Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
BY
SARAWUT POLVONGSRI
Solar water heating system (SWHS) uses solar energy in thermal form. The
working principle is to convert and transfer the energy to water from low to high
temperatures. The hot water is mainly used in households, hotels, hospitals, or even in
industries. The SWHS consists of two main components; solar collector and hot water
storage tank. The system could be designed as free convection of which the water
circulation is based on the temperature difference of the water in the solar collector
and that in the storage tank and forced convection of which the water circulation is
controlled by an external pump. Generally, the temperature of hot water is not more
than 40-60 o C which uses in the hotel, hospitals and households, the flat-plate solar
collector is popular for the production of hot water.
The important parts of a flat-plate solar collector as shown in Figs 1and 2 are
black absorber plate-and-tube for transferring the absorbed heat to a fluid in the tube;
transparent cover to the solar radiation that reduces convection and radiation losses to
the atmosphere; and insulation to reduce conduction losses from the absorber surface.
, (1)
.
m
, (2)
, (3)
Figure 4 Test and predata periods for the efficiency tests (τ = collector time
constant1 fixed test mount)
Solar irradiance
The Standard requires that the diffuse irradiance on the aperture plane be a
maximum of 20% of the total irradiance on the collector aperture plane. The diffuse
fraction can be calculated by the following equation (ASHRAE 93-2003).
cos (4)
1)
Figure 5 Variation of solar irradiance, fixed test mount
Incidence angle
The incidence angle, θ, is the angle between the incident direct beam
radiation and the normal to the collector plane. ASHRAE 93-2003 defines the
following incidence angle modifier-related requirements:
Experimental Determination of Collector Thermal Efficiency: For tests
conducted to determine the thermal efficiency at near-normal incident conditions, the
angle of incidence shall be in the range in which the incident angle modifier varies no
more than ±2% from the normal incidence value. For tests conducted to determine the
incident angle modifier, the orientation of the collector shall be such that the collector
Ambient temperature
The range of ambient temperatures of all data periods shall be less than 30°C
(54°F) (ASHRAE 93-2003). This requirement relates different data points of one
complete test with each other. Within one test period, the test standard requires to
“maintain” the ambient temperature within a variation of ±1.5°C (2.7°F) during the
pre-data period. Although not mentioned explicitly in the standard, the same
requirement should be applied for the data period
Wind speed
The Standard requires the wind speed lie between 2.2 and 4.5 m/s (5 and 10
mph) (ASHRAE 93-2003). This requirement applies to the test period and a MAX(10
min,2τ) interval prior to the test period. The Standard further stipulates that some
collectors with glass glazing may require a longer interval of up to 20 minutes or four
time constants. If taken literally, this requirement would mean that ahead of every test
period (which is defined by the Standard as the time over which quasi-steady-state
This interpretation would further increase the required pre-data time period.
It is more likely that there is an inconsistent use of the expression “test period” in the
Standard. If the requirements for the wind speed are applied in the same way as those
for the solar irradiance, the requirements for the wind speed must be met prior to the
data period instead of the whole test period. This alternative interpretation is shown in
Figure 7.
1)
Figure 7 Variation of wind speed, alternative 2 fixed test mount
Flow rate
The heat transfer fluid flow rate remains fixed for all data points. The
recommended mass flow rate per aperture area for a liquid fluid is 0.02 kg/s-m2 (14.7
lbm/hr-ft2). An exception is made for collectors which are designed for special flow
rates. These collectors should operate with their design flow rates (ASHRAE 92-
2003). The flow rate shall be maintained constant at the recommended flow rate
within ±0.005 gpm (0.000315 liter/sec).
For the collector actually tested at MATC, the recommended flow rate is 3.2
gpm. A difference of 0.005 gpm requires maintaining the operating flow rate to within
0.0022% of its nominal value! This requirement is very restrictive when compared to
Inlet temperature
The Standard requires that the inlet temperature be maintained constant
(within ±1°C [±1.8°F], ASHRAE 93-2003) during the pre-data and data periods.
However, the standard requires the inlet temperature to be controlled within ±0.05°C
(±0.09°F) during the complete test period. Why is a device required in the test setup
which can control the inlet temperature within ±0.09°F, if the allowed inlet
temperature variation for steady state conditions is ±Max of (1.8°F, 2%), which is in
the lowest case 20 times greater than the control unit could provide? Again, there
seems to be inconsistencies in the variation in controlled and uncontrolled variable
related to collector testing. The variables that have extremely narrow tolerances
significantly complicate the data collection process for measuring collector
performance.
The tests were performed following the ASHRAE Standard 93-2003 with the
flow rate of 1.2 liter/min-m2 and then the flow rates were varied between 0.8 - 1.6
liter/min-m2. The inlet temperature was adjusted in a range of 35 - 65 oC by the
electric heater. The tests were carried out around noon on some clear sky days. The
mass flow rate of each fluid flow was read directly from a rotameter with an accuracy
of ± 0.0035 Liter/min, the temperatures of the fluids at the inlet and the outlet ports of
the solar collectors and the ambient temperature were measured and recorded by a set
of K-type thermocouples with an accuracy of ± 0.1 oC. A pyranometer having an
accuracy of ± 55 W/m2 was used to measure the solar radiation incident on the solar
collector. During the experiment a fan was used to control the wind speed over the
collectors at the average value of about 3.35 m/s. The method of performance test can
be as following:
Methods
1. Open pump (P1) and set the inlet Temperature (35, 40, 45, 50, 55, 60 and 65 o C).
2. Set the mass flow rate ex. 2.6 liter/min (0.043 liter/s).
3. When the system is in steady state, record the data such as inlet temperature (Tfi) and
outlet temperature (Tfo) , solar radiation (IT) , and ambient temperature (Ta).
4. Analyze data and calculate thermal efficiency as follow in Table 1.
Q coll m f C p (T fo T fi ) (T fi Ta )
coll FR ( ) e FRU L
I T Ac I T Ac IT
(6)
coll
FR ( ) e
FR U L
Y
X
T fi Ta
IT
Table 2: Solar Collector Testing , Mass flow rate (mf.)= 2.59 liter/min (0.043 liter/s)
Tfi set mf IT Tfi Tfo Ta Qcoll (Tfi-Ta)/IT ηcoll
o
C Liter/s W/m2 o
C o
C o
C W
0.043 833.00 34.81 41.38 25.05
0.043 836.00 34.42 41.28 24.55
35
0.043 837.00 34.61 41.18 24.85
0.043 839.00 34.42 41.38 25.05
Average 0.043 836.25 34.56 41.30 24.88
0.043 866.00 39.77 45.85 24.55
0.043 866.00 39.48 45.75 24.85
40
0.043 864.00 39.38 45.65 24.75
0.043 864.00 38.98 45.55 25.05
Average 0.043 865.00 39.40 45.70 24.80
0.043 886.00 44.54 50.32 25.35
0.043 888.00 45.03 50.42 25.55
45
0.043 886.00 45.03 50.72 25.35
0.043 885.00 44.83 50.72 25.35
Average 0.043 886.25 44.86 50.54 25.40
0.043 889.00 49.99 55.09 26.24
0.043 889.00 49.80 55.38 27.14
50
0.043 887.00 49.50 55.28 26.44
0.043 887.00 49.10 54.89 26.74
Average 0.043 888.00 49.60 55.16 26.64
0.043 879.00 54.26 59.16 26.14
0.043 881.00 54.66 59.46 26.44
55
0.043 883.00 54.46 59.75 26.94
0.043 881.00 53.96 59.56 26.84
Average 0.043 881.00 54.33 59.48 26.59
0.043 834.00 59.42 63.73 27.14
0.043 832.00 59.52 64.03 27.84
60
0.043 835.00 58.92 64.03 27.24
0.043 834.00 58.72 63.63 27.64
Average 0.043 833.75 59.15 63.85 27.46
0.043 802.00 64.18 68.00 27.84
0.043 802.00 63.88 68.20 27.34
65
0.043 801.00 63.29 67.90 27.04
0.043 799.00 63.39 67.50 27.14
Average 0.043 801.00 63.69 67.90 27.34
From Table 2 could be found the performance curve as shown in Table 3 and Figure8.
0.70
0.60
Efficency (%)
0.50
0.40
y = ‐6.5656x + 0.7123
0.30
R² = 0.8421
0.20
0.10
0.00
0.000 0.010 0.020 0.030 0.040 0.050
Tfi‐Ta/IT
Exercise
Reference
Development and Validation of Flat-Plate Collector Testing Procedures –
Report 1 Solar Energy Laboratory.
ANSI/ASHRAE Standard 93-2003, Methods of Testing to Determine the
Thermal Performance of Solar collectors. ISSN 1041-2336, ASHRAE, Inc., 2003,
1791 Tullie Circle, Ne, Atlanta, GA30329
Polvongsri, S. and Kiatsiriroat, T. 2011. Enhancement of Flat-Plate Solar
Collector Thermal Performance with Silver Nano-fluid. The Second TSME
International Conference on Mechanical Engineering, Krabi, Thailand.
Polvongsri, S. and Kiatsiriroat, T. Performance Analysis of Flat-plate Solar
Collector Having Silver Nano-Fluid as a Working Fluid. Heat transfer engineering
international journal, the electronic final copy will be published to internet (Taylor &
Francis online website) around April/May 2014.