Sei sulla pagina 1di 54

5\. '. A .J...

National Research Conseil national


1+1 Council Canada de recherches Canada

IftC·ClftC
Guideline for Seismic
Upgrading of Building
Structures
Guideline for Seismic
Upgrading of Building
Structures

Prepared by:
Institute for Research in Construction
National Research Council of Canada

Funded by:
Public Works and Government Services Canada
British Columbia Buildings Corporation
Canada Mortgage and Housing Corporation
Institute for Research in Construction

© National Research Council of Canada


December 1995
ISBN 0-660-16262-8
NRCC 38857

NOTICE

This Guideline has been prepared by the Institute for Research in Construction (IRC) for the
organizations listed above. With the agreement of these organizations the Guideline is being
made available to interested individuals or organizations for their information and review. This
Guideline is not to be interpreted as replacing or superseding applicable building regulations.
Neither IRC nor the sponsoring organizations assume any liability for the use of this document.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Preface

Summary Background
This Guideline provides information This Guideline is based in part on
and advice on the seismic upgrading of NEHRP Handbook of Techniques for Seismic
existing building structures, and is intended Rehabilitation of Existing Buildings, 4 but the
for use by qualified structural engineers. It is material has been reorganized and shortened
a companion document to the recently considerably. Also, this document contains
published Guidelines for Seismic Evaluation of more guidance on innovative techniques than
Existing Buildings l and the Manualfor does the NEHRP Handbook.
Screening of Buildings for Seismic
Investigation,2 both of which are related to the The first draft of this Guideline was
National Building Code of Canada. 3 produced with the support of Public Works
and Government Services Canada. Based on
The Guideline describes conventional comments received, the draft has been
techniques of seismic upgrading of building improved for publication with the support of
structures and discusses their relative merits B.C. Buildings Corporation and Canada
based on the objectives of seismic upgrading Mortgage and Housing Corporation.
and the principal considerations in their choice
and design. It also describes innovative The Guideline was prepared by the
seismic upgrading techniques such as following persons:
supplementary damping and contains
references to more detailed information on D.E. Allen, IRCfNRC, Ottawa, Ontario
such techniques. It does not include Principal Investigator
techniques for upgrading of non-structural
building components. Main Contributors:
L. Bell CWMM, Vancouver, B.C.
S. Cherry University of British Columbia,
Vancouver, RC.
F. Knoll Nicolet Chartrand Knoll Ltee.,
Montreal, Quebec
R. Lo Klohn Crippen Consultants Ltd.,
Richmond, B.C.
l.R. Rainer IRCfNRC, Ottawa, Ontario

The review of the draft document by B.C.


Hydro, Hydroelectric Engineering Division, is
gratefully acknowledged, as are the comments
received from a number of other individuals
and companies.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Table of Contents

1. INTRODUCTION 1 5. UPGRADING TECHNIQUES·


1.1 Purpose of the Guideline l SPECIAL 29
1.2 Scope and Limitations 1 5.1 Supplementary Damping 29
1.3 How to Use the Guideline 1 5.2 Base Isolation 31
5.3 FRP Overlays and Encasements 33
2. SEISMIC DEFICIENCIES OF
THE BUILDING STRUCTURE 3 6. UPGRADING TECHNIQUES·
2.1 Lack of Integrity/Redundancy 3
FOUNDATIONS 35
2.2 Inadequate StrengthlDuctility 3
6.1 Conventional Techniques for
2.3 Inadequate Stiffness/Adjacent
Upgrading Foundations 36
Buildings 3
6.2 Soil Stabilization 38
2.4 Irregularities/Load Transfer .4
REFERENCES 43
3. PRINCIPLES OF SEISMIC
UPGRADING 5
APPENDIX A: CHECKLIST OF
3.1 Objectives of Upgrading 5
SEISMIC UPGRADING TECHNIQUES ... .45
3.2 Conventional Upgrading
Techniques 5
3.3 Special Upgrading Techniques 7
3.4 Considerations in the Choice of
Upgrading Techniques 7
3.4.1 Structural Considerations 7
3.4.2 Other Considerations 10
3.5 Design Criteria, Testing of Special
Devices ll

4. UPGRADING TECHNIQUES·
CONVENTIONAL 13
4.1 New Shear Walls, Bracing or Moment
Frames 13
4.2 Upgrading Existing Moment
Frames 15
4.3 Upgrading Existing Braced
Frames 17
4.4 Upgrading Existing Shear Walls 18
4.5 Upgrading Existing Diaphragms 23
4.6 Techniques for Lateral Support of
Walls and Parapets 27
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Chapter 1

Introduction

1.1 Purpose of the 1.3 How to Use the


Guideline Guideline
Many buildings in seismic areas The Guideline should first be read
across Canada were built before there was an from the beginning. Afterwards it may be
adequate understanding of earthquake convenient to begin with Appendix A, which
resistance. Many of these buildings would be contains checklist tables of upgrading
deemed unsafe by cunent building codes. techniques, one table for each major structural
Also, because code requirements are written system. These techniques are described in
for the design of new buildings and not for the more detail in Chapters 4 to 6, identified by the
evaluation of existing buildings, the cost of appropriate page and figure numbers in the
upgrading an existing building to the cunent Appendix A checklist tables. The relative
code can be very large, as well as destructive merits of each technique are based on
to its heritage value. A set of alternate objectives and principles involved in seismic
procedures for evaluating existing buildings upgrading described in Chapter 3. Chapter 2
was therefore prepared by NRC and published reviews the types of seismic deficiencies found
in the Guidelines for Seismic Evaluation of in existing buildings.
Existing Buildings l (hereafter refened to as
"Guidelines for Seismic Evaluation"). The design of upgrading of existing
buildings involves a greater number of
This new Guideline was prepared to uncertainties and constraints than the design of
help engineers design the seismic upgrading new buildings. Consequently, more judgment
using appropriate techniques for conecting the is needed for design of the upgrading,
seismic deficiencies identified using the above including the choice of techniques, than in the
NRC evaluation guidelines. The techniques design of new buildings. In addition, seismic
described herein include conventional methods upgrading is a relatively new activity and
that were employed in the past, as well as innovative techniques are in various stages of
recently developed special procedures, such as development. This document, therefore, places
supplementary damping and base isolation. more emphasis on principles, experience, and
The document discusses the relative merits of access to information than on specific
the vatious techniques, based on earthquake requirements and criteria.
engineering principles, observed seismic
perfonnance, construction procedures, and
costs.

1.2 Scope and Limitations


This document provides descriptions
and discusses the relative merits of various
techniques for seismic upgrading of buildings
found by evaluation to be seismically deficient.
It is not intended for the repair of seismically
damaged buildings, although some of the
techniques may be useful for such repairs. The
techniques are described generically,
accompanied by sketches to illustrate concepts.
This document does not provide specific
design criteria or specific details suitable for
direct application, nor does it recommend
specific devices.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Chapter 2

Seismic Deficiencies of the


Building Structure
The choice of techniques for seismic 2.2 Inadequate Strength!
upgrading of a building structure depends on Ductility
its seismic deficiencies. Appendix C of the
Guidelines for Seismic Evaluation l provides a
The safety of a building, as well as
master list of 123 potential deficiencies. For
the control of damage to the structure,
this document it is useful to combine these
depends very much on the behaviour of the
deficiencies into the following more general
building structure when subjected to large
categories:
earthquake forces. The safety depends not
• Lack of integrity/redundancy
only on the strength of the building structure
• Inadequate strength/ductility
but on its behaviour under cyclic overloading -
• Inadequate stiffness/adjacent buildings
its ductility, its energy-absorption capacity
• ItTegularities/load transfer.
and its stiffness. In the case of moment
frames, the safety of the building also
These categories are broken down depends on the ability of the frames to
into more specific deficiencies in Tables Al to support the vertical loads in displaced
A6 in Appendix A. As a background to the configuration (the P-6 effect). Most
principles of seismic upgrading (Chapter.3~, evaluation statements in the Guidelines for
the categories are discussed in more detaIl In Seismic Evaluation! concern such properties.
this chapter.
Ductility under cyclic loading is
2.1 Lack of Integrity! therefore an important consideration, but it is
Redundancy often difficult to achieve through upgrading of
existing structures. It can be achieved,
If the structure is not integrally however, by altering the structure by vaIious
connected, it will start to come apart dming a techniques, as described in Chapter 3.
strong earthquake. Expelience shows that t.he
most serious deficiency leading to progreSSIve 2.3 Inadequate Stiffness!
collapse of a building is lack of adequate Adjacent Buildings
anchorage of masonry or precast elements
(walls, columns, beams, slabs) to the
Earthquake experience has shown
diaphragms and to each other. Other. .
that the lateral stiffness of the vertical structure
deficiencies in integrity relate to contInmty of
is a major factor in the prevention of life-
diaphragms (such as wood or precast concrete),
threatening failures and in the control of
especially around openings, and tying together
building damage. Lateral stiffness ther~fore
of shear walls (tie-downs and connections
becomes an important factor to be conSidered
between infill and frames).
in the choice of upgrading for buildings in
medium to high seismic zones. It is less
Redundancy is another property of a important in low seismic zones becaus~
building structure which, as shown by seismic ground displacements are relatIvely
earthquake experience, helps prevent failures.
small.
Redundancy concerns not only the redundancy
of the structure in resisting lateral loads
Adequate in-plane stiffness of
(multiple shear walls and frames) but also .its
horizontal diaphragms (wood, metal deck) is
ability to resist vertical loads after local faIlure
also an important consideration in preventing
of a component such as a shear wall.
instability failure of masonry walls in high
Redundancy, however, is not always an
seismic zones. This is covered in Appendix A
advantage, especially when the "redundant"
of the Guidelines for Seismic Evaluation. !
elements are of a blittle character, as discussed
later.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Compatibility in lateral stiffness of the 2.4 Irregularities/Load


vertical elements of the building, including
Transfer
architectural components, is another impOliant
consideration. The stiff elements attract the
Dissymmetry in the layout of the
load and therefore fail first, whereas the
lateral load-resisting structure or in the mass
flexible elements do not carry much load until
distribution can cause major torsional
after the stiff elements have failed. If, as a
movements in an earthquake. Sudden changes
consequence of this, part of the building loses
in stiffness or discontinuities in both vertical
its vertical support, a dangerous progressive
and horizontal elements attract large local
collapse can occur.
forces or deformations, leading to local
rupture. Types of ilTegularities that attract
Related to lateral stiffness of the large localized forces include:
vertical structure is pounding from adjacent
• open fronts (shops, garages, etc.) in
buildings or from adjacent parts of the same
exterior walls at ground floor level
building separated by movement joints. Tall
• columns supporting shear walls
moment-frame buildings are flexible and can
• short concrete columns in moment frames
impact adjacent low stiff buildings. Damage (e.g., due to partial infills)
can be very severe, particularly if storey levels
• shear walls or bracing offset from floor to
do not line up. Impacts can also occur within a
floor.
building if heavy components are not laterally
supported by the structure.
Open fronts of buildings are a soft
storey condition which has resulted in many
collapses in recent earthquakes. Columns
SuppOliing shear walls are subjected to very
large overturning forces, and short concrete
columns attract large lateral forces and fail in a
brittle shear mode. Offset shear walls or
bracing result in large localized diaphragm
forces.

o
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Chapter 3

Principles of Seismic Upgrading

3.1 Objectives of Upgrading 3.2 Conventional


Upgrading Techniques
Once rehabilitation of a building is
deemed necessary for safety or other reasons Conventional upgrading techniques
(e.g., post-disaster function), there are a do not require special devices or new
number of objectives, including life safety, that materials. The following basic techniques are
must be considered in the choice and design of cUlTently used for seismic upgrading:
the seismic upgrading. These may be listed as
follows: New Shear Walls. This includes
(I) life safety reinforced concrete, reinforced masonry,
(2) prevention of damage to building plywood-sheathed wood-stud walls and steel-
components and contents (damage control) plate shear walls. New shear walls should
(3) minimum disruption of building use during preferably be located between existing
upgrading columns and connected to them, not only
(4) proper functioning of the building after because this arrangement is structurally more
upgrading effective but also because it may avoid the
(5) acceptable building appearance and necessity of new foundations. New shear
heritage value walls can be used to reduce torsional or other
(6) minimum cost. forces due to irregularities, as well as to
increase strength and stiffness of the existing
Objectives (3) to (6) are usually structure.
interrelated in the sense that they seek
minimum structural intervention, provided the New Bracing. This can be executed
objectives of life safety and damage control are in steel, wood, or occasionally in reinforced
met. Minimum intervention will vary concrete. New bracing is usually in the
substantially from building to building and its vertical plane but can also be in the horizontal
achievement is very much a practice-oriented plane. The bracing should preferably be
exercise involving considerable interaction of located within existing frames for the same
the engineer with the architect, owner and reasons that shear walls should be located
contractors. This chapter first summarizes between columns. As is the case for shear
available upgrading techniques and then walls, new bracing can be used to reduce
discusses the principles the engineer will have torsional or other forces due to irregularities of
to consider in the choice and design of the the structure, as well as to increase the
upgrading. strength and stiffness of the vertical structure
or diaphragms. A new technique is to
incorporate special damping devices in new
bracing; this is discussed in 5.1.

Infills. The systems described above


for new shear walls can also be used to fill
openings that are no longer needed in existing
walls or diaphragms. Infills enhance stiffness
as well as strength of existing walls or
diaphragms. However, adequate strength of
surrounding frame members must be assured.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Overlays. This includes cast-in-place Anchorage devices will also be useful


concrete (shotcrete, toppings, etc.) and when tying adjacent buildings or building
plywood. Mesh-reinforced cements or plaster portions together, in order to make them act as
and fibre-reinforced plastics (see 5.3) may also a unit and to avoid collision and hammering.
be used for safeguarding brittle components Vertical tie-downs through floors, splices
such as hollow clay tile or concrete columns. between diaphragm elements (e.g., at opening
Overlays increase strength and stiffness of corners or between beams at supports) also
shear walls and diaphragms, and can be used as provide integrity to the structure.
a means of tying different elements together for
better integrity of the structure. Precast assembly-type structures have
not performed well in recent earthquakes as a
Strengthening Members. This result of connection failures and relative
includes adding components to strengthen or movements at the joints between the precast
stiffen existing members, or to make them elements. One remedy is to strengthen and
more ductile. A variety of methods exist, stiffen the ties.
including reinforcing existing masonry (hollow
block or coring of brick masonry), encasing Chords/Collectors. A chord is a
with reinforced concrete, steel plates or fibre- continuous member placed along the outside
reinforced plastics, and lateral bracing to edge of the diaphragm. It acts as a flange to
reduce buckling length. Sometimes it is more resist diaphragm moment. A collector is a
economical and faster to replace existing member incorporated in the diaphragm which
members with new ones, as in the case of 'collects' diaphragm shear and transfers it to
bracing systems. Sometimes it is better to the vertical structure. Chords and collectors tie
strengthen existing components, such as diaphragms together and transfer diaphragm
unreinforced load-bearing masonry. Besides forces into the vertical structure. Sometimes
increasing strength, member strengthening can reinforced-concrete toppings, plywood
be used to make the structure more ductile by sheathing or steel trusses can accomplish the
altering the mechanism of failure, for example same objective. Collectors are sometimes
by making reinforced-concrete columns called 'drag-struts.'
stronger than the beams.
Foundations. Upgrading of
Strengthening Joints. This includes foundations is generally expensive and should
converting shear connections into moment be avoided if possible except where, as shown
connections in steel frames, strengthening by earthquake experience, foundation failure
bracing connections so that yielding takes results in severe consequences as, for example,
place in the bracing members rather than brittle due to liquefaction, slides or pile failures. See
failure in the joints, nailing of wood sheathing, Guidelines for Seismic Evaluation 1 for the
or welding of metal deck for strengthening evaluation of foundations. There are a number
diaphragms. Strengthening joints can be used of techniques for stabilizing liquefiable soils,
to increase the strength of the structure and to sensitive clays, weak soils, or foundations on
make the structure more ductile by altering the slopes.
mechanism of failure.
New or enlarged foundations may be
Anchorage/Ties. This includes required for new gravity loads or for large
anchorage of walls to floor or roof diaphragms overturning forces created by new shear walls
for lateral support of the walls and for transfer or bracing. Conventional upgrading techniques
of shear from the diaphragms to the vertical include the addition of piles and the widening
structure. It also includes anchorage of the of existing footings, but generally it is easier to
vertical structure into the foundations. build new foundations away from existing
Anchorage devices provide integrity to the ones. Soil and rock anchors are very cost
structure and are generally the most effective effective in controlling uplift, both for
technique in terms of cost-versus-life-safety upgrading of existing footings and for
benefit. installing new ones.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

3.3 Special Upgrading 3.4 Considerations in the


Techniques Choice of Upgrading
Techniques
A number of recently developed
techniques are available which use special The six objectives listed in Section
devices or new materials, and more are 3.1 provide the basis for the choice of
expected to be developed in the future. Those upgrading techniques to achieve minimum
discussed in Chapter 5 of this Guideline intervention. The following is intended to
include the following: help the engineer in this task by a discussion
of structural considerations related to
Supplementary Damping. In this seismicity and structural behaviour, and other
technique, dynamic displacements and forces considerations related to the upgrading
in the building are reduced by the action of construction process, the effect of upgrading
energy-dissipating devices located at places of on the function and appearance of the
relative motion between storeys of the building, and cost.
building. The devices convert kinetic energy
into heat through sliding, yielding or viscous 3.4.1 Structural Considerations
flow mechanisms. The technique is most
suitable for flexible structures such as moment Seismicity. The seismic ground
frames and is used in association with bracing motion con'esponding to a design earihquake
or stiff/strong cladding. depends not only on the seismic zone but also
on local ground conditions. Soft soils filter
Base Isolation. In this technique, out high-frequency rock motions but amplify
much of the earthquake ground motion is considerably the motions associated with low
prevented from being transmitted to the frequencies, and these can develop a
building by means of isolation devices located resonance condition in the building stlUcture,
at the base of the building; these are very depending on its natural frequency. In the
flexible in shear, or they slide. The result is a following, the seismicity in terms of the
considerable reduction in building velocity-related seismic zone, Zv' should, for
accelerations and forces, particularly for stiff buildings on soft soil, be considered a level
buildings on firm ground. greater than the National Building Code
(NBC) value.
FRPIFRC Overlays or Encasing.
This includes composite overlays of fibre mesh For low seismic zones (Zv of 2 or
and cement plaster or epoxy. It is applied to less) the main concern is the integrity of the
existing masonry for improved shear resistance stlUcture, specifically anchorage of masomy
and lateral strength and to concrete columns walls to the diaphragms and lateral support of
for better confinement and ductility. parapets, precast panels and masonry
partitions. This means that the provision of
anchorage and lateral suppOli are likely to be
the principal upgrading techniques used.

For medium to high seismicity (Zv >


2), a broader range of potential deficiencies of
the structure must be addressed. Not only
integrity, but lack of strength/ductility, lack of
stiffness and ilregularities of the structure
become important. Often these deficiencies
occur simultaneously. For example, high
torsion, inadequate strength and excessive
drift are frequently correlated as a result of
irregularities in the building structure, as
discussed later. For this reason it is desirable
to use an upgrading technique such as well-
placed new shear walls or bracing that
simultaneously resolve these three major
deficiencies. New shear walls or bracing may,
however, require new foundations, as
discussed later.

o
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Irregularities. The most serious Irregularities such as setbacks in the


irregularities are soft or weak storeys and vertical structure, re-entrant comers or split-
dissymmetry resulting in high torsion. Short level offsets in diaphragms are generally
columns in concrete frames and discontinuities resolved by strengthening techniques
in the vertical structure, such as offset shear (connections, splices, overlays, etc.) at these
walls, are also critical. For these types of critical locations. Diaphragms may require
deficiencies the most effective technique is to local strengthening for large shear forces
reduce irregularities by improving the load generated by shear walls that are offset from
path. This is achieved by adding new storey to storey.
components in the weak or soft locations (see
Figure 3-1 for torsion), or by removing stiff Obviously, the building will have to
non-structural components that cause high be reanalyzed if there are significant changes
forces in brittle components, such as short to the vertical structure. If there still remain
concrete columns. The most effective significant offsets of centres of stiffness and
technique such as new shear walls or bracing centroids of mass between floors, then a
may, however, not be acceptable for other dynamic analysis should be carried out to
reasons (layout, building function, aesthetics or determine member forces as required by the
heritage aspects, etc.). NBC. 3 Dynamic analyses of structures
composed of timber framing, masonry or
precast concrete may be unreliable, however,
+ unless calibrated to measured dynamic
properties of the building structure.

LtChange in
centre of rigidity
Compatibility. This term refers to
the ability of parallel elements of the vertical
structure to work together to provide a system
that behaves well in an earthquake. A very
ductile but flexible moment frame is not
compatible with a stiff brittle shear wall.
.'\.oCI.... 0 •••• 0 •••• The provision of such a frame as a second line
of defence will not prevent collapse in
~ Add new stiff situations where shear walls that are required
elements to reduce to carry gravity loads suddenly collapse in an
eccentricity earthquake.

A satisfactory solution is to produce a

+~
•• system that is protected from deformations
•• affecting the integrity of the walls, i.e. through
elements that are of sufficient stiffness as well
Q as strength. This can be done in different
••
(ange in :entre
of rigidity

o•
• ways: by making the walls adequately strong
to resist the forces they will attract; by
improving their deformability; or by adding
•• independent but sufficiently stiff elements.
••
• • • • .[J • • • • .[J • • • • .[J • • • • CJ

Figure 3-1 Upgrading a Structure to


Reduce Torsion

o
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

The consequences of adding new System Behaviour. As in the seismic


structural components to the existing structure design of new structures, in the design of
are large local forces transmitted into existing upgrading it is desirable to achieve a system
materials. Careful attention should therefore behaviour with the following properties under
be given to the transfer of forces into the seismic actions: composite action and fuse
existing components by suitable connection behaviour.
details.
The goal of composite action is
Compatibility considerations also achieved by adding new components in such a
apply to overlays where there may be way as to make the existing and new
differential movements due to shrinkage, components act together compositely and to
temperature and possibly creep. correct the deficiencies of the existing
structure. For example, lack of integrity is
Foundations. Foundation upgrading corrected by providing new or improved
is usually expensive and, depending on the connections. The provision of new
occupancy and use of the building, can be components which stiffen the existing
disruptive. Often it is possible to upgrade the structure, for example, helps prevent damage to
building structure without upgrading the brittle components such as unreinforced
foundations, particularly in regions of low to masonry.
medium seismicity.
The goal of fuse behaviour is
One of the major disadvantages of achieved by making the structure perform in
new shear walls or bracing is that they may such a way that it 'yields' rather than
require new foundations. One way of avoiding 'fractures,' thereby preventing a progressive
or minimizing foundation upgrading for new collapse. In assessing the effectiveness of fuse
shear walls or bracing is to incorporate the new behaviour; it is useful to follow the behaviour
walls or bracing within existing structural of the upgraded structure under increasing
frames. Another is to install supplementary lateral load, and to establish a sequence of the
damping devices in the structure to reduce failure modes in various components (yielding,
earthquake forces into the foundations. buckling, rupture, uplift, etc.).

Uplift of the foundations is often Base isolation and supplementary


considered a deficiency which should be damping make use of the fuse concept, as does
corrected, but in many cases this may not be a ductile stable yielding failure mechanism in
necessary. The Guidelines for Seismic the beams of frames, in contrast to a brittle
Evaluation I do not include anchorage to the unstable failure mechanism in the columns.
foundations as a deficiency in low seismic For the same reason, a rocking mechanism in
zones. Whether or not uplift of the foundations masonry walls is preferred to a blittle shear
is a serious deficiency depends on the amount failure. Similarly it is preferable to allow uplift
of uplift and the damage that might occur as a at the base of concrete shear walls rather than
consequence of this movement. In fact, permit sudden failure in shear or compression,
foundation uplift may in some cases be particularly if the shear walls are brittle as is
considered as a positive feature, as discussed often the case in old buildings.
below under "System Behaviour."
The degree to which the fuse concept
Another way to avoid foundation can be relied on, however, depends on the
upgrading is to use a longer length of shear resulting displacements and the consequential
wall or more bracing, especially in the lower damage. Displacements can be estimated on
floors. For example, long lengths of an the basis of NBC elastic seismic forces (not
existing wood wall could be used as a shear reduced by the R factor) combined with
wall with only minor nailing and anchOling; realistic stiffness values for the resisting
such surfaces usually require a general elements of the structure.
architectural upgrade anyway.

o
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Damage Control. Control of damage Disruption. Disruption of the use and


to non-structural building components and to occupancy of the building during the upgrading
building contents may be required for life- can be another major consideration if the
safety (falling components, blockage of exits), building remains in operation during the
to protect investment, or to maintain building upgrading. For this reason seismic upgrading
function following an earthquake. Damage of the building structure is best carried out
control is therefore often a major consideration dming a major renovation of the building,
in the choice of upgrading techniques. preferably when the building is unoccupied. In
some cases this option is not available, and the
Anchorage of building components to upgrading must be carried out in stages,
the main structure is one technique for damage shifting people and operations around,
control. This Guideline restricts itself to undertaking work outside business hours, etc.
anchorage and suppat1 of walls (non-structural In such cases, the duration of the disruption
as well as structural) and parapets. and its extent throughout the building becomes
a major consideration in the choice of
Control of displacements of the upgrading techniques and the design of details.
structure (e.g., storey drift) to values which can
be tolerated by non-structural components is A special danger during upgrading is
another technique, as is reduction of seismic fire caused by welding sparks; precautions
building accelerations (which might damage should be taken to prevent the occurrence of
special machinery or artifacts) by special such fires.
upgrading techniques such as base isolation or
supplementary damping. Building Function. New structural
components, such as shear walls or bracing,
3.4.2 Other Considerations can negatively affect layout (traffic flow),
daylight or other features of the building which
Apart from concerns about structural relate to its use. For this reason, moment
safety and serviceability, there are other frames may be preferable to shear walls in
considerations that have a major impact on the certain locations. Thick overlays such as
choice of techniques and the design of details. concrete toppings increase floor elevation,
requiring adjustments to stairs, doors,
Accessibility. This refers to the ability elevators, etc.
to gain access for the upgrading work,
including the repair or replacement of building Aesthetics. Some upgrading
components and materials, the need for techniques are aesthetically unacceptable (see,
scaffolding, cranes, etc., and the ability to carry for example, Figure 4-5). Cross-bracing can
out the work in the available space. Difficult often have similar effects, and therefore
access is a major factor affecting upgrading moment frames are preferred in some
techniques and cost. Foundations are the least locations, such as the front of a store.
accessible components of the structure and, as However, attention must be paid to stiffness
a consequence, usually the most costly to considerations to avoid a soft-storey situation,
upgrade; techniques should therefore be sought resulting in large torsional displacements.
to avoid foundation work.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Heritage Values. Seismic upgrading 3.5 Design Criteria, Testing


of historic or unique buildings can be
of Special Devices
especially challenging. Heritage values are
best served by the principle of minimum
This Guideline does not contain
structural intervention, where the existing
specific requirements for upgrading, including
building components/materials having heritage
structural design criteria, or requirements for
value are not substantially altered, or are
the testing and maintenance of special
altered in a way that respects and maintains the
devices. A major project in the U.S. (refelTed
heritage value of the existing building. This
to as the ATC-33 project) is cUlTently
often requires considerable attention to the
underway to develop specific requirements
design of details. Obviously the intervention
and criteria by 1997, and these may
must also comply with the objectives desclibed
subsequently be adapted for Canadian
in 3.1 of life safety, damage control, and cost.
practice. In the meantime the criteria spelled
out in the Guidelines for Seismic Evaluation 1
Such helitage concerns should
may be applied to establish the adequacy of
therefore be addressed early in the choice of
the seismic upgrading. However, the
upgrading techniques and in the design of
reduction factor of 0.6 for evaluation
details in close cooperation with the architect,
contained in the Guidelines for Seismic
owner and conservation professional or
Evaluation should be increased to 1.0 for
organizations such as the Heritage
design of the upgrading, except in cases where
Conservation Program of Public Works and
it can be justified in terms of the objectives of
Government Services Canada.
this Guideline (risk to life, cost, damage
control, heritage). Generally a more effective
Cost. The cost of seismic upgrading approach than reduced load factors is to catTy
of an existing structure can be substantially out a staged upgrading based on risk
higher than the cost for seismic resistance in a mitigation and cost. More specifically, the
new structure. Cost can sometimes be reduced following documents should be consulted for
by using one technique to eliminate a number design criteria and testing of special devices:
of deficiencies, or by choosing new structural
components that make the new and existing
(1) For upgrading existing unreinforced
components act compositely. Techniques that
masonry bearing wall buildings, Appendix
eliminate the need for foundation upgrading or
A of the Guidelines for Seismic
ex'tensive structural upgrading can also be cost
Evaluation. 1
effective.
(2) For supplementary damping and base
isolation, the NEHRP Recommended
Provisions for Development of Seismic
Regulations for New Buildings 5 in
conjunction with the CUlTent National
Building Code and the relevant CSA
standards 6-9 (see also Sections 5.1 and
5.2).

For foundations, the strength


properties of most soils may be increased fo.r
short term seismic forces, as recommended m
the Guidelines for Seismic Evaluation. l
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Chapter 4

Upgrading Techniques -
Conventional
Conventional seismic upgrading 4.1 New Shear Walls,
techniques include standard strengthening Bracing or Moment
methods - placing connectors (anchors, nails,
welds, bolts, dowels, splices, etc.) between Frames
existing structural components; connecting new
components (members, overlays, infills) to New shear walls may consist of
existing components; building new sub-systems reinforced concrete, reinforced masonry,
such as shear walls, bracing systems or piles and plywood on studs, or steel. New bracing is
connecting them to the existing structure. generally steel but could be timber, and new
Another conventional technique, not discussed in moment frames are generally made of steel or
this chapter, is to remove one or more upper reinforced concrete. These systems can be
storeys of the building in order to reduce the placed within the building, as interior or
seismic forces to a safe level. These exterior walls or bracing (Figure 4-la, b), or
strengthening methods make use of standard outside the building as buttresses
construction procedures. Techniques requiring (Figure 4-1 c). Exterior buttresses may have an
specialized devices or materials, such as advantage in that work can be cmTied out
supplementary damping, base isolators and fibre- primarily from the outside, minimizing
reinforced plastic or cement overlays are disruption and damage to interior finishes,
considered in Chapter 5. Techniques for equipment, etc.
upgrading foundations are discussed in Chapter 6.
Preferably, new shear walls or
This chapter provides brief descriptions bracing should be continuous to the
of techniques that can be used for upgrading the foundations. If not, the diaphragms may have
building structure, including a discussion of to be upgraded where vertical shear walls or
their relative merits based on the objectives and bracing are offset between floors.
principles described in Chapter 3.
Choice of System: It is generally
The details shown in Figures 4-1 best to choose a new system that is compatible
to 4-16 are generic and are intended to with the existing structural system.
illustrate concepts. Each detail must be Compatibility in this Guideline usually refers
designed to be workable under the conditions to compatibility in the load-displacement
that actually exist. response to a horizontal force. A new ductile
moment frame, for example, is not compatible
Care must be taken in the detailing to with an existing blittle shear wall. If the new
ensure that load paths are achieved. In general, system is in the same line of resistance as an
the use of large gusset plates, long fillet welds existing system, or between two similar
or stitching with many anchors is existing systems joined by a rigid diaphragm,
recommended to avoid concentrated forces at then the new and old systems are essentially
the interface of old and new components. parallel and should, preferably, be compatible.
There is less need for compatibility if the stiff
A global structural outlook must be system is ductiie or if the incompatible
maintained when developing an upgrade systems are not acting in parallel.
solution since an inappropriate solution may
change the seismic characteristics of the
building. For example, infilling a metal deck
with concrete to increase its capacity will also
increase gravity loads and possibly increase
forces in some vertical elements because the
diaphragm is much more rigid.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

4'++--r-H--+-+--"!"T"~Grouted dowels

a) New shear wall (reinforced concrete or masonry)

b) New bracing (HSS or double angles preferred)

Tie to suit existing


conditions

Concrete, masonry or
steel buttress wall

Soil or rock anchors


if required
d) New bracing (or shear walls) to reduce
C) External buttresses diaphragm sheaa

Figure 4-1. Nett' Shear Walls or Vertical Bracing

New moment frames or eccentric Earthquake forces due to irregularities


bracing are more compatible with existing such as torsion, or offsets in the vertical
moment frames and, if drift is not a problem, structure, can be substantially reduced by
may be more effective and less costly, appropriate location of the new elements,
especially if the structure is accessible from the Earthquake shear forces in the diaphragms can
inside, A problem to be considered with new be reduced by adding new lines of lateral
steel moment frames in an existing facility is support as shown in Figure 4-1d,
the difficulty of moving large beams within a
confined space, Because foundation upgrading is
usually expensive, it is desirable to try to make
Location. Location of new shear use of existing foundations by locating new
walls or bracing is a key decision which shear walls or bracing within existing frames or
depends on non-structural as well as structural to use light bracing instead of heavy shear
considerations, walls, To reduce uplift and avoid upgrading of
foundations, it is sometimes advantageous to
Structural considerations in the lengthen bracing or shear walls so as to avoid
location of new shear walls or bracing include large overturning moments in one place, If
the symmetry of the structure (torsional foundation upgrading is required, it may be
effects), the need for foundation upgrading, the better, however, to locate new shear walls or
need for new collectors/connectors for bracing away from existing foundations (inside
transfelTing diaphragm shear into the new shear or outside the building) because it is often
walls or bracing, and whether the horizontal easier to build new foundations than to upgrade
diaphragm is flexible or rigid, Sometimes the existing ones,
latter is difficult to establish, in which case
both assumptions should be considered,
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Non-structural considerations 4.2 Upgrading Existing


affecting location include disruption if the
building is to remain operational during
Moment Frames
upgrading, and the effects of the new shear
walls or bracing on building function (layout, In medium to high seismic zones it is
daylighting), building appearance and heritage often more effective to incorporate new shear
walls or bracing into existing frames than to
value. For special service buildings such as
hospitals, disruption can be a major problem upgrade existing moment frames. On the
other hand, upgrading existing moment frames
and must be kept to an absolute minimum, for
example by locating new shear walls or may be effective for low-rise buildings,
especially if it avoids foundation upgrading
bracing outside the building. Occasionally
these can conveniently be located within new and if the structure is easily accessible.
additions to the building. Heritage
considerations, on the other hand, tend to Conventional techniques for
require that new shear walls or bracing be upgrading existing moment frames include the
placed unobtrusively inside the building. New following:
shear walls or bracing can also create
obstructions to the functional use of the Steel Moment Frames:
building and can affect the appearance of the • Cover plates, clips and stiffeners
building and its interior daylighting. However, (Figure 4-2)
concrete shear walls or buttresses can include • Gusset plates, knee braces
fairly large openings provided they are • Reinforced concrete encasement
properly designed. The location of new shear (Figure 4-3a)
walls and bracing, therefore, must be worked • Steel jacketing (Figure 4-3b)
out in close cooperation with the architect and • Lateral bracing of unsupported flanges
the owner of the building.
Concrete Moment Frames:
Steel frames can be used as an • Steel jacketing (Figure 4-3b)
exterior skeleton to transfer forces from the • Reinforced concrete encasement,
horizontal diaphragms to the foundations. (Figure 4-3a) or FRP encasement
When such frames are used, consideration (Chapter 5)
must be given to maintenance; appropriate • Repair of precast connections.
shapes should be used such as tubes or HSS
sections with details that drain properly. Steel moment frames are generally
Building secmity should also be considered as the easiest to upgrade, but if welding is used,
some an'angements of members may be easily it must be ensured that the existing steel is
climbable. weldable. Recent earthquake experience with
brittle failures at weld locations indicates that
In summary, new shear walls or bolted connections may be preferable to
bracing should be considered especially where welded connections. Reinforced and precast
the existing building has the following concrete frames are more difficult to upgrade,
deficiencies: mainly because it is difficult to overcome
• Soft storeys deficient reinforcing or connection details.
• High torsion
• High storey drifts Moment frames with existing infills
• Pounding of masonry require special attention. Because
• Masonry or other components sensitive to of the rigid infill, these systems act as shear
storey drift. walls and attract large forces. Failure can
occur due to
• lateral instability of the infill,
• crushing or splitting of the infill due to
large in-plane forces,
• shear or tension failure of frame columns.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

New reinforcing

Angles bolted or welded


to existing steel

Figure 4-2. New or Improved Moment Connections

(a) Concrete encasement of columns

Ties

Cover removed ... ~ ./

l:i;,: := Lo=n~g=it=U=d:in~a=1=:S;:::~JE';~;Og 000"". , , / '<>:<y: Ties

reinforcement steel column

(b) Steel jacketing

~AngleS
~welds
~Straps

Figure 4-3. Encasing or Jacketing Existing Members


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Three upgrading strategies for infilled 4.3 Upgrading Existing


frames are:
Braced Frames
(1) make the infill and frame act effectively as
a shear wall (see Section 4.4),
Existing braced frames are usually
(2) isolate the infill frame by means of gaps
made of steel, but wood braced frames also
and resilient materials, while ensuring
occur. The types of steel bracing are shown in
lateral stability of the infill,
Figure 4-4. Cross-braced frames are most
(3) introduce new shear walls or bracing to
typical of older buildings, and these va~ from
stiffen the structure against infill damage
flexible rod bracing (tension only) to stIff
while ensuring lateral stability of the infil!.
bracing which is strong in both compression
and tension. Stiff cross-bracing that is
The first strategy is effective if the connected together where the bracing intersects
infilled walls have sufficient capacity, the
generally exhibits ductile behaviour i~
second if the frames have sufficient capacity earthquakes. Tension-only cross-bracmg
and drift is not a problem, and the third will exhibits poor behaviour because of yield
remedy both deficiencies. Lateral stability of elongation combined with 'slapping' of loose
the infill is ensured by direct contact with the
rods. Other types of bracing shown in Figure
frame around its perimeter, by lateral supports
4-4 include K bracing, and chevron or V-
at the top (see Figure 4-16b) or by wall bracing, which also perform poorly compared
mullions or basketing with plaster/wire mesh to stiff cross-bracing. This is because
or FRC overlays (see Section 5.3). compression buckling of a brace results in
Alternatively the infills can be replaced by
large unbalanced forces normal to the column
other materials. or beam at the brace intersection. A new type
of eccentric bracing has been developed which
If an exterior wythe of masonry is exhibits very ductile seismic behaviour. This
located outside the frame, it may be vulnerable bracing is discussed in 5.1.
to delamination at the collar joint. Many brick
masonry walls constructed of several wythes Deficiencies most frequently found in
have inadequate connection (e.g., no headers or
existing braced frames are strength/ductility of
collar joints) between the wythes. This must the connections or members of the bracing
be considered when developing an upgrade system (including columns and beams),
procedure.
unfavourable type or configuration of the
bracing system, and excessive drift in high
seismic zones.

Diagonal Cross

Chevron v K

Eccentric

~
~Linkbeam
(ductile fuse)

Figure 4-4. Bracing Types

.k. ,.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Two upgrading strategies are: 4.4 Upgrading Existing


upgrade the existing bracing system, or add
Shear Walls
new bracing or shear walls. Both should be
evaluated in terms of the objectives and
Four main types of shear walls are
principles described in Chapter 3.
common in existing buildings: reinforced
concrete or masonry, precast concrete,
For buildings more than three storeys unreinforced masonry, and wood sheathing on
in height, in medium to high seismic zones, studs. Behaviour varies considerably with
consideration should be given to replacement type. Wood sheathing, reinforced concrete and
of a tension-only bracing system by other reinforced masonry are the best performers,
means.
precast concrete less so, unreinforced brick or
block masonry are relatively poor performers,
Conventional techniques for while unreinforced hollow clay tile is the worst
upgrading existing braced frames include: performer because of its friability.
• Strengthen or replace connections
• Strengthen or replace members Because new shear walls often need
• Replace with better type of bracing new foundations, increasing the
(Figure 4-1 b) strength/ductility of existing shear walls is
• Improve anchorage to the foundation sometimes preferable. However, where large
in'egularities exist in the building resulting in
The choice of technique will depend poor load transfer that produces high tors.ion,
on accessibility and the bracing configuration: new walls or bracing may be more effectIve.
K-, V- or chevron bracing is sometimes
difficult to strengthen and may have to be Conventional techniques for
replaced by another type. upgrading existing shear walls include:
Wood bracing is sometimes difficult Reinforced Concrete or Masonry:
to upgrade and members that are severely • Infills (Figure 4-5)
checked have to be replaced. The ductility of Reinforced concrete overlays (Figure 4-6a)
wood bracing is governed by the connection • Steel plating or bracing overlay
• Coupling beams
details and often the greatest improvement is
obtained by providing connections that result • Post-tensioning
in ductile behaviour of the structure.

Infills (Reinforced concrete or masonry)

Close existing opening with


reinforced concrete or
reinforced masonry

n ,-,
::
,-,
:: n n n n n
'::: ~

'...
:C Dowels
.... :::' epoxy-grouted
in drilled holes
'... :::'

'::: :::.

'::: '*',
' ... ,....:'

"'.' '.' '.' '.' '.' '.' '.' '.'

Figure 4-5. Infills (Vertical)


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Precast Concrete:
• Infills (Figure 4-5)
• Reinforced concrete overlays (Figure 4-6a)
• Connection strengthening
• Pilasters/beams
• Tie-downs
Unreinforced Masonry:
• Reinforced concrete overlays (Figure 4-6a)
• Vertical reinforcing (Figure 4-7)
• Pilasters/columns
• Wire mesh/cement plaster or FRC
• Replacement
Wood:
• Additional nailing
• Plywood/OSB overlays (Figure 4-6b)
• Metal tie-downs and anchors (Figure 4-8)

(a) Reinforced concrete overlay (b) Plywood overlay

Holes sloped Stainless


for easy steel rods '--_*,,"-- Nails
grouting installed and
grouted from
exterior
Masonry Plywood
or concrete

Brickwork
Dowels (min 3 wythes)

Figure 4-6. Overlays (Vertical)


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

(a) Block masonry


Bars inserted directly from
top or side cut

.~_-r- Side cut

(b) Brick masonry centre coring

Cored and grouted


with rebars

Figure 4-7. Reinforcing Existing Masomy


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

(a) Foundation anchorage - Wood construction

j...------ Clip may be


I ,- required
it""
..' :>! . .
I

"""'Vi bolt

,........... strap

.......

(b) Vertical tie-downs - Wood construction

Tension
splice

Tension
splice strap

Figure 4-8. Vertical Tie-Downs and Anchorage


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Infills are often less costly, but they Concrete block walls can be upgraded
may be unacceptable for reasons of for both in-plane and out-of-plane forces by the
appearance. Overlays are less disruptive if installation of vertical reinforcement in the
applied from the outside, but heritage or hollow cores (Figure 4-7a). The concrete in
appearance considerations usually require them the roof bond beam is chipped out and a
to be applied from the inside or on interior reinforcing bar is inserted and anchored to the
shear walls. Concrete overlays increase shear foundation by a grout-filled hole.
capacity and provide lateral support to existing Alternatively, hollow cores may be opened by
masonry, but may require foundation saw-cuts near the top of each storey for
upgrading. Coupling beams between shear inserting reinforcing bars. The reinforced core
walls which behave in a ductile manner may is then filled with concrete. If intermediate
sometimes be cost-effective because they not bond beams exist, they are carefully chipped
only reduce wall overturning forces but out locally. An advantage of this procedure is
improve the overall ductility of the connected that work can be carried out from the exterior,
system. Consideration should be given to the Though the exterior face exhibits some
effects of relative movements between new patching, it is usually covered with an air
overlays/infills and existing shear walls, e.g., barrier, insulation and a new finish. A similar
shrinkage cracks and bowing. technique is used for brick masonry (minimum
thickness 300 mm) by drilling vertical cores
The continuity of the shear wall (l00 mm diameter) down through the masonry
system should be ensured by providing a and placing reinforcing steel and grout
continuous load path in shear, tension and (polymer cement) in the cored holes
compression. Existing concrete walls deficient (Figure 4-7b). The technique provides greater
in zone reinforcement can be upgraded by lateral stability and better rocking resistance of
adding concrete nibs or bolting on steel narrow walls. For both methods the
members. Foundation tie-downs for precast reinforcing may be post-tensioned.
walls to convert them into vertical cantilevers
or additional shear transfer connections may be Alternatively, unreinforced masonry
used as alternatives to strengthening existing can be upgraded by fibre-reinforced plasters
connections. Tie-down splices and shear (see 5.3) and by reinforced concrete overlays,
transfer connections may be required in wood including the option of removing the outer
shear walls, particularly for shorter walls, wythe to reduce weight and space.
whereas longer wood-stud shear walls may not
require tie-downs.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

4.5 Upgrading Existing Steel Deck Diaphragms:


Diaphragms • Welding
• Reinforced concrete overlay (Figure 4-9b)
Steel bracing (Figure 4-10)
Existing diaphragms are generally a • Shear studs, anchor bolts, dowels for shear
probl.em only for medium to high seismicity
transfer (Figure 4-11)
locatIOns; however, transfer of shear from the
• Steel chords, framing (Figure 4-11)
diaphragm into the vertical structure may be a
probl~m in lower seismic zones. Earthquake
Steel-Braced Diaphragms:
expenence shows that most diaphragm failures
• Replacement, reinforcement or addition of
are connection failures rather than failure of
members or connections
the diaphragm itself.
• Secondary bracing
• Steel deck and/or reinforced concrete
Two main types of diaphragms are
overlay with shear studs (Figure 4-9b)
common: flexible diaphragms consisting of
wood or metal decking, and rigid diaphragms
Concrete Diaphragms:
such as concrete slabs, concrete-filled metal
• Reinforced concrete overlay (Figure 4-9c)
decks, or floor structures which are
Opening infills
horizontally braced. Rigid diaphragms transfer
• Additional dowels for shear transfer
inertial storey forces to the vertical structure
(Figures 4-9c, 4-13)
according to the relative stiffness of the vertical
• Collectors under the diaphragms
components. Flexible diaphragms tend to
• New chords, framing (Figures 4-13, 4-14)
behave as beams between lateral supports and
transfer inertial storey forces to the lateral
supports. In high seismic zones, flexible It is usually more economical to
?iap~ragms may deform excessively, resulting
upgrade wood roof diaphragms from above
m failure of masonry walls (see Appendix A of rather than by installation of bracing or
Guidelines for Seismic Evaluation 1). plywood from below. This is because work
from below may interfere with mechanical,
electrical, sprinkler and architectural systems.
Diaphragms act as horizontal beams
On the other hand, it is sometimes more
in both bending and shear. It is therefore
economical to upgrade steel deck diaphragms
im~ortant that the integrity of the diaphragm be
from below by the addition of horizontal
achIeved. Integrity is achieved by the use of
bracing.
co~tinuous chords or ties near the perimeter,
splIces or reinforcing at re-entrant comers, and
collectors to transfer shears from the Cost and disruption are determined to
diaphragm into the vertical structure. a large extent by accessibility (removal and
replacement of non-structural components such
as flooring and partitions) and the extent of
Conventional techniques for
floor area requiring alteration. Reinforced
upgrading existing diaphragms include:
~oncrete toppings have the disadvantages of
mcreased floor elevation (requiring changes to
Timber Diaphragms: stairs, doors, etc.), increased dead load, and
• Nailing, stapling of existing diaphragms
sometimes increased torsion associated with
Plywood overlay (Figure 4-9a)
stiff diaphragms.
• Cross-walls (see Appendix A of Guidelines
for Seismic Evaluation 1)
Substantial upgrading of the
• Nailing, bolting for shear transfer
diaphragm can sometimes be avoided by
(Figure 4-12)
introducing additional vertical shear walls or
• Spliceslblocking for chords, collectors
bracing (see 4.1).
(Figures 4-12, 4-14)
• New chords, collectors
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

(a) Plywood on Sheathing (b) Concrete on Metal Deck

rl°
Od Nails

T~.~~
Shear connectors (channels, angles etc.
or screws installed from above or below)

(c) Concrete on Concrete

Edge reinforcing
Grouted dowel at openings

.~
/

Roughen / clean concrete

Figure 4-9. Overlays for Diaphragms

(a) New bracing for steel


construction

Horizontal bracing

(b) New bracing for Chord


joists on concrete Horizonta~,I=~:tlJ
or masonry walls bracing ~
system

Bracing (from below or above)


welded to joists and chord

Figure 4-10. Bracing for Diaphragms


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

New chord
and anchor

plate and anchor

angle (collector)

~ Steel strap anchored to deck/chord


Welds to strap and deck, as required
Steel angle anchored to ledger/wall, as required

Figure 4-11. Shear Transfer and Chords (Metal Deck Diaphragms)

Clip angles

Figure 4-12. Shear Transfer and Chords (Wood Diaphragms)

Masonry Concrete
Precast slab Precast slat

Chord
Increased for
shear transfer

Figure 4-13. Shear Transfer and Chords (Concrete Diaphragms)


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

(a) Collector in wood diaphragm


Collector
be required
directions)

(b) Reinforcing an opening

"
:::..£-IA
III~
:: :
- - - -I It- - - - - - - - - - - - -
III
~I I- - -
(c) Splicing a glulam beam
====:=: ------------ ,,(1- ~ ==:::
I I I
I I I
I I r
I I I
I I I
I r I
I I I
I I I
I I I
I I I
I I I

====. =t I I
_ _ _ _ _ _ _ __ _ _ _
I
===:::
-- -1 i~ --------- -,~
:::J

Welds
I II ILl- '

Section A-A

Steel angle or strap

Figure 4-14. Collectors and Splices for Diaphragms


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

4.6 Techniques for Lateral Techniques for anchorage or lateral


Support of Walls and support of walls and parapets are relatively
simple, but care must be taken to ensure that
Parapets details are designed for load transfer and that
the work is properly carried out. For example,
Lack of wall anchorage and slender connections that depend on tension
unsupported parapets are the most prevalent perpendicular to the grain in wood components
life-threatening structural deficiencies in connecting the anchor to the diaphragm must
existing buildings. Upgrading for these be avoided. Another common problem arises
deficiencies is generally much less costly and when lateral supports of the top of a wall do
less disruptive than for other deficiencies of the not permit vertical deflection of the structure
building structure. above, thereby creating a load-bearing wall.

Both load-bearing and non-load- Conventional techniques for lateral


bearing walls should be addressed. Unbraced support of walls and parapets include:
masonry and wood-stud partitions are common
along egress routes. These partitions may Exterior Masonry/Concrete Walls:
support ceilings and other non-structural • Anchor bolts (Figures 4-11, 4-13, 4-15)
elements. • Grouted dowels (Figures 4-9c, 4-13)
• Overlays (Figure 4-6a) or back-up walls

Blocking

+ + + +

Typical clip angle tie Metal strap anchor


Through rod

220min~/ i

1/ '.• . • . .• :.·.•i•. ••...••. Alternate anchorage


1. _ / // .-
><>.-/__/-/:--~ Concrete or masonry

Anchor bolt (check for shear) Flooring


Chord angle Sleeve nut
Steel strap welded to chord

Blocking
Joist
Grouted anchor

Figure 4-15. Lateral Support of Exterior Walls


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Exterior Curtain Walls: To minimize disruption, anchorage of


• Connectors which allow racking exterior walls should preferably be caniect out
from the outside. Work will have to be carried
Masol1l)' Parapets and Other Appendages:
out from the inside where the exterior is
• Bracing and anchoring (Figure 4-16a)
inaccessible or where the appearance of the
• Reduction in parapet height
anchors is unacceptable.
Veneers:
• Veneer anchors In many cases it is necessary to
Partitions: upgrade not only the connections but also to
• Lateral supports (Figure 4-16b) consider deficiencies of the wall itself. For
• Overlays or back-up walls example, unreinforced masonry walls may
require the additional support that is provided
Smaller, more numerous anchors by vertical reinforcing (Figure 4-7), overlays
rather than large anchors spaced far apart are (Figure 4-6a) or beam/column back-ups.
preferred to achieve a ductile type of failure.

(a) Masonry parapet support

Channel anchored to parapet


Brace

Anchor

(b) Masonry partitions

Steel angle

Gap
Steel Twith
vertical siot

Figure 4-16. Lateral Support of Parapets and Partitions


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Chapter 5

Upgrading Techniques • Special

This chapter provides guidance on The consequence of incorporating


three innovative upgrading techniques: supplementary damping devices is reduced
supplemental damping, base isolation, and dynamic amplification of earthquake ground
FRPIFRC overlays. It also references motions in the building, in particular reduced
procedures for evaluating buildings that interstorey displacements as compared to
incorporate special damping and isolation those that would occur without the devices.
devices. These techniques and devices are If, however, the existing structure is laterally
relatively new and in various stages of very stiff (e.g. a shear wall) and brittle, then
development. Therefore the guidance is, to a it is generally not possible for the devices to
large extent, qualitative and the collaboration work sufficiently to reduce damage to the
of specialist consultants may be required. building. If the structure is laterally flexible
(e.g. a moment frame), then the devices can
References for more detailed work effectively to substantially reduce the
information are given for each special interstorey displacement that would otherwise
technique. occur during the earthquake, resulting in less
damage to the building. If, however, there are
5.1 Supplemental Damping stiff and brittle infills attached to a flexible
structure, they will act as brittle shear walls
and fail before the devices work effectively.
It is well known that inelastic
structural behaviour dissipates seismic energy Stiff infills or panels should therefore be either
detailed to allow interstorey drift, or, if they
that is fed into the building structure. As a
consequence, the design lateral forces for are strong enough, be attached to the structure
with damping devices in order to contribute to
which the structure must be designed are
reduced. The NBC accounts for this by the the energy dissipation.
force modification factor R which ranges from
I to 4; the higher the factor the better the A number of buildings in Canada,
energy dissipation. In addition to energy the United States, Japan, Mexico, and other
dissipation due to inelastic structural countries have recently been seismically
behaviour, energy is also dissipated as a result upgraded with such devices. One of the
of inelastic deformation of non-structural principal benefits of this type of retrofit is
building components and by sliding friction avoidance of the need for foundation
between these components. Such energy upgrading. The damping devices are usually
dissipation is taken into account in the incorporated into new or existing bracing of
evaluation criteria for unreinforced masonry the structure, in connections between non-
buildings (Appendix A of Guidelines for structural panels and the structure, or at other
Seismic Evaluation 1) arising from inelastic locations where relative movements will occur
action of the wood diaphragms and partitions. during an earthquake.

Supplemental damping devices can be


inserted in a building to reduce the dynamic
response by removing much of the energy
induced in the structure by an earthquake.
When appropriately installed, these devices
allow seismic design to be shifted from the
conventional reliance on ductility of the main
structural elements to energy dissipation in the
added devices. The devices help protect the
building from severe damage or collapse by
limiting resonance build-up and consequently
reducing inelastic deformation of the structure.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

p
(Ib) A (kN)
2000 8.9

-0.7 0.7 (in.)


Friction
damper Viscoelastic damper
-17 17(mm)

50 cycles Frequency 2.5 Hz

-2000+ -8.9 0.2 Hz


t Frequency 0.5 Hz

700

350
Z
~
Metallic w
0
yield a:
0
damper LL
-350

-700
-0.36 -0.18 0.00 0.18 0.36
y (rad)
Figure 5-1. Hysteresis cruces for damping devices (Reprinted by permission)JO, 11

There are three main types of to the fundamental building frequency. The
damping devices - friction, metallic-yielding, damping devices, however, stiffen the
and viscous/viscoelastic. Types and building, consequently there is a decrease in
applications are described in Passive Energy its period T in addition to an increase in its
DissipationlO and Proceedings of Seminar on damping. This results in two benefits, first a
Seismic Isolation ll . An indication of their reduced dynamic amplification at the original
energy-dissipative behaviour is shown by building frequency due to the increased
hysteresis test curves in Figure 5-1. damping, second a reduced displacement due
to a decrease in period. This may not result in
Eccentric bracing, covered in a decrease in base shear, but this is not so
Appendix D of CSA Standard S16.1, 6 acts as serious because the added braced dampers
an energy dissipating element, except that the carry part of the lateral load. Figure 5-2b
'device' is part of the structure and therefore shows that increasing lateral stiffness as well
not supplemental or easily replaceable. as damping is particularly beneficial for
structures founded on soft soil.
It is important that the damping
devices be tested prior to installation for For efficient operation the supplementary
assurance of their behaviour. It should also be devices should be located in the regions of the
ensured that their behaviour is maintained building where significant inter-storey
during the life of the building. displacements occur. For stability of the
structure, the lateral resistance of the structure
Design Principles and Analysis. should increase with increasing displacement.
A general idea of the effect of supplemental It is therefore important that, except for the
damping on structural response can be devices, the structural system remain elastic,
obtained by examining the earthquake or nearly so, during the design earthquake. It
response spectrum for normal damping may be necessary to use conventional
(5 percent critical) and supplemental damping techniques to strengthen some structural
(25 percent critical approx.) such as shown for components, such as columns in lower storeys
two typical cases in Figure 5-2. Figure 5-2 that attract extra axial loads from the new
shows that if the structure is upgraded without braced devices. Because of the added
changing its period, the reduction in response damping, however, these loads are likely to be
is the difference between the lower and the smaller than those resulting from the presence
upper response spectrum values corresponding of the new bracing alone.

J< •
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

(a) 1985 Chile earthquake (b) Lorna Prieta earthquake


(Llolleo record - firm ground) (Santa Cruz record - soft ground)
3 20 1.6 60.5
.5 Cl
soE
- - - ---
Cl Damping ratio
C" E C
0.05 0.25
~
.12
§
1 ~ 1.0
2 / 40

<Il
/
/
/

10 i
.!!!
"0
~
30j
<Il

"0

1!! - - -- 1!!
1!! 0.5 201!!

i i i
CIl
10 i
CIl CIl OCll
0 0
2 3 4 5 0 2 3 4 5
Period, seconds Period, seconds

Figure 5-2. Exarnples of Earthquake Response Spectra for Acceleration and Di:,placement
(Reprinted by permission) 10
__ spectral acceleration, - - - spectral displacement

The devices and their locations 5.2 Base Isolation


should be designed to achieve maximum
effective energy dissipation in the structure, 12 Base isolation uncouples a building
in order to minimize inter-storey from its foundation, allowing it to "float" on
displacements and avoid excessive forces, flexible elements. This limits the energy
particularly those which would require new transfened into the building by an earthquake.
foundations, collectors, connections, etc. The Isolation protects a building in two ways.
design of upgrading involving supplemental First, the isolators reduce the overall lateral
damping devices therefore requires more stiffness of the building and, as a result, the
effort than a design using conventional fundamental period of the building is shifted
upgrading techniques. However, in some outside the period region over which most of
cases the benefit can be considerable in the energy of the earthquake is concentrated.
reduced cost and disruption. Thus most of the seismic energy is not
transmitted to the building. Second, the
Specific requirements for the design isolators dissipate energy which reduces
of building systems containing damping resonance build-up that might occur at a
devices, and for their testing and maintenance, natural frequency of the isolated building.
are cunently being developed. Tentative The isolators, however, should be stiff enough
requirements for their use in new buildings to prevent unacceptable building sway under
are contained in NHERP Recommended wind loads.
Provisions;5 many of these requirements also
apply to the upgrading of existing buildings. The fundamental period of a base-
The NHERP Recommended Provisions allows isolated building should be substantially
a static analysis for buildings under certain greater than both its fixed-base equivalent and
conditions, including buildings with devices the predominant periods of the ground
that are viscous or viscoelastic. Otherwise a motion. Otherwise, the long period
dynamic procedure involving either the earthquake motions conesponding to the
response spectrum method or, more generally, fundamental lateral period of the isolated
a time-history nonlinear analysis is required. building will be amplified. Base isolation is
The latter method is specified in NHERP therefore generally unsuitable for buildings on
Recommended Provisions for friction or yield very soft soils (e.g. Mexico City) or for tall
devices, or where structural response will be buildings whose fundamental lateral
significantly nonlinear in a design frequency without base isolation approaches
earthquake. that for the building mass resting on the base
isolators. To control such low-frequency
A number of applications are motions, the base isolation system must
described in Passive Energy DissipationlO and dissipate energy, typically an equivalent
Proceedings of Senlinar on Seismic damping ratio of 0.10 to 0.20.
Isolation. II
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Basic Model Effect of soil conditions


U2
z
o
~
a::
Building: w
..J
High stiffness, W
low damping U
U
«
..J
«
a::
....u
w
a..
CIl
Isolators: TI PERIOD
Low stifness,
hign damping

Effect of base isolation

z ....z
o w
~
a:: ~
:E
w ~
w 0.05 u 0.05
..J
«
W 0.10 ..J
a.. 0.10
() CIl 0.20
U 0.20
« is
..J ..J
« «
a::
a:: ....
t; u
w
w a..
a.. CIl
CIl
TI PERIOD TI PERIOD

Figure 5-3. Effect of Base Isolation (Reprinted by permission)Jl


TF = Fixed base period, T j = Building period with base isolation

These considerations become evident One advantage of base isolation is


by comparing the response spectra of that it results in a substantial reduction of
Figure 5-3 for a stiff building (T = 0.5 s) building accelerations, such that the risk of
versus a very flexible building (T = 2 s) and damage to the building and its contents is
for firm ground versus soft soil. small, increasing the likelihood of continued
function of the building during and after an
During an earthquake, large lateral earthquake. Base isolation also protects
displacements will occur above the isolators at contents such as instruments, computers and
the base of the building. Therefore, moveable precious artifacts in museums. However,
joints are required in the services to the additional conventional upgrading of the
building (pipes, sidewalks, etc.). There must building may be required in high seismic
also be a substantial separation of the building zones. Another possible advantage is that
from adjacent properties. Because base installation of the isolators at the foundations
isolation involves considerable upgrading of may be less disruptive to the use of the
the building foundations, it is generally building than conventional upgrading
considered economically viable only for techniques.
important special-purpose and heritage
buildings in medium to high seismic zones.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Currently there are three main types 5.3 FRP/FRC Overlays and
of base isolation devices: elastomeric, sliding Encasements
and hybrid. The most popular ones in use
consist of deep elastomeric pads laminated
Fibreglass has been used for many
with steel plates, which incorporate high
years to upgrade wood boats. Fibre-reinforced
damping rubber or a lead core to provide
plastics (FRP) and fibre-reinforced cements
energy dissipation. Sliding isolatio~ devices.
(FRC) incorporating glass, carbon a.nd ?ther
have also been used in North Amenca. Hybnd
materials are now being used for seIsmIC
isolation systems combine sliding with
upgrading of buildings. Current applications
elastomeric damping. More information on
include FRC overlays of masonry walls and
these devices is contained in Proceedings of
partitions, and FRP encasement of concrete
Seminar on Seismic Isolation. 11
columns and architectural terra-cotta.
A base isolation system should
Masonry Walls/Partitions. Fibre-
provide increasing resistance with increasin~
reinforced cement (FRC) strengthening of
displacement so that the building returns to Its
existing masonry is currently used for seismic
original position after the earthquake.
upgrading in New Zealand and Australia. 16
The FRC system is a plaster skin process
Requirements for the design of base (Figure 5-4) which can be used for improving
isolated buildings and for the testing and
both in-plane and out-of-plane strength of
maintenance of base isolators are contained in masonry walls. 17 The FRC process consists of
the NHERP Recommended Provisions. 5
one or more layers, depending on the strength
Although these requirements apply to new
required, of a particular high tensile strengt~
buildings, many of them would also be
woven fibreglass mesh which is embedded m
appropriate for existing buildings. The . a fibre-reinforced plaster. The process can be
NEHRP publication contains three analysIs
applied to one or both sides of a wall. Z?ne
procedures in order of increasing complexity steel with plaster thickening may be reqUIred at
and wider application - a static procedure, a
the ends of shear walls. The manufacturers
spectrum procedure and a time-history
have developed some specialized details for
dynamic procedure. The conditions for which
developing continuity and for connecting the
the procedures may be used relate to soils,
walls to the floors and roofs.
proximity of active faults, seismicity, bUil.ding
period, building irregularities and propertIes of
the isolation system. Fiberglass reinforced cement strengthening

Further information, including a


number of applications, are described in An
Introduction to Seismic Isolation, 13
Proceedings of Seminar on Seismic Isolation, 11
Proceedings of a Seminar and Workshop on
Base Isolation and Passive Energy
Dissipation, 14 and Seismic Retrofit of
Historical Buildings Conference Workshop. 15

I, ,.'

-..
'
"
"
.". , ... ,
,. - -..... ,

Figure 5-4. FRC Strengthening of Masonry


Walls
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Encasement of Concrete Columns. flexural mode. The lateral stiffness of the


FRP overlays of concrete columns is currently column between floors is not increased
being used for seismic upgrading of columns substantially (such stiffness would attract
in a number of bridges and buildings in the more earthquake load to the column) because
United States l8 , 19. A fibre/epoxy jacket is FRP wrapping is much stronger in the
wrapped around the column in large bands of circumferential direction than in the
woven unifabric and this cures in place longitudinal direction. In cases where the
(Figure 5-5). The jacket may be post- confinement stress is not needed, non-post-
tensioned circumferentially by injecting grout tensioned FRP encasement can be used to
under pressure into a bladder wrapping increase shear strength in order to ensure
between the FRP jacket and the concrete ductile flexural behaviour. For more
column. The effect of the post-tensioning is to information see Fibre Wraps Migrate East. 19
confine the concrete column so as to prevent A similar technique involving the application
failure of reinforcement at critical laps near of FRP overlays to existing masonry walls is
the joints and to increase the shear resistance also under investigation.
of the column such that it fails in a ductile

8!l!22m::!!:!!l!~~~ Fiber/Epoxy Wrap

A
Section A·A

Existing Concrete Column

Figure 5-5. FRP Encasement of Concrete Columns


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Chapter 6

Upgrading
Techniques - Foundations
Historically, few foundations on level Objectives (1) and (2) are generally
competent ground have failed during achieved by the application of conventional
ear1hquakes. Foundation failures have techniques for upgrading described in 6.1 or
occurred where the underlying soils have by the application of soil stabilization
comprised loose saturated sandy or silty soil, or techniques described in 6.2. Objective (3) is
very soft sensitive clays, or where foundations generally achieved by the application of
have been located on steep slopes. techniques described in 4.2 to 4.4 and 6.1.
Objective (4) is achieved by the application of
The advice of a competent soil stabilization techniques described in 6.2.
geotechnical engineer and/or geologist should Objective (5) is achieved by the application of
be sought whenever the building is located on conventional techniques described in 6.1 and
soft or loose soil or where geological seismic the use of special devices described in 5.2.
site hazards exist.

Upgrading of foundations is generally


expensive because of access difficulties. The
need to upgrade the foundation to resist gravity
and seismic forces, however, arises in
circumstances that require one or more of the
following five objectives to be met:

(1) to provide new foundations for vertical


elements added in the upgrading;
(2) to enhance the bearing, uplift and lateral
capacity of the existing foundation;
(3) to strengthen the connections between the
foundations and vertical elements;
(4) to prevent potential loss of soil support
(e.g., by soil stabilization), and
(5) to implement base isolation.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

(a) Underpinning an existing footing (b) Transmitting existing


footing load to competent
subsoil using soil anchors

~ Attached to the
Preloading jack and foundation with
pocket (if required) brackets or
concrete cap

(c) Addition of needle beam and drilled


piers to an existing strip footing

Reinforced concrete
needle beam (above or
below footings)

Drilled
concrete piers

Figure 6-1. Conventional Upgrading of Foundations

6.1 Conventional Techniques: Existing continuous


(strip) or spread footings may be subjected to
Techniques for excessive bearing pressure or even uplift.
Upgrading Foundations Techniques to alleviate these conditions
include:
Seismic upgrading of the superstructure may • underpinning the existing footing so that
require upgrading of the foundation, the upgraded footing is founded on
particularly if there are new shear walls or competent subsoil (Figure 6-la)
bracing. The foundations need to • adding soil anchors (Figure 6-1 b), drilled
accommodate increased gravity loads as well piers, or piles (Figure 6-1 c)
as seismic shear and overturning forces. An • increasing the number of vertical load-
increased allowable bearing capacity is usually carrying elements in the superstructure.
appropriate for short-term seismic forces.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Pile foundations may be Foundation uplift may not be a


subjected to excessive tensile and compressive problem (see Section 3.4.2), but if it is, the
loads from the combination of seismic and uplift capacity of an existing foundation may
gravity loads. Their lateral capacity may also be increased by adding soil anchors, drilled
be inadequate for transfening the seismic piers, or piles. The ability to do this will
shears from the pile caps and the piles to the depend on access and available headroom in
subsoil. The pile foundation capacity can be the interior of the building. An alternative is
increased by: to provide additional vertical resisting
• driving additional piles and enlarging the elements to distribute the overturning forces
existing pile cap to other vertical members or to tie adjacent
• introducing tie beams between pile caps footings together with a reinforced-concrete
to assist in redistributing the loading. beam so as to mobilize the resistance of the
adjacent footings.
Mat foundations may
occasionally have inadequate moment While additional piles may be
capacity to resist the combined gravity and provided for upgrading a pile foundation, the
overturning forces. This deficiency may be existing pile cap may not be able to distribute
conected by providing a locally thickened the loads efficiently to the new piles. In such
reinforced-concrete section such as inverted cases it may be necessary to shore up the
column capitals. column and replace the old pile cap with a
new one that includes the new piles. Deep tie
To prevent foundation damage beams to distribute some of the pile load to
due to seismic shear, the passive resistance of adjacent pile caps that have unused capacity
the founding soil can be mobilized by is usually more cost-effective than installing
introducing perimeter and tie beams or shear new piles.
keys which extend into the underlying soil.
These can also be used for tying footings
together and redistributing forces.
Alternatively, anchors, drilled piers or raked
pile~ can also be used.

For buildings constructed on


steep hills, the columns and piers should be
designed to resist earthquake loads, and
foundations should rest on stable ground.
Piles with adequate lateral capacity should be
used for buildings over the water along bay
shores and river banks.

Relative Merits. Conventional


procedures such as those shown in Figure 6-1
may be effective for some applications.
Because foundation upgrades tend to be costly
and disruptive, other seismic upgrading
schemes should be considered, such as soil
stabilization or additional shear walls, bracing
or buttresses. Underpinning existing footings
is usually not appropriate for buildings
founded on a thin clay crust overlying
liquefiable soils (e.g., some buildings in
Richmond, B.C. - see Earthquake Design in
the Fraser Delta. 20)
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

6.2 Soil Stabilization Soil Improvement: History, Capabilities and


Outlook,22 Soil Improvement: State-of-the-
Seismic soil failures causing building art,23 Improvement of Liquifiable Foundation
damage include: loss of soil strength due to Conditions,24 Soil Improvement: Ten Year
build-up of dynamic pore pressure, Update,2S and Grouting, Soil Improvement and
liquefaction, lateral spreading of soil, Geosynthetics. 26 The selection of the most
excessive horizontal and vertical ground appropriate and economical technique for a
movements due to settlement of natural soil particular project depends on many factors,
deposits or man-made fills, slope instability, including site and ground conditions, subsoil
or fault movements. Chapter 10 of the grain size distribution, effects on sUlTounding
Guidelines for Seismic Evaluation16 and the environment, adjacent buildings, and cost.
Canadian Foundation Engineering Manual 21 Different techniques are often combined on the
provide guidelines for evaluation of these same project to obtain the optimum
issues. The maintenance of slope stability in remediation scheme. The effectiveness of the
diverse geological and topographic settings is scheme can often be checked by in situ soil
mainly a geotechnical problem and is beyond testing or full-scale load testing. These
the scope of this document. In general, a techniques are continually evolving as new
competent geotechnical engineer should be technology becomes available and new
engaged to assist the owner or structural applications are found.
engineer to assess the geotechnical issues
involved. Applicable grain-size ranges for soil
stabilization techniques are shown in Figure 6-
The following describes soil 2. Superimposed in Figure 6-2 is a grain-size
stabilization techniques and provides general range for subsoils susceptible to liquefaction.
guidance which may be used to prevent loss The application of these techniques for
of soil support in an earthquake. existing structures and foundations, however,
is often limited by the following constraints:
Soil stabilization techniques have • limited access or headroom for
been developed for many applications in construction equipment
geotechnical engineering, including ground • limits for vibration or physical impacts on
improvement, foundation rehabilitation, existing structures
groundwater control, excavation support and • disruption to the functional use of the
pollution control. Comprehensive state-of- building and the adjacent area
the-art reports and practical applications of • field control and checking required to
soil stabilization techniques are contained in ensure the quality of soil improvement.

Grain-size range of soils


Gravel susceptible to liquefaction

1 00 -+_.l.-{I...;I:--_-is:::.:a;;,;,n.:;;d=---........,""'7=---~-I!......---....:S=.;i.:.:.lt---.lI-_r_...;c::.:.:la::..yL-_l1
\~-+-I__-!.--'---+-I\~
- t----\-T-"':7'±--:::::--~.,...-+-....;\1,-,
\ Vi ro - Comoaction \ \
-t----\T-1--:-;~--;::'__:_--+-~\~--+-c
\ Vibro - Reolacement \ 1<
-j-;::~q::;===~=~::::t:
2 \ Comoaction Pi es \ I{
- \
Jet Grout \
50 -t-----t\----;::::--:--:t::---:---\--, ,
\ Chemical i,Grout\\ <II
-
<Gravel Drains I Drainaae \i\ells \
- \
\ Comoactibn Grout \
-
\ \
~ I \ Soil r ixinq \

o -1- ...l....-_\~----l ---ll__


\.ll...1_ _ ---J
10 1.0 0.1 0.01 0.001 0.0001
Particle Size, mm

Figure 6-2. Applicable Grain-Size Ranges for Soil Stabilization Techniques


GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Table 6-1. Soil Stabilization Techniques for Existing Buildings

Soil Improvement Function


Technique Densification Rei nforcement Consideration Drainage
Chemical grouting Y
Compaction grouting Y Y
Minipiles Y
Vertical Drainage Wells Y
Jet Grouting y
Soil Mixing Y
Vibro-Compaction Y
Vibro-Replacement Y
Compaction Piles Y

Soil stabilization techniques used for Some techniques are more adaptable
seismic upgrading of existing foundation soils for use inside an existing building, such as
are listed in Table 6-1, together with their chemical and compaction grouting, drainage
basic soil improvement functions. These wells and minipiling. Other techniques such
functions include: as minipiling or jet grouting may involve
• densification of loose soils or drilling inclined holes from outside the
strengthening of weak soils beneath building. Finally, there are techniques
existing structures and/or in adjacent areas involving equipment that is mainly suitable for
on sloping ground, use in open space, such as soil mixing, vibro-
• underpinning and strengthening the subsoil compaction and vibro-replacement, and
support of existing foundations, compaction piles. In adopting any of these
• improvement of subsoil for the installation techniques, careful selection of competent and
of new foundations, and experienced specialist contractors as well as a
• drainage of subsoils to mitigate seismic well-planned quality control program during
pore pressure build-up. construction are essential.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

(a) Chemical grout (b) Compaction grout


(Permeation) (Displacement)

(c) Minipiles (d) Jet grouting

Steel rod, or casing


or reinforced cage

Tremied concrete

(e) Soil mixing (I) Vibro-compaction


or vibro replacement

Soil-cement
mixed in situ

Figure 6-3. Soil Stabilization, Minipiles

Chemical grouting (Figure 6-3a) Minipiles, also known as pinpiles or


involves injecting solutions of two or more micropiles, are drilled and grouted piles with
chemicals into the soil pores to form solid diameters less than about 300 mm (see
precipitates or sandstone-like masses. The Figure 6-3c). They can be installed with
method relies on grout permeation and is relatively small equipment in confined spaces
effective in clean cohesionless soils. not accessible to conventional piling
Compaction grouting (Figure 6-3b), on the equipment. They are used to transmit loads to
other hand, injects low slump grout under high competent materials and can be used to
pressure to densify soils by displacement. provide compression, tension or shear
The method can be used to reinforce the weak capacities. They can also be used to stabilize
subsoil undemeath existing footings in most a slope.
subsoils. Foundation heaving, however,
should be carefully controlled.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

For relief or prevention of potential Vibro-compaction or vibro-flotation


dynamic pore water pressures developed in the involves the insertion of a powerful vibrating
subsoils, vertical gravel drains or drainage probe into the ground to densify granular soils
wells can be installed around and/or inside with less than about 20% silt and clay fines
structures. If properly installed, the gravel (see Figure 6-3f). Vibro-replacement uses a
drains will prevent liquefaction by mitigating similar powerful depth vibrator to densify the
pore pressure build-up caused by earihquake soils, as well as to install compacted gravel or
shaking. Drainage wells can also be installed stone columns. This technique can be used in
with permanent dewatering to lower the finer soils where the stone columns act to
groundwater table below the subsoil zone reinforce the soil mass. Compaction piles are
susceptible to liquefaction. used to densify granular subsoils by the
displacement of the soils around the driven
Jet grouting (Figure 6-3d) uses high- piles. Because of the size of crane or rig
velocity water jets to cut and lift the soil to the involved, these techniques are mainly used for
surface, creating a cavity into which cement improving the condition of a sloping ground
slurry is injected. This technique can be used around the existing buildings in order to
in practically all soils to form soil-cement minimize the impact of deformations of
columns or "soilcrete," and is useful for surrounding soil on the building.
underpinning or strengthening existing
foundations. A technique similar to jet
grouting is soil mixing (Figure 6-3e) for which
a large-diameter auger or a series of augers
penetrate and mix the soil in situ with a
controlled amount of cement slurry to form
soil-cement columns. The soil mixing
technique, however, requires a relatively large
crane or rig.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

References

1. Institute for Research in Construction, 10. Hanson, R.D., ed., Passive Energy
Guidelines for Seismic Evaluation of Dissipation. Earthquake Spectra 9
Existing Buildings. National Research (1993):319-636.
Council of Canada, Ottawa, Ontario,
1993,150 p. (NRCC 36941). 11. Passive Energy Dissipation and Active
Control. In: Seminar on Seismic Isolation
2. Institute for Research in Construction, (2 vol.), Applied Technology Council ATC
Manual for Screening of Buildings for 17-1, March 1993.
Seismic Investigation. National Research
Council of Canada, Ottawa, Ontario, 12. Cherry, S. and A Filiaitrault, Seismic
1993,90 p. (NRCC 36943). Response Control of Buildings Using
Friction Dampers. Earthquake Spectra 9
3. Associate Committee on the National (1993):447-466.
Building Code, National Building Code of
Canada 1990. National Research Council 13. Skinner, R.E., WN. Robinson, and G.H.
of Canada, Ottawa, Ontario, 423 p. McVerry, An Introduction to Seismic
(NRCC 30619). Isolation. John Wiley & Sons, New York,
N.Y.,1993.
4. Federal Emergency Management Agency,
NEHRP Handbook of Techniques for 14. Base Isolation and Passive Energy
Seismic Rehabilitation of Existing Dissipation. Proc. of seminar and
Buildings. Report FEMA-ln, workshop, Applied Technology Council
Washington, D.C., 1992. ATC 17. March 1986.

5. Federal Emergency Management Agency, 15. Look, D.W, ed., The Seismic Retrofit of
"Provisions." Part 1 of NEHRP Historical Buildings. Proc. of conference
Recommended Provisions for the and workshop, Assoc. for Preservation
Development of Seismic Regulations for Technology (Western Chapter). San
New Buildings. Report FEMA-95 (2 Francisco, CA, 1991.
vol.), Washington D.C. 1991.
16. Refits Prepare Buildings for Earth
6. CSA Standard CAN/CSA SI6.1-M89, Tremors. Architecture NZ
Limit States Design of Steel Structures. (MaylJune 1993): 102-103.
Canadian Standards Association, Rexdale,
Ontario, 1989. 17. Smith, A.H., T.W Robertson, and D.J.A.
Hamp, POLYPLAST - A Plaster
7. CSA Standard CAN/CSA-086.1-M89, Strengthening System for Masonry Walls.
Engineering Design in Wood (Limit States In: Transactions of the Inst. of Prof.
Design). Canadian Standards Association, Engineers, New Zealand 20 (Nov.
Rexdale, Ontario, 1989. 1993): 1-9.

8. CSA Standard CAN3-A23.3-M84, Design 18. Seismic Retrofit Cuts Installation Costs.
of Concrete Structures for Buildings. Better Roads 63 (May 1993):20-22.
Canadian Standards Association, Rexdale,
Ontario, 1984. 19. ASCE, Fibre Wraps Migrate East. Civil
Engineering, 64 (July 1994):7, p. 11.
9. CSA Standard CAN3-S30A-M84,
Masonry Design for Buildings. Canadian 20. Earthquake Design in the Fraser Delta.
Standards Association, Rexdale, Ontario, Task Force Report. Department of Civil
1984. Engineering, Univ. of British Columbia,
Vancouver, B.C., 1991.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

21. Canadian Geotechnical Society, Canadian Supplementary Reading


Foundation Engineering Manual, 3rd ed.,
BiTech Publishers, 528 p., 1992. Canadian Sheet Steel Building Institute,
Diaphragm Action of Cellular Steel Floor and
22. ASCE, Soil Improvement: History, Roof Deck Construction. Information Bulletin
Capabilities and Outlook. Geotechnical No.3, Willowdale, Ontario, 1972.
Engineering Division, ASCE, 1978.
Associate Committee on the National Building
23. Mitchell, lK., Soil Improvement: State- Code, Supplement to the National Building
of-the-Art. In: Proc. 10th International Code of Canada 1990. National
Conference on Soil Mechanics and Research Council of Canada, Ottawa, Ontario,
Foundation Engineering, Vol. 4, 1990, 259 p. (NRCC 30629).
Stockholm, Sweden, 1981.

24. Ledbetter, R.H., Improvements of


Liquefiable Foundation Conditions
Beneath Existing Structures. Department
of the Army, U.S. Army Corps of
Engineers, Technical Report REMR-GT-2,
1985.

25. Welsh, J.P., ed., Soil Improvement - A Ten


Year Update. ASCE, Geotechnical
Special Publication No. 12, 1987.

26. Borden, R.B., R.D. Holtz, and 1. Juran,


eds., Grouting, Soil Improvemem and
Geosynthetics. Proc. of conf. held by
ASCE Geotechnical Division, Louisiana,
Feb. 25-28, 1992.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Appendix A
Checklist of Seismic Upgrading
Techniques

This Appendix provides a checklist of overlay, anchorage details, etc.) for each
techniques cunently used to upgrade buildings category are described in more detail in
containing seismic deficiencies. The checklist Chapters 4 to 6, along with their relative
is organized in tables, where each table lists merits based on the principles described in
techniques for deficiencies related to a Chapter 3. For easy access, Tables Al to A6
subsystem of the existing building structure, list the appropriate pages and figures for each
i.e. moment frames, braced frames, shear walls, technique category in Chapters 4 to 6. More
diaphragms, lateral support of walls and detailed checklists of conventional techniques
foundations. for each category are contained in Chapters 4
and 6. To relate the deficiencies listed in
The techniques are listed in terms of Tables Al to A6 to those found by application
categories (infills, overlays, connections, new of the Guidelines for Seismic Evaluation, I see
walls or bracing, collectors, etc.). Specific Chapter 2.
techniques (nailing, concrete overlay, plywood

Table A1. Moment Frames (Steel, Concrete)


Upgrading Technique
Deficiency Strengthen Strengthen New Walls, Supplementary
Connections Members* Infills or Damping or
or Anchors* Bracing Base Isolation
p.15-16 p.15-16 p.13-15 p.29-33
Figure 4-2 Figure 4-3 Figure 4-1
Drift Y Y Y
Connection Strength y y y
Member Strength/Ductility y y y
Short Concrete Columns y y
Failure of InfHI Y Y
Uplift Y Y

* For specific techniques, see p. 15.

Table A2. Braced Frames (Steel, Concrete, Wood)


Upgrading Technique
Deficiency Strengthen Strengthen New Walls, Supplementary
Connections Members* or Bracing Damping or
or Anchors* Base Isolation
p.17-18 p.17-18 p.13-15 p.29-33
Figure 4-1
Torsion Y Y
Member Strength y y y
Connection Strength y y y
Uplift Y Y

* For specific techniques, see p. 18.

... .
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Table A3. Shear Walls (Concrete, Masonry, Wood)


Upgrading Technique
Deficiency Infills* Overlays* Reinforcing, New Walls Base
Tie-Downs or Isolation
or Anchors* Bracing
p.18-22 p.18-22 p.18-22 p.13-15 p.31-33
Figure 4-5 Figure 4-6 Figure 4-7, 4-8 Figure 4-1
Torsion Y Y Y
Strength y y y y
Lateral Support
(see Table AS) Y Y
Coupling Beams Y Y Y
Interpanel Connection
(Precast) Y Y
Cripple Foundation Walls y
Uplift Y Y

* For specific techniques, see p. 18-19.

Table A4. Diaphragms (Concrete, Steel, Wood)


Upgrading Technique
Deficiency Overlays*t Horizontal Collectors, Strengthen NewWalls**
Bracing* Splices, Connections* or
Chords* Vert. Bracing
p.23-24 p.23-24 p.23-26 p.23-26 p.13-15
Figure 4-9 Figure 4-10 Figure 4-11 Figure 4-11 Figure 4-1
to 4-14 to 4-14
Shear Strength y y y
Horizontal Drift Y Y Y
Shear Transfer Y Y y y y
Integrity Y Y Y Y

* For specific techniques, see p. 23.


t Includes nailing or welding of existing decking to structure.
Includes cross-partitions acting as dampers.
GUIDELINE FOR SEISMIC UPGRADING OF BUILDING STRUCTURES

Table AS. Lateral Support of Walls (Masonry, Precast)


Upgrading Technique
Deficiency Anchors, Local Bracing* Overlays* Vertical
Connections* Reinforcing
p.27-28 p.27-28 p.18-22 p.19-22
Figure 4-15, 4-16 Figure 4-16 Figure 4-6 Figure 4-7
Insufficient Anchorage Y Y
Slenderness y y y

* For more specific techniques, see p. 19, 27 and 28.

Table A6. Foundations (Concrete, Masonry, Wood)


Upgrading Technique
Deficiency Soil Stabilization New Piles or Piers New Footings
p.38-41 p.36-37 p.36-37
Figure 6-2, 6-3 Figure 6-1 Figure 6-1
Bearing Capacity y y
Settlement y y
Liquefaction Y
Slides y

Potrebbero piacerti anche