Dear Sir
Your feedback on Report No.0636 is highly appreciated as it gave valued inputs. The pertinent
observations as fallows
In the Sheet 2 of the report the test voltage value mentioned 178kV instead of 168kV(actual)
which is a typographical mistake, Please correlate with the respective waveform.
Voltage waveform with identification number 31A was little higher side (0.73%) than the
standard allowed limit which can be acceptable as it is not inferior to the standard.
Dear Sir,
Refer to the attached Impulse test report on 12.5MVA transformer please find comments by NTPC
1
highlighted, Voltage values are little more than the allowed limits of +10% Tolerance. We tried to convince NTPC
explain that during testing voltage control with in permissible values is very difficult .But they need clarifications
from CPRI on this to accept the report. Please provide clarifications.