Type here SPAM 150 C
Customer reference: Title:
Type here Setting proposal for Motor Protection
Motor: Prepared by: Sheet:
ACW Pump 3/7/2005 ASK 1/6
Checked by: Revision:
3/7/2005 MSK A
MOTOR DATA:
Rated power PnM = 132.0 kW
Rated voltage UnM = 0.4 kV
Rated current InM = 228.0 A
Starting current Is = 6.00 × InM
Starting time ts = 1.0 s
Ambient temperature > 40 °C
PHASE CURRENT CT DATA: CT primary = 300 A
CT secondary = 1 A
relay input = 1 A
NEUTRAL CURRENT CT DATA: CT primary = 300 A
CT secondary = 1 A
relay input = 1 A
RELAY SETTINGS:
Thermal overload unit: Setting range:
Full load current (0,5...1,50 × In) IQ = 0.76 × In
Safe stall time (2,0...120 s) t6x = 3.5 s
Weighting factor (20...100%) p= 50 %
Prior alarm level (50...100%) Qa = 95 %
Restart inhibit level (20...80%) Qi = 54 %
Cooling time constant (1...64 × tH) kc = 4
Start-up supervision unit:
Start current (1,0...10 × In) Is = 2.28 × In
Start-up time (0,3...80 s) ts = 1.50 s
High-set overcurrent unit:
Start current (0,5...20 × In or ¥) I>> 6.84 × In * Doubling disabled
Operate time (0,04...30 s) t>> 0.04 s
Earth-fault unit:
Start current (1,0...100% In) I0 = 10.00 % In
Operate time (0,05…30 s) t0 = 0.05 s
Phase unbalance unit:
Start current (10…40% IL or ¥) DI = 26.0 % IL 15.0 % NPS
Operate time (20…120 s) tD = 20.0 s
Undercurrent unit:
Start current (10…40% IQ or ¥) I< not in use % IQ
Operate time (2…600 s) t< not in use s
Cumulative start time counter:
Restart inhibiting
Start count setting (5…500 s) Stsi = 5.0 s * 2 starts / hour
Countdown rate of
start-up time counter (2…250 s/h) DSts/Dt = 2.0 s/h
Remarks:
Project name: Protection device:
A BB
Type here SPAM 150 C
Customer reference: Title:
Type here Setting proposal for Motor Protection
Motor: Prepared: Sheet:
ACW Pump 3/7/2005 ASK 2/6
Checked: Revision:
3/7/2005 MSK A
A BB
Type here SPAM 150 C
Customer reference: Title:
Type here Setting proposal for Motor Protection
Motor: Prepared by: Sheet:
ACW Pump 3/7/2005 ASK 3/6
Checked by: Revision:
3/7/2005 MSK A
Operation Characteristics
Relay trip curve: cold
Relay trip curve: hot
Start-up supervision
Column H
Column J
Relay trip curve: hot
Relay trip curve: cold
Start-up supervision
Column H
1000
100
10
Time [s]
0.1
0.01
1 10
I/IQ
0.01
1 10
I/IQ
Remarks:
Project name:
Project name: Protection device:
A BB
Type here SPAM 150 C
Customer reference: Title:
Type here Setting proposal for Motor Protection
Motor: Prepared by: Sheet:
ACW Pump 3/7/2005 ASK 4/6
Checked by: Revision:
3/7/2005 MSK A
Cold starts
1 10
2
0.9 9
0.8 8
0.7 7
Used thermal capacity [%]
0.6 6
2
0.5 5
I/IQ
0.4 4
0.3 3
0.2 2
0.1 1
0 0
0 5 10 15 20 25 30 35 40 45 50
Time [s]
Remarks:
Prior load
1 10
2
0.9 9
0.8 8
Used thermal capacity [%]
0.7 7
0.6 6
2
0.5 5
I/IQ
0.4 4
0.3 3
0.2 2
0.1 1
0 0
0 5000 10000 15000 20000 25000 30000 35000
Time [s]
Remarks:
Hot starts
1 10
2
0.9 9
0.8 8
0.7 7
Used thermal capacity [%]
0.6 6
2
0.5 5
I/IQ
0.4 4
0.3 3
0.2 2
0.1 1
0 0
0 5 10 Time [s] 15 20 25
0.2 2
0.1 1
0 0
0 5 10 Time [s] 15 20 25
A BB
SPAM 150 C
Customer reference: Title:
Type here Setting proposal for Motor Protection
Motor: Prepared by: Sheet:
ACW Pump 3/7/2005 ASK 5/6
Checked by: Revision:
3/7/2005 MSK A
Unbalance Protection
100
10
t[s]
2.96
1
10 100
D I / IL [%]
Remarks:
Project name:
Type here
Customer reference:
Type here
Project name: Protection device:
A BB
Type here SPAM 150 C
Customer reference: Title:
Type here Setting proposal for Motor Protection
Motor: Prepared by: Sheet:
ACW Pump 3/7/2005 ASK 6/6
Checked by: Revision:
3/7/2005 MSK A
Remarks: