In power engineering, a one-line diagram or single-line diagram (SLD) is a simplified notation for
representing a three-phase power system. The one-line diagram has its largest application in power
flow studies. Electrical elements such as circuit breakers, transformers, capacitors, bus bars, and
conductors are shown by standardized schematic symbols.
Balanced systems
The theory of three-phase power systems tells us that as long as the loads on each of the three
phases are balanced, we can consider each phase separately. In power engineering, this
assumption is often useful, and to consider all three phases requires more effort with very little
potential advantage. An important and frequent exception is an asymmetric fault on only one or two
phases of the system.
A one-line diagram is usually used along with other notational simplifications, such as the per-unit
system.
A secondary advantage to using a one-line diagram is that the simpler diagram leaves more space
for non-electrical, such as economic, information to be included.
Unbalanced systems
When using the method of symmetrical components, separate one-line diagrams are made for each
of the positive, negative and zero-sequence systems. This simplifies the analysis of unbalanced
conditions of a polyphase system. Items that have different impedances for the different phase
sequences are identified on the diagrams. For example, in general a generator will have different
positive and negative sequence impedance, and certain transformer winding connections block zero-
sequence currents. The unbalanced system can be resolved into three single line diagrams for each
sequence, and interconnected to show how the unbalanced components add in each part of the
system.
How to calculate and draw a single line diagram of the three-phase, 60-Hz system
power system with generators, motors, transformers and lines.
Calculation Procedure
1. Identify the Appropriate Symbols
For electric power networks an appropriate selection of graphic symbols is shown
in Figure 1 (common power symbols used in single line diagrams):
Figure 3 – Identification for wye-connected generator or motor. (a) Solidly grounded. (b)
Grounded through an inductance. (c) The transformer is identified as being delta-wye, with the
wye side solidly grounded.
Per-unit method of solving of 3-phase
problems
For the system shown in Figure 4, draw the electric circuit or reactance
diagram, with all reactances marked in per-unit (p.u.) values, and find the
generator terminal voltage assuming both motors operating at 12 kV, three-
quarters load, and unity power factor.
Figure 4 – Single line diagram of electric-power system supplying motor loads. Specifications
are given in above table.
Calculation Procedure in 8 steps
1. Establish Base Voltage through the System
By observation of the magnitude of the components in the system, a base value
of apparent power S is chosen. It should be of the general magnitude of the
components, and the choice is arbitrary. In this problem, 25,000 kVA is chosen
as the base S, and simultaneously, at the generator end 13.8 kV is selected as
a base voltage Vbase.
The base voltage of the transmission line is then determined by the turns ratio of
the connecting transformer:
(13.8 kV)(69 kV / 13.2 kV) = 72.136 kV
The base voltage of the motors is determined likewise but with the 72.136
kV value, thus:
(72.136 kV)(13.2 kV / 69 kV) = 13.8 kV
The selected base S value remains constant throughout the system, but the
base voltage is 13.8 kV at the generator and at the motors, and 72.136 kV
on the transmission line.
For motor A:
X”A = (0.15 p.u.) (25,000 kVA / 15,000 kVA) (13.0 kV / 13.8 kV) = 0.222 p.u.
2
For motor B:
X”B = (0.15 p.u.)(25,000 kVA /10,000 kVA)(13.0 kV / 13.8 kV) = 0.333 p.u.
2
Figure 5 – Single line reactance circuit diagram (reactances shown on a per-unit basis)
7. Calculate Operating Conditions of the Motors
If the motors are operating at 12 kV, this represents 12 kV/13.8 kV = 0.87 per-
unit voltage. At unity power factor, the load is given as three-quarters or 0.75
p.u.
Thus, expressed in per unit, the combined motor current is obtained by using the
equation:
Iper unit = per-unit power/per-unit voltage = 0.75/0.87 = 0.862 ∠0° p.u.
8. Calculate the Generator Terminal Voltage
The voltage at the generator terminals is:
Related Calculations
In the solution of these problems, the selection of base voltage and apparent
power are arbitrary. However, the base voltage in each section of the circuit must
be related in accordance with transformer turns ratios.