Hat type
・NS-SP-10H
900
■ Characteristic of Hat-type sheet piles
1.Rapid construction
- Installed combined pile which has 900mm width sheet pile
2.Reduction of steel weight of walls
- Slender section and 100% full sectional performance
3.Utility for any requirements
- Assorted section type and high applicability
HAT-Type
10H 25H
13.2
10.8
300
230
900 900
U-Type
45H 50H
17
15
370
368
900 900
45% number of piles reduction
U-wide Type(U600)[Ⅱw]
400mm
U Type(U400)[Ⅱ]
Neutral axis of each piles and that of interlocked wall are equivalent
900mm
Hat Type(Hat900)[10H]
Slip at Joint
y1
e
600mm y y0
M
Neutral
実際の中立軸 axis
Neutral
U-wide
鋼矢板1枚でのaxis
Type(U600)[Ⅱw]
of practical wall
of中立軸
pile
Class 1 or 2 Class 3
where :
Wel is the elastic section modulus determined for a continuous wall;
Wpl is the plastic section modulus determined for a continuous wall;
γM0 Partial safety factor (=1.0)
βB is a reduction factor that account for a possible lack of shear force
transmission in the interlocks.
βB = 1.0 for Z-piles and triple U-piles
βB ≤ 1.0 for single and double U-piles 10
Reduction factor for U-type sheet piles
EI eff D EI
where:
I is the second moment of area of the continuous wall
E is Young’s modulus
βD is to account for the possible reduction due to insufficient shear force
transmission in the interlock.
βD = 1.0 for Z-piles and triple U-piles
βD ≤ 1.0 for single and double U-piles
The numerical value for βB and βD are given in the National Annex.
11
Reduction factor for U-type sheet piles
Reduction factor for U-type sheet piles in the National Annex
12
Reduction factor for U-type sheet piles
Countermeasures for enhancing the reduction factor
13
Influence of interlock integrity
70000
Moment of Inersia per 1m wall width(m3/m)
60000
50H
50000
45H ▽23%
40000 Joint efficiency
=0.6
30000 25H ⅤL
▽34%
20000
10H ▽36% Ⅳ
10000
Ⅲ
0 Ⅱ
80 120 160 200 240
Unit weight per 1m wall width (kg/m2)
Similar with Z-type piles, for a wall using Hat-type steel piles, the
reduction factors are NOT required (βB = 1.0 , βD = 1.0 ) because
interlocks are located at the most outer edge of the wall, which
means that the shear force does not occur in the interlocks.
Structural Test Plan (NTU in Singapore)
• Place : Nanyang Technological University
(Supervised by Dr. Chiew Sing-Ping)
• Machinery : 100t Compression machine
• Specimen : Hat-type sheet pile (10H×2 piles)
(Manufactured in Japan)
• Measurement: Load, Displacement, Strain
P/2 P/2
■ Load-Deflection behavior
800
Pmax=694kN
700
600
Calculated Plastic Load
500
Load(kN)
300
200
150
Neutral Line
100
Arrangement of strain gages
50
0
-4000 -3000 -2000 -1000 0 1000 2000 3000 4000
strain at Center(μ)
Strain was distributed from above to bottom and the value
become 0 at neutral line so the Navier hypothesis is applicable
Additional concerns of sheet piles
(for SYW295)
H-beam
Fillet
welding
(partial)
600
Theoretical Yield Moment
Hat + H 400
200
Experimental Value
Calculated Value
0
U-type 0.000 0.005 0.010 0.015
Curvature (1/m)
2) 100% Joint Efficiency Neutral
Axis of wall
Flexural Test
Neutral
Axis of pile
Neutral
Axis
Numerous sectional properties
■ Optimization of design 【2 Sheet pile & 1 H beam combined type】
【1 Sheet pile & 1 H beam combined type】
Easy Fabrication in Construction Site
In Singapore (2014)
In Indonesia (2013)
Fabrication manual
In Indonesia (2013)
Outline
256kg/m(0.7 : Z equivalent)
Unit weight 342kg/m(1.0)
173kg/m(0.5 : I equivalent)
2 Piles InstalIation 1 Pile InstalIation
Installation Installed U-type and soldier pile Installed HAT and H
separately at the same time
Development for HAT+H in Singapore
-Piling test- -Publish technical papers-
Thank you very much