Fully automatic
Current and Voltage
Transformer test set
iCT1
2
Key features
WI-FI
Ethernet &
USB port
Description Application
iCT1 is a fully automatic Current and Voltage Transformer test • Factory
set, especially designed for testing CTs, VTs and Combined . iCT1 performs tests according to the international
Transformers.
standards
iCT1 grants a faster testing, thanks to its 5-TAP switchbox which
. High accuracy CT’s up to class 0.1
allows to connect directly up to 5 taps, in this way the connection
. Time saving testing, that allows a faster stage production
of the device is made only one time and without the need of any
further manual operation. • Commissioning
The main tests performed by iCT1 are: Excitation, Accuracy, . Only one device for testing Current and Voltage
Ratio & Phase Error, Resistance and Burden and they are all Transformers and Combined Transformers
executed in fully automatic mode, without user intervention. . Able to test Current Transformers with a very high
All tests are performed by generating current and voltage.
saturation voltage, up to 30 kV
All the functionalities are managed by a 7’’ color LCD touch . Easy to carry
screen interface, designed for the outdoor environment.
Test results are kept in a local memory or in a USB pen drive,
and can be transferred to a PC along with settings, using ethernet
(plug or wireless) connection.
Combined Transformer
Current Voltage
Transformer Transformer
iCT1
4
Burden
Excitation curve
No load current
Excitation curve DC method
. ALF / ISF
Purpose of the test is to calculate the ALF/ISF value using the
Winding Resistance test results and the Burden Secondary Side
test results. ALF = Accuracy Limit Factor and ISF = Instrument
Security Factor. Input parameters: Burden and Winding test results.
Results: ALF value.
CT / VT Test Set
5
. Burden
HVB4000 High voltage booster for VTs
The burden measurement is performed applying low AC voltage
to the VT burden, and measuring the corresponding current. This option allows increasing the test voltage up to 4 kV, in order
to perform more accurate tests on high voltage CVT.
. Leakage Current Output current and voltage are measured and sent back to iCT1
The test is performed connecting the high AC voltage source while the power is taken on the output voltage plugs.
between the VT secondary cabling and the ground or between The HBV4000 option characteristics are the following:
the VT primary and secondary windings.
• Input: from ICT 1, via the booster connector
• Output voltage: up to 4 kV
Test Plan Editor • Input power: 500 VA
• Weight: <15 kg
The Test Plan Editor is an innovative and advanced software
module, allowing the operator to define a sequence of tests.
The operator defines the desired sequence of tests and sets the
parameters of each test: the Editor creates a sequence of tests to Other Characteristics
be performed automatically. The feature is available for the tests
of both Current and Voltage transformers. Memory
• Up to 64 test plans
DC Method Test • More than 1,000 test results
Technical Specification
Output Characteristics
Main generator Low AC voltage
The main generator has 5 outputs: • Maximum output voltage: 180V AC
• High AC voltage • Maximum output current: 3.5A AC
• Low AC current • Maximum output power:
• Low DC current - Supply 230V : 400 VA (Power values with cosj< 0.225)
• Low AC voltage - Supply 110V : 350VA (Power values with cosj< 0.175)
• Low voltage for excitation curve DC method
Low voltage for excitation curve DC method
High AC voltage • Maximum output voltage: 200V DC
The high AC voltage output up to 2kV is coming from a transformer • Maximum output current: 2Arms, 15A peak
that provides to insulate the outputs from the power supply.
• MAX Voltage 2000 V Output frequency
• MAX Current 1 A • Frequency: 15Hz – 400Hz
• Frequency resolution: 10mHz
Low AC current • Frequency accuracy: < 100 ppM; output voltage > 200 V
The output current can be manually adjusted using the front panel
controls Other features of main outputs
• Imax 6A AC • Zero crossing control: the generation starts and stops on the
• Vmax 100V AC zero crossing
• Max Power 200VA • Over-current: alarm message
• Thermal protection for: Power supply, Power amplifier,
Low DC current Power transformer. The operator is alerted by a message.
Output current can be manually adjusted using the front panel
controls.
• Imax 6A DC
• Vmax 30V DC
• Max Power 180W
15 A 1 mA
DC current 1,5 A 0,1 mA < 0,025 % < 0,025 % ± 0,05 % ± 0,05 %
0,15 A 0,01 mA
300 V 15 mV
AC voltage 30 V 1,5 mV
primary side < 0,02 % < 0,02 % ± 0,05 % ± 0,05 %
3V 0,15 mV
300 mV 0,015 mV
2100 V 100 mV
AC voltage 200 V 10 mV < 0,02 % < 0,02 % ± 0,05 % ± 0,05 %
secondary side 20 V 1 mV
2V 100 μV
Accuracy for VT ratio measurement 12183 iCT1 Standard test set with cable kit
10183 iCT1 Advance test set with cable Kit
Ratio range Typical accuracy Maximum accuracy 10185C iCt1 Software licence
17183 HVB4000 4kV High voltage booster for VT
1 ÷ 400 ± 0,03 % ± 0,2 % test
15183 Transit case
400 ÷ 1000 ± 0,05 % ± 0,3 %
18183 Long cables test kit 18m for EHV CT
1000 ÷ 2500 ± 0,05 % ± 0,5 %