Sei sulla pagina 1di 3

PROJECT NO.

PO. 4500098732 / 10 / 01.01.2018


PROJECT TITLE

Supply of PF Process Calculation Spreadsheet (Excel


Forma)
E T
H E
DOCUMENT TITLE

E S
P L
Pump Sizing Calculation

M
SA

DATE REV. REASON FOR REVISION PREP. CHKD. APPD. APPD.

DOC. NO. CEPL-PC-001-CA-015 PAGE 1 of 3 REV. 0


Pump Sizing Calculation
DOC. NO. CEPL-PC-001-CA-015 REV. 0
PROJECT NO. PO. 4500098732 / 10 / 01.01.2018 PAGE NO. 2 of 3
PROJECT TITLE Supply of PF Process Calculation Spreadsheet (Excel Forma)
BASIS

Calculation Objective

Calculation Basis

E T
E
Calculation Methodology

SH
L E
P
Assumptions

M
Software used
SA
Conclusions

References

Attachments
Pump Sizing Calculation
DOC. NO. CEPL-PC-001-CA-015 REV. 0
PROJECT NO. PO. 4500098732 / 10 / 01.01.2018 PAGE NO. 3 of 3
PROJECT TITLE Supply of PF Process Calculation Spreadsheet (Excel Forma)

This spreadsheet provides the pump sizing calculations (Hydraulic power, Shaft power and NPSHA)

Input Results
Hydraulic Power:
The ideal hydraulic power to drive a pump depends on;
* Mass flow rate
* Liquid density
* Differential head
Ph (kW) = q ρ g h / (3.6 *10^6)   

20 q Flow capacity (m /h)


3

E T
E
3
1000 ρ Density of fluid (kg/m )

H
2
9.81 g Gravity (9.81 m/s )

Suction head
0 PA Suction vessel pressure (m)

E S Discharge head
0 PB Discharge vessel pressure (m)
2
7 HA Static head (m) L
ΔPA Frictional pressure drop (m)

P
35 ΔPB Frictional pressure drop (m)
30 HB Static head (m)

M
5 PS Total suction head (m) 65 PD Total discharge head (m)

SA
60 h Differential head (m)
3.3 Ph(kW) Hydraulic power (kW)

Shaft Power:
The shaft power is the power transferred from the motor to the shaft of the pump.

P s(kW) = P h(kW) / η

75% η  Pump efficiency


4.4 Ph(kW) Shaft power (kW)

NPSHA :
The NPSHA (Net Positive Suction Head, Available) depends on;
* Pressure at pump suction (m)
* Ambient Pressure (m)
* Vapor Pressure (m)

NPSHA = Pressure at pump suction + Ambient Pressure - Vapor Pressure

NPSHA = 5 + 10.3 - 0.5

NPSHA = 14.8 m

Potrebbero piacerti anche