Sei sulla pagina 1di 92

King Fahd University of Petroleum & Minerals Dr.

Rashid Allayla

Civil Engineering Dept.


CE 331 Engineering Statics
Dr. Rashid Allayla
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Hydrology:
According to the US Federal Council for Science and Technology (ad hoc Panel on
Hydrology , 1962) hydrology is a “science that treats all the waters of the earth, their
occurrence, circulation and distribution, their chemical and physical properties, and their
reaction with their environment including their relations to living things” Application of
hydrology include:

 Determining water balance of a region (see subsequent discussion)


 Predicting floods and droughts
 Designing irrigation projects
 Preventing catastrophic events due to excess flooding
 Provide means to supply drinking water to communities
 Helps design dams, reservoirs, sewers, bridges and other structural and hydrologic
projects

Hydrologic Cycle:
Hydrologic cycle is the water circulatory system on earth. The cycle has no
beginning or end as the evaporated water rises to atmosphere due to solar energy. The
evaporated water can be carried hundreds of miles before it is condensed and returned to
earth in a form of precipitation. Part of the precipitated water is intercepted by plants and
eventually returned to the atmosphere by evapotranspiration from plants and upper layers
of soil, runs overland eventually reaching open water bodies such as streams, oceans or
natural lakes or infiltrates through the ground forming deep or shallow groundwater
aquifers. A good portion of the precipitated water evaporates back to the atmosphere
thereby completing the hydrologic cycle. Elements of hydrologic cycle are:

 Evaporation, E
 Transpiration, T
 Precipitation, P
 Surface runoff, R
 Groundwater flow, G, and,
 Infiltration, I

A full discussion of each of the elements will be discussed in detail in subsequent chapters.
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Hydrologic Cycle in Visual Form:

(From Purdue University)

Fate of Precipitation

Goes into groundwater Falls into ground forming


Storage or retained as surface runoff, lakes, rivers
soil moisture or reservoirs

3
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

System Concept in Hydrologic Cycle:

n Transpiration
P
r
e
c Atmosphere
i
p
i
t
a Evaporation
t Transpiration
i
o Surface RO
I
n Vegetation
n
f
i Surface Streams/Lakes/Rivers
i Rivers
t
r Exfiltration
a Precipitation
t Evaporation
i Soil Surface
o runoff
n Interflow
Capillary Rise Groundwate
Percolation
Aquifers r Oceans
Illustration courtesy of: Colorado Division of Water Resources, Office of theflow
State Engineer
Aquifers Oceans

Hydrologic Budget

The hydrologist must be able to estimate components of hydrologic cycle in order


to design projects and, more importantly protect the public from excessive floods and
draughts. This can be accomplished by careful accounting technique that is not unlike
keeping track of money in the bank.

Salary Bank Activity Statement


Cash in & of account
Cash out

Precipitation Watershed outflow Inflow Change in Storage

In engineering hydrology, the hydrologic budget is a quantitative accounting technique


linking the components of hydrologic cycle. It is a form of a continuity equation that
balances the gains and losses of water with the amount stored in a region. The components
of water budget are inflow, outflow and storage.

 INFLOWS -  OUTFLOWS =  STORAGES, Or, in mathematical term,

4
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

I – O = ∂S / ∂t

Breaking system into individual component as shown in schematic figure:

P – E + ([(Rin + Gin)] – (Rout + Gout)] – T = dS/dt


Where:
P: Areal mean rate of precipitation (L/T)
E: Evaporation (L/T)
Rin, Gin: Inflow from surface and groundwater (L/T)
Rout, Gout: Outflow from surface and groundwater (L/T)
S: Storage (L) and,
T: Transpiration (evaporation from plants, L/T)

E P
Gup T
Ground Surface
Rout
Rin

Gin Gout

I
Water Table

All the above is measured in volume per unit area of watershed.

Breaking the above into surface and subsurface balance equations:

Surface: P + Rin – Rout + Gup – I - E - T = ∆ Ss

Subsurface: I + Gin - Gout – Gup = ∆ Sg

The water budget formula is often used to estimate the amount of evaporation and
evapotranspiration. Combining & dropping subscripts to represent net flows we get
hydrologic budget formula,

P - R - G - E - T =  S / ∆t

Balance Equation for Open Bodies with Short Duration:

And, for an open water bodies, short duration,

5
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

I - O =  S/ t
Where,

I = inflow volume per unit time


O = Outflow per unit time

Balance Equation for Urban Drainage:

For urban drainage system, ET (evapotranspiration) is often neglected,

P-I-R-D=0

P = precipitation
I = infiltration
R = direct runoff
D = Combination of interception and depression storage

Illustrative Example:

In a given year, a 10,000 Km2 watershed received 30 cm of precipitation. The annual


rate of flow measured in the river draining the area is 60 m3/sec. Estimate the
Evapotranspiration. Assume negligible change of storage and net groundwater flow.
Solution:

Combining E and T, then ET = P – R

In the above, the precipitation term P is given in cm and the runoff term R is given in discharge
unit. Since units in the equation must be consistent, and since the area of the watershed is
constant, the volume of flow into the watershed is converted to equivalent depth.

Volume due to runoff = 60 m3/s x 86400 sec/day x 365 day/yr = 1.89216 x 109 m3

= 1.89216 x 109 m3 x (100 cm/m)3 = 1.89216 x 1015 cm3

Equivalent depth = volume of water / area of watershed


= 1.89216 x 1015 / [(10,000) (100,000 cm/km)2 ] = 18.92 cm

Amount of Evapotranspiration ET = P – R = 30 – 18.92 = 11.08 cm / yr

6
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example: (From Viessman 2003)

The drainage area of a river in a city is 11,839 km 2. If the mean annual runoff is
determined to be 144.4 m3/s and the average annual rainfall is 1.08 m, estimate the ET losses
for the area. Assume negligible changes in groundwater flow and storage (i.e. G and ΔS = 0) .

Solution:

Then: ET = P – R, converting runoff from m3/yr to m/yr, then,

R = [144.4 m3/s x 86400 s/day x 365 day/yr] / [11,839 km2 x 106 m2/km2] = 0.38 m
Precipitati

ET = P – R = 1.08 – 0.38 = 0.7 m

7
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example:

At a particular area, the storage in a river reach is 40 acre – ft. The inflow at that time was
measured to be 200 cfs and the outflow is 300 . The inflow after 4 hours was measured to be
260 and the outflow was 270. Determine a) the change in storage during the elapsed time
and b) The final storage volume.

a) Average inflow rate = ( 200 + 260 ) / 2 = 230 cfs


Average outflow rate = ( 300 + 270 ) / 2 = 285 cfs and Since : I - O =  S/ t

 S/ t = 230 – 285 = - 55 cfs

 S = (- 55) (4 hr) = - 220 cfs-hr = (- 220 cfs-hr) (60 x 60 Sec / 1-hr ) ( 1 acre – ft / 43,560 ft3 ) =
= - 18.182 acre-ft

b) S2 = 40 – 18.182 = 21.82 AF

Illustrative Example:

At a particular area, the storage in a river reach is 40 acre – ft. The inflow at that time was
measured to be 200 cfs and the outflow is 300 . The inflow after 4 hours was measured to be
260 and the outflow was 270. Determine a) the change in storage during the elapsed time
and b) The final storage volume.

a) Average inflow rate = ( 200 + 260 ) / 2 = 230 cfs


Average outflow rate = ( 300 + 270 ) / 2 = 285 cfs and Since : I - O =  S/ t

 S/ t = 230 – 285 = - 55

 S = (- 55) (4 hr) = - 220 cfs-hr = (- 220 cfs-hr) (60 x 60 Sec / 1-hr ) ( 1 acre – ft / 43,560 ft3 ) =
= - 18.182 acre-ft

b) S2 = 40 – 18.182 = 21.82 AF

8
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Precipitation:

Precipitation is the discharge of water out of the atmosphere. The principal form of
precipitation is rain and snow and to a lesser extent is hail, sleet. The physical factor
producing precipitation is the condensation of water droplets due to atmosphere cooling.
The chief source of moisture producing precipitation is evaporation from oceans,
seas. Only one tenth of the precipitation comes from continental sources in the form of soil
evaporation and transpiration. Some of the precipitated water returns back to oceans and
seas but the major portion is retained as replenishment to surface water bodies,
groundwater recharge and soil and plant moisture, The steps required to form precipitation
include:

a) Cooling which condensate moist air to near saturation,

b) Phase change of water vapor to liquid or solid and,

c) Growth of water droplet to perceptible size. This mechanism requires cloud


elements to be large enough so that their falling speed can exceeds the upward
movement of the air. If the last step does not occur, cloud will eventually
dissipate.

Droplets become heavy enough to fall (0.1 mm)

Cloud

Droplet breaks
down to smaller
size & returns to atmosphere

Further Condensation

Droplet forms by condensation Rain drop


On particles of aerosols (0.001-10μm) (0.1-3mm)

9
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Distribution of Precipitation:

Total Precipitation

Evap. Evap.

Land Surface Vegetation Stream/Lake/river/


Sea
Direct Surface RO Direct Surface RO
Infiltration

Soil Interception & i


Depression Storage ii
t t

Percolation When filled Total Rain

If pervious Infilt- ii
Ration
Aquifers t
Direct RO Intercep-
tion
& Depr-
ssion ii
Storage
t
Impervious
Overland
Flow
(Direct ii
RO)
t
Stream/lake/river/sea

10
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Measurement of Precipitation:

1. National Weather Service Gage: 20.3 cm


Receiver
( Collector )
Side view
One-tenth
the area of
the collector

Measuring
tube (0.1
inch of rain
will fill tube
to 1 inch
depth)

Errors:
 Splashing Measuring
 Moisture deficiency of gage stick
 Wind blowing

2. Tipping Bucket Gage:

Counter
(Will tip over
when filled
by 0.01 inch
of rain) to
record
intensity of
- Interception: The amount of precipitation that is intercepted by vegetation.
To measuring tube rain

11
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

- Depression Storage: This is the part of precipitation that is intercepted by holes


in the ground and uneven surfaces. This part of storage will eventually be
evaporated or slowly seeps underground.
- Infiltration: This portion of precipitation makes its way to replenish groundwater
through seepage.
- Overland Flow: This portion of precipitation is the access water after the local
rate of infiltration reaches its maximum. It develops as a film of water that moves
overland eventually reaching streams, reservoirs or lakes.

Methods of Estimating Areal Precipitation in the Ground:


a) Arithmetic Mean: Equal weights are assigned to all gage stations.

Watershed Precipitation Equivalent depth of total


gage rain at watershed.

b) Thiessen Polygon: Each gage is assigned an area bounded by a perpendicular bisect


between the station and those surrounding it. The polygon represent their respective areas
of influence (see figure). The average precipitation is calculated as:

Average PPT = ∑ Ai pi / AT

Illustrative Method:

Observed Area of Polygon Precipitation x Area


Precipitation (L2) (L3)
(L)

P1 A1 P1 A1

P2 A2 P2 A2

P3 A3 P3 A3

Pn An Pn An

Average P = ( P1 A1 + P2 A2 + P3 A3 + …. + Pn An ) / (A1 + A2 + A3 + …. + An )

12
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Theissen method provides weighting


factors for each gage by enabling data
from adjacent areas to be incorporated
Watershed in calculating the mean value of
precipitation

Perpendicular bisector
Area a representing gage P1

Computation Procedure:

The average precipitation is computed


by multiply the precipitation of each
station by its assigned area, adding
Polygon them and dividing the total area of the
watershed.
Average PPT = ∑ aipi / AT

c) Isohyetal Method: The area between two successive isohyets is measured using
planimeter or simply by counting sub grids. The average precipitation is computed by
multiplying the average precipitation between two successive isohyets by the inter-
Isohyetal area, adding them and dividing by the total area of the watershed.

Average PPT = ∑ ai pi / AT

Lines of equal rainfall (Isohyets)


Watershed
Rain Gage

o a1”
o
o o
a2”
o o
o a3”
o
o
o a4”
o

a5”

The method of calculation is similar to that of Thiessen method except the area is the one
bounded by two isohyets.

13
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example:

80 mm

100 mm
90 mm
110 mm

100 mm

80 mm

Average PPT Area Product

87* 120 10440

95 156 14820
Ave PPT = 65610/ 666
105 190 19950
= 98.51 inch
105 140 14700

95* 60 5700
Σ 666 Σ 65610

Adjusted values

14
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Alternative Method:

Inverse Distance Method: The method is based on the assumption that the precipitation at a
given point is influenced by all stations. The method of solution is to subdivide the
watershed area into m rectangular areas. The mean precipitation is calculated using the
following formula:
m n n
P = 1/A ∑ Aj ( ∑ dij –b )-1 ∑ d ij –b P i
j=1 i=1 i=1
Where: m is the number of the subareas, Aj is the area of the jth sub area, A is the total area,
dij is the distance from the center of the jth area to the ith precipitation gage, n is the number
of gages and b is a constant and in most applications, it is taken as equal to 2. Note that if b
is 0, the equation is reduced to the following: P = 1/A ∑ Aj Pi

Which is simply the arithmetic mean.

1 2 3 4 5 6 7
O d2,18 O d5,18
8 9 10 11 12 13 14

15 16 17 18 19 20 21

22 23 24 25 26 27 28
O d22,18 O d26,18

O: Precipitation Gage

For example, the precipitation over sub area 18 is determined as:


4 4
P18 = [ ∑ d-2 i,18 Pi / ( ∑ d-2 i,18 )
i =1 i =1

Illustrative Example:

The sub areas shown below are 4.5 km2 each, find the precipitation x in subarea shown below:
Y = 1.5 km
X = 3 km X = 3 km X = 3 km
1 d= 3 km 2 d = 4.5 km 3
X
Unknown PPT
P = 0.2 “ P = 0.15”

P2 = ∑ d -2 i , 2 Pi / (∑d -2 i , 2)
P2 = [d-21,2] P1 / [d -2 1 , 2 + d -2 3,2] + [d-23,2] P3 / [d -2 1 , 2 + d -2 3,2]

P2 = [ (3) -2 ] (0.2) / (0.111+ 0.0494) + (4.5) -2 (0.15) / (0.111+ 0.0494 = 0.13854 + 0.04619 = 0.1847

15
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Methods of Estimating Missing Precipitation:


a) Normal Ratio Method:

The missing precipitation at station x is calculated by using weights for precipitation at


individual stations. The precipitation at station x is,
n
Px = ∑ w i Pi
i=1
where n is the number of stations and wi designates the weight for station i and computed
as
w i = Ax / n Ai

Where Ai is the average annual rainfall at gage i, Ax is the average annual rainfall at station x
in question.

Combining the above two equations,


n
Px = (AX / n) ∑ Pi / Ai
i =1

Illustrative Example:

The following data was taken from 5 gage stations:

Gage Average Annual Rainfall (cm) Total Annual Rainfall (cm)


A 32 2.2
B 28 2.0
C 25 2.0
D 35 2.4
X 26 ?

Solution:

Px = wA PA + wB PB + WC PC + WD PD

= (Ax / n AA) PA + (Ax / n AB) PB + (Ax / n AC) PC + (Ax / n AD) PD

= (26 / 4 x 32) (2.2) + (26 / 4 x 28) (2.0) + (26 / 4 x 25) (2.0) + (26 / 4 x 35) (2.4) = 1.877 cm

Then: Px = 1.877 cm
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

b) Quadrant Method:

To account for the closeness of gage stations to the missing data gage, quadrant method is
employed. The position of the station of the missing data is made to be the origin of the four
quadrants containing the rest of stations. The weight for station i is computed as:
4
wi = ∑ ( 1 / d2i )
i=1

and the missing data is calculated as,


n n
Px = ∑wi . Pi / ∑ wi
i=1 i=1

Illustrative Example:
Point PPT PPT ∆Y ∆X (D2)* W=1/D2 PxW ∆x
xC

A ?? 0 0 - ++ ++ xD ∆y xB

B 1.6 2 4 20- 0.05 0.08 A


xF
C 1.8 6 1 37 0.027 0.49
xE
D 1.5 2 3 13 0.0769 0.1154

E 2.0 3 3 18 0.056 0.1112

F 1.7 2 2 8 0.125 0.2125

PA = 0.5677 / 0.3345
* D2 = ΔX2 +ΔY2 ∑ 0.3345 0.5677
= 1.7

Gauge Consistency:
Double Mass Curve

This is a method used to check inconsistency in gage reading. The inconsistency could be
attributed to environmental changes such as sudden weather changes that adversely effect
gage reading, vandalism, instrument malfunction, etc. Double Mass Curve is a plot of
accumulated annual or seasonal precipitation at the effected station versus the mean
values of annual or seasonal accumulated precipitation for a number of stations
surrounding the station that have been subjected to similar hydrological environment and
known to be consistent. The double mass curve produced is then examined for trends and
inconsistencies which is reflected by the change of slope. A typical Double Mass Curve of
infected station (station A) versus mean values of similar stations is shown below:

17
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Station A (mm)
PA

Part 1 Part 2
PA2
2000

1995
PA1
1990
1985
1980

1975 PB1 PB2 PB


12 Station Mean PB (mm)

Method of Correction: (READ ONLY)


As shown in the figure, the slope of the Double Mass Curve changed abruptly from m 1 prior
to 1990 to m2 after 1990. The record can then be adjusted using the following ratio:
Pa = (ma/mo) po where: ma (adjusted) & mo (observed)
In the above, subscript a denotes adjusted and o denotes observed. If the initial part of the
record need to be adjusted then m2 is the correct slope and PA2 and PB2 are correct. So, if m2
is the correct slope, the slope m1 should be removed from PA1 and replaced by m2 by using
the formula: p A1 = (m2 / m1) P A1 where pA1 is the adjusted data.

Adjustment of segment 1 Adjustment of segment 2

m2
m2

m1
P1 m1
P2

p1 = (m2 / m1) P1 p1 = (m1 / m2) P2

18
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example (McCuen 1998)

Gage H was permanently relocated after a period of 3 years. Adjust the double mass curve and find the values
of h79, h80 and h81.

year E F G H Total Cumulative Cumulative h


∑E+F+G E+F+G H
1979 22 26 23 28 71 71 28 24.7
80 21 26 25 33 72 143 61 29.1
81 27 31 28 38 86 229 99 33.5
82 25 29 29 31 83 312 130
83 19 22 23 24 64 376 154
84 24 25 26 28 75 451 182
85 17 19 20 22 56 507 204
86 21 22 23 26 66 573 230

19
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Evaporation:

Evaporation is the process by which water is transferred from liquid state to gaseous state
through transfer of energy. When a sufficient kinetic energy exists on the surface, water
molecules can escape to the atmosphere by turbulent air.

Factors Affecting Evaporation:


Temperature: It is a measure of combined potential and kinetic energy of the body’s atom.

Humidity and Vapor Pressure: The amount of water vapor in the atmosphere is very small
compared to the other elements that exist (like Oxygen, Nitrogen, CO2, etc.). However, Water
vapor in the air plays an important part in controlling weather patterns and evaporation
processes. When the air is dry, evaporation takes place, causing an increase in the quantity
of vapor in the air and an increase in vapor pressure. This process will continue until vapor
pressure in the air is equal to vapor pressure at the surface. At this point, saturation will
occur and further evaporation ceases.

Dry air O O O O O O O O O O

Initial condition: As evaporation continues, pressure of air When vapor


Dry air causing increases due to pressure of vapor (note: If pressure = surface
evaporation pressure of dry air is P1 and pressure of vapor pressure,
indicator is P2, the vapor pressure is P2 – P1 saturation occurs.

Denoting e as the vapor pressure and es as the saturated vapor pressure, the relative
humidity is defined as,

R = e / es

Vapor pressure is commonly expressed in bars, where,

1 bar = 105 Newtons / square meters (106 dynes / cm2)


1 mb = 1000 dynes / cm2 = 0.03 Hg

Radiation: (From AMS Glossary): It is the process by which electromagnetic radiation is


propagated through free space. The propagation takes place at the speed of light (3.00 x 108

20
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

m s−1 in vacuum) by way of joint (orthogonal) oscillations in the electric and magnetic fields.
This process is to be distinguished from other forms of energy transfer such as 1.
conduction and convection. 2. Propagation of energy by any physical quantity governed by
a wave equation.

Wind Speed: Wind speed varies with the height above water surface. It can be calculated
using the empirical formula,

V/VO = (Z/ZO)0.15

Where V is the wind speed in mi/hr at Z height, VO is the wind speed at height ZO measured
in ft of the anemometer (instruments designed to measure total wind speed)

Measurement of Evaporation:
a) Evaporation Pans: The most popular method of estimating evaporation. The best known
is the US Weather Bureau Class A Pan. (complete description of Class A Pan can be found
in AMS Glossary link): The U.S. Weather Bureau evaporation pan (Class-A pan) is a cylindrical container
fabricated of galvanized iron or other rust-resistant metal with a depth of 25.4 cm (10 in.) and a diameter of
121.9 cm (48 in.). The pan is accurately leveled at a site that is nearly flat, well sodded, and free from
obstructions. The water level is maintained at between 5 and 7.5 cm (2 and 3 in.) below the top of the rim, and
periodic measurements are made of the changes of the water level with the aid of a hook gauge set in the still
well. When the water level drops to 17.8 cm (7 in.), the pan is refilled. Its average pan coefficient is about 0.7.

21
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

From: The Earth & Geographic Sciences Department / University of Mass, Boston

b) Empirical Formulas:

Using mass transfer, evaporation takes the following general form:

E = C f(u)(e –ea)

Where K is constant, f(u) is a function of wind speed at a given height, e is the actual vapor
pressure at a given height, and es is the saturated vapor pressure at water surface,

The rate of evaporation from a lake can be calculated using empirical laws,

E = C (es – e) (1 + W/10) ……………………… Meyer (1944)

Where, E: Lake evaporation (inches / day)


es – e: Water vapor deficit (difference between saturated vapor pressur and actual
vapor pressure of atmosphere in-Hg)
C: Constant (0.36 for open water, 0.5 for wet soil)
W: Wind Speed 25 ft above water level (mph)

E = (0.013 + 0.00016 u2) e [(100 – Rh) / 100] ………………. Dunne ((1978)

Where, Rh: The relative humidity in %


e: Vapor pressure of air (mill bars)
u2: Wind speed 2 m above water in km/day

22
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example:

Use Meyer formula and Dunn formula to find the lake evaporation for a lake with mean value of air temperature
is 87 F, and for water temperature is 63 F, average wind speed is 10 mph and relative humidity is 20%.

Solution:

-Using Meyer formula: From table, the saturated vapor pressure, e s (@63oF= air temp) = 0.58 in. Hg
es (@87oF = water temp) = 1.29 in. Hg
E = C (es – e) (1 + W/10)
e = 1.29 x 0.20 = 0.26 in Hg / (0.03 Hg/mb) = 8.7 mb

For open water, C = 0.36 then E = 0.36 (0.58 – 0.26) [1+10/10 = 0.23 in/day

-Using Dunne’s formula:

E = (0.013 + 0.00016 u2) e [(100 – Rh) / 100]


Some Empirical Equations:
Converting wind speed to km/day = (10 mph) (24hr/d) (1.6 km/mi) = 384 km/d

E = [0.013 + (0.00016 x 384)] (8.7) [(100-20)/100]

= 0.518 cm/day or = 0.204 in/day which is comparable to the previous value.

23
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Author Equation Explanation


C=15 for small, shallow water and 11
Dalton E (i/mo) = C(eO-ea) for large deep water

ea measured 30 above ground surface


Meyer E (i/mo) = 11 (1+0.1 ug) (eO-ea)

u = speed of wind
Horton E (i/mo) = 0.4 [2 – exp(-2u)]) (eO-ea)

u2 = wind speed 2 meters above


Penman E (i/day) = 0.35 (1+0.24 u2) (eO-ea) surface

Ta = Average Temp OC + 1.9OC


Harbeck E(i/day)=0.001813 u (eO-ea)[1-0.03(Ta-Tw)] TW = Average water surface
temperature

Coaxial Chart: Penman (1948)


Penman developed an equation based on aerodynamic and energy balance equations for
daily evaporation E and later Kohler (1955) developed an expression for lake evaporation in
inches per day that is based on Penman’s theory, If E L designates average daily lake
evaporation (in/day), then,

EL = 0.7 [EP + 0.00051 P αP (0.37 + 0.0041 uP) (T0 –Ta)0.88


To Outer face Temp of pan O F
Lake Evap. in/day Ta Air Temp. in o F
Windspeed in mi/day
Advected Energy (For given Temp & wind speed ,use chart to obtain αP)
Atmospheric pressure in in-Hg

αP = 0.13 + 0.0065T0 – (6.0 x 10-8 T03) + 0.016 uP0.36 (Use Chart below to obtain αP)

Steps of Using the Coaxial Chart:


- From pan water temperature (measured in oF) and pan wind speed (measured mi/day), use chart
A to obtain αP .
- From wind speed uP start at the upper left hand of the coaxial chart (chart B) to the elevation (in
feet) above mean sea level.
- Turn right to the value of αP in the lower left chart.
- Turn left to the value of (T0 – Ta) in the lower right chart.
- Turn left to pan evaporation in the upper right chart.
- Turn right to read lake evaporation.

24
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

NO SCALE

Elev. above Sea level (ft)


αP
Pan Evaporation (in/day)

400 Pan wind movement (m/d)


100 50
0
Finish

Start
EL (in/d)

αP
Pan water temperature

T0 - Ta in O F

25
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Infiltration:
Infiltration: is a process of water entry into a soil through surface it is influenced by the
extent of vegetal cover, conditions of soil, rainfall intensity, physical properties of soil and
quality of water.

Percolation: is the movement of water within soil profile, a process that follows infiltration.

Infiltration Rate: is the rate at which water enters soil measured in L/T.

Cumulative Infiltration: is the volume of infiltrated water at given time, measured in L.

Infiltration Capacity: Is the maximum rate at which a given soil can absorb, a potential value
that may or may not be satisfied following rain. It is measured in L/T.
Elements of Infiltration

Storm Conditions: Underground Conditions: Soil Surface Conditions:


- Rainfall intensity - Vegetation Covers
- Rainfall duration -Transmission characteristics of - Compaction/cracks/
- Evaporation underlying soil - Degree of urbanization
- Transpiration -Volume of storage available
below ground

Infiltration Capacity:
Infiltration capacity is an aspect of infiltration that is associated with soil. It is
defined as the maximum amount of water per unit time that can be absorbed under given
conditions. The greater the infiltration capacity of soil, the greater amount of water that can
be infiltrated.
Infiltration capacity is measured using infiltrometers which is a device consisting of ring
tube inserted into the soil. Water is poured and maintained at constant level and
replenishment rate is measured.
A better method for measuring infiltration rate is through the use of hydrograph analysis.
Hydrographs will be discussed in detail later.

26
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Empirical Models of Infiltration:

Horton Model:
Horton theorized that the process of infiltration is analogues to exhaustion process where
the rate of performing work is proportional to the amount of work remaining to be
performed. At the beginning of rainfall, the soil surface possesses a high degree of soil
absorption capacity. At this point, the infiltration capacity is maximum. As more water
enters the soil, the infiltration capacity is reduced with time and eventually reaching a
constant value.

Initial
Initial infiltration
infiltration capacity
capacity (Very hungry for dinner!)
f f
Rain (FOOD!)
Rain Final infiltration
Final capacity
infiltration capacity
(L/T)
(L/T) (Cant eat anymore but can
Horton Curve munch forever!)

time
Horton Curve) time
Amount of infiltrated water

Horton Infiltration Formula:

K: Constant depending on soil & surface & cover conditions, t is time

f = f∞ + (f0 – f∞) e-Kt


Initial infiltration capacity (L/T)

Final infiltration capacity (equilibrium capacity)

Infiltration capacity at a given time t

The assumption inherent is that water is always “ponded”


Horton equation requires evaluation of f0, f∞ and K .which can be derived from infiltration tests

27
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Observations:
- If rainfall intensity exceeds the infiltration capacity, the infiltration capacity
decreases exponentially.

- The area under the curve is the volume of infiltration. However, the actual
infiltration rate is equal the infiltration capacity f only when rain intensity, less
the rate of retention, equals or exceeds the capacity f (see figure below).

Depression Storage

Hyetographs of rain intensity vs. time

Horton Curve
f = f∞ + (f0 – f∞) e-Kt

- The value of f is maximum ( = f0 ) at the beginning of the storm. This becomes


constant ( =f∞ ) as the soil becomes saturated.

- When rain intensity at any given time is less than the infiltration capacity,
adjustments to the infiltration capacity curve must be made.

- Infiltration capacity depends on soil type (such as porosity and pore-size


distribution), moisture content, vegetative cover, and soil content of organic
matter (organic content enhances infiltration because it increases porosity).The
values of f0 and k can be calculated by observing the variation of infiltration with
time, plotting f vs. t and selecting two points from the graph. The two values can
then be determined from Horton equation.

Illustrative Example

Given initial infiltration capacity of 60 cm/day and time constant, k of 0.4 hr-1. Derive infiltration
capacity vs. time curve if the equilibrium capacity is 10 cm/day. Estimate the total infiltrated
water in m3 for the first 10 hours for a 100 km2 watershed.

Solution:

Horton curve: f = f∞ + (f0 – f∞) e-Kt Substituting yields: f = 10 + (50) e-0.4t Integrating yields:

V = ∫[10 + 50 e-0.4t] dt

V = [10t - (50/0.4)e-0.4t│0 to 10 = [(10)(10) - (50/0.4)e-4] – [ 0 - (50/.4) (1) = 222.7cm

Volume in = (222.7 / 100 cm/m)100 km) (1000 m/km)2 = 2.227 x 108 m3

28
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Correction of Horton Curve:


It is often the case that the intensity of rain is much smaller than the values of initial
infiltration capacity f0 and the equilibrium capacity f∞ of the soil. Since the Horton’s formula
assumes that the intensity of rain is always larger than the infiltration capacities of the soil,
solving the equation for f as function of time only, would show continuous decrease in f
even if the rain intensities are very low and much less than the soil capacity (see figure)

Infiltration capacity decreases


even though rain intensity is
low.

Problem!!
‫مشكله‬ τ
0 t1

Equivalent time τ for the actual The accumulated water, which is found here by
Accumulated infiltration integrating Horton formula between 0 and t1 ,
does not represent the actual infiltrated water
because the actual rain is less than what Horton
formula predicted.
∆t

τ
Volume of water infiltration that has been over- estimated by Horton curve!

What to do? It is clear that if the total intensity of rain at the first time increment is less
than the infiltration capacity, it is more reasonable to assume that the reduction in f is
dependent on the infiltrated volume of water rather than the elapsed time. Therefore, it
becomes necessary to shift the curve to t = τ, which would produce an infiltrated volume
equal to the volume of the actual rainfall.

In order to accommodate for the possible infiltration deficiency, the following procedure is
employed:

Let f(t) be the maximum infiltration capacity of the soil at given time (as prescribed by
infiltration capacity curve), then

∆F = ∫t to ∆t f (t) dt

Where ∆F is the amount of infiltrated water between t and ∆t. Depending on the initial
intensity of rain compared to the maximum infiltration capacity f, the equation for f(t) can
take one of two forms:

29
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

If: 1) i . dt ≥ ∆F, then τ = ∆t where i is the rain intensity between t to ∆t

Then: f0 (new) = f∞ + (f0 – f∞) e - K t which is simply the Horton formula

But, if: 2) i . dt < ∆F, then τ < ∆t

Then: f0 (new) = f∞ + (f0 – f∞) e - K τ

Application of the above equations for every time step results in actual infiltration.

Steps:
1) Draw the infiltration Capacity curve (Horton Curve, fig. A).
2) Establish Mass curve (f vs. volume) by finding the area under Horton curve at Δt.
This is calculated by multiplying the average value of f by Δt

Horton Curve

( fi + fi+1 ) / 2
Δt

fi fi+1
3) After establishing the mass curve from Horton curve (Fig. B), compute the volume of
rain that is actually infiltrated during the interval when i < f and find the
corresponding infiltration capacity (f1) from the established mass curve (f fig. B)

4) The new infiltration capacity curve is now drawn where f0 = f1 at t = t (fig D)

Horton Curve Mass Curve = ∫ f(t)


Horton Curve f f Vs F (mass) curve
F@ τ
f1

Volume under curve = F


Fig A F1 F Fig B
τ

revised Horton
f1 curve

Fig C Fig D
τ
t t
Actual infiltrated water (total rain @ t)

30
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example: (Example 2.14 Kupta)

Given: A storm pattern shown below on a watershed that has the following elements of
Horton Curve:
f0 = 11.66 in/hr, h∞ = 0.83 and k = 0.07
Required: Find the revised Capacity curve and the excess rain.

T, minutes Intensity (in/hr)


0-10 3.5
10-20 3.0
20-30 8.0
30-40 5.0
40-50 1.5
50-60 2.4
60-70 1.5

Solution:
The infiltration capacity curve (Horton Curve); f = 0.83 + 10.83 e-0.07t

Steps:

1) Find the cumulative infiltration under Horton Curve by finding the area under Horton
curve. This is accomplished by multiplying ∆t (column 3) by average f (column 4), finding
∆F (column 5) and adding the cumulative values of ∆F ’s (column 6):

Time (minutes) f (in/hr) ∆t (min) Average f ∆F (in)(1) Σ∆F (in)


(1) (2) (3) (4) (5) (6)
0 11.66
10 8.94 1.49 1.49
10 6.21
10 4.86 0.81 2.3
20 2.5
10 2.83 0.47 2.77
30 2.16
10 1.83 0.31 3.08
40 1.49
10 1.33 0.22 3.30
50 1.16
10 1.08 0.18 3.48
60 0.99
10 0.95 0.16 3.64
70 0.91

(1) ∆F = (10)/(60 min/hr) [8.94) = 1.49

31
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

2) During the first 20 minutes, the amount of rain fell is < the infiltration capacity as
prescribed by the Horton Curve. The amount of rain is:

= 3.5 (10 min /60 m/h) + 3 (10 min / 60 min/hr) = 1.08 in

Plot accumulated infiltration F against f to establish mass curve. For example plot f = 11.66
correspond to F = 0, f = 6.21 correspond to F = 1.49 and so on. The resulting cumulative
infiltration curve is shown below:
f
12

10
7.5
8

0 1 2 3 4
F
3) Horton Curve can now be shifted by setting f0 = 7.5 instead of 11.66 occurring at t’ = 0
where t’ is the time counted 20 minutes after the start of the rain. The modified Horton
equation become:

f = 0.83 + (7.5 - 0.83) e-0.07 t’ f @ t’ = 20

4) Using the revised equation, the infiltration capacity for different times is calculated as
shown in the following table:

t’ (min) Time from beginning of storm f using t’


(1) (2) (3)
0 20 7.5
10 30 4.14
20 40 2.47
30 50 1.65
40 60 1.24
50 70 1.03

32
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

5) Compute the excess rain as follows:

Time Revised ∆t Ave f Σ ∆F(1) Rainfall (i) (∆t) (2) Excess


(min) Curve (min) (in/hr) (in) intensity i (in) Rain (3)
(1) (in/hr) (3) (4) (5) (6) (7) (8)
(2)
0 - - - - - - -
10 - - - - - - -
20 7.5
10 5.82 0.97 8.0 1.33 0.36
30 4.14
10 3.31 0.55 5.0 0.83 0.28
40 2.47
10 2.06 0.34 1.5 0.25 -0.09
50 1.65
10 1.45 0.24 2.4 0.4 0.16 – 0.09
=0.07
60 1.24
10 1.13 0.19 1.5 0.25 0.06
70 1.03

(1): ∆F = (10/60) [5.82] = 0.97


(2): (8)(10/60) = 1.33 (3): (8-5.82) (10/60) =0.36
12

10 Horton Curve

9 Excess Rain

7 Modified Horton
Curve

4 3.5

3 3.0

0 10 20 30 40 50 60 70

33
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

PHI INDEX, Φ:

A simple way of approximating the amount of direct surface runoff is through the use of Φ-
Index. It is defined as the average rainfall intensity above which the volume of excess rain
equals direct runoff. The value of Φ is adjusted (up or down) such that the computed
direct runoff equal that of excess rain.

Method of Estimating Φ:

a) Estimate the volume of direct runoff (Vo)


b) Plot rainfall intensity vs. time.
c) Make initial value of Φ.
d) Compute the excess rain volume above Φ (V).
e) Check if V=Vo.
f) Adjust Φ until the volume until V=Vo.

Unfortunately the Φ-Index determined from a single storm is not generally applicable
to other storms.

Runoff:

34
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Surface runoff is a term used to describe the flow of water, from rain, snowmelt, or
other sources, over the land surface. Runoff is a major component of the water cycle

Measurement of Streamflow:

Measuring Stream Gage:

Stream gage is an automated equipment housed in the an enclosed gauging station


where stream stage can be continuously monitored and reported to high accuracy. The
equipment is powered by linking battery-powered stage recorders with satellite radios that
enable transmission of stage data to computers.

Approximate this segment of


Channel as rectangle, measure
the velocities @ y = 0.2 and 0.8
of the depth and multiply the
average by the cross sectional
area of the segment

Bottom of channel

From USGS

Measurement of Discharge:

a) Floating Devices, Current Meter (From USGS)

The USGS Type AA current meter is commonly known as the Price-type current
meter. This current meter is suspended in the water using a cable with sounding weight or
wading rod (taking the tail section off) and will accurately measure streamflow velocities
from 0.1 to 25 feet per second (0.025 to 7.6 meters per second). The main features of this
meter are the uniquely designed bucket wheel shaft bearings and the two post contact
chamber. The bucket wheel has six conical shaped cups, is five inches in diameter.

From USGS

b) Weirs:

35
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Rectangular Weir:

1 2 L
Equation: Kinetic Energy is
Neglected H h
h H
H + V21/2g = h + V22/2g
V2 = SQRT[2g(H-h)]

Flow through dh of area Ldh is:


dA = L dh
dQ=Ldh SQRT[2g(H-h)]

Integrating from 0→H

Q = 2/3 Cd L (2g)1/2 H3/2


Where: Cd: Discharge coefficient

V-Notch Weir:
θ

H h H
H θ
dA = b dh
dA = 2h tan θ/2 dh
Since: V2 = SQRT[2g(H-h)] dA = b dh
dQ = Cd (2h tan θ/2 dh) SQRT[2g(H-h)]

Integrating from 0→H

Q = 8/15 Cd (2g)1/2 tan θ / 2 H5/2


Where: Cd: Discharge coefficient and θ is the V-notch angle

Broad - Crested Weir:

36
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

H = h + v2/2g h h H
Q = Cd L h SQRT[2g(H-h)]
Q = Cd √2g L (2/3 H) SQRT[H-2/3 h) Then: h
H

Q = 0.385 Cd (2g)1/2 b H3/2


Where: Cd: Discharge coefficient L

Overflow Spillways:

+x

Ho
+y

Q = 2/3 Cd L (2g)1/2 Ho3/2 .

Where: Cd: Discharge coefficient

37
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Stage-Discharge Relations (Rating Curves) (READ ONLY)

Stage-discharge relation is a plot of on arithmetic graph with discharge on the horizontal


axis and the corresponding gauge height on the vertical axis. The relation of stage to
discharge is not always unique relationship. The rise and the fall of flood waves and the
backwater development caused by intersecting streams and other forms disturbances may
effect the slope of the energy line which in turn effects the discharge. Therefore, in order to
obtain a correct correlation between stage and discharge, an auxiliary stage near the main
station is required.

Constant Fall Rating Curve:

If the slope of the energy line is approximately the same as the slope of the water surface,
the discharge is proportional to the square root of the water surface (Manning & Chezy
Equations):

Q = f ( S1/2 )

The ratio of any two discharges Q and Q0 at a given station corresponding to the same
stage but different slopes S and S0, then,

Q/Q0 = (S/S0)1/2

From above, it is evident that if we establish an auxiliary stage downstream from the main
gage, then:

Q/Q0 = (F/F0)m

Where F0 is constant fall that corresponds to Q0, m is constant between 0.4 and 0.6.

V21 /2g Energy Line F


Water Surface

V22
Datum
2g

Bottom of Channel y

Methodology:

a) Make series of current meter measurements to calculate y Vs.Q corresponding to


fall F.
b) By interpolation, draw a curve that corresponds to F=1. This is the boundary that
separates F/F0 > 0 from F/F0 < 0 values.

38
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

c) It is now possible to Find Q0 from reading base stage.


d) Plot correction curve Q/Q0 vs. F/F0.
e) By measuring Q and F for a given base stage, find the corresponding Q0 from the
correction curve.
f) Plot the data Q/Q0 vs. F/F0 on log – log scale to obtain m.
g) The above equation can now be used to obtain any value of Q with the help of
simultaneous measurement at the base gage and the auxiliary gage.
Gage Height (Stage)

F/F0 > 0 1.5


1.2 0.5 F/F0 < 0
0.7
1.3 0.4
Curve corresponds to F=1
1.4
0.3

1.0 0.8
1.1 Q/Q0

0.6 F/ F0
Q Q0
Discharge →

log Q/Q0

m
1

log F/F0

39
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example:

For a given river, the following data were obtained by stream gauging. Estimate the flow rate when the main
gage reads 30.0 ft and auxiliary gage reads 28.0 ft.

Main Stage, ft Auxiliary Stage Q (cfs)


30 29.0 250
30 27 470

Solution:

Q1 / Q2 = [(F1/L) / (F2/L)]m

250/470 = [(30-29)/(30-27)] m → 0.5319 = 0.3333 m → m = log (0.5319) / log (0.3333) = 0.5746

250/Q3 = (1/2)0.5746 → Q3 = 250 / 0.5 0.5746 = 372.32 cfs

40
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Rainfall Runoff Relationships:

Hydrograph Analysis:

A hydrograph is a graphical representation of discharge verses time. It describes


the changes of flow rate in a given catchments area following a rain event. The hydrograph
is constructed from monitoring stream stages and the stage-discharge relationship of the
stream located at the outlet of the watershed in question.

Rain

Basin

Outlet

Rising limb: f (rain, basin) Crest: All water reached outlet Drainage from underground

Components of Hydrograph:
- Surface Runoff: It is the component of rain, which flows overland eventually
reaching stream or channels.
- Interflow: It is the component of rain, which moves at shallow depths
underground eventually reaching stream channels.
- Channel Precipitation: It is the component of rain, which falls directly on the
stream.
- Base flow: It is part of stream water that is contributed by groundwater and
delayed subsurface runoff.

The part of precipitation that contributes directly to direct runoff is often referred to as
effective runoff. The time to peak of hydrograph depends on rain characteristics, which
include intensity and duration, and characteristics of watershed, which include size, slope,
shape and storage capacity. The last segment of the hydrograph is the recession curve
which depends on the characteristics of the watershed and independent of the rain
characteristics.

41
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Storm Duration
Point of inflection
Direct R.O.
i
Recession Curve
Q (independent Hydrograph here represents period of
of rain no direct runoff and water coming into
The Crest characteristics stream reflects discharge from
groundwater. The shape depends
characteristics of the watershed.
Groundwater depletion

Rising limb Crest


(Concentration Curve)

Beginning of
new storm

Channel PPT Interflow


Groundwater flow

Time of concentration t
Time Base

Physical Analogy:

Direct R.O.

Channel PPT

GW Flow
Interflow

Watershed

42
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Base Flow Separation:

When a hydrograph of a particular storm is constructed, it becomes necessary to


separate the hydrograph into at least two components, namely base flow and direct runoff.
Separation of base flow from direct runoff is not always an easy task because, following a
large storm, the river stage rises rapidly at a rate faster than the rise of water table, as a
consequence, the flow reverses direction. As the stream stage starts to fall, the water from
the banks start to drain back into the stream.

After Storm

Stream Stage Rising


Base Flow = +
Stream Stage
Falling
Before Storm
Negative base flow

Separation Techniques:

- Straight-line separation: It is the simplest base flow separation. The separator is


a horizontal line drawn from the point of the start of the direct runoff to a point in
the recession curve. At this point, it is assumed that the base flow starts and the
direct runoff ends.

- Fixed arc-length Separation: This procedure extends the recession curve of the
previous rain to a point directly below the peak then a straight line is drawn to a
point N days after the peak where N is calculated as,

N = A0.2

N is the time in days and A is the drainage area in square miles. The reason for extending
the recession curve and, in effect, reducing the base flow is that contribution from
groundwater is reduced considerably due to the bank storage effect.

Hydrograph Time Relationships:

Travel time: The time it takes for the direct runoff originating at a point in the channel inside
the watershed to reach the outlet of the watershed.
Access –rainfall release time (time of concentration): The time it takes for the last drop of rain to
reach the outlet of the watershed. It is the same as the time difference between the end of
rain and the cessation of direct runoff. Time of concentration is the same for a given
watershed regardless of the characteristic of the storm. This is the bases for constructing
unit hydrographs.

43
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Time base: It is the time between the beginning and end of direct runoff. Ideally, time base is
the same if rain characteristics are the same for a given catchment area.

The equation for time base is, tb = ts + tc

Where tb is the time base, ts is the duration of rain and tc is the time of concentration.

Example:
Shown is a hydrograph of a particular rain in a particular basin. Separate the direct runoff using
straight-line separation and Arc length separation and find the direct runoff. Assume the drainage area = 1000
mi2.
Solution: N = (1000)0.2 = 3.98 days

Discharge m3/s
90

80

70

60

50

40

30

20

10
3.98 d
0
0 2 4 6 8 t Day 10 12 14 16 18

Time : 4 6 8 10 12 14 16
Q: 30 45 70 84 74 50 30
Base Flow (Straight.Line): 30 30 30 30 30 30 30
D.R.O (Str.Line) : 0 15 40 54 44 20 0
Base (Arc L): 30 25 23 20 35 50 -
D.R.O. (Arc L ) 0 20 47 64 39 30 -

Vol. of D.R.O (SL) = {(1/2) [(0 + 15) + (15 + 40) + (40 + 54) + (54 + 44) + (44 + 20) + (20 + 0)}(2 dayx86400 s/d) = 2.989 x 10 7 m3

Amount of direct runoff in meters = 2.989 x 107 / (1000 mi2 x 2590000 m2 /mi2 ) = 0.012 m

Volume of D.R.O. (AL) = {(1/2) [(0 + 20) + (20 + 47) + (47 + 64) + (64 + 39) + (39 + 30)} (2 day x 86400) = 3.1968 x 107 m3

Amount of direct runoff in meters = 0.01234 m

44
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

The Unit Hydrograph:

Observation has proven that, since the physical characteristics of a watershed


(such as shape, size, slope and topography) remain unchanged over different cycles of
rainstorms, one would expect that the resulting hydrographs produced by similar storms
would be similar. It is therefore, safe to assume that, for a given watershed, “different
storms of similar duration would produce the same hydrograph base and the resulting peak
flows would vary directly with the rain intensity and the volume of direct runoff”.
Sherman (1932) introduced the concept of unit hydrograph. He defined it as the
hydrograph of a given watershed resulting from effective rainfall producing 1 inch of direct
runoff distributed uniformly over the basin. The assumptions inherent in the unit
hydrograph theory are:

- There is direct proportionality between effective rainfall and surface runoff. An


effective rainfall of two units of T duration would produce twice the runoff of one
unit rainfall of the same duration.
- The effective rainfall is uniformly distributed within its duration.
- The effective rainfall is uniformly distributed throughout the basin.
- Once a unit hydrograph for a catchment area is derived, it can be used as a base
to represent the response of the catchment area to different storms. If two
successive rains of T duration produce two different direct runoffs, then the
hydrograph produced is the sum of the two runoff producing hydrographs of 2T
duration.
- The ordinates of direct runoff of common-base hydrographs are directly
proportional to the amount of direct runoff represented by each hydrograph.

There are inherent weaknesses in the unit hydrograph theory as well. It is obvious that if the
catchment area is saturated prior to the rain, much of the rain will contribute to direct runoff
and any extra rainfall in the same time period will produce proportionally extra runoff. This
is obviously not the case for catchment areas of high initial moisture deficiency. Another
weakness in the theory pertains to the assumption of uniform time and areal distribution of
rain in the basin. It is obvious that this assumption fails for both complex rains and for
catchment areas having nonhomogeneous composition.

Derivation of Unit Hydrograph:

Before proceeding to develop representative unit hydrograph for a certain


catchment area, it is essential that the unit hydrograph be a product of many rainfall-
producing hydrographs resulting from various storms of the same duration and different
magnitudes, rather than the product of a single storm. This is necessary because, for
reasons previously mentioned, similar rains may not necessarily produce similar
hydrographs. In addition, the intensity and distribution of rainfall over the catchment area
must be uniform and simple.

45
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Steps: - Separate direct runoff from groundwater using one of the methods described earlier.
- Measure the total volume direct runoff
Q
Volume of direct runoff : QTi
QBi
= ∑ [ (QTi+1 + QTi) / 2 - (QBi+1 + QBi) / 2 ] x ∆t
= VRO = Area Under Curve (R.O.)
Δt t
- Divide the ordinates of the total runoff (QT - QB) by the total
volume of direct runoff measured above to obtain the
ordinates of the unit hydrograph (QUH = QS / VRO). Where VRO
is Volume of runoff measured in (L) and

QS = QT - QB
-The effective duration of the unit hydrograph is the same as the original hydrograph.

It is important to note that the unit hydrograph represents a given basin and rain of specific
duration. Since most storms do not have the same characteristics of the unit hydrograph, it
is necessary to construct another unit hydrograph having the same rain characteristics
before any attempt to construct the hydrograph.

Construction of Unit Hydrographs:


Example:
Construct a unit hydrograph from the following hydrograph. The area is 2 mi 2. Use straight-line
separation and construct a hydrograph representing the following complex rain pattern.

Q i
2 hr effective rain NO SCALE!
400
Losses =0.1
1.2” 2.2” 1.8”
300 NO SCALE!
Q
cfs
200

100

t ( hr) t ( hr)
0 1 2 3 4 5 6 7 8 2 4 6

t (hrs) Q (cfs) Base Flow (cfs) D.R.O. (cfs)

1 75 75 0
2 110 75 35
3 205 75 130
4 305 75 230
5 280 75 205
6 205 75 130
7 130 75 55
8 75 75 0

46
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Volume of direct runoff = (1/2) [(0+35) + (35+130) + (130+230) + (230+205) + (205+130) + (130+55) + (55+0)] (3600
s/hr) = 2.826 x 106 ft3

Effective runoff in inches = (2.826 x 106 ft3) (12 inches / ft) / [(2 mi2) (5280 ft/mi)2] = 0.61 inches
Now calculate the ordinates of U.H. by dividing the ordinates of the hydrograph by 0.61”

t (hrs) D.R.O. (cfs) QU.H = Q/0.61


x 1000
1 0 0
2 35 57.4
3 130 213.1
4 230 377.0
5 205 336.1 Ordinates of the 2-hr unit hydrograph
6 130 213.1
7 55 90.2
8 0 0

The hydrograph of the complex rain is found by multiplying the ordinates of U.H. by the effective rain
(rainfall minus the losses) and shifting the resulting hydrographs by two hours and adding ordinates.

t (hrs) QU.H QUH x 1.1 QUH x 2.1 QUH x 1.8 Hydrograph Ordinates

0 0 0 - - 0 Hydrograph resulting from the


1 57.4 63.1 - - 63.1 complex storm
2 213.1 234.4 0 - 234.4
3 377.0 414.7 120.5 - 535.2
4 336.1 369.7 447.5 0 817.2
5 213.1 234.4 791.7 103.3 1129.4
6 90.2 99.2 705.8 383.6 1089.4 No Scale
7 0 0 447.5 678.6 1126.1
8 0 0 189.4 605.0 794.4
9 0 0 0 383.6 383.6
10 0 0 0 162.4 162.4
11 0

Important Note: Add base flow (75 cfs) to ordinates to obtain full hydrograph.

NO SCALE!

NO SCALE! Final hydrograph without


base flow
UH
U.H. x 1.1
U.H. x 2.1
U.H. x 1.8

0 2 4 ….

47
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Conversion of Small T Hydrograph to larger T Unit Hydrograph:

Given: t-hr U.H. Required: T-hr unit hydrograph (T > t )


Method: Lag unit t-hr unit hydrograph by t to obtain T-hr hydrograph.

Add t-hr unit hydrograph to another t-hr unit hydrograph but shifted by t-hours. The two unit
hydrographs will produce a hydrograph of 2t duration totaling two inches of rain. The new hydrograph
represents rain intensity of 1/t (because intensity is 2”/2t). The new 2t unit hydrograph is obtained by dividing
ordinates by 2.

Resulting 4-hr
hydrograph
2-hr U.H.
Two 2-hr U.H.

2 hours shift
t

Given: T-hr U.H. Required: t-hr unit hydrograph (T > t )


Method: Use S-Curve described below.

S curve:

S-Curve is a hydrograph resulting from addition of infinite series of unit hydrographs of


specific duration, each lagged by its duration t. It is only necessary to add a limited number
of unit hydrographs to reach equilibrium of constant direct runoff discharge. If T is the time
base of the unit hydrograph and t is the duration then only T/t unit hydrographs need to
combined to produce equilibrium.

Q I x t = 1 inch
T-hr S Curve
ΔQ
Q

T-hr
U.H.’s
Ordinates of U.H. of t-
hr duration
t = (T/t) ΔQ

T t

48
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Example on the Use of S-Curve to Obtain Unit Hydrograph of Different Duration:

The following unit hydrograph results from 2–hr storm. Determine the 1-hr unit hydrograph.

Time (hr): 0 1 2 3 4 5 6
Q (m3/s): 0 0 1.42 8.5 11.3 5.66 1.45 0

To construct S-Curve follow the following schematic calculations:

Given: 2-hr unit hydrograph Required: 2-hr S-curve

Time (hr) 2-hr U.H. S-Curve additions 2-hr S-Curve


0 0 - -
1 a - a
2 b - b
3 c A = (a) c+a
4 d B= (b) → d + (B=b) = d + b
5 e C = (c + A) → e + (C=c+a) = e + c + a
6 f D = (d + B) → f + (D=d+b) = f + d + b
7 g E = (e + C) → g + (E=e+c+a) = g + e + c + a
8 h F = (f + D) → h + (F=f+d+b) = h + f + d + b
9 i G
10 j H
11 k I = (i + G) → k+i+G

Inserting numbers:
Time (hr) 2-hr U.H. S-Curve additions 2-hr S-Curve
0 0 - -
1 1.42 - = 1.42
2 8.5 - = 8.5
3 11.3 = (1.42) 11.3+1.42 = 12.72
4 5.66 = (8.5) 5.66+8.5 = 14.16
5 1.45 = (11.3+1.42) 1.45+11.3+1.42 = 14.17
6 0 = (5.66+8.5) 0+5.66+8.5 = 14.16
7 = (1.45+11.3+1.42) 1.45+11.3+1.42 = 14.17

The 1 hour unit hydrograph is calculated by lagging the 2 – hr S-Curve by 1 hour and
multiplying ordinates by 2/1 (old duration divided by new duration)

Time 2-hr S-Curve Lagged S-Curve ∆S 1-hr UH = (Column 4) (2/1)


(1) (2) (3) (4)
0 0 0 0 Multiply ΔS by the
1 1.42 0 1.42 2.84 factor (2/1) to obtain
2 8.5 1.42 7.08 14.16 1 hr UH
3 12.72 8.5 4.22 8.44
4 14.16 12.72 1.44 2.88
5 14.17 14.16 0 0

49
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Flood Routing:

Flood routing is a “bookkeeping” technique that uses continuity to predict temporal and
spatial variation through river reach or a reservoir. It is a mathematical description of the
behavior of the flood waves that move through a point along the stream. The outcome of the
routing is a discharge hydrograph Q = Q(t) measured at a prescribed point along a stream
from a known hydrograph upstream or downstream and a known characteristics of the
stream. Waves are generated as a result of inflow or outflow into the channel as a result of
rain, channel failure, tides or releases from reservoirs.

Event

Q = Q(t) Q = Q(t)
Inflow Outflow

Sudden opening of sluice gate

Upstream flow Downstream flow


wave wave

Storage Routing:

The rate of change of storage is defined by the continuity equation:


Sudden closure of sluice gate

Reservoir Routing:

Referring to the figure below, the inflow and outflow are plotted in the same graph. Area A
represents the volume of water that is available in the reservoir at time t 1. At t > t1 , outflow
exceeds inflow and the reservoir empties by an amount equal to B.

(Inflow Volume) A
Inflow outflow Storage in channel (outflow volume) B
Water released
I = O here
Reservoir Peak of
outflow

The rate of change in storage is defined by the equation:

I – O = ∂S / ∂t

50
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

If the average rate of flow during a given time period is equal to the average flow at the
beginning and the end of the period (i.e. short time period), the routing equation takes the
following form:

( I1 + I2 ) ∆t - ( O1 + O2 ) ∆t = s2 – s1
2 2
Where subscripts 1 and 2 refer to the beginning and end of the time period. In the above
equation all elements are known except O2 and s2 and a second equation is needed in order
to solve for O and s.

Routing procedure:

For a large reservoir where water velocity is low, the pool level of the reservoir is near
horizontal which allows a relationship between upstream head H and weir geometry to be
established. The form of equation which was discussed earlier is:

O = CLH 3/2

Where C is the weir coefficient, H is the upstream depth and L is the width of the weir. The
active storage can be found by measuring the height of the reservoir and the planimetering
the reservoir surface area from topographic maps. The storage and the outflow can now be
established as shown in the following graph:
Spillway Discharge O = CLH 3/2 →

s Vs. H (Measured)

O Vs. H Calculated From


Spillway formula

H
Reservoir volume s →
The routing equation can be written as: (I 1 + I 2) + (2s 1 / ∆t – O 1) = (2s 2 / ∆t + O 2)

Solution Method:

 Establish 2s / ∆t + O as a function of H from H vs. s data and from the spillway discharge formula O =
CH3/2.
 At the beginning of routing period, all values in the left-hand side are known and the values at the
right-hand side are computed.
 From the computed value of 2s/∆t + O, a new value of H is interpreted from 2s/∆t + O vs. H data.
 From the computed value of 2s/∆t + O, and O, find s.
 Using Spillway formula, find O from H.
 From the new values of s and O find 2s/∆t – O.
 Add (I1 + I2) and 2s/∆t – O to obtain a new value of 2s/∆t + O.
 Repeat step 3-7 to find new values of s, O, H, 2s/∆t – O and 2s/∆t + O.
 Obtain a new value of s from the calculated value of 2s/∆t + O curve established earlier.
 From the values of 2s/∆t + O and O, a new value of s is calculated.

51
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example:

The inflow hydrograph of a given reservoir is as follows:

I (cfs)
200 ( cfs)

150

100

50

00 1.0 2.0 3.0 Time (day)

Time
(days): 0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Flow
(cfs): 0 50 100 150 200 100 66.67 33.33 0.00

The crest discharge formula is described by the following formula:

O = C L H3/2

Where: O is the outflow, L is the length and H is the head above the crest. The characteristics of the
spillway are as follows: C = 3, L (Length of the spillway) = 35 ft and H0 (Initial crest height of the
spillway) = 50 ft.

Stage Vs. Storage is as follows:

Stage (ft)

208.75

52.0 175.00

141.25
51.5
(ft)
107.50
51.0

73.70
50.5
Storage ( x 106 ft3)
50 .
0 50 100 150 200
50.0
50

52
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Step 1: Calculate outflow O and 2s/∆t + O for ∆t = 0.5 day

Table 1:
Water Surface El. Head H (1) Storage(From Data) Outflow (2) 2s/∆t + O
(ft) (ft) (ft3 x 106) (cfs) (cfs)
(1) (2) (3) (4) (5)
50.0 0.0 40.00 0.00 160.00
50.5 0.5 73.70 37.1 331.9
51.0 1.0 107.50 105.0 535.00
51.5 1.5 141.25 192.0 757.00
52.0 2.0 175.00 297.0 997.00
52.5 2.5 208.75 415.00 1250
O = C L H3/2
(1) Elevation above the crest
(2) From spillway formula

Step 2: Plot O vs. Stage from values obtained in column 4:

0 50 100 150 200 250 300 350 400 450 500

Step 2: Conduct Flood Routing Computation to Time Vs. Elevation / Storage:

Table 2:
Time Inflow I1 + I2 Outflow Storage, s 2s1/∆t – O1 2s2/∆t + O2 Water Elevation
(Day) (cfs) (cfs) (cfs) (ft3 x 106) (cfs) (cfs) (ft)
(1) (2) (3) (4) (5) (6) (7) (8)
--- 0 0 0 40 160 160 50.0
0 0 50 0 40 160 210 50.15
0.5 50 150 6.10 52.5 203.9 353.90 50.55
1.0 100 250 42.83 86.95 304.97 554.97 51.05
1.5 150 350 112.97 128.04 399.17 749.17 51.52
2.0 200 300 196.77 159.05 439.43 739.43 51.46
2.5 100 100 185.23 135.67 357.43 457.43 50.81
3.0 0 0

From: H = 0.55 → O = CLH3/2 From: (I1+I2) + (2s/∆t-O1)→(150) + 203.9) = 353.9 From Table 1 @ 353.9 cfs
= 42.83
From: 2s/∆t + 6.1 = 353.9 → s = 86.95

53
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Hydrographs of Basin Outflow:

The Rational Method:

In some engineering designs such as design storm water-sewer system, estimates


of peak flow rate from a small basin is required. Hydrologic methods including the rational
method is employed to estimate peak flow used for such designs.
The underlying assumption of the rational method is that a catchment area has a
specific time of concentration which is defined as the time needed for water to travel from
the most remote point of the area to travel through the outlet. The basic equation of the
rational method is,

Q = CiA

Where: Q is the peak flow, C is runoff (rational) coefficient and A is the area of the
watershed. Note that if Q is in m3 / s, i in mm / hr, A in km2, the equation should be written
as,

Q = 0.278 CiA

Although the rational equation is dimensionally consistent, it yields correct values for Q in
cfs, i in inches per hour and A in acres. The figure below is provided by the US Department
of Transportation for frequency correction factor. The table shows some typical values of
the rational coefficient C for various surface areas.

Note that the runoff coefficient varies from 0 to 1 which embodies a number of variables
that include rainfall duration and intensity, soil type, shape and slope of the watershed,
design frequency, amount of depression storage and interception

Application of Rational Method:

1) Estimate the time of concentration which is the time required for water to travel from
the most remote area to reach the outlet. For combination of various routes, t c is
taken as the longest time of travel to the outlet.

2) Estimate the runoff coefficient C.

3) Select a return period Tr and find the intensity of rain that will be equaled or
exceeded once every Tr. This is obtained from IDF curves (Published by US National
Weather Service See Figure)

4) Determine peak flow from the rational formula. This value is then used for design of
storm systems.

54
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Intensity-Duration-Frequency Curves (US National Weather Service):

Runoff coefficients for Various Areas:


Business: Downtown Area 0.70 – 0.95
Business: Neighborhood Areas 0.50 – 0.70

Residential: Single-family areas 0.30 - 0.50


Multi units, detached 0.40 - 0.60
Multi units, attached 0.60 - 0.70
Residential (suburban) 0.25 – 0.40
Apartment dwelling areas 0.50 – 0.70

Industrial: Light areas 0.50 – 0.80


Industrial: Heavy areas 0.60 - 0.90

Park, cemeteries 0.10 – 0.25

Playgrounds 0.20 – 0.35

Railroad yard areas 0.20 – 0.40

Unimproved areas 0.10 – 0.30

55
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative Example:

Find the 50 year design storm for a the following composite area: A business downtown area
with C = 0.8 in the left and a park with C = 0.2 in the right. The lateral time of flow in the left
portion is 10 minutes and in the right is 40 minutes. The travel time in the gutter is 8 minutes.

10 minutes 10 minutes

40 minutes
Business Park

8 minutes
2000 ft

18 minutes

500 ft 2000 ft

From IDF chart, for 50 year design and tc = 18 minutes, i = 7 inches / hr.

Assume Business area controls, then tc = 18 minutes

Area of the watershed = Area of the business section + effected portion of the park

Area of the business section = (500)(2000) / (43560 ft2/acre) = 22.96 acres


Area of the park ={ {[(10/40) (2000) + (18/40) (2000)]/2} (2000) } / (43560) =32.14 acres

Q = C1 i1 A1 + C2 i2 A2

= (0.8) (7inches/hr)(22.96 acre) + (0.3) (7) (32.14) = 196.07 cfs

Assume the park controls, then: tc = 40 + 8 = 48 minutes

From chart, for 50 year design and tc = 48 minutes, i = 4.8 inches / hr

Area of the park = (2000) (2000)/43560 = 91.83

Q = (0.8) (4.8) (22.96) + (0.2) (4.8) (91.83) = 176.32

Since Q business > Q Park , then Q = 196.07 cfs is used for drainage design.

56
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Illustrative example:

A composite residential and park areas is proposed for construction. The inlet times to the
manholes for areas AA to AC are 20, 35, 41 and 53 minutes respectively. The coefficients C for
areas AA to AC are 0.8, 0.3, 0.6 and 0.25 respectively. The time of travel between manhole 1 to 2 is
5 minutes, 2 to 3 is 7 minutes and between 3 and 4 is 10 minutes. Find the 10-year peak flow at
each inlet that will be used for storm design.

AA = 3.3 Acres
AB = 4 Acres
AC = 4.5 Acres
A4 AD = 5.4 Acres

1
2 3

Inlet 1:
Contribution from area A = 20 minutes, then from IDF chart @ 10-yr storm and @ tC = 20
minutes, i A = 5.6 in/hr
Q1 = CiA =(0.8) (5.6 in/hr) (3.3 acres) = 14.78 cfs

Inlet 2:
Contribution from area A = 20 minutes + 5 minutes = 25 minutes
Contribution from area B = 35 minutes
Therefore, since (tc)B > (tc)A , contribution from area B to inlet 2 controls, then from the IDF @ 10-
yr storm and @ tC = 35, i B = 4.6 in/hr
Q2 = CiA =(0.8) (4.6 in/hr) (3.3 acres) + (0.3) (4.6 in/hr) (4 acres) = 17.66 cfs

Inlet 3:
Contribution from area A = 20 minutes + 5 minutes + 7 minutes = 32 minutes
Contribution from area B = 35 minutes + 7 minutes = 42 minutes
Contribution from area C = 41 minutes
Therefore, since (tc)B > (tc)A and (tc)B > (tc)C , contribution from area B to inlet 3 controls, then
from the IDF @ 10-yr storm, and @ tc = 42 minutes, i B = 4.0 in/hr
Q3 = CiA =(0.8) (4 in/hr) (3.3 acre) + (0.3) (4 in/hr) (4 acres) + (0.6) (4 in/hr) (4.5 acre) = 26.16 cfs

Inlet 4:
Contribution from area A = 20 minutes + 5 minutes + 7 minutes + 10 minutes = 42 minutes
Contribution from area B = 35 minutes + 7 minutes + 10 minutes = 52 minutes
Contribution from area C = 41 minutes + 10 minutes = 51 minutes
Contribution from area D = 53 minutes
Therefore, since (tC)D > (tc)A , (tc)D > (tc)B and (tc)D > (tc)C , contribution from area B to inlet 3
controls, then from the IDF @ 10-yr storm, and @ tD = 53 minutes, i B = 3.5 in/hr
Q4 = CiA = (0.8) (3.5 in/hr) (3.3 acre) + (0.3) (3.5 in/hr) (4 acres) + (0.6) (3.5 in/hr) (4.5 acre) + (0.25)
(3.5 in/hr) (5.4 acre) = 27.61 cfs

57
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Civil Engineering Dept.


CE 331 Engineering Hydrology
Dr. Rashid Allayla

58
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Groundwater Hydrology

Introductions & Definitions:

Porous Media A medium of interconnected pores that is capable of transmitting fluid.


These pores often referred to as “interstices”. Interstices can be fully saturated or
partially saturated.

Aquifer is any porous formation that can transmit water at economic (usable) quantity. It
comes from the Latin words aqua (means water) and Ferro (to bear).

Classification of Aquifers:

A confined aquifer also known as artesian aquifer is a formation containing


transmittable quantities water that is under pressure greater than atmospheric pressure.
Confined aquifer is bounded from above and from below by impermeable formations.
The pressure at this type of aquifers is greater than atmospheric. Unconfined aquifer,
also known as water-table aquifer is an aquifer with free water surface that is open to
atmosphere. The upper surface of the zone of saturation is the water table. It is the
upper portion of the saturated zone and is open to atmosphere. Unconfined aquifers
that contain Aquitard and and/or Aquiclude may contain additional water tables.
A piezometric surface is the contour of water elevation of wells tapping confined
aquifers. The contours provide indications of the direction of groundwater flow in the
aquifers. If the piezometric surface falls below the top formation of confined aquifers (as
shown in the left figure next page), the aquifer at that point is a water-table aquifer and
the surface becomes water-table surface. It is easy to confuse water-table surface with
piezometric surface when both confined and unconfined aquifers exist on to of each
other. But , in general, the two surfaces do not coincide. A piezometer is a device, which
indicates the water pressure head at a point in the confined aquifer. It consists of casing
that is open in both sides and fits tightly against the geological formation making up the
aquifer. The height to which water rises in the piezometer is the water pressure head.

Piezometric Surface

Upper Rock Formation

Piezometer

Direction of
Flow
Lower Rock
Formation

Direction 59
Of
Flow
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Piezometric Surface
H = P/γ + Z
Piezometer

nn Water Table
P/γ = 0

P/

Confined Unconfined
Aquifer Aquifer Aquifer

Z P/γ

Porosity: It is the ratio of the volume of interconnected voids within the soil to the total
volume of the soil. If VV designates the volume of “interconnected” voids, VS is the bulk
volume and VT is the total volume of the soil media, the porosity θ is defined as:

θ = VV / VT = (VT-VS) / VT = 1 – VS/VT

Volumetric Water content: It is the ratio of the volume of water to total volume of soil
sample.

θW = VW / VT

Degree of Saturation: It is the ratio of the volume of water to the volume of voids. The
soil is said to be saturated when the degree of saturation is 100%.

S = VW / VV

Moisture Content: It is the ratio of the weight of water to the weight of solid.

W = WW / WS

Effective Porosity: It is the ratio of the volume of interconnected voids that allow free
water flow to the total volume of soil sample. The value of effective porosity is always
less than soil porosity because of the existence of micro voids that do not allow free
flow of water. The difference between effective porosity and porosity is more
pronounced in silt and clay than in medium to coarse sand.

VV Va

VW VT

VS VS

60
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

EXAMPLE:

A 130 cm3 soil sample weighs 200 grams when it was at field moisture. After drying the
sample, it weighed 180 grams. The volume of solid is 69 cm3 Find: 1) Volumetric water
content, 2) Total porosity and 3) Degree of Saturation and 4) moisture content.

1) Volumetric water content = Volume of Water/Total Volume = Vw / V = (200-180) / 130 =


0.15

2) Total porosity Volume of voids / Total volume = VV / V = (130-69) / 130 = 0.47

3) Degree of saturation = θ / θs = (Vw / V) / (VV / V ) = 0.15 / 0.47 = 0.32

4) Moisture content = WW / WS = (200-180) / 180 = 0.111

Distribution of Pressure:

The force that balances the gravity force and holds water in equilibrium is,

∂P / ∂ z = - γ

Where P is the pressure and γ is the unit weight of water. Integrating,

P = - γz + C

Selecting water table as the datum, pressure above water table is negative and pressure
below is positive. One can ask how does water stay in voids and not drain. The answer
is because of Surface Tension.

Specific Storage, SS and Storage coefficient, S:

Specific storage is the amount of water in storage (aquifer) that is released from a unit
volume of aquifer per unit decline of head. It has the dimension of (1/L). For two
dimensional aquifer analysis, a more useful storage parameter is the one that integrates
the storage over the depth of the aquifer. This is called storage coefficient. For confined
aquifers it is defined as the amount of water released from aquifer per unit area of
aquifer per unit decline of head:

S = SS b Vw/(VTx1/L)

Where b is the thickness of the aquifer. For unconfined aquifers, S is given the term
“specific yield", Sy. It is defined as the amount of water released from a column of
aquifer per unit area per unit decline of head. Sy is, therefore, a measure of how much
water can drain away from the rock when subjected to gravity force versus how much
water the rock actually holds. Since surface retention is proportional to the water-
holding capacity of soil particles, the grain size of the soil plays important role in
determining the magnitude of specific yield. The smaller the particle, the larger the
surface area, the larger the surface tension, the less the specific yield. This is the
reason why pumping from sandy aquifer yields more water than aquifers made of clay.

61
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Unit Cross Section of Aquifer

Piezometric Surface 1

Amount of head decline

Confined Aquifer Piezometric Surface


WT 1 WT 2

1.unit area

∆h
S Sy

Confined Aquifer Water-Table Aquifer

Typical values of S: S ranges from 10-4 to 10-6 and Sy ranges from 0.2 to 0.3 (Bear ‘72)

EXAMPLE:

The average volume of a confined aquifer is 2.5 x 107 m3. The storage coefficient of the
aquifer at a location where the thickness b = 30 m is 0.005. Estimate the volume of water
recovered by reducing the pressure head by 20 meters.

Using the definition of storage coefficient S as the volume of water released from
storage per unit area of aquifer per unit decline of head :

S = Vv / (AT)(Δh) where area AT (Area of aquifer) = 2.5 x 107 / 30 = 8.3 x 105 m2

Then Volume of water recovered Vv = S x AT x Δh =(0.005) (8.3 x 105) (20) = 8.3 x 104 m3.

62
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Groundwater Motion: Darcy’s Empirical Equation:

The French engineer Henry Darcy introduced Darcy’s Law in 1856 when he was
investigating flow under foundations in the French city of Dijon. The law is a generalized
relationship between the flow of fluid and the change in head in porous media under
saturated conditions. Darcy concluded that Q, measured in volume of water per unit
time, is directly proportional to the cross-sectional area of the porous medium
transmitting water, the difference in head between the entrance and the exit and
inversely proportional to the length separating the points. This law is valid for any
Newtonian fluid and, with some modification; it could describe flow in unsaturated zone.

Darcy’s Experiment:

Henry Darcy conducted an experiment to determine the relationship between discharge


and head variation across a porous medium.

In general, flow of pore water in soils is driven from positions of higher total head
towards positions of lower total head. The level of the datum is arbitrary. It is the
differences in total head that determines discharge. Introducing the hydraulic gradient
as the rate of change of total head along the direction of flow.

▼h= ∆h / L

∆h

hout
L

hin

Area Q (Discharge)

Porous Media

Porous Ceramic

For a one dimensional flow perpendicular to the cross sectional area, Darcy found that,

Q = - A K Δh / L

Where the minus sign is placed in the right side because the head loss (∆h = h2 – h1) is negative
and Q must be positive. In the equation, Q is the volumetric flow rate (measured in L3 / T), A is
the flow area perpendicular to the flow direction (m2 or ft2), K is the hydraulic conductivity of the
porous medium (measured in L / T), L is the flow path length (measured in L), h is the hydraulic

63
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

head (measured in L) and ∆h is the change in h over the path L. The hydraulic head at a
specific point, h is the sum of the pressure head and the elevation, or

h = (p/γ + z)

Darcy’s Formula in Three-dimensional Form:

q = -K ▼h

where ▼h (Del h) is (∂h/∂x) i + (∂h/∂y) j + (∂h/∂z) k and q is the vector velocity discharge
equal to Q/A.

Introducing the term intrinsic permeability, k,

K=kγ/μ

K=kν/g

Where K is the hydraulic conductivity (L/T), k is the intrinsic permeability, γ is the unit
weight of water and μ and ν are the dynamic kinematic viscosities of water. In the above
formula, it is apparent that K depends on both fluid properties (γ / μ ) and soil property
(k). Various formulas relate k to properties of porous medium. One of them is,

k = C d2 where k is measured in cm2 and d depends on dimensional property of soil.

In the above equation, C is a dimensionless constant that varies from 45 for clay sand to
140 for pure sand. From the above definition, k has the dimension L2. Intrinsic
permeability pertains to the relative ease with which a porous medium can transmit a
liquid under a hydraulic gradient. It is apparent from the definition of k that it is a
property of the porous medium and is independent of the nature of the liquid or the
potential field, whereas the hydraulic conductivity K is dependent on both soil medium
(represented by k) and fluid properties (represented by viscosity μ & unit weight γ.

Units:
The standard unit used by hydrologists for hydraulic conductivity, K is meter per
day. In laboratory, the standard unit is in gallons per day through area of a porous
medium measured in ft2. In the field, hydraulic conductivity is measured as the
discharge of water through a cross-area of an aquifer one foot thick and one mile wide
under a hydraulic gradient of 1 ft/mile (Bear 1979).

The value of k in length units is very small. One practical unit employed to represent k is
Darcy, which is defined as,

1 Darcy = 9.87 x 10-9 cm2 ≡ 1.062 x 10-11 ft2

64
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Laboratory Measurement of Hydraulic Conductivity:


Measurement of hydraulic conductivity through field aquifer tests provides more
reliable results than in laboratory tests because, field tests involve large magnitudes of
porous medium compared to small laboratory samples. Field tests will be discussed
when aquifer testing method is covered. In laboratories, hydraulic conductivity is
measured using Permeameters. Two commonly used permeameters are shown below;
one is constant head where the difference between water levels reflects the head loss
between inlet and outlet of the soil sample. In the falling-head permeameters, the rate of
discharge through the sample decreases with time as the driving head decreases. The
equations used for the two measurements are,

a) Constant Head Permeameters:

K = QL / ∆h

Constant Variable
Head Inflow Head inflow

dh

∆h

h0

h(t)

Soil Sample

65
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

b) Falling Head Permeameters:

Darcy states that:

Q = - K Δh(t) / L

But: Q = a dh(t) / dt

a dh(t) / dt = - KA (Δh(t) /L then: dt = - a L dh(t) / [Δh(t) KA]

Integrating both sides from t=0 to t=t Then:

t = - (a L / KA) ln h(t)||From h0 to ht

t = - (aL / KA) [ln h(t) – ln h0]

t = (aL / KA) [ln h0 – ln h(t) = (aL/KA) ln[h0/ h(t)] Which gives:

K = (a L / t A) ln[h0/ h(t)]
Darcy’s law shown above is limited to flow that is one–dimensional and
homogeneous incompressible medium. Introducing the concept of specific discharge q,
Darcy’s law becomes,

q = K Δh / L

In the above, q is also referred to as the Darcy flux. It is fictitious form of velocity
because the equation assumes that the discharge occurs throughout the cross sectional
area of soil in spite of the fact that solid particles constitute a major portion of the cross
sectional area. The portion of the area available to flow is equal to θA, where θ is the
porosity (as defined as the volume of pore relative to the total volume of the medium).
The average “real” velocity is, therefore is,

v=q/θ

V q

The energy loss Δh is due to the friction between the moving water and the walls of the
solid. The hydraulic gradient is simply the difference between the head at inlet and head
at the outlet divided by the distance between the inlet and the outlet. Note that the flow
prescribed by Darcy’s law,

1) Takes place from higher head to lower head and not necessarily from higher pressure to lower
one.
2) Darcy’s law specifies linear relationship between velocity and hydraulic head. This relationship
is valid only for small Reynolds number. At high Reynolds number, viscous forces do not govern
the flow and the hydraulic gradient will have higher order terms.

66
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Non-Homogeneity (Heterogeneity) and Anisotropy:

A medium is non-homogeneous when elements such as hydraulic


conductivity vary with space. Rarely is an aquifer actually homogeneous, and due to the
difficulties in solving non-homogeneous aquifer system, flow nets are often employed to
transform such system before employing such solutions. A medium is an anisotropic if
the hydraulic conductivity is directional. In non-homogeneous aquifers, Darcy’s
equation is still valid because the value of K(x,y,z) is still a scalar and lies outside the
head gradient. Non-homogeneity in aquifers is often the result of stratification of the
aquifer. The individual stratum may be homogeneous but the values of K may vary
between one layer to the other making the whole system non-homogeneous

Nonhomogeneous /
Homogeneous / Isotropic Isotropic

Homogeneous / Nonhomogeneous /
Anisotropic Anisotropic

Nonhomogeneouity:

Area A Area B (KA )x ≠ (KA )x


(KA )y ≠ (KA )y

67
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Groundwater Flow Equation:

The derivation of groundwater equation is based on the conservation of mass


between one point in flow to another coupled with the application of Darcy’s law. For
incompressible flow, the continuity equation states that,

∂2h / ∂x2 + ∂2h / ∂y2 + ∂2h / ∂z2 = 0,

and for in one-dimensional flow, the equation is,

∂2h / ∂x2 = 0

a) Steady One-Dimensional Flow in Confined Aquifer:

Assume a flow situation shown below. The head upstream is H1 and the head
downstream is H2. The hydraulic conductivity is K and the length of flow is L. The
distribution of head as function of x is found using the above Laplace equation in x-
direction.

Piezometric head
Area = A

H1
H2
K

∂2h / ∂x2 = 0 Integrating twice,

h =C1 x + C2

Applying the boundary condition

h = H1 @ x=0 and h = H2 @ x=L

h = [(H2 – H1) / L] x + H1

The discharge is found by employing Darcy’s law Q = - KA dh/dx

Q = KA (H1 – H2) / L

Note that for flow in unconfined aquifer, there is no direct solution available even in one
dimension. The reason is that the water table is part of the unknown upper boundary
and the location of the water table is required (a priori) before one can proceed to solve
the equation. This would lead us to make further simplification to linearized the equation
that describes the flow in unconfined aquifers (Dupuit assumption).

68
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

b) Steady One-Dimensional Flow in Unconfined Aquifer:

Dupuit Assumption:

The equation describing steady flow of water in unconfined aquifer assuming K


is independent of position is,

∂2h2/∂x2 + ∂2h2/∂y2 + ∂2h2/∂z2= 0

The solution of the above equation yields the location of the water table h(x,y,z) which is
function of position and, for unsteady flow, a function of time. However, the location of
the water table is required (a priori) before one can proceed to solve the equation. The
difficulties associated with solution of this equation lead us to seek some
approximations. This is known as the Dupuit approximation.

qs
H1

H2

Actual water table Parabolic distribution

h = f (x)
h = f (x, z)

For one-dimensional flow:

∂2h2/∂x2 = 0

Integrating twice and applying the boundary condition:

h = H1 @ x = 0 & h = H2 @ x = L

h2 = [(H22 – H12 )/ L] x + H12

The discharge is found by employing Darcy’s law Q = -K (hx1) dh/dx. Differentiating:

2h dh/dx = [(H22 – H12) / L]

-2 Q / K = [(H22 – H12) / L]

Q = K/2L (H12 – H22)

Measured in L3 / time per unit width of aquifer.

69
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Example:

The upstream elevation of the water-table of the unconfined aquifer shown below is 85
meters above horizontal impermeable boundary and the elevation of the downstream
water-table is 74 meters. The width of the aquifer is 200 meters, the length is 5 km, and
the hydraulic conductivity of the aquifer is 8.357 m/day. Find the discharge across the
aquifer.

Water-table

85 m Cross sectional Area =


A = h x 200

74 m

Head h
5000 m
200 m

Solution:

Q = - K (h x b) dh / dx

Q ∫x = 0 → 5000 (dx) = - K b ∫h = 85 → 74 (h) dh


X= 5000 h=85
Qx│ =+Kb h2 / 2│
X=0 h=74

Q = ( 8.357 m/d) (200 m) [ 0.5 (852 – 742) / (5000 m) = (835.7) (1749)

= 292.33 m3/day

Verify the answer using the equation derived in previous page:

Q = K /2L [H21 – H22]

= (8.357 m/day) / (10000) [ 852 – 742 ] = (0.0008357)(7225 – 5476) (200)

= 292.33 m3/day OK

70
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Steady State Solution of Groundwater Equation (Radial Symmetry):

1) Steady Flow to A Well in Unconfined Aquifer (Radial Symmetry):

Figure below shows a well fully penetrating the saturated unconfined aquifer. The
assumption inherent here is that the aquifer is radially symmetric, homogeneous and isotropic.

Q Observation well

s r h
Assumed equipotential H
∆r
Surfaces (Dupuit
assumption)

Cylindrical Cut

Considering cylinder around the well extending from rw to R where rw is the radius of the
well and R is the radius of influence (which is defined as the distance from the well to
the point where drawdown is negligible), the linearized form of differential equation for
steady, radial flow in unconfined aquifers is defined from the following differential
equation:

∂2h/∂r2 + (1/r)∂h / ∂r = 0

Which is the radial form of Laplace equation ▼2 h = 0. The boundary condition can now
be stated as,

h = hw at: r = rw and: h = H at r = R

In the above: H is the static head before the start of pumping and R is the radius of
influence. From Darcy’s Law, the discharge across a cylinder (shown in the above
figure) becomes:

Qw = 2πr h K dh/dr Cross Sectional Area (cylinder)

= 2πr K d/dr (h2/2)

Employing the boundary condition h = hw @ r = rw and h = H at r = R

H2 – h2w = Q / π K ln (R/rw) = sw hw ≈ H

For small drawdown sw (drawdown at the well) , H2 – h2w = (H – hw) (H + hw) = sw (2H) The
Solution become,

sw = Q/2πT [ln (R/rw)]

71
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

where T is the known as the coefficient of transmissibility KH. Note that the equation
can only be applied to aquifers that are infinite in their lateral extension. To find the
drawdown between two points in the aquifer, the equation become,

s1 – s2 = Q/2πT [ln (r1/r2)]

The drawdown at any point in the unconfined aquifer is,

s = sw -Q/2πT [ln (r / rw)]

It is apparent from the above equation that, to obtain maximum discharge, the well
would have to penetrate to the impermeable boundary. However, this is not
economically feasible. Studies found that wells, which penetrate a depth greater than
two-thirds of the saturated zone, would not yield significantly more discharge.

b) Steady Flow to a Well in Confined Aquifers

Considering a cylinder around the well extending from Rw to R and bounded by


the upper and lower impermeable boundaries,

Qw = 2πr b K dh/dr Note: we substituted thickness b for h


Q
After integration, the equation for piezometric head become, b

H – h = Q/2πbK ln (R/r) or,

H – h = Q/2πT ln (R/r)

The above equation can be applied to any two points r1 and r2

s1 – s2 = Q/2πT [ln (r1/r2)]

Example:

72
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

A 0.5 meter well fully penetrates an unconfined aquifer of 100 meters in depth.
Two observation wells located 50 and 100 meters apart have drawdown of 5 meters and
4.5 meters. If K is 5 meters per day what is the discharge?
Solution:

h12 – h22 = Q / πK ln (r1 / r2)

h1 = 100 - 5 = 95, h2 = 9025

h2 = 100 – 4.5 = 95.5, h2 = 9120.25

9025 – 9120.25 = Q / (π) (5) ln (50/100) Then Q = 9525 x π x 5 x 0.6931 = 2158.54 m3/day

PW OW 1 OW 2

100 m

h1 h2

Example:

A 0.5 meter well is pumping from confined aquifer of 50 meter in depth at a rate of 1000
m3 / day. After a long time of pumping, the drawdown at the well is 4 meters and the
drawdown at r = 10 m is 3 meters. Find the hydraulic conductivity of the aquifer.

Solution:

s – sw = - (Q / 2πT ) [ln (r/rw)] = (1000 m3/d/ 2πT) ln (10/0.5)


3 – 4 = (1000 / 2πT) ln (20) Then: T = (1000) (2.996) / 4.28 = 699.93
Then K = 699.93 / 50 = 14 m/d

Pumping Near Hydro-Geologic Boundaries (Recharge Source)

Consider pumping around fully penetrating stream (recharge boundary). When


pumping occurs, the drawdown will increase and the cone of depression will expand
until it hits the recharge source. At this point on, the cone of depression cannot spread

73
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

beyond the recharge source and no drawdown will take place beyond this point. The
drawdown at any point in the system is calculated by placing an imaginary recharge
(production) well pumping from an infinite aquifer and placed at the exact opposite
distance to the recharge source. The recharge well operates simultaneously and at the
same pumping rate as the real well. Remember that after this point in time, the flow into
the well is no longer radially symmetric because the source of water is the stream.

Buildup due to recharge


Stream level Stream level
Qin

Qout

Drawdown
Due to pumping
with Cone of
Resultant cone Infinite aquifer Depression
Of depression (no Due to
Source) pumping
with
Infinite
aquifer (no
a Source)
-a

Recharge source

Recharge source

Water level
Static
Line
(non-
Pumping)

The solution of problems involving pumping near sources in an aquifer can be


illustrated as follows:

It is required to find the drawdown at any point in an aquifer for steady flow to a
well located at point P(x0,0). The line x = 0 is a contentious stream boundary infinite in
extent at y axis.

74
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Recharge boundary P (x,y)

Image well -Q ri r Pumping well


Q

(-x0 , 0) (x0 , 0)

Image Real
region region

The drawdown at any point in the real region in the aquifer P(x,y) is the sum of
drawdown of two wells, each operating in a fictitious infinite field. The equation of the
drawdown is the sum of the drawdown due to pumping well (+Q) and recharge well (-Q).
If r is the distance to the real well and ri is the distance to the imaginary well, then the
drawdown at any point is,

s(x,y) = (Q/2πT) ln (R/r) + (-Q/2 π T) ln (R/r i)

= (Q/2πT) ln (r i /r)

= (Q/4πT) ln {[ (x + x0)2 + y2] / [ (x - x0)2 + y2]}

where R is the radius of influence of the well. Note that the assumption here is that R >
x0 otherwise the recharge boundary will have no effect on drawdown. The superposition
in side view is illustrated by the first graph in the previous page.

The procedure illustrated in the above example is known as the method of images. Note
that the gradient of the head (or drawdown) is zero at any point in the recharge
boundary (line x = 0). If more than one recharge boundary exists in the system, the
method of superposition still applies and the total drawdown will be the sum of all
drawdown due to imaginary wells with distances ri to the point in question and the
drawdown to the pumping well.

s(x,y) = Σi = 1,n si + sPW

Pumping Near Hydro-Geologic Boundaries (Impermeable Boundary)

75
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Consider pumping around fully penetrating impermeable boundary. When pumping occurs,
the drawdown will increase and the cone of depression will expand until it hits the impermeable
boundary. At this point on, the cone of depression cannot spread beyond the impervious boundary
and the rate of drawdown accelerates. The drawdown is calculated by placing a fictitious pumping
(discharge) well placed at the exact opposite distance to the impervious boundary. The imaginary
discharge well operates simultaneously and at the same pumping rate as the real well. Remember
that, after this point in time, and just like the case in recharge boundary, the flow into the well is not
radially symmetric flow.

Buildup of Static line (no


drawdown due to Qout pumping)
impermeable
QOUT

Resultant cone Drawdown


Of depression Due to pumping with
Image well
with impermeable Infinite aquifer with
boundary no boundary)
Real region Image region
a -a

Impermeable Boundary

Water table
Static
Line
(no-
Pumping)

Impermeable
Boundary

The solution of problems involving pumping near impermeable boundary in an


aquifer can be illustrated as follows:

76
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

It is required to find the drawdown at any point in an aquifer for steady flow to a
well located at point P(x0,0). The line x = 0 is a contentious impermeable boundary
infinite in extent at y axis.

Impermeable boundary P (x,y)

ri r

Pumping Well (+Q) Pumping well (+Q)


x
(-x0 , 0) (x0 , 0)

Image Real
region region

The drawdown at any point in the real region in the aquifer P(x,y) is the sum of
drawdown of two wells, each operating in a fictitious infinite field. The equation of the
drawdown is the sum of the drawdown due to pumping well (+Q) and recharge well (-Q).
If r is the distance to the real well and ri is the distance to the imaginary well, then the
drawdown at any point is,

s(x,y) = (Q/2 π T) ln (R/r) + (Q/2 π T) ln (R/ri) = (Q/2 π T) ln (R2/rri)

= (Q/2 π T) ln { R2/ {[ (x - x0)2 + y2]1/2 [ (x + x0)2 + y2]1/2}

Where R is the radius of influence of the well. Note that the assumption here is that R >
x0 otherwise the impermeable boundary will have no effect on drawdown. The
superposition in side view is illustrated by the first graph in the previous page.

d) Image Well System:

77
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Method of images also applicable in a system of wells that is bounded by two


types of boundaries at angles less than 180 degrees. Some are shown in the following
illustrations,

O Real pumping well


o Image pumping well
X Image recharge well O. P (x,y)

(+b, -a)3
b
IWX PW O
-Q +Q a

I W X (-b, -a)2 I W 0 (b, -a)1


-Q +Q

Drawdown at any point in the real domain is,

sP = sr + s1 – s2 – s3
= (Q/2πT) [ln ( R/r) + ln (R/ri1) – ln (R/ri2) –ln (R/ri3)

= (Q/2πT) [ln ( ri2ri3 / rri1)

= (Q/2πT) {ln [(b+x)2 + (y+a)2]1/2 [(b+x)2 + (y-a)2]1/2 / [(x-b)2 + (a-y)2]1/2 + [(x-b)2 + (y+a)2]1/2

The equation becomes,

sP (x,y) = (Q/4πT) ln { [(b+x)2 + (y+a)2] [(b+x)2 + (y-a)2] / [(x-b)2 + (a-y)2] + [(x-b)2 + (y+a)2]}

78
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

0 Real pumping well . P (x,y)


o Image pumping well
x Image recharge well
PW
b
-Q x (-b , a)3 0 +Q
a

+Q o (-b , -a)2 -Q x (b , -a)1

sP = sr – s1 + s2 – s3
sP = = (Q/2πT) [ln ( R/r) - ln (R/ri1) + ln (R/ri2) – ln (R/ri3)

= (Q/2πT) [ln ( ri1ri3 / rri2)

0 Real pumping well


. P (x,y)
o Image pumping well
x Image recharge well
PW
b
+Q o (-b , a)3 0 +Q

-Q x (-b , -a)2 -Q x (b , -a)1

sP = sr – s1 – s2 + s3

79
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Transient Well Hydraulics


Groundwater flow in confined and unconfined aquifers is transient (variable with
time) when the piezometric surface or water table position changes with time. The
solution is obtained by solving the linearized form of Boussinesq equation, which
employs Dupuit assumption. In the following analysis, the aquifer is assumed
homogeneous, isotropic, for the case of confined aquifers, the thickness is constant,
and in both cases, storativity of the aquifer is constant. Furthermore, the release of
water from the aquifer is immediate upon decline of head. It is important to note that,
upon employment of Boussinesq equation, it is apparent that the restrictive nature of
Boussinesq equation is more pronounced in unconfined aquifers than in confined
aquifers.

The linearized form of differential equation of flow of groundwater in radial symmetry


was presented earlier as,

∂s/∂t = α [∂2s/∂r2 + (1/r)∂s / ∂r] s is the drawdown

The equation of drawdown in transient flow conditions becomes,

s = Q/4πT ʃ U→∞ e-U / u du and u = r2 S/4Tt

Or, in short

s = Q/4πT W (u)

which is the non-equilibrium equation describing transient flow of groundwater to a well


developed by Theis (1935).

The well function W (u) is can be expanded in an infinite series as follows,

W (u) = -0.5772 – ln u + u – u2/2.2! +u3/3.3! – u4/4.4! + ……………………

For small values of u (say u<0.01, i.e. for small r and/or large time), the W function can
be approximated by the first two terms and the equation can be approximated as,

s (r,t) = Q/4πT [ -0.5772 + ln(1/u)]

Substituting for u = r2 S/4Tt, the approximate equation become,

s (r,t) = Q/4πT ln (2.246Tt / r2S)

The above equation approximates the drawdown in both confined and unconfined
aquifers with S represents storage coefficient for confined aquifers and apparent
specific yield for unconfined aquifers. In addition, T would be = b K for confined aquifers
and = ĤK for unconfined aquifers where Ĥ represents an “average” saturated thickness.

80
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Observations Concerning Well Function Equation: s = Q/4πT W (u) , u = r2S/4Tt

 Transmissibility T: Effects the shape of the drawdown. If transmissibility is high,


the drawdown is narrow and deep. If the transmissibility is low, the drawdown is
wide and shallow.
 Storativity S: Effects the amplitude of the drawdown. The lower the storativity,
the deeper the drawdown.
 The well function equation developed above can be applied to unconfined
aquifers in the most restrictive sense. The assumptions inherent in the
application of this equation to unconfined aquifers are that gravity drainage is
instantaneous and no delayed yield occurs. The other assumption is that flow is
horizontal and drawdown is too small compared to the overall saturated
thickness of the unconfined aquifer. In this approach, which is by far the
simplest, is to use the same equation as the confined aquifer equation but with
different arguments. For instance, the transmissibility Kb is replaced by the
value KH where H either is the initial saturated thickness or “averaged”
thickness of unconfined saturated zone.
 The exact solution of the integral equation predicts that the cone of depression
around the well develops instantaneously and extends infinitely.
 Since u is a function of r, then as r → ∞, u → ∞ and W (u) → 0. This makes
s → 0 and for all practical purposes, the drawdown becomes negligible for a
finite radius. Mathematically, however, the equation suggests that the radius of
influence R grows infinitely with time.
 Since R is function of t1/2, the cone of influence expands rapidly initially and
slows down thereafter.
 The equation of R tells us that, given the same pumping conditions the cone of
influence is larger in aquifers with small S compared to those of large S. This
means that in an unconfined aquifer (which has much larger S than confined
aquifers), the cone of influence does not have to expand as fast as the cone of
influence in confined aquifers to account for the same value of Q.
 Physical limit of cone of influence is replenishment source (such as rivers, lakes
or sea).
 Mathematically, steady state conditions will never prevail because u is not
constant.
 A condition known as pseudo-steady state occur by setting u equal or less than
an arbitrary value of 0.01 if attention is restricted to regions around the well and
pumping takes place at sufficiently long time. Remember that pseudo-steady
state does not imply steady state conditions where s does not vary with time, it
rather imply that, at regions not far from the well, the rate of fall of the
piezometric surface or the water table is the same everywhere at this region and
the rate of change in drawdown is independent of distance r.Pseudo-Steady
state is defined by the formula:

s (r,t) = Q/4πT ln (2.246Tt / r2S)

The Transient Groundwater Equation:

81
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

s = Q/4 π T [W (u)]

W (u) = -0.5772 – ln u + u – u2/2.2! +u3/3.3! – u4/4.4! + …………………… u = r2 S/4Tt

For Psydo-Steady State: u ‹ 0.01 Then

s = Q/4πT [ - 0.5772 + ln(1/u)]

Values of u vs. W (u) (After Wenzel 1942):

u W(u) u W(u) u W(u) u W(u)


1.00E-15 33.96 9.00E-12 24.86 1.00E-07 15.24 9.00E-04 6.44
2.00E-15 33.27 1.00E-11 24.75 2.00E-07 14.85 1.00E-03 6.33
3.00E-15 32.86 2.00E-11 24.06 3.00E-07 14.44 2.00E-03 5.64
4.00E-15 32.58 4.00E-11 23.36 4.00E-07 14.15 3.00E-03 5.23
5.00E-15 32.35 5.00E-11 23.14 5.00E-07 13.93 4.00E-03 4.95
6.00E-15 32.17 6.00E-11 22.96 6.00E-07 13.75 5.00E-03 4.73
7.00E-15 32.02 7.00E-11 22.81 7.00E-07 13.6 6.00E-03 4.54
8.00E-15 31.88 8.00E-11 22.67 8.00E-07 13.46 7.00E-03 4.39
9.00E-15 31.76 9.00E-11 22.55 9.00E-07 13.34 8.00E-03 4.26
1.00E-14 31.66 1.00E-10 22.45 1.00E-06 13.24 9.00E-03 4.14
2.00E-14 30.97 3.00E-10 21.35 2.00E-06 12.55 1.00E-02 4.04
3.00E-14 30.56 4.00E-10 21.06 3.00E-06 12.14 2.00E-02 3.35
4.00E-14 30.27 5.00E-10 20.84 4.00E-06 11.85 3.00E-02 2.96
5.00E-14 30.05 6.00E-10 20.66 5.00E-06 11.63 4.00E-02 2.68
6.00E-14 29.87 7.00E-10 20.5 6.00E-06 11.45 5.00E-02 2.47
7.00E-14 29.71 8.00E-10 20.37 7.00E-06 11.29 6.00E-02 2.3
8.00E-14 29.58 9.00E-10 20.25 8.00E-06 11.16 7.00E-02 2.15
9.00E-14 29.46 1.00E-09 20.15 9.00E-06 11.04 8.00E-02 2.03
1.00E-13 29.36 2.00E-09 19.45 1.00E-05 10.94 9.00E-02 1.92
2.00E-13 28.66 3.00E-09 19.05 2.00E-05 10.24 1.00E-01 1.82
3.00E-13 28.26 4.00E-09 18.76 3.00E-05 9.84 2.00E-01 1.22
4.00E-13 27.97 5.00E-09 18.54 4.00E-05 9.55 3.00E-01 0.91
5.00E-13 27.75 6.00E-09 18.35 5.00E-05 9.33 4.00E-01 0.7
6.00E-13 27.56 7.00E-09 18.2 6.00E-05 9.14 5.00E-01 0.56
7.00E-13 27.41 8.00E-09 18.07 7.00E-05 8.99 6.00E-01 0.45
8.00E-13 27.28 9.00E-09 17.95 8.00E-05 8.86 7.00E-01 0.37
9.00E-13 27.16 1.00E-08 17.84 9.00E-05 8.74 8.00E-01 0.31
1.00E-12 27.05 2.00E-08 17.15 1.00E-04 8.63 9.00E-01 0.26
2.00E-12 26.36 3.00E-08 16.74 2.00E-04 7.94 1.00E+00 0.219
3.00E-12 25.96 4.00E-08 16.46 3.00E-04 7.53 2.00E+00 0.049
4.00E-12 25.67 5.00E-08 16.23 4.00E-04 7.25 3.00E+00 0.013
5.00E-12 25.44 6.00E-08 16.05 5.00E-04 7.02 4.00E+00 0.0038
6.00E-12 25.26 7.00E-08 15.9 6.00E-04 6.84 5.00E+00 0.0011
7.00E-12 25.11 8.00E-08 15.76 7.00E-04 6.69 6.00E+00 0.00036
8.00E-12 24.97 9.00E-08 15.65 8.00E-04 6.55 7.00E+00 0.00012

82
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

EXAMPLE

Well is being pumped at constant rate of 0.004 m3/s. The transmissibility of the aquifer is
0.0025 m2/s the distance to observation well is r = 100 meters and the storage coefficient
is 0.00087. Find the drawdown in the observation well after 20 hours of pumping using
the Theis well function and pseudo-steady state approximation and compare the
results.

Solution:

u = r2S /4tT = (100)2 (0.00087) / [(4)(20x3600)(0.0025) = 0.0121

From u vs. W(u) table @ u=0.0121 , W(0.0121 = 3.895

s = Q/4πT (3.895) = [0.004 / (4π)(0.0025)] [3.895] = 0.4959 m

Using the approximate solution s = Q/4πT [ -0.5772 + ln(1/u)]

s = (0.004) / [(4 π)(0.0025)] [-0.5772 + ln (1/0.0121] = 0.4886 m

The two answers are approximately the same because u is very small.

EXAMPLE:

After 2 hours of pumping in an aquifer, it was observed that the radius at which
drawdown is negligible is 400 meters. At what radius would the drawdown be negligible
after 5 hours of pumping? Assume pseudo-steady state prevail.

At pseudo-steady state, 1/u

s = Q/4πT [ -0.5772 + ln (4tT/R2S) ≡ Q/4πT [ln [(0.561)( 4tT/R2S)]

s = Q/4πT [ ln (2.246 (Tt / R2S))

0 = ln [(2.246 t / R2) (T/S)]

1 = (2.246) (2)/160000) T/S T/S = 2.81 x 10-5

For 5 hrs of pumping,

0 = ln [2.246 (5) / R2] (2.81 x 10-5) Then,

R2 = (5) (2.246) / (2.81 x 10-5) Then: R = 632.46 m

EXAMPLE:

A pumping well is bounded by a straight stream and a parallel impermeable


boundary as shown that are 20 meters apart. The well is located at the middle. Pumping
starts at Q = 1000 m3/d. If T = 500 m3/d , find the

83
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

drawdown at the well after 10 days of pumping. Assume R = 500 m and rPW = 0.5 m and
Sy = 0.1.

Image impermeable Image recharge

20m

PWi

Recharge Impermeabl
e

The transient drawdown equation is,

s = Q/4πT W(u), where,

u = r2S / 4Tt,

Taking four image wells from each side,

sT = sPW + (- siRW20 - siRW40 + siPW60 + siPW80 )LEFT + ( siPW20 - iRW40 – iRW60 + siPW80 )RIGHT

= sPW - 2 siRW40 + 2 siPW80, the rest cancel each other.

The drawdown at the well is,

sT = Q/4πT [ W(uPW) - 2 W(uiRW40) + 2 W(uiRW80)]

uPW = (0.5)2 (0.1) / (4)(500)(10) =0.00000125,

uiPW40 =(40)2 (0.1 / (4) (500)(10) = 0.0008

uiPW80 =(80)2 (0.1) / (4) (500)(10) = 0.032

The total drawdown become,

sT = (1000) / (4 π) (500) [13.03555 – (2) (6.5545) + (2) (2.8845)]

= 0.1592 [13.03555-13.109+5.769]

Drawdown at the well after 100 days of pumping: sT = 0.91 m

Aquifer Tests
Aquifer tests are field tests that are performed to determine field data under
controlled conditions. The outcome of the field tests are the hydrologic parameters of
the aquifer such as storage coefficient, apparent specific yield, hydraulic conductivity

84
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

and transmissibility of the aquifer. The obtained values of the tested aquifer can be used
for designing well field and predicting future drawdown. They can also be used for
assessing groundwater supply, and estimating inflow and outflow to and from
groundwater basins.

The outcome of aquifer properties obtained from field tests will eventually be compared
to the values obtained from theoretical considerations. For this reason, it is important
that elements such as boundary conditions, initial conditions and the physical
characteristics of the chosen sites match closely the ones assumed in theory. The other
important consideration is to minimize uncertainties associated with the selection of
pumping wells and the placement of observation wells. For example, data obtained from
partially penetrating wells are difficult and uncertain to analyze than the fully penetrating
wells. In addition, the proper choice of the number and the location of observation wells
would minimize uncertainties associated with measuring hydraulic parameters of the
aquifer.

In order to ensure that the water level properly represents the average
piezometric head below water table, the casing in the observation wells should be
perforated and should penetrate the entire saturated zone. In confined aquifers,
piezometer should be sealed properly in order to ensure against water transport from
one stratum to another.

During aquifer test analysis, the number and the appropriate spacing of
observation wells play an important part to insure the integrity of data collected.
According to Walton (1987), no less than three observation wells should be selected and
spaced at one logarithmic cycle from one another. Because the radius of influence
expands more rapidly in confined aquifers than in unconfined aquifers, observation wells
should be placed at greater distances from each other than in unconfined aquifers.

When hydro geologic boundary is present, and in order to minimize their effect,
pumping well should be placed at least one saturated thickness away from the boundary. In
addition, the observation wells should be spaced along a line through the production well and
parallel to the boundary. This is made to minimize the effect of the boundary on distance-
drawdown data.

Finally, the hydrologic data collected for unconfined aquifers using aquifer test analysis
represent mean values of that portion of aquifer bounded by the initial saturated zone and the of
cone of depression and does not represent the entire saturated thickness. Furthermore, the best
estimates of the aquifer properties can be obtained from tests that are conducted over a long
time when delayed drainage is not a factor influencing the apparent specific yield.

a) Analysis of Aquifer Test Data Using Theis Solution:


This method utilizes type curve matching technique. This method involves matching
logarithmic time-drawdown or distance-drawdown graphs obtained from the field measured
values of time, drawdown or distance, drawdown data with the theoretical logarithmic well
function curves (type curves) of W(u) vs. u. The procedure is illustrated as follows:

85
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

1. At a given time or at a given location obtain measured field data of drawdown


and plot drawdown s vs. r2 / t on a log-log paper.

2. Plot “type” curve of W(u) versus u choosing appropriate cycle(s) on a log-log


paper of the same size.

3. Super-impose the two plots data by keeping the coordinate axis of the two
curves parallel until best fit is obtained.

4. Select any arbitrary point in the graph. Read the values of W(u) *, u* and the
corresponding values of s* and (r2/t)*

5. The values of T and S are calculated using the formulas: T = Q W(u)*/4πs* and
S = 4Tu*/(r2/t)*

W(u) w(u*)*
s*

r2/t*

r2/t
u* u Log-Log Graphs

b) Analysis of Aquifer Test Data Using Cooper-Jacobs Method


It was noted by Cooper and Jacob (1946) that for small u (large values of t or
small values of r), the non-steady equation for s become,

s (r,t) = Q/4πT (0.5772 – ln r2S/Tt)

or, in terms of decimal log scale, the equation become,

s (r,t) = 2.303 Q/4πT log (2.246Tt / r2S)

Plotting the drawdown s versus the logarithm of time t would form a straight line. The x
axis intercept is at t = t0 @ s = 0, therefore:

0 = 2.303 Q/4πT log (2.246Tt0 / r2S)

For this to happen, 2.246Tt0 / r2S must = 1


Therefore:

86
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

S = 2.246Tt0 / r2
=1
and the slope over one cycle is:

s (r,t) 10t - s (r,t) t = ∆s = 2.303 Q/4πT log [(2.246T10t / r2S)/ 2.246Tt / r2S)]

Therefore:

T = 2.303 Q/4π ∆s

The procedure is summarized as follows:

1. For stationary reading, measure s at different times.

2. Plot s vs. log t on a semi-log paper.

3. Find the slope by reading the difference between two points across one log
cycle ∆s*.

4. Find the horizontal intercept t0* on the log t axis.

5. The values of S and T are calculated from the formulas:

S = 2.246Tt0* / r2, and

T = 2.303 Q/4π ∆s*.

An alternative method is to measure s at different observation wells (different r) at given time,


plot s versus r on logarithmic paper, find the slope across one cycle (∆s*) and find the intercept
r0* on the log r axis. The values of S and T are calculated from the formulas: S = 2.246Tt / r02 and
T = 2.303 Q/4π∆s*.

∆s

Semi-log graph
t t0

87
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Note that s versus t is a straight line as long as the assumption of small value of u is
still valid. However, it is apparent that when time is small, this assumption can no
longer be valid as shown in the above chart. It is also important to note that using
non-equilibrium equation is valid for unconfined aquifers as well as long as the
measured drawdown is small in relation to the overall saturated thickness of the
unconfined aquifer.

Example:

In order to Illustrate the use of the methods discussed above, the following is a data
collected from an observation well during a test in unconfined aquifer in Fort
Collins, Colorado (McWhorter & Sunada 77):
s (m) 0.025 0.050 0.055 0.110 0.170 0.180 0.220 0.300 0.370 0.450 0.53

r2/t 88.9 53.3 47.1 25.0 16.7 15.1 11.1 6.25 4.12 2.47 1.55

s (m) 0.620 0.640 0.650

r2/t 0.98 0.82 0.78

Plotting W(u) versus u, the coordinates of match point W(u) = 1.0 u = 0.1 s =
0.183 and r2 / t = 6.2 then T = (1.872)(1.0) / 4 π (0.183) = 0.814 m2/min and Sya =
(4) (0.814) (0.1)/ 6.2 = 0.053

0.01 0.1 1.0


10.0

1.0 W(u)

1.0

0.1

Match
Point

0.1

0.01

r2/t 1.0 10.0 100.0

Example:
Data collected during a test of a confined aquifer by U.S. Geological Survey is as
follows:

88
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Time: (min): 1 2 3 4 5 6 8 10 50

DD s (m): 0.2 0.3 0.370 0.415 0.450 0.485 0.530 0.570 0.850

Time: (min): 60 80 100 120 150 180

DD s (m): 0.875 0.925 0.965 1.000 1.045 1.070

r = 61 m and Q = 1.894 m3 /min

Plotting the given data on a semi log paper,

1.2

S
(m)

0.8

∆s = 0.4 m
Per Log
cycle
0.4

1 t t0 = 0.4 min 10 100


0.0

The slope of the line is ∆s = 0.4, then

T = (2.303) (1.894) / 4π (0.4) = 0.868 m2 / min

The extrapolated t at s = 0 is 0.4 minute, then

s = (2..246) (0.868) (0.4) / (61)2 = 2 x 10-4

EXAMPLE:

89
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Calculate the limit of the pseudo-steady state region around the well if Q = 100 m3 / hr, S
= 0.09, T = 36 m2 / hr and t = 10 hrs.

r2 / 4αt = r2 / 4 (T/S)t
= 0.01 then
r = [(0.01)(4)(36/0.09)(10)]1/2
= 12.65 m.

The Pseudo-steady state does not apply beyond this limit

Drawdown with Variable Pumping Rates:


The linearity principle of groundwater equation allows for the application of the
principle of superposition of drawdown resulting from variation of pumping rates. The
principle of superposition also applies to drawdown recovery following well shutdowns.
If amount of water pumped changes from Q1 to Q2, the resulting drawdown is described
by the following equation,

s = (Q1/4πT) W(r2S/4Tt) + (Q2 – Q1) W [ r2S/4T (t-ti)] for t>ti

Or, in general,

s = 1/4πT Σ ∆Qii+1 W [r2S/4T(t-ti )]

The equation states that the resulting drawdown is equal to the drawdown from t = 0 to t
= t2 with Q = Q1 plus drawdown resulting from an “imaginary” well pumping at a rate of
Q = ∆Q placed in the same position and pumping from t = t1 to t = t2.

90
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Q2

Q3
Q1

t2

t4
t’
t1 t’’ t’’’ t3

DD due Q1 @ t’ DD due Q2 – Q1@ t” DD at t’’’ due to – Q2 Recovery

If Q2 is zero then, s = (Q/4πT) W [ r2S/4T (t-ti)]

If Q2 is zero and r2S / 4t T < 0.01 then s = (Q/4πT ln [t /(t-t1)]

ti t

Buildup Recovery

91
King Fahd University of Petroleum & Minerals Dr. Rashid Allayla

Example:

A well discharging a confined aquifer with Q = 40.2 ft3/minute. The aquifer


transmissibility is 2270 ft2/day and its storage coefficient is 4x10-4. The pumping
lasted for 10 days and then shut down. Find the drawdown after: a) 15 days and 1
month.

Solution:

Drawdown after 15 days:

s = Q/4πT W(r2S/4T(10)-Q/4πT W(r2S/4T(15-10) =Q/4πTW[(0.25)(0.0004)/[(4)(2270)(10)]

- Q/4πTW[(0.25)(0.0004) [4π(2270)] / [(4)(2270)(5)]


-
= (40.2)(60x24) / [4π(2270)] W[(1.1x10-9) – W(2.2x10-9)]

From table: W(1.1 x10-9) = 20.08


W(2.2 x 10-9) = 19.37
Then: s = 6.3753 (20.08-19.37) = 4.53 ft

92

Potrebbero piacerti anche