves fitted to various treated fresh air handling units. Nos 24 3,200 76,800 2220 53,280 5116 122,784
0
6 Supplying, installing, testing and commissioning of double skin
construction draw thru type AIR HANDLING UNITS as per specification,
each complete with filter section, water coil of copper tube & aluminium
fins construction each for chilled water, squirrel cage induction motor,
centrifugal fan with forward curved fan blades, belt drive and vibration
isolators, coil size shall be selected for a maximum face velocity of
500 feet/minute and total static pressure shall be minimum 40mm WG
( minimum 25 mm external static) or as required to overcome system
pressure drops. Motor shall be suitable for 415±10%/230 volts, 50
cycles, 3 phase/Single phase/AC supply. All public area air handling
units shall have minimum 6 row cooling coil .Treated fresh air units
shall be provided with 8 row deep cooling coil and shall be
complete with thermal break profile.

0
Air moving and tonnage capacities shall be as follows 0
LOWER BASEMENT 0
6.1 LAUNDRY-TFA(8 ROW) - C.S.AHU - 1200 CFM - 9.79 TR No. 1 85,916 85,916 37000 37,000 55519 55,519
6.2 MAINTENANCE ROOM - C.S.AHU - 1135 CFM - 2.6 TR No. 1 74,256 74,256 30710 30,710 55068 55,068
0
UPPER BASEMENT 0
6.3 LT PANEL ROOM - C.S.AHU - 4833 CFM - 7.5 TR No. 1 151,725 151,725 68100 68,100 120407 120,407
6.4 TRAINING ROOM - C.S.AHU - 1349 CFM - 4.1 TR No. 1 77,324 77,324 31880 31,880 59526 59,526
6.5 CONFECTIONERY& BAKERY - C.S.AHU - 1823 CFM - 3.8 TR No. 1 86,969 86,969 36970 36,970 66510 66,510
6.6 GARDE MANAGER - C.S.AHU - 1320 CFM - 2.6 TR No. 1 76,096 76,096 31700 31,700 59324 59,324
6.7 OFFICE - C.S.AHU - 2125 CFM - 4.6 TR No. 1 93,197 93,197 38580 38,580 74497 74,497
6.8 STORAGE AREA - C.S.AHU - 1564 CFM - 5 TR No. 1 81,263 81,263 34290 34,290 61015 61,015
6.9 AHU FOR LOCKER ROOMS - C.S.AHU - 4793 CFM -16.1 TR No. 1 147,041 147,041 67920 67,920 120130 120,130
6.10 LAUNDRY RELATED AREA-TFA(8 ROW) - C.S.AHU - 4975 CFM No. 1 180,024 180,024
-40.8 TR 83120 83,120 135787 135,787
6.11 KITCHEN-TFA(8 ROW) - C.S.AHU - 600 CFM - 4.9 TR No. 1 74,570 74,570 32710 32,710 55584 55,584
0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.3
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
GROUND FLOOR 0
6.12 PREFUNCTION * - F.M.AHU - 4543 CFM - 10.7 TR Nos. 2 152,851 305,702 73740 147,480 125154 250,308
6.13 FUNCTION ROOM-2 * - F.M.AHU - 6552 CFM - 18.3 TR No. 1 198,097 198,097 94850 94,850 158492 158,492
6.14 FUNCTION ROOM-1 * - F.M.AHU - 8006 CFM - 23.7 TR No. 1 218,350 218,350 105230 105,230 174569 174,569
6.15 COFFEE SHOP * - F.M.AHU - 8987 CFM - 23.1 TR No. 1 245,640 245,640 118130 118,130 201700 201,700
6.16 SPECIALITY RESTURANT * - F.M.AHU - 4317 CFM - 11 TR No. 1 151,074 151,074 71840 71,840 123588 123,588
6.17 FRONT OFFICE & LOBBY * - F.M.AHU - 12386 CFM - 24.1 TR No. 1 319,117 319,117 156840 156,840 240781 240,781
6.18 LOBBY BAR * - F.M.AHU - 4847 CFM - 12.5 TR No. 1 155,874 155,874 75440 75,440 127261 127,261
6.19 KITCHEN-TFA(8 ROW) - F.M.AHU -6350 CFM - 42.39 TR No. 1 237,701 237,701 110270 110,270 179524 179,524
0
MEZZANINE FLOOR 0
6.20 CHAIRMAN SUITE - C.S.AHU - 2383 CFM - 4.2 TR No. 1 98,973 98,973 42430 42,430 77579 77,579
6.21 HALL-1 -C.S.AHU - 1442 CFM - 3.8 TR No. 1 80,050 80,050 33310 33,310 60169 60,169
6.22 HALL-3 * -C.S.AHU - 1715 CFM - 4.4 TR No. 1 83,078 83,078 36350 36,350 65114 65,114
6.23 HALL-4 -C.S.AHU - 1689 CFM - 4.3 TR No. 1 82,819 82,819 35010 35,010 64934 64,934
6.24 HEALTH CLUB CORRIDOR * - C.S.AHU - 2738 CFM - 6.2 TR No. 1 106,925 106,925 48250 48,250 80686 80,686
6.25 GYM * - F.M.AHU - 6358 CFM - 17.9 TR No. 1 196,168 196,168 90910 90,910 157149 157,149
6.26 EXECUTIVE OFFICES * - C.S.AHU - 3660 CFM -7.3 TR No. 1 123,844 123,844 56470 56,470 100013 100,013
6.27 IT OFFICES * - C.S.AHU - 1917 CFM -3.9 TR No. 1 88,781 88,781 37420 37,420 66514 66,514
0
FIRST FLOOR 0
6.28 TFA-1 (8 ROW) - V.F.M. AHU - 2100 CFM -17.2 TR No. 1 109,617 109,617 50640 50,640 85388 85,388
6.29 TFA-2 (8 ROW) - V.F.M. AHU - 3050 CFM -25 TR No. 1 134,096 134,096 68710 68,710 112363 112,363
0
SECOND FLOOR 0
6.30 TFA-1 (8 ROW) - V.F.M. AHU - 2100 CFM -17.2 TR No. 1 109,617 109,617 50640 50,640 85388 85,388
6.31 TFA-2 (8 ROW) - V.F.M. AHU - 3050 CFM -25 TR No. 1 134,096 134,096 68710 68,710 112363 112,363
0
THIRD FLOOR 0
6.32 TFA-1 (8 ROW) - V.F.M. AHU - 2100 CFM -17.2 TR No. 1 109,617 109,617 50640 50,640 85388 85,388
6.33 TFA-2 (8 ROW) - V.F.M. AHU - 3050 CFM -25 TR No. 1 134,096 134,096 68710 68,710 112363 112,363
0
FOURTH FLOOR 0
6.34 TFA-1 (8 ROW) - V.F.M. AHU - 2100 CFM -17.2 TR No. 1 109,617 109,617 47610 47,610 85388 85,388
6.35 TFA-2 (8 ROW) - V.F.M. AHU - 3050 CFM -25 TR No. 1 134,096 134,096 68710 68,710 112363 112,363
NOTE: 0
C.S.AHU- CEILING SUSPENDED AIR HANDLING UNIT 0
F.M.AHU- FLOOR MOUNTED AIR HANDLING UNIT 0
V.F.M.AHU- VERTICAL FLOOR MOUNTED AIR HANDLING UNIT 0
0
* - AHU'S SHOULD BE WITH FACTORY FABRICATED AIR INTAKE
PLENUM FROM THE SAME SUPPLIER. 0
0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.4
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
7 Supply, installation, testing and commissioning of non-ducted split
airconditioning units comprising indoor units with three speed evaporator
fan motor, fan, cooling coil and insulated drain pan enclosed in plastic
casing complete with cordless remote control and outdoor unit complete
with Reciprocating / rotary compressor,condenser fan and coil enclosed
in sheet metal cabinet powder coated.Units shall be suitable for
operation on 230 Volts 50 Hz single phase supply.Prices quoted shall be
inclusive of power wiring from socket to indoor / outdoor unit,control
wiring between indoor and outdoor unit. The quote shall also include
Stablizer & necessary MS frame work or civil pedestals for outdoor units
made out of M25 grade cement concrete with necessary re-
inforcement.Capacities shall be as follows:
0
7.1 2.0 TR 0
a Supply Nos. R.O 32,000 40610 45571
b Installation Nos. R.O 1,500 8860
0
8 Supply,installation,testing and commissioning of chilled water cassette
type units complete with three speed evaporator fan motor, fan, 3 row
deep cooling coil, cleanable fabric filter and insulated drain pan enclosed
in plastic casing complete with cord less remote control. All cassette type
units shall be suitable for 220±6% volts, 50 cycles, single phase power
supply. Cassette units shall be of following refrigeration capacities as
listed.Units shall also be capable of handling sensible and latent load
capacities as indicated in the tender.Price quoted shall be inclusive of
factory fitted 2 way motorized modulating chilled water valve, ball valve
with strainer at inlet and ball valve without strainer at outlet.

0
8.1 1 TR / 400 cfm Nos. R.O 19,200 22220 37365
8.2 1.5 TR / 600 cfm Nos. R.O 21,200 24260 40872
8.3 2.325 TR / 660 cfm Nos. 4 21,200 84,800 28770 115,080 35803 143,212
0
0
9 Supply, installation, testing and commissioning of FAN SECTIONS
complete with backward curved DIDW centrifugal fans, motor and belt
drive. The motor shall be squirrel cage and suitable for 415 V + 10%
volts three phase 50cycle, AC supply . Fan section used for fresh air
system shall be provided with 10 microns filter section and only fan
section for exhaust air system. The fan shall be low RPM.The air moving
capacities shall be as follows.
0
9.1 30300 Cfm/40mm static ( First Basement Floor-Car Park Exhaust) No. R.O 196,789 109270 186488
9.2 42500 Cfm/40mm static ( Second Basement Floor-Car Park Exhaust) No. 1 396,672 396,672 213820 213,820 234168 234,168
9.3 22200 Cfm/75mm static ( Terrace Floor) -Ground Floor Kitchen No. 1 287,809 287,809 194630 194,630 232111 232,111
9.3 12900 Cfm/75mm static ( Terrace Floor) -Ground Floor Kitchen No. 1 186,267 186,267 125790 125,790 140111 140,111
9.4 10000 Cfm/75mm static ( Terrace Floor) -Upper Basement Floor Kitchen No. 1 148,069 148,069 99490 99,490 110969 110,969
NOTE: 0
Except the for the car park exhaust fans the other fans shall be with
casing.And for the kitchen exhaust fans the belt and motor should not be
in the Air strem. 0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.5
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
0
10 Supplying, installing, testing and commissioning of double skin
construction draw thru type AIR HANDING UNITS (FAN SECTION
ONLY) as per specification, each complete with squirrel cage induction
motor, forward/backward curved centrifugal fan belt drive and vibration
isolators. Motor shall be suitable for 415±10% volts, 50 cycles, 3 phase
AC supply and static pressure shall be 1.5 inches. The Fresh air fan
sections shall be with 10micron prefilter and the Exhaust fans shall
be without filter.Air moving capacity shall be as follows:

0
LOWER BASEMENT 0
Laundry Ventilation : 0
10.1 7766 Cfm ( Fresh air) Nos. 1 134,684 134,684 80240 80,240 88413 88,413
10.2 7766 Cfm (Exhaust air) Nos. 1 119,048 119,048 72060 72,060 76753 76,753
0
UPPER BASEMENT 0
STP Ventilation : 0
10.3 10000 Cfm ( Fresh air ) Nos. 1 140,747 140,747 83230 83,230 112102 112,102
10.4 10000 Cfm ( Exhaust air ) Nos. 1 125,110 125,110 75230 75,230 100367 100,367
Corridor Ventilation 0
10.5 6575 Cfm ( Fresh air for TFA & AHU) Nos. 1 112,756 112,756 68360 68,360 88413 88,413
10.6 3900 Cfm ( Fresh air for Bakery) Nos. 1 60,331 60,331 49490 49,490 54789 54,789
10.7 3286 Cfm ( Exhaust air for Laundry related areas) Nos. 1 46,497 46,497 41260 41,260 51947 51,947
Kitchen Ventilation : 0
10.8 9000 Cfm (Fresh air ) No. 1 134,684 134,684 80240 80,240 112749 112,749
HVAC/PHE Plant room Ventilation : 0
10.9 28000 Cfm (Fresh air & Exhaust air ) No. R.O 320,159 190650 249083
0
GROUND FLOOR 0
10.10 Kitchen Fresh air-15800 cfm Nos. 1 187,977 187,977 112890 112,890 160650 160,650
10.11 Kitchen Fresh air-14000 cfm Nos. 1 181,225 181,225 109350 109,350 135041 135,041
0
MEZZANINE FLOOR 0
10.12 Fresh air fan for AHU-2913 cfm Nos. 1 49,604 49,604 45160 45,160 53779 53,779
0
TERRACE FLOOR 0
10.13 7000 Cfm -Staricase pressurisation No. 1 114,288 114,288 72060 72,060 88413 88,413
10.14 6000 Cfm -Staricase pressurisation No. 1 94,302 94,302 58710 58,710 70231 70,231
10.15 5000 Cfm -Staricase pressurisation No. 1 56,015 56,015 52470 52,470 70231 70,231
10.16 3000 Cfm -Liftwell pressurisation Nos. 2 46,497 92,994 41260 82,520 54789 109,578
10.17 3600 Cfm No. R.O 46,497 47390 54789
10.18 5400 Cfm No R.O 56,015 55000 70231
0
11 Supplying, installing, testing and commissioning of SISW (Single inlet
single width) centrifugal fan as per specification, with statically and
dynamically balanced backward curved blades, galvanized steel
housing, maintenance free bearings, belt driven complete with totally
enclosed fan cooled squirrel cage induction motor, centrifugal fan belt
drive and vibration isolators. Motor shall be suitable for 415±10% volts,
50 cycles, 3 phase AC supply.

0
0
11.1 10000 Cfm ( Terrace Floor) -Upper Basement Floor Kitchen Exhaust No. R.O 146,994 89670 148530
11.2 12900 Cfm ( Terrace Floor) -Ground Floor Kitchen Exhaust No. R.O 171,464 104070 172856
11.3 22200 Cfm ( Terrace Floor) -Ground Floor Kitchen Exhaust No. R.O 416,471 248250 408946
11.4 35100 Cfm ( Terrace Floor) -Ground Floor Kitchen Exhaust No. R.O 693,200 411100 673810
0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.6
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
12 Supplying, installing, testing and commissioning of ELECTROSTATIC
PRECIPITATION BASED DRY TYPE SCRUBBER UNIT for Kitchen
exhaust. The unit shall be made of 1.0/1.5 mm thick galvanized sheet,
High bake epoxy powder coated, washable aluminum mesh pre-filter,
Stainless steel spiked ionizers to create high voltage DC field. Unit shall
have aluminum collector plates with an average efficiency of 90-95% in
single pass, collector cell should be removable for cleaning.The units
should be able operate on 220V/1 ph/ 50Hz & power consumption not
more than 60 watts per 7500CFM.The unit shall be integrated &
connected with Kitchen Exhaust fan (included in item 7.3 & 7.4) including
all necessary accessories to complete the installation. Air moving
capacities shall be as follows :

0
12.1 For Upper Basement Kitchen- 5000 cfm (For 10000 cfm) Nos 2 183,920 367,839 373120 746,240 87953 175,906
12.2 For Ground Floor Kitchen- 7500 cfm (For 22200 cfm) Nos 3 275,880 827,640 452110 1,356,330 87953 263,859
12.3 For Ground Floor Kitchen- 6500 cfm (For 12900 cfm) Nos 2 239,638 479,277 452110 904,220 87953 175,906
0
13 Supplying, installing, testing and commissioning of weather
proof,corrosion resistant DOUBLE SKIN CONSTRUCTION SCRUBBER
UNIT for Kitchen exhaust. The unit shall comprise of Centrifugal fan of
the below mentioned capacity ,Air intake section with Volume Control
Damper, double bank spray air washer complete with sump, water
circulation pumps (1W+1S/B), stainless steel drain pan along with inter
connecting piping, fittings, eliminators drive along with motorised
actuated damper at discharge.The unit shall be with all necessary
accessories to complete the installation. The make up line for water from
the main tank to the system and drain line from the system to the nearest
drain to be considered in the scope of work.Air moving capacities shall
be as follows :

0
13.1 Upper Basement-Kitchen exhaust- 10000 cfm - 80 mm External static Nos R.O 171,000 191640 372763
13.2 Ground Floor-Kitchen exhaust-12900 cfm - 80 mm External static No. R.O 220,590 245310 521442
13.3 Ground Floor-Kitchen exhaust-22200 cfm - 80 mm External static No. R.O 356,820 420810 992785
13.4 Ground Floor-Kitchen exhaust-35100 cfm - 80 mm External static Nos R.O 564,300 663130 1550097
0
14 Supply of AXIAL FANS for exhaust air suitable for installing in any
position in Horizontal or vertical. The motor shall be totally enclosed fan
cooled squirrel cage and suitable for 415 V + 10% volts three phase
50cycle, AC supply. The fan shall be low RPM.The air moving capacities
shall be as follows: 0
0
14.1 Basement Car parking Exhaust (Emergency Mode fans)
0
14.1.1 41640 Cfm /40mm static ( First Basement Floor) * Nos. 2 320,131 640,263 180110 360,220 167229 334,458
14.1.2 58500 Cfm/40 mm static ( Second Basement Floor) * Nos. 2 393,538 787,077 218510 437,020 183245 366,490
0
14.2 Basement Car parking Fresh air 0
14.2.1 10625 cfm/50 mm static(Second Basement Floor)-with attenuator Nos. 4 336,652 1,346,609
sections on both side of the fan - * 186380 745,520 80972 323,888
0
14.3 Basement Car parking Exhaust(Normal Mode fans) 0
14.3.1 15150 cfm/25 mm static (First Basement Floor)-with attenuator sections Nos. 2 189,704 379,408
on both side of the fan - * 110440 220,880 68288 136,576
14.3.2 21250 cfm/25 mm static (Second Basement Floor)-with attenuator Nos. R.O 235,539
sections on both side of the fan 136580 253410
14.3.3 30300 cfm/25 mm static (First Basement Floor)-with attenuator sections Nos. R.O 309,222
on both side of the fan 178360 330819
14.3.4 42500 cfm/25 mm static (Second Basement Floor)-with attenuator Nos. R.O 454,542
sections on both side of the fan 256220 480975
0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.7
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
14.4 DG Ventilation: 0
14.4.1 33000 Cfm/40 mm static ( Fresh & Exhaust ) Nos. 4 254030 1,016,118 151330 605,320 150710 602,840
0
14.5 HVAC/PHE Plant Ventilation : 0
14.5.1 28000 Cfm/40 mm static ( Fresh & Exhaust )-with attenuator sections on Nos. 2 326,810 653,619
both side of the fan 189400 378,800 102797 205,594
NOTE: 0
* - The fans shall be selected for 2 HRS Fire rating for a rated duration of
2 Hrs. 0
0
15 Supplying, installing, testing and commissioning of Rectangular IN-Line
fans (FAN SECTION ONLY) as per specification, each complete with
totally enclosed fan cooled squirrel cage induction motor, centrifugal fan
direct drive and vibration isolators. Motor shall be suitable for 220±10%
volts, single phase AC supply and static pressure shall be 30mm WG.
0
0
Toilet Exhaust : 0
15.1 2200 Cfm ( Mezzanine Floor Toilet Exhaust ) No. 1 25,375 25,375 22440 22,440 28577 28,577
15.2 1200 Cfm ( Ground Floor Toilet Exhaust ) No. 2 21,326 42,652 19260 38,520 23445 46,890
15.3 180 Cfm ( Guest room Toilet Exhaust-Terrace Floor) No. 1 14,105 14,105 15790 15,790 18630 18,630
15.4 360 Cfm ( Guest room Toilet Exhaust-Terrace Floor) Nos. 7 18,019 126,132 19500 136,500 23080 161,560
15.5 720 Cfm ( Guest room Toilet Exhaust-Terrace Floor) Nos. 9 18,019 162,170 19500 175,500 23080 207,720
15.6 1200 Cfm ( Guest room Toilet Exhaust-Terrace Floor) Nos. 2 21,326 42,652 22610 45,220 27487 54,974
Mezzanine Floor: 0
15.7 1520 Cfm ( Mezzanine Floor -Fresh air for AHU ) No. 1 21,326 21,326 19260 19,260 23445 23,445
0
16 Supplying, installing, testing and commissioning of direct driven
PROPELLER FANS Each fan shall be complete with permanent split
capacitor or shaded pole motor with suitable starter, power and control
cabling, earthing etc. upto the equipment mounting plate speed
regulator for single phase fan accessories like wire guard, birdscreen,
gravity louvers for weather protection as required. Fan selection
arrangement and Electrical characteristics shall be as follows :

0
16.1 300 mm dia fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.
(Upper Basement Storage Area Exhaust) Nos. 1 13,153 13,153 8910 8,910 7862 7,862
0 0
17 Supplying, installing, testing and commissioning of single phase circular
in-line fan of capacity 600 CFM against 20 mm static Nos. R.O 14,155 9450 16649
0 0
18 Supplying, installing, testing and commissioning of single phase circular
in-line fan of capacity 100 CFM against 20 mm static(Mezzanine Floor-
Chairman's toilet Exhaust ) No. 1 7,508 7,508 5900 5,900 9704 9,704
0 0
19 Supplying, installing, testing and commissioning of single phase circular
in-line fan of capacity 210 CFM against 20 mm static(Mezzanine Floor-
Fresh air fan for AHU ) No. 1 9,672 9,672 7060 7,060 11754 11,754
0 0
20 Supplying, installing, testing and commissioning of single phase circular
in-line fan of capacity 376 CFM against 20 mm static(Mezzanine Floor-
Fresh air for AHU's ) No. 1 9,672 9,672 7060 7,060 11754 11,754
0 0
21 Supplying, installing, testing and commissioning of single phase circular
in-line fan of capacity 676 CFM against 20 mm static(Mezzanine Floor-
Fresh air for AHU's ) No. 1 14,155 14,155 9450 9,450 16003 16,003

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.8
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
Jet Fans: 0
22 Jet fans shall be complete with sound attenuators with protection grille at
both sides. Fan motor shall be of two speed to operate on normal mode
and fire mode. Fans shall be selected for 2 hours fire rating. Air quantity
under normal mode shall be 1906cfm and 3813cfm at fire mode. (The
actual number of jet fans required should be confirmed based on
the CFD analysis)
0
22.1 Lower Basement Nos. 11 93,480 1,028,280 52060 572,660 109854 1,208,394
22.2 Upper Basement Nos. 7 93,480 654,360 52060 364,420 116404 814,828
0
23 Micro processor panel for the Lower basement having 11 jet fans,1
no. 42500 cfm DIDW normal exhaust fan,4 nos. 10650 cfm normal fresh
air Tube Axial fans and 2 nos. of 58500 cfm emergency Tube axial fans
complete with starter, overload relay protection, internal power & control
wiring etc., Quoted price shall be inclusive of 5Nos. of Carbon Monoxide
(CO) sensors, logic controllers, CFD analysis and necessary wiring.
No. 1 607,237 607,237 568330 568,330 541774 541,774
0
24 Micro processor panel for the Upper basement having 7 jet fans,1 no.
15150 cfm Tube Axial normal exhaust fans and 2 nos. of 41640 cfm
emergency Tube axial fans complete with starter, overload relay
protection, internal power & control wiring etc., Quoted price shall be
inclusive of 5Nos. of Carbon Monoxide (CO) sensors, logic controllers,
CFD analysis and necessary wiring.
No. 1 329,259 329,259 383100 383,100 312561 312,561
SUB TOTAL COST 17,915,929 12,643,670 12,669,954

TOTAL CARRIED TO SUMMARY

C CONDENSER AND CHILLED WATER PIPING:

1 Providing and fixing in position the following MS class ‘C’ pipes for
chilled water and condenser water piping cut to required lengths and
installed with all welded joints, providing and fixing in position the
necessary fittings like elbows, tees and reducers, mating flanges &
sockets complete with supports as per specifications.
0
1.1 300 mm dia MS pipes RM R.O 4,998 5770 4506
0
1.2 250 mm dia MS pipes RM 155 3,451 534,905 4930 764150 3774 584,970
0
1.3 200 mm dia MS pipes RM 165 2,943 485,595 3910 645150 2925 482,625
0
1.4 150 mm dia MS pipes RM 50 2,280 114,000 2090 104500 1515 75,750
0
1.5 125 mm dia MS pipes RM 110 1,553 170,830 1820 200200 1284 141,240
0
1.6 100 mm dia MS pipes RM 165 1,338 220,770 1400 231000 1029 169,785
0
1.7 80 mm dia MS pipes RM 168 1,070 179,760 990 166320 743 124,824
0
1.8 65 mm dia MS pipes RM 60 750 45,000 790 47400 610 36,600
0
1.9 50 mm dia MS pipes RM 60 606 36,360 630 37800 464 27,840
0
1.10 40 mm dia MS pipes RM 420 477 200,340 450 189000 357 149,940
0
1.11 32 mm dia MS pipes RM 660 361 238,260 390 257400 301 198,660
0
1.12 25 mm dia MS pipes RM 655 330 216,150 310 203050 226 148,030
0
1.13 20 mm dia MS pipes RM 1440 228 328,320 250 360000 169 243,360

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.9
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
0
2 Providing and fixing in position the following GI class ‘B’ pipes for
chilled water and condenser water piping cut to required lengths and
installed with all welded joints, providing and fixing in position the
necessary fittings like elbows, tees and reducers, mating flanges &
sockets complete with supports as per specifications. 0
0
2.1 300 mm dia GI pipes RM 230 4,398 1,011,540 6530 1501900 3607 829,610
0 0
2.2 200 mm dia GI pipes RM 100 2,888 288,800 4350 435000 2441 244,100
0
3 Providing and fixing in position the following butterfly valves complete
with insulation as per specifications: 0
0
3.1 300 mm dia Valves. Nos. 3 21,287 63,861 17030 51090 28735 86,205
0 0
3.2 250 mm dia Valves. No 3 17,049 51,147 11430 34290 22523 67,569
0 0
3.3 200 mm dia Valves. Nos. 36 17,049 613,764 8610 309960 10826 389,736
0 0
3.4 150 mm dia Valves. Nos. 8 6,384 51,072 4790 38320 5869 46,952
0 0
3.5 125 mm dia Valves. Nos. 2 5,945 11,890 4380 8760 5190 10,380
0 0
3.6 100 mm dia Valves. Nos. 4 4,731 18,924 3550 14200 4141 16,564
0 0
3.7 80 mm dia Valves. No. 4 3,781 15,124 2780 11120 3275 13,100
0 0
3.8 65 mm dia Valves. Nos. 17 3,251 55,267 2600 44200 2863 48,671
0 0
3.9 50 mm dia Valves. Nos. 18 2,894 52,092 2300 41400 2515 45,270
0
4 Providing and fixing in position the following Motorised butterfly valves
complete as per specifications: 0
0
4.1 250 mm dia Valves. Nos. R.O. 62,500 32000 73457
0 0
4.2 200 mm dia Valves. Nos. 10 50,000 500,000 26660 266600 47709 477,090
0
5 Providing and fixing in position the following manual balancing valves
complete with insulation as per specifications 0
0
5.1 250 mm dia Valves. Nos. R.O. 82,798 54600 61430
0 0
5.2 200 mm dia Valves. Nos. 16 70,000 1,120,000 46550 744800 52128 834,048
0 0
5.3 150 mm dia Valves. Nos. 0 35,975 24120 0 26957
0 0
5.4 100 mm dia Valves. Nos. 2 18,404 36,808 12430 24860 13723 27,446
0 0
5.5 80 mm dia Valves. Nos. 2 10,941 21,882 7370 14740 8160 16,320
0 0
5.6 65 mm dia Valves. Nos 7 11,852 82,964 8220 57540 8923 62,461
0 0
5.7 50 mm dia Valves. Nos. 9 7,979 71,811 5180 46620 5913 53,217
0 0
5.8 40 mm dia Valves. Nos. 28 5,310 148,680 4440 124320 3887 108,836
0 0
5.9 32 mm dia Valves. Nos. 14 4,296 60,144 3980 55720 3121 43,694
0 0
5.10 25 mm dia Valves. Nos 5 3534 17,670 3530 17650 2429 12,145
0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.10
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
6 Providing and fixing in position of the following ball valves complete
with insulation as per specifications : 0
0
6.1 40 mm dia Valves. Nos. 59 1,800 106,200 1990 117410 1786 105,374
0 0
6.2 32 mm dia Valves. Nos. 31 1,500 46,500 1680 52080 1503 46,593
0 0
6.3 25 mm dia Valves. Nos. 117 1,300 152,100 1340 156780 1144 133,848
0 0
6.4 20 mm dia Valves. Nos. R.O. 1,000 1190 1009
0
7 Providing and fixing in position of the following ball valves with Y
Strainers complete with insulation as per specifications : 0
0
7.1 25 mm dia Valves. Nos. R.O. 1,600 1750 1628
0 0
7.2 20 mm dia Valves. Nos. R.O. 1,600 1640 1518
0
8 Providing and fixing in position the following check valves complete with
insulation as per specifications : 0
0
8.1 200 mm dia valves Nos. 8 13,700 109,600 10890 87120 13187 105,496
0 0
8.2 150 mm dia valves Nos. 3 10,275 30,825 6860 20580 8164 24,492
0
9 Providing and fixing in position the following 'Y' strainers complete with
insulation as per specifications : 0
0
9.1 250 mm dia Valves. Nos. R.O. 15,000 13360 19469
0 0
9.2 200 mm dia Valves. Nos. 8 12,000 96,000 9410 75280 12787 102,296
0 0
9.3 150 mm dia Valves. Nos. 3 9,000 27,000 6070 18210 8264 24,792
0 0
9.4 100 mm dia Valves. Nos. R.O. 6,000 3820 4817
0 0
9.5 80 mm dia Valves. Nos. 2 4,800 9,600 3020 6040 4068 8,136
0 0
9.6 65 mm dia Valves. Nos 7 3,900 27,300 2720 19040 3445 24,115
0 0
9.7 50 mm dia Valves. Nos. 8 3,000 24,000 2440 19520 2923 23,384
0 0
9.8 40 mm dia Valves. Nos. 4 2,400 9,600 1880 7520 2190 8,760
0 0
9.9 32 mm dia Valves. Nos. 11 1,920 21,120 1760 19360 2079 22,869
0 0
9.10 25 mm dia Valves. Nos 5 1,500 7,500 1660 8300 1922 9,610
0
10 Providing and fixing in position the following Pot strainers 0
0
10.1 200 mm dia Nos. 3 23,460 70,380 17100 51300 21171 63,513
0 0
10.2 250 mm dia Nos. 1 27,020 27,020 34690 34690 31147 31,147
0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.11
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
11 Supply, installation, testing and commissioning of flexible connections
of suitable pressure rating to be installed at pumps and
chillers/condenser suction and discharge. 0

11.1 200 mm dia pipes Nos. 24 7,530 180,720 6140 147360 5531 132,744
0 0
11.2 150 mm dia pipes Nos. 6 5,270 31,620 4600 27600 4589 27,534
0
12 Supplying, installation, testing and commissioning of Auto air vents Nos. 80 1,030 82,400 1010 80800 985 78,800
0 0
13 Providing and fixing in position the industrial type pressure gauges with
gun metal valves. Nos 104 1,220 126,880 1390 144560 1026 106,704
0 0
14 Providing and fixing in position the mercury-in- glass industrial type
thermometers. Nos 82 1,220 100,040 1390 113980 1026 84,132
0 0
15 Providing and installing of 1000 liters capacity Sintex Expansion Tank.
Tank shall be provided with float valve of 40 mm dia, necessary inlet /
outlet / overflow connections. Quoted price inclusive of 32mm thick
nitrile rubber insulation and finished with protective coating for the
following capacities. No. 18893 0
0
16 Supply, installation, testing and commissioning of an insulated roof
mounted chilled water expansion tank, 6 mm thick MS plate construction.
The tank shall be sized 1200 mm x 1200 m x 1200 mm high complete
with necessary connection for piping and vent. Insulation shall be
covered with sand cement plaster and water proofing.
No. R.O 31,000 145480 0 251912
0
17 Supplying, installing, testing and commissioning of CLOSED LOOP
PRESSURISED CHILLED WATER EXPANSION TANK suitable for total
volume of water in chilled water circuits along with necessary
accessories such as pumps (1working +1standby),2 Nos. pressure
switches, 2 Nos. connections to chilled water pump header(to be
supplied by low side contractor) etc. in order to keep chilled water
system under pressure and to prevent entrapment of pressure. The tank
shall be pre-charged steel expansion tank with replaceable heavy duty
butyl rubber bladder. The tank shall have 50 mm system connection and
20 mm drain and charging valve connection to facilitate the on site
charging of the tank to meet system requirement. The tank shall be fitted
with lifting rings and a floor mounting skirt for vertical installation. The
tank must be constructed in accordance with section VIII of the ASME
Boiler and pressure vessel code and stamped 125 PSI working pressure.
The complete system shall be sourced from single manufacturer and
supplied and installed with all accessories and safety fixtures required
for proper functioning of the

complete hydronic system 0


17.1 Tank capacity 500 Liters / Maximum operating pressure 16 Bar Nos 1 106,500 106,500 113490 113490 100445 100,445
0
18 The centrifugal air separator along with necessary accessories and
supports, to prevent entrapment of air in the system.The separator must
be constructed in accordance with section 8 of ASME boiler and
pressure veassal code and stamped 125psi working pressure.The tank
shall be fitted with lifting rings and floor mounting skirt for vertical
installation.The air separator shall be sized for 1200 GPM flow rate and
90% air separation efficiency.The air seperator shall be suitably sized for
Header size 250-mm dia.

18.1 Air seperator of capacity 1764 GPM(250 mm dia) for chilled water circuit Nos 1 43,540
50660 50660 37012 37,012
0 0
19 Structural Steel supports for positioning the pumps Kgs 1000 44 44,000 120 120,000 76 76,000

SUB TOTAL COST 8,544,175 8,540,740 7,194,834

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.12
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT

D AIR DISTRIBUTION

1 Supply, Fabrication, installation and testing of factory fabricated sheet


metal ducting complete with flanges in accordance with the approved
shop drawings and as required by the specifications as per SMACNA
standards.

Maximum Gauge Joint


Duct Size
1.1 UPTO 700 mm 26 4 BOLT TDC Sqm 2250 610 1,372,500 580 1,305,000 728 1,638,000
1.2 701 - 900 mm 24 4 BOLT TDC Sqm 600 610 366,000 670 402,000 824 494,400
1.3 901-1000 mm 22 4 BOLT TDC Sqm 90 680 61,200 770 69,300 918 82,620
1.4 1001-1200 mm 22 4 BOLT JTR Sqm 130 680 88,400 770 100,100 918 119,340
1.5 1201-2100 mm 20 4 BOLT JTR Sqm 220 780 171,600 910 200,200 1020 224,400
1.6 2101-2400 mm 18 4 BOLT JTR Sqm 20 920 18,400 1080 21,600 1190 23,800
1.7 2401-2700 mm 16 4 BOLT JTR Sqm 30 820 24,600 1320 39,600 1470 44,100
0 0
2 Supply, Fabrication, installation and testing of sheet metal ducting (For
above 500 Pa ESP-For Kitchen Exhaust)complete with flanges in
accordance with the approved shop drawings and as required by the
specifications. 0 0
0 0
Maximum Gauge Joint 0 0
Duct Size 0 0
0 0
2.1 UPTO 450 mm 26 4 BOLT TDC Sqm 55 610 33,550 580 31,900 728 40,040
2.2 451 -750 mm 24 4 BOLT TDC Sqm 220 610 134,200 670 147,400 824 181,280
2.3 751-900 mm 22 4 BOLT TDC Sqm 15 680 10,200 770 11,550 918 13,770
2.4 900-1000 mm 22 4 BOLT JTR Sqm 10 680 6,800 770 7,700 918 9,180
2.5 1001-1200 mm 20 4 BOLT JTR Sqm 160 780 124,800 910 145,600 1020 163,200
2.6 1201-1800 mm 18 4 BOLT JTR Sqm 85 920 78,200 1080 91,800 1190 101,150
2.7 1801-2400 mm 16 4 BOLT JTR Sqm 300 820 246,000 1320 396,000 1470 441,000
0 0
3 Supply, assembling, installation,testing of factory fabricated pre
insulated double walled spiral ducts and duct fittings like Flanges,
gaskets, Bends, Reducers, Tees, Branch collars , offsets and end caps.
The insulation material shall be 25 mm thick, 24 kg/cum density
fibreglass covered with fibregalss tissue paper. The quoted price
inclusive of supports. The distance between supports shall not exceed
2400mm. The ducts shall be in accordance with the approved shop
drawings and as required by the specifications.
0 0
0 0
Duct Size Inner Gauge Outer Gauge 0 0
0 0
3.1 UPTO 650 mm 24 24 Sqm 50 3,150 157,500 1780 89,000 2501 125,050
3.2 675 - 900 mm 22 22 Sqm 50 4,500 225,000 2180 109,000 3074 153,700
3.3 925 -1250 mm 20 20 Sqm R.O 6,300 2690 3838
0 0 0
4 Supply, fabrication, installation and testing the flexible connections
constructed of fire resistance flexible double canvas sleeve as per the
approved shop drawings. Nos. 48 3,600 172,800 2530 121,440 2083 99,984
0 0 0 0
5 Supply, installation and testing of galvanized steel construction Louver
dampers within ducts to be provided with suitable ducts lever and
quadrants for manual control of volume of air flow and for proper
balancing of the air distribution system. Sqm 25 6,280 157,000 5120 128,000 9088 227,200

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.13
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
0 0 0
6 Supply, installation, testing and commissioning of motorised combined
smoke & fire damper complete with control panel, inter connecting wiring
at locations shown in approved shop drawings and as per specifications.
0 0 0
6.1 Supply and installation of motorized Smoke & Fire Dampers complete
with 150mm casing and 1.6 mm GSS 400mm long sleeve, with spring
return type motorized actuators as per specifications. The fire dampers
shall be UL 555 - 1995 certified for a rating of 90 Mins.Sizes shall be as
follows:
0 0 0

FOR AHU'S (IN SUPPLY & RETURN AIR DUCTS) AND IN FRESH AIR
SUPPLY UNITS(SUPPLY DUCTS ONLY)
0 0 0
WIDTH HEIGHT 0 0 0
6.1.1 500 250 Nos. 1 12,946 12,946 9630 9,630 8770 8,770
6.1.2 1000 500 Nos. 1 17,880 17,880 12920 12,920 12417 12,417
6.1.3 600 250 Nos. 1 17,922 17,922 9900 9,900 9065 9,065
6.1.4 300 300 Nos. 1 12,543 12,543 9250 9,250 8356 8,356
6.1.5 650 400 Nos. 1 15,118 15,118 11090 11,090 10365 10,365
6.1.6 800 750 Nos. 1 19,269 19,269 13850 13,850 13441 13,441
6.1.7 250 300 Nos. 1 12,543 12,543 9090 9,090 8180 8,180
6.1.8 600 600 Nos. 1 15,935 15,935 11620 11,620 10982 10,982
6.1.9 1350 300 Nos. 1 16,560 16,560 12040 12,040 11443 11,443
6.1.10 650 350 Nos. 1 14,595 14,595 10740 10,740 9981 9,981
6.1.11 400 300 Nos. 1 12,865 12,865 9580 9,580 8711 8,711
6.1.12 700 250 Nos. 1 13,751 13,751 10170 10,170 9361 9,361
6.1.13 600 250 Nos. 1 13,347 13,347 9900 9,900 9065 9,065
6.1.14 500 250 Nos. 2 12,943 25,886 9630 19,260 8770 17,540
6.1.15 800 300 Nos. 1 14,796 14,796 10880 10,880 10128 10,128
6.1.16 950 400 Nos. 1 16,213 16,213 11810 11,810 11186 11,186
6.1.17 1200 850 Nos. 1 23,032 23,032 16180 16,180 16146 16,146
6.1.18 1200 750 Nos. 1 21,608 21,608 18040 18,040 15105 15,105
6.1.19 800 750 Nos. 2 19,269 38,538 13850 27,700 13441 26,882
6.1.20 1300 700 Nos. 1 26,353 26,353 15330 15,330 15192 15,192
6.1.21 900 300 Nos. 1 15,279 15,279 11200 11,200 10483 10,483
6.1.22 1000 350 Nos. 1 15,796 15,796 11530 11,530 10879 10,879
6.1.23 400 450 Nos. 1 13,830 13,830 10230 10,230 9419 9,419
6.1.24 650 250 Nos. 1 13,550 13,550 10040 10,040 9212 9,212
6.1.25 800 700 Nos. 1 18,714 18,714 13480 13,480 13031 13,031
6.1.26 800 500 Nos. 1 16,491 16,491 11990 11,990 11391 11,391
6.1.27 750 600 Nos. 1 17,186 17,186 12180 12,180 11904 11,904
6.1.28 800 450 Nos. 1 15,935 15,935 11620 11,620 11391 11,391
6.1.29 900 300 Nos. 1 15,279 15,279 11200 11,200 10483 10,483
6.1.30 750 350 Nos. 1 15,328 15,328 10930 10,930 10394 10,394
6.1.31 450 350 Nos. 2 13,468 26,936 9980 19,960 9153 18,306
6.1.32 650 300 Nos. 2 14,073 28,146 10390 20,780 9597 19,194
6.1.33 450 450 Nos. 1 14,192 14,192 10470 10,470 9685 9,685
6.1.34 300 250 Nos. 1 12,543 12,543 9090 9,090 8180 8,180
6.1.35 450 300 Nos. 1 13,107 13,107 9740 9,740 8887 8,887
6.1.36 750 300 Nos. 1 14,556 14,556 10710 10,710 9952 9,952
6.1.37 500 300 Nos. 1 13,347 13,347 9900 9,900 9065 9,065
6.1.38 350 300 Nos. 1 12,624 12,624 9410 9,410 8534 8,534
6.1.39 750 750 Nos. 3 18,750 56,250 13500 40,500 13057 39,171
6.1.40 1200 600 Nos. 1 19,473 19,473 9630 9,630 13542 13,542
6.1.41 1250 600 Nos. 1 19,829 19,829 15250 15,250 13802 13,802
6.1.42 1000 600 Nos. 1 19,269 19,269 13850 13,850 13441 13,441
6.1.43 1300 700 Nos. 1 21,726 21,726 15330 15,330 15192 15,192
6.1.44 1100 450 Nos. 1 17,811 17,811 12880 12,880 12365 12,365
6.1.45 900 600 Nos. 2 18,437 36,874 13300 26,600 12826 25,652
6.1.46 700 500 Nos. 2 15,796 31,592 12070 24,140 10879 21,758
6.1.47 1050 550 Nos. 1 18,957 18,957 13640 13,640 13210 13,210
6.1.48 500 450 Nos. 1 14,556 14,556 10710 10,710 9952 9,952
0 0 0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.14
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
7 Supply, installation, testing and balancing of powder coated Extruded
Supply/return air Aluminium Grilles in accordance with the approved
shop drawings and specifications. 0 0 0
0 0 0
7.1 With horizontal fixed bars Sqm. 100 9,000 900,000 3910 391,000 7688 768,800
0 0 0 0
8 Supply and installation of aluminum opposed blade collar dampers Sqm 84 1,500 126,000 3730 313,320 5103 428,652
0 0 0
9 Supply, installation,testing and balancing of aluminum powder coated
square ceiling supply air diffusers with removable core and anti
smudge ring and volume control dampers as per approved shop
drawings and specifications with standard flange size. 0 0 0
Powder coated extruded aluminium construction. 0 0 0
NECK SIZE 0 0 0
9.1 150x150 Nos. 153 1,200 183,600 940 143,820 802 122,706
9.2 225x225 Nos. 61 1,800 109,800 1030 62,830 1108 67,588
9.3 300x300 Nos. 32 1,900 60,800 1190 38,080 1482 47,424
9.4 375x375 Nos. 28 2,000 56,000 1580 44,240 1948 54,544
9.5 450x450 Nos. 10 2,200 22,000 2090 20,900 2468 24,680
9.6 525x525 Nos. 20 2,500 50,000 2730 54,600 3278 65,560
0 0 0
10 Supply, installation,testing and balancing of aluminum powder coated
square ceiling return air diffusers with removable core and anti smudge
ring and without volume control dampers as per approved shop drawings
and specifications with standard flange size.
0 0
Powder coated extruded aluminium construction. 0 0 0
NECK SIZE 0 0 0
10.1 150x150 Nos. R.O 1,000 470 642
10.2 225x225 Nos. 34 1,160 39,440 520 17,680 832 28,288
10.3 300x300 Nos. 32 1,550 49,600 590 18,880 1031 32,992
10.4 375x375 Nos. 28 1,800 50,400 860 24,080 1290 36,120
10.5 450x450 Nos. 10 1,800 18,000 1210 12,100 1566 15,660
10.6 525x525 Nos. 20 2,000 40,000 2060 41,200 2101 42,020
0 0
11 Supply, installation, testing and balancing of 2-slot powder coated
aluminum slot diffusers out of extruded aluminum construction. RMT R.O 600 650 1382
0 0 0 0
12 Supply, installation, testing and balancing of hit and miss dampers
suitable for above slot diffusers RMT R.O 600 340 217
0 0 0 0
13 Supply, installation, testing and balancing of 3-slot powder coated
aluminum slot diffusers out of extruded aluminum construction. RMT R.O 900 920 1872
0 0 0
14 Supply, installation, testing and balancing of hit and miss dampers
suitable for above slot diffusers RMT R.O 900 460 279
0 0 0
15 Supply, installation, testing and balancing of aluminum powder coated
fresh air intake and exhaust louvers complete with bird mesh and
damper Sqm. 15 5,000 75,000 6300 94,500 13577 203,655
0 0 0
16 Supply, installation, testing and balancing of aluminum anti-backdraft
dampers as per specifications Sqm. 2 3,000 6,000 5610 11,220 7855 15,710
0 0 0 0

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.15
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
17 Supply, installation, testing and balancing of plenum of size 200 x 200 x
200 mm for connecting Toilet exhaust air grille and flexible duct with
necessary fittings for ceiling mounting made of 24G GSS as per
approved drawings and specifications. Nos. 210 500 105,000 670 140,700 642 134,820
0 0 0
18 Supply, installation, testing and balancing of acoustically lined plenum of
size for connecting supply air diffusers and flexible duct with necessary
fittings for ceiling mounting, made of 24G GSS lined with 25mm thick
fiber glass & 28G perforated Aluminium sheet, selected for 500fpm outlet
velocity as per approved drawings and specifications.
0 0 0
DIFFUSER NECK SIZE 0 0 0
18.1 150x150 Nos. 153 400 61,200 990 151,470 764 116,892
18.2 225x225 Nos. 61 450 27,450 1310 79,910 1031 62,891
18.3 300x300 Nos. 32 500 16,000 1520 48,640 1329 42,528
18.4 375x375 Nos. 28 600 16,800 1840 51,520 1719 48,132
18.5 450x450 Nos. 10 700 7,000 2160 21,600 2239 22,390
18.6 525x525 Nos. 20 800 16,000 2580 51,600 2667 53,340
0 0 0
19 Supply and installation of factory fabricated insulated round flexible
ducting connecting main / branch ducts to diffuser plenum 0 0 0
0 0 0
19.1 100 mm dia Rmts 500 160 80,000 170 85,000 304 152,000
19.2 150 mm dia Rmts 230 180 41,400 210 48,300 324 74,520
19.3 200 mm dia Rmts 92 205 18,860 250 23,000 358 32,936
19.4 250 mm dia Rmts 48 250 12,000 290 13,920 406 19,488
19.5 300mm dia Rmts 42 270 11,340 340 14,280 452 18,984
19.6 350mm dia Rmts 45 320 14,400 390 17,550 521 23,445
0 0 0
20 Supplying, installing and testing of rigid PVC pipes for condensate drain
complete with using solvent welded PVC fittings like Tees, Elbows,
Couplers, Unions, Reducers, brushings etc. structural steel supports as
required / directed at site including cutting chases and fitting the same
with cement concrete / cement mortar as required. 0 0 0
0 0 0
20.1 50 mm dia PVC pipes RM 50 293 14,650 160 8,000 252 12,600
20.2 40 mm dia PVC pipes RM 367 247 90,649 120 44,040 202 74,134
20.3 25 mm dia PVC pipes RM 1242 155 192,510 70 86,940 126 156,492
0
SUB TOTAL COST 6,871,525 6,248,080 0 7,802,996
.. 0
E. TOILET EXHAUST SYSTEM - GUEST ROOM TOILETS 0
0
1 Supplying, laying, jointing, testing and commissioning of approved make
UPVC pipes SWR pipe for GUEST ROOM TOILET EXHAUST laid inside
the shaft, cut to required lengths including all necessary fittings and
specials such as Bends, junctins, offsets, tees,access pieces. Fixing at
wall/ceiling levelby necessary supports by clamps & hangers etc. Making
proper connection with cement solvent/rubber ring joint of required depth
including cutting, chases/holes in walls, etc., and making good the same
after pipe have been duly laid and tested completely.

0
0
1.1 110 mm dia Rmts 520 83 43,160 210 109,200 271 140,920
1.2 150 mm dia Rmts 1400 200 280,000 380 532,000 597 835,800
1.3 200 mm dia Rmts 100 300 30,000 570 57,000 951 95,100
1.4 250 mm dia Rmts 20 400 8,000 840 16,800 1486 29,720

TOTAL CARRIED TO SUMMARY 361,160 715,000 1,101,540

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.16
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
F THERMAL INSULATION
1 Supply, installation and testing of acoustic lining with in supply air ducts
as per the specifications. All ducts shown cross hatched on the
approved shop drawings shall be provided with acoustic lining as per the
specifications.

1.1 Acoustic lining of ducts out of 25mm thick 32 Kgs/Cub Mtr density
fiberglass wool covered with RP tissue and finished with 26 gauge
perforated Aluminum sheet.as per specifications SQM. 600 400 240,000 380 228,000 633 379,800
0 0 0
2.1 19 mm thick closed cell elatomeric Nitrile rubber insulation for supply air
in return air path.Ducts to be cleaned, approved adhesive to be applied
All longitudinal and transverse joints shall be sealed by providing 6 mm
thick 50 mm wide nitrile rubber tape. The adhesive shall be strictly as
recommended by the manufacturer. SQM. 1890 550 1,039,500 510 963,900 463 875,070
0 0 0
2.2 25 mm thick closed cell elatomeric Nitrile rubber insulation for treated
fresh air ducting.Ducts to be cleaned, approved adhesive to be applied
All longitudinal and transverse joints shall be sealed by providing 6 mm
thick 50 mm wide nitrile rubber tape. The adhesive shall be strictly as
recommended by the manufacturer. SQM. 600 500 300,000 810 486,000 598 358,800
0 0
3 Supply and installation of acoustic lining of walls and ceilings of AHU
rooms out of 50mm thick fibreglass insulation material of density 32
KG/Cub.Mtr fixed on 22 gauge 25mm x 50 mm GI channels in 600 x
600mm grid covered with fibreglass tissue paper and 26 gauge
perforated aluminum sheets as per the approved shop drawings &
specifications.
0 0
0 0
3.1 50 mm thick acoustic lining. SQM. 640 400 256,000 700 448,000 991 634,240
0 0 0
4 Supply and installation of 25 mm thick Nitrile rubber insulation for Under
deck insulation for the Air conditioned area roof exposed to Sun. SQM. R.O 725 880 728
0 0 0
5 Supply and installation of Underdeck insulation for exposed concrete
slab with 50 mm Thick TF grade EPS material of density 32kg/m3 with
all top quality bitumen, shalikote,28 guage wire net and framework with
all other accessories to complete the installation.
SQM. 2300 800 1,840,000 250 575,000 381 876,300
0 0
6 Thermal insulation of chilled water and condensate piping: 0 0
0 0
6.1 Supplying, installing and testing of 25 mm thick insulation with protective
coating out of 7 mil thick fiberglass fabric covered with one coat of epoxy
or fire proof acrylic compound on chilled water and condensate drain
piping and fitting like valves, flanges union, etc. as per the approved
shop drawings and specifications.. All longitudinal and transverse joints
shall be sealed by providing 6 mm thick, 50 mm wide nitrile rubber tape.
The adhesive shall be strictly as recommended by the manufacturer.
0 0
0 0
6.1.1 25 mm dia MS pipes RM 655 425 278,375 380 248,900 271 177,505
0 0 0
6.1.2 20 mm dia MS pipes RM 1440 400 576,000 370 532,800 253 364,320

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.17
RAS ADYAR HOTELS PVT LTD HVAC TAAMAESEK

HVAC BOQ
TMA VOLTAS STERLING WILSON
SL. NO. DESCRIPTION UNIT QTY RATE AMOUNT
RATE AMOUNT RATE AMOUNT
0 0
6.2 Supplying, installing and testing of 32 mm thick insulation with protective
coating out of 7 mil thick fiberglass fabric covered with one coat of epoxy
or fire proof acrylic compound on chilled water and condensate drain
piping and fitting like valves, flanges union, etc. as per the approved
shop drawings and specifications.. All longitudinal and transverse joints
shall be sealed by providing 6 mm thick, 50 mm wide Nitrile rubber tape.
The adhesive shall be strictly as recommended by the manufacturer.
0 0
0 0
6.2.1 80 mm dia MS pipes RM 168 666 111,888 890 149,520 553 92,904
0 0 0
6.2.2 65 mm dia MS pipes RM 60 565 33,900 750 45,000 500 30,000
0 0 0
6.2.3 50 mm dia MS pipes RM 60 487 29,220 590 35,400 448 26,880
0 0 0
6.2.4 40 mm dia MS pipes RM 420 412 173,040 510 214,200 413 173,460
0 0 0
6.2.5 32 mm dia MS pipes RM 660 385 254,100 460 303,600 384 253,440
0 0
6.3 Supplying, installing and testing of 38 mm thick (19 mm + 19 mm or any
equivalent thickness in two layers) insulation with protective coating out
of 7 mm thick fiberglass fabric covered with one coat of epoxy or fire
proof acrylic compound on chilled water and condensate drain piping and
fitting like valves, flanges union, etc. as per the approved shop drawings
and specifications.. All longitudinal and transverse joints shall be sealed
by providing 6 mm thick, 50 mm wide Nitrile rubber tape. The adhesive
shall be strictly as recommended by the manufacturer.

0 0
0 0
6.3.1 300 mm dia MS pipes RM R.O 1,800 2100 1454
0 0 0
6.3.2 250 mm dia MS pipes RM 155 1,530 237,150 1750 271,250 1268 196,540
0 0 0
6.3.3 200 mm dia MS pipes RM 165 1,280 211,200 1420 234,300 1081 178,365
0 0 0
6.3.4 150 mm dia MS pipes RM 50 1,031 51,550 1100 55,000 895 44,750
0 0 0
6.3.5 125 mm dia MS pipes RM 110 913 100,430 910 100,100 802 88,220
0 0 0
6.3.6 100 mm dia MS pipes RM 165 792 130,680 750 123,750 708 116,820
0 0
6.4 Supplying, installing and testing of 13 mm thick insulation with protective
coating out of 7 mm thick fiberglass fabric covered with one coat of
epoxy or fire proof acrylic compound on condensate drain piping as per
the approved shop drawings and specifications. The adhesive shall be
strictly as recommended by the manufacturer.
0 0
0 0
6.4.1 50 mm dia PVC pipes RM 200 375 75,000 360 72,000 217 43,400
0 0 0
6.4.2 40 mm dia PVC pipes RM 370 340 125,800 290 107,300 195 72,150
0 0 0
6.4.3 25 mm dia PVC pipes RM 1250 260 325,000 180 225,000 162 202,500

SUB TOTAL COST 6,388,833 5,419,020 5,185,464

TOTAL COST 41,495,622


OVERHEADS 15% 6,224,343

GRANT TOTAL COST 47,719,966 34,500,000 0 34,988,107

DEVIATION OF VENDORS FROM TMA -27.70% -26.68%

LI L2

SPECTRAL SERVICES CONSULTANTS


HVAC-BILL OF QUANTITIES Page No.18
SUMMARY OF COSTS - HVAC

No. DESCRIPTION AMOUNT

A INSTALLATION, TESTING AND COMMISIONING OF


EQUIPMENT (IMPORTED) -OWNER SUPPLIED AT SITE
FREE OF COST

B SUPPLY,INSTALLATION, TESTING AND COMMISIONING OF


EQUIPMENT (INDEGENOUS)

C CONDENSER AND CHILLED WATER PIPING:

D AIR DISTRIBUTION

E TOILET EXHAUST SYSTEM - GUEST ROOM TOILETS

F THERMAL INSULATION

GRAND TOTAL

ALL INCLUSIVE MAINTENANCE CONTRACT

After the expiry of the defects liability period of one year from the date of certification of completion, the owner may at his
discretion chose to activate the All Comprehensive Maintenance Contract.
The Annual Maintenance Contract shall be applicable to the entire airconditioning covered under this tender for BELL
TOWER HOTELS., Bangalore and shall be fully comprehensive i.e., inclusive of maintenance of all materials / equipment
supplied by the cont
All inclusive maintenance contract (AMC) for the HVAC system shall be placed upon the contractor at the beginning of each
year.
Prices quoted shall be for the following:

DESCRIPTION AMOUNT

All- inclusive Maintenance Contract for the first year after the DLP period of 12 months.

All- inclusive Maintenance Contract for the second year after the AMC period of 1st year.

All- inclusive Maintenance Contract for the third year after the AMC period of 2nd year.

RAS HOTELS - CHENNAI 19 of 33 SPECTRAL, BANGALORE


HVAC - Schedule of Quantities 11/19/2019 HVAC
All- inclusive Maintenance Contract for the fourth year after the AMC period of 3rd year.

All- inclusive Maintenance Contract for the fifth year after the AMC period of 4th year.

The payment for Maintenance Contract shall be made on quarterly basis of each quarter. Client reserves the right to terminate
the
Maintenance contract by giving three months notice without assigning any reason thereof.

RAS HOTELS - CHENNAI 20 of 33 SPECTRAL, BANGALORE


HVAC - Schedule of Quantities 11/19/2019 HVAC
ion, the owner may at his

his tender for BELL