General Model S2LP131


Specifications Fire and Gas
Communication Module
GS 32P06K52-01EN

n GENERAL
This document describes about Model S2LP131 fire and gas communication module (*1) used with a safety control
station (SCS) for performing fire and gas communication.
The fire and gas communication function is one of safety subsystem communication function to safety perform
communication with the subsystem devices. By using the SCS’s fire and gas communication function, the gas
concentration data from wireless gas detector (GS01) (*2) can be referred to via a fire and gas communication
module.
This fire and gas communication module can be mounted on a safety control unit (S2SC70). It can also be
mounted on a safety node unit (SNB10D), which is connected to S2SC70.
*1: Supported by ProSafe-RS R4.05.00 or later.
*2: Wireless gas detector “GS01” is a product of GasSecure AS which is a subsidiary of the German company Drägerwerk AG
& Co. (as of November, 2019)

Fire and gas communication module


SCS

Ethernet cable Ethernet cable


(PROFINET) (PROFINET)
HUB

YFGW410

YFGW410 YFGW410

F01E.ai

Figure System configuration example of the fire and gas communication module

n HARDWARE SPECIFICATIONS
Hardware specifications of S2LP131 fire and gas communication module are as shown below.

Table Fire and Gas communication module hardware specification

Item Specifications
Model S2LP131
Physical layer interface IEEE802.3 100BASE-TX
Connector RJ-45 (ISO/IEC8877 comply) (*1)
Transmission speed 100 Mbps
Transmission route 2 x 2 twisted, symmetrical and shielded copper cable (*1)
Transmission distance 1 segment, 100 m (in between SCS and YFGW410, or SCS and HUB)
Installation method Mounted on S2SC70 or SNB10D
No. of ports One port
Communication protocol PROFINET
Maximum current consumption 0.8 A
Weight Approx. 0.31 kg
*1: The cables and connectors must comply with the PROFINET standards.

Yokogawa Electric Corporation GS 32P06K52-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Nov. 2017(YK)
3rd Edition Nov. 15, 2019(YK)
<<Contents>> <<Index>> 2
n OPERATING ENVIRONMENT
Hardware requirements
The fire and gas communication module runs on the following SCS.
S2SC70S, S2SC70D
Software requirements
The fire and gas communication module runs on the control function of the following SCS.
RS4F1500 Safety Control Function (for S2SC70)
Engineering requirements
Engineering work can be performed with RS4E5100 safety system engineering and maintenance function.
Also engineering for field wireless system and configuration of wireless gas detector (GS01) are required separately.

n INSTALLATION ENVIRONMENT
RS4F1500 safety control function (for S2SC70)

No. of S2LP131 to be mounted Max. 8 units / SCS (*1)


Max. 128 devices / S2LP131
No. of PROFINET devices (YFGW410)
(Max 128 pairs for YFGW410 dual-redundant operation)
Max. 60 devices / S2LP131 (*2)
No. of PROFIsafe devises (GS01)
Max. 320 devices / SCS (*2)
Max. 500 data (1,000 words) / S2LP131
Safety subsystem communication capacity
Max. 2,000 data (4,000 words) / SCS
No. of communication definition 200 definitions / S2LP131 (*3)
*1: The dual-redundant configuration of S2LP131 is not supported.
*2: Under the following conditions, this number of GS01 can be connected to S2LP131 or SCS.
- SCS acquires 6 data (gas concentration data, self-diagnostics information, and battery life) from GS01 by the 3
communication definitions.
- SCS acquires 1 data (operation condition information) from YFGW410 / YFGW510 by the 1 communication definition.
- The total number of devices of YFGW410 and YFGW510 connected to S2LP131 is 20 devices.
- The total number of devices of YFGW410 and YFGW510 connected to SCS is 80 devices.
→ 60 devices (GS01 / S2LP131) x 3 definitions + 20 devices (YFGW410 / YFGW510) x 1 definition =200 definitions / S2LP131
→ 320 devices (GS01 / SCS) x 6 data + 80 devices (YFGW410 / YFGW510) x 1 data = 2000 data / SCS
*3: The gas concentration data is 4 data-size per one definition, and the self-diagnostics information or the operating condition
information is 1 data-size per one definition.

All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation GS 32P06K52-01EN Nov. 15, 2019-00
<<Contents>> <<Index>> 3
n FIRE AND GAS COMMUNICATION FUNCTION
Fire and gas communication function is for SCS to acquire the gas concentration data from wireless gas detector
(GS01) via S2LP131 fire and gas communication module mounted on SCS and field wireless system comply with the
ISA100.11a standards.
Field wireless system used as communication paths consists of Field Wireless Management Station (YFGW410),
Field Wireless Access Point (YFGW510), and Field Wireless Media Converter (YFGW610). Field wireless system
has architecture to segregate station and antenna, thus, achieves reliable and flexible system operation by the dual-
redundant configuration for each devices.

 System configuration
A system configuration example to connect ProSafe-RS system, field wireless system, and wireless gas detector is
shown as below.

AD Server

Ethernet

SENG HIS/ENG
(AD Organizer, SCS Manager,
 PROFINET Configurator )

Vnet/IP

SCS
S2LP131

FWMC

HUB

Field network (PROFINET)


HUB
YFGW410
YFGW410
Ethernet

YFGW610
Metal network cable

Optical fiber cable

YFGW510 YFGW510 YFGW510

GS01 Configurator
Field Wireless network
(ISA100.11a)

GS01 GS01 GS01 GS01

F02E.ai

SENG: Safety engineering station


SCS: Safety control station
HIS: Human interface station
ENG: Engineering station
FWMC: Field Wireless Management Console

Figure Example of system configuration

All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation GS 32P06K52-01EN Nov. 14, 2017-00
<<Contents>> <<Index>> 4
SCS
SCS is a safety control station which has functions such as safety control function, sequence of event recorder
(SOER) function, and CENTUM VP integration function. SCS communicates with GS01 by PROFIsafe protocol
to refer gas concentration data detected by GS01 as safety application input. SCS also refers operating
conditions information of YFGW410 and YFGW510, and self-diagnostics information of GS01 by interference-free
communication.

S2LP131
S2LP131 is a fire and gas communication module for connecting SCS and GS01.
S2LP131 has one PROFINET port (based on Ethernet) to connect to YFGW410s via network switch (*1).
*1: Network switch (HUB) must be complied with the PROFINET standards.

SENG
SENG is a station to perform engineering and maintenance of ProSafe-RS.
SENG has functions such as automation design organizer (AD Organizer), SCS manager, and other optional
functions. Configuration of S2LP131, definition of communication input / output, and setting of device operating
conditions and alarm management are performed by AD Organizer.
The parameters of PROFINET protocol and PROFIsafe protocol are configured by using the PROFINET configurator
(*1) launched from AD Organizer.
*1: PROFINET configurator (SYCON.net-SLP/YOKO) is provided by Hilscher GmbH.

AD Server
AD Server is a station to manage all engineering data such as RS project generated by SENG.

HIS/ENG
HIS/ENG is a station to perform operating, monitoring, and engineering of CENTUM VP, and it can be installed in the
same computer as SENG (*1).
HIS can monitor operating conditions and alarm messages of S2LP131 by using ProSafe-RS’s CENTUM VP
integration function. HIS can also monitor operating conditions of the field wireless system and gas concentration data
and self-diagnostics information of GS01 acquired by S2LP131 using tag name access.
*1: When SENG and HIS/ENG are installed in a single computer, use ProSafe-RS R4.05 or later and CENTUM VP R6.07
or later. PROFIBUS-DP configurator of CENTUM VP, PROFINET configurator of CENTUM VP and/or PROFINET
configurator of SENG cannot be launched at the same time.

YFGW410 (*1)
YFGW410 is a field wireless management station and has a function as a gateway to field wireless devices. The dual-
redundant configuration of YFGW410 is supported.
It is recommended to segregate the network segment using VLAN function of HUB in case of connecting YFGW410 to
S2LP131, and YFGW410 to FWMC in a single HUB.
For details of YFGW410, refer to the GS "YFGW410 Field Wireless Management Station” (GS 01W02D01-01EN).
*1: Firmware revision R2.01.04 or later is required.

YFGW510
YFGW510 is an access point of field wireless networks based on ISA100.11a, and connects YFGW410 to GS01.
YFGW510 supports the DuoCast function specified in ISA100.11a which enables simultaneous communication with
two YFGW510s, to create a redundant communication path and increase the reliability of the field wireless network.
For details of YFGW 510, refer to the GS "YFGW 510 Field Wireless Access Point" (GS 01W02E01-01EN).

YFGW610
YFGW610 is a field wireless media converter to convert the signals between 100BASE-TX (metal network cable) and
100BASE-FX (optical fiber cable). It is used when the wiring between YFGW410 and YFGW510 is placed outdoors or
covers a long distance.
For details of YFGW 610, refer to the GS "YFGW 610 Field Wireless Media Convertor” (GS 01W02D02-01EN).

All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation GS 32P06K52-01EN Nov. 15, 2019-00
<<Contents>> <<Index>> 5
GS01
GS01 is a wireless gas detector compliant with the wireless communication standard ISA100.11a. It is acquired SIL 2
certification from a safety certification organization (Exida) and supports PROFIsafe protocol compliant with the IEC
standards.
GS01 detects hydrocarbon gas even in low temperature and high humidity place in short order by infrared sensor
using infrared of 3 wavelengths (*1). In addition, GS01 can operate for a long period of time due to the low power
design and built-in battery pack (*2).
For provisioning of GS01 and setting safety parameters, use GS01 configurator.
*1: Detection time is 5 seconds or less for methane and propane.
*2: Battery life is up to 2 years in the standard usage and standard environment.

FWMC (Field Wireless Management Console)


FWMC is a console to perform engineering of a field wireless system. It is used to set the mapping of PROFINET and
field wireless definition for the PROFINET communication between S2LP131 and YFGW410.
FWMC can also be used to monitor the condition of devices in the field wireless system.

l Communication between SCS and GS01


In the fire and gas communication function, communication between SCS and GS01 is performed by PROFIsafe
protocol. Communication between S2LP131 and YFGW410 is performed by PROFINET protocol, and communication
between YFGW410 and GS01 is performed by ISA 100.11a protocol.

SCS GS01

Safety Application Safety Application

PROFIsafe S2LP131 YFGW410/YFGW510 PROFIsafe

ESB Bus ESB Bus PROFINET PROFINET ISA100.11a ISA100.11a

ESB bus communication PROFINET communication Field Wireless communication


(ISA100.11a)
PROFIsafe communication
F03E.ai

Figure Flow of communication data

l Communication function specification


In the PROFINET standard, I/O data used for data exchange is called a module (hereinafter PROFINET module). For
the fire and gas communication function, the PROFINET module is defined by using the PROFINET Configurator. The
PROFINET modules that can be used for the fire and gas communication function are shown below.

Table PROFINET modules

Module ID Data type Description


Input (Unsigned 8-bits) Data quality status (*1)
GS01_SAFE_RS
Input (Float 32-bits) Gas concentration data
DIAG_STATUS Input (Unsigned 32-bits) Self-diagnosis information of GS01
GW_STATUS Input (Unsigned 16-bits) Operating condition of YFGW410
BBS_STATUS Input (Unsigned 16-bits) Operating condition of YFGW510
BATTERY_LIFE Input (Integer 16-bits) Battery level of GS01

*1: Data quality status indicates the quality of gas concentration data, specified in the ISA 100.11a standard.

All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation GS 32P06K52-01EN Nov. 14, 2017-00
<<Contents>> <<Index>> 6
n EXTERNAL DIMENSIONS
l S2LP131 Fire and Gas communication module

Unit: mm

32.8 125.5

RUN INFO
RCV/SND
LINK
STATUS ACT DX

130

F04E.ai

Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined
nominaltolerance is ± 1.5 mm
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.

n MODEL AND SUFFIX CODES


Description
Model S2LP131 Fire and Gas Communication Module
-S Standard Type

Suffix 0 With no explosion protection


Codes 1 With explosion protection
1 With ISA Standard G3

CONFORMIY STANDARDS
n
Refer to “ProSafe-RS Standards Compliant Models” (GS 32P01B60-01EN).

n ORDERING INFORMATION
Specify the model, suffix code(s).
For selecting the right products for explosion protection, please refer to TI 32S01J30-01E without fail.

n TRADEMARKS
• ProSafe, CENTUM, PRM, STARDOM, FAST/TOOLS, Exaopc, FieldMate, and Vnet/IP are either registered
trademarks or trademarks of Yokogawa Electric Corporation.
• Other company and product names appearing in this document are registered trademarks or trademarks of their
respective holders.

All Rights Reserved. Copyright © 2017, Yokogawa Electric Corporation GS 32P06K52-01EN June 15, 2018-00