Sei sulla pagina 1di 14

FOR APPROVAL

A 01.OCT.2019 SP DV ITN FOR APPROVAL


REV DATE PREPARED CHECKED APPROVED STATUS
Owner

Owner’s Engineer

Contractor

Sub-Supplier

Project

JAWA 9 & 10 COAL FIRED STEAM POWER PLANT


Document Title

DESIGN CRITERIA – WATER TREATMENT PLANT


Document Type
■ Basic Engineering Document □ Detail Engineering Document □ Vendor Document □ Other

Document No.

J910-DD02-P0GDF-125134
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134

RECORD OF REVISION
Rev. Date Page Affected Description of Revision

A 03.OCT.2019 First Issue

Rev.A 2 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134

CONTENTS

1. GENERAL ............................................................................................................................ 4
2. BACKGROUND .................................................................................................................. 4
3. PROCESS DESCRIPTION ................................................................................................ 4
3.1. CLARIFICATION SYSTEM ............................................................................................. 4
3.2. DESALINATION SYSTEM ............................................................................................... 5
3.3. DEMINERALISATION SYSTEM .................................................................................... 6
3.4. REMINERALISATION SYSTEM .................................................................................... 6
4. CODES AND STANDARDS ............................................................................................... 6
5. DESIGN CRITERIA ........................................................................................................... 7
5.1. CLARIFICATION SYSTEM ............................................................................................. 7
5.2. DESALINATION SYSTEM ............................................................................................... 7
5.3. DEMINERALISATION SYSTEM .................................................................................. 12
5.4. REMINERALISATION SYSTEM .................................................................................. 13
5.5. SEA WATER ANALYSIS ................................................................................................ 13
6. PERFORMANCE GUARANTEE.................................................................................... 14
7. REFERENCE ..................................................................................................................... 14

Rev.A 3 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134

1. GENERAL
This document provides in brief the design criteria for the Water Treatment Plant that will treat the sea
water for plant requirement of Jawa 9&10 2x1000 MW coal fired steam power plant.

The intent of this design criteria is to cover the basic design criteria for “Water Treatment Plant.” A
brief description and salient feature of the various sub system are defined here for the basis of design.

2. BACKGROUND

This Plant will be located on a site in Suralaya, Cilegon City, Banten Province, Indonesia. This Plant
will be consisting of two (2)-Unit Ultra Super Critical Coal Fired Steam Power Plant including
associated infrastructure for coal supply and grid connection with a total nominal Plant capacity of 2 x
1000 MW (net)

3. PROCESS DESCRIPTION

The purpose of the water treatment plant is to produce demineralized water through UF-RO-EDI units.
Settlement basin will be provided as a pretreatment to the water treatment plant. The water treatment
plant shall be common for both units of 1000 MW.
The water treatment plant will be sized for the water requirement of the complete 2x1000 MW plant
such as Service water requirement, Potable water requirement, and DM water requirement. The
treatment plant will consist of the following
1) Clarification system
2) Desalination system
3) Demineralization system
4) Remineralization system
The clarification system and desalination system will cater to the complete requirement of the plant.
The Demineralization system will cater to the requirement of the DM water requirement. The
remineralization system will cater to the requirement of the potable water requirement of the plant.

The scope of the water treatment plant starts at the inlet of the Lamella type clarifier and ends at the
inlet of the DM water storage tank.

3.1. CLARIFICATION SYSTEM

2x100% Seawater makeup pump (not in the scope of WTP Package) will be provided. This pump will
take suction from seawater intake area and pump the water to 2x 100% settlement basin. Settlement
basin is provided to remove the suspended solids and silt in the basin by gravity. The settlement basin
shall be two pass with bottom slope arrnagment. Desilted seawater will be collected in the pump
chamber.

Rev.A 4 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134

3.2. DESALINATION SYSTEM

2x100% MMF feed water pumps will be provided which will take suction from the pump chamber in
the settlement basin and pump to 3x50% Multi Media Filter (MMF). Sodium Hydroxide and Ferric
Chloride (FeCl3) will be dosed at the discharge of MMF feed pump. MMF is used for removal of
suspended solids, turbidity and some parts of colour and odour from water. During filtration process
largest particles are filtered by filter media. The type of filter media used in this filter will be sand,
anthracite and gravel. The type of filter internal will be bed plate nozzle or head and laterals.

The outlet water from the MMF will be fed to 2x100% Ultra Filtration system (UF). The UF will
remove the finest impurities retained after the filter. The UF system shall consists of the following
items:
a) 2x100% Ultrafiltration system
b) 2x100% UF air blowers
c) 2x100% UF backwash pumps
d) CIP System.

The filtered water from the ultrafiltration system will be stored in the Filtered water storage tank. The
UF backwash pumps will take suction from this tank for backwashing of UF System. The filter
backwash pump will be provided for backwashing of multimedia filter. The filter backwash pump will
take suction from filtered water storage tank. A CIP system will be provided for cleaning of the
ultrafiltration membrane. The recovery of the UF system will be 95%.

2x100% SWRO feed Pump will be provided which will take suction from Filtered water storage tank
and send the water to 2x100% Micron Cartridge Filter. 3x100% SWRO high pressure pump will pump
the water to 2x100% Seawater Reverse Osmosis (SWRO) units. High pressure energy in the
concentrate (Brine) is recovered through 2x100% Turbo charger and transferred the energy to SWRO
membrane feed stream. The recovery of the SWRO units will be 40%. A portion of permeate from the
SWRO membrane is transferred to the Service / fire water storage tank and potable water storage tank
after remineralization. Antiscalant dosing system, SBS dosing system and sulphuric acid dosing system
will be provided for the SWRO system.

Remaining portion of the permeate from SWRO will be transferred to 1x100% SWRO permeate water
storage tank. 2x100% BWRO feed water pumps will take suction from SWRO permeate water storage
tank and send the water to 2x100% Micron Cartridge Filter. 3x100% BWRO high pressure pump will
pump the water to 2x100% BWRO Unit. Caustic dosing and Antiscalant dosing will be done at the
inlet of the BWRO unit. A common CIP/CEB system will be provided for both SWRO and BWRO
Units. The recovery of the BWRO units will be 85%.

Rev.A 5 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134

3.3. DEMINERALISATION SYSTEM

The permeate from the BWRO will be stored in BWRO permeate storage tank. 2x100% EDI feed
pump will take suction from the BWRO permeate water storage tank and pump to 2x100% EDI units.
The recovery from the EDI units will be 95%. The EDI unit will be flushed out automatically based on
the preset timings from the PLC.

3.4. REMINERALISATION SYSTEM


A portion of desalinated water from the SWRO permeate is stored in the service / fire water storage
tank after remineralization which will be pumped to service water, fire water requirements by
dedicated water transfer pumps. SWRO permeate water is also taken to potable water storage tank for
potable purpose after remineralization.

Calcium bicarbonate and sodium bicarbonate dosing are provided for enriching the minerals in service
water. Further, NaOCl dosing is provided for the potable water as disinfectant along with Calcium
bicarbonate and sodium bicarbonate dosing. The remineralization plant will produce water which will
confirm to US Federal (EPA) drinking water standards or International Finance Corporation’s
Environmental, Health, and Safety Standards.

4. CODES AND STANDARDS

The water treatment plant will be designed in accordance with the latest edition of following codes and
standards.
• American Iron and Steel Institute (AISI)
• American Water Works Association (AWWA)
• American Society for Testing of Material (ASTM)
• American National Standard Institute (ANSI)
• American Society of Mechanical Engineers (ASME)
• American Society for Testing and Materials (ASTM)
• American Petroleum Institute (API)
• American Welding Society (AWS)
• British Standards Institution (BS)
• German Standardization Institute (DIN)
• Hydraulic Institute Standard (HIS)
• Japan International Standard (JIS)
• Indonesian National Standards (SNI)
• International Standards Organization (ISO)
• International Electritechnical Commission (IEC)

Rev.A 6 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134
5. DESIGN CRITERIA

The capacities indicated in this section are minimum capacity as per the contract, However the same
will be finalized based on water requirement for the plant and the regeneration / backwash water
requirement as per the final selected vendor during detail engineering.

Water treatment plant will be sized considering the following


a) To supply DM plant for generating DM Water required for 2 x 1000 MW units.
b) To supply service water for the complete plant.
c) To supply potable water requirement for the complete plant.

5.1. CLARIFICATION SYSTEM

Two (2x100%) Seawater Makeup pump will be provided at the seawater intake area. This pump will
supply the water to the water treatment plant. The pump discharge will be of above floor discharge and
driven directly by constant speed cage induction motors.

Name : Seawater makeup pump


Qty : 2x100%
Type : Vertical wet pit
Material of construction : SS316L (with Cathodic
Protection).

Seawater make up pump will discharge the water to the 2x100% settlement basin for settlement. The
settlement basin shall be two pass with bottom slope arrnagment.

Name : Settlement basin


Qty : 2x100%
Material of construction : RCC

Desilted seawater will be collected in the pump chamber.

5.2. DESALINATION SYSTEM

Two (2x100%) MMF Feed pump will pump the water from the pump chamber in the settlement basin
to 3x50% Multimedia Filter. The material of construction for casing, impeller and shaft for the MMF
Feed pump will be of Duplex stainless steel.

Name : MMF Feed pump


Qty : 2x100%

Rev.A 7 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134
Type : Vertical wet pit
Material of construction : Duplex Stainless steel

The MMF will be of horizontal cylindrical type. The filtration velocity will be of 10-15 m3/hr/m2. The
filter media will be Sand, anthracite and gravel. The material of construction for the shell will be
carbon steel with rubber lining.

Name : Multi Media Filter


Qty : 3x50%
Type : Horizontal, cylindrical
Material of construction : Carbon Steel with rubber lining

Filtered water from the MMF outlet will be fed to 2x100% Ultra filtration membrane. UF will remove
the finest impurities before sending to RO system. The recovery from UF membrane will be
approximately 95%. The outlet from UF will be stored in 1x100% filtered water storage tank. 2x100%
Filter backwash pump will be provided for backwashing of multimedia filter. The filter backwash
pump will take suction from the filtered water storage tank. 2x100% Filter backwash blower will be
provided for multimedia filter

Name : Filter backwash pump


Qty : 2x100%
Type : Horizontal Centrifugal
Material of construction : Duplex Stainless steel

Name : Filter backwash blower


Qty : 2x100%
Type : Horizontal Centrifugal
Material of construction : Carbon steel or equivalent.

Name : Ultra-Filtration
Qty : 2x100%
Recovery : 95%
Material of construction
Shell : PVC or equivalent.
Membrane : PVD (Polyvinylidene Fluoride) or
equivalent

Name : Filtered water storage tank


Qty : 1 no.
Material of construction : RCC.

Rev.A 8 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134

2x100% UF backwash pump will be provided for backwashing the UF membrane. This pump will take
suction from filtered water storage tank and will be of Horizontal centrifugal type and the Material of
construction will be of Duplex Stainless steel.

Name : UF Backwash Pump


Qty : 2x100%
Type : Horizontal Centrifugal.
Material of construction : Duplex Stainless Steel

2x100% SWRO feed Pump will be provided which will take suction from the filter water storage tank
and pump to SWRO system through 2 x 100% micron cartridge filter.

Name : SWRO feed Pump


Qty : 2x100%
Type : Horizontal Centrifugal.
Material of construction : Duplex Stainless Steel

Name : Micron Cartridge Filter for SWRO


Qty : 2x100%
Type : Vertical, Cylindrical.
Material of construction : Casing: Carbon steel with Rubber
lining
Filter Element: PP

3x100% SWRO High pressure pumps will be provided which will pump the water from the MCF
outlet to SWRO unit. 2 x100% SWRO units are provided to reduce the salt concentration which will be
the feed water for BWRO units.

Name : SWRO high pressure Pump


Qty : 3x100%
Type : Horizontal Centrifugal.
Material of construction : Duplex Stainless Steel

Name : SWRO Membrane


Qty : 2x100%
Type : Spiral Wound
Capacity : 150 m3/h (Minimum)
Recovery : 40% (Minimum)
Material of construction

Rev.A 9 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134
Pressure Vessel : FRP or equivalent
Membrane : Polyamide or equivalent

Name : SWRO permeate water storage tank


Qty : 1 no.
Capacity : Will be sized for one hour
requirement of the normal
operation of the plant.
Material of construction : Mild Steel with Epoxy paint

SBS dosing and Antiscalant dosing will be done at the inlet of the SWRO units. For this purpose,
1x100% SBS dosing tank with 2x100% SBS dosing pump and 1x100% Antiscalant dosing tank with
2x100% antiscalant dosing pump will be provided.

The permeate water from the SWRO units will be stored in SWRO permeate water storage tank. 2 x
100% BWRO feed pump will be provided which will take suction from SWRO permeate tank and send
to 2x100% Micron Cartridge Filter. 3x100% BWRO High pressure pump will be provided which will
pump the water from MCF outlet to 2x100% BWRO Units.

Name : BWRO feed Pump


Qty : 2x100%
Type : Horizontal Centrifugal.
Material of construction : SS 316 or equivalent

Name : Micron Cartridge Filter for BWRO


Qty : 2x100%
Type : Vertical, Cylindrical.
Material of construction : Casing: Carbon steel with Rubber
lining
Filter Element: PP

Name : BWRO high pressure Pump


Qty : 3x100%
Type : Horizontal Centrifugal.
Material of construction : SS 316 or equivalent.

Name : BWRO Membrane


Qty : 2x100%
Type : Spiral Wound
Recovery : 85% (Minimum)

Rev.A 10 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134
Material of construction
Pressure Vessel : FRP or equivalent
Membrane : Polyamide or equivalent

Name : BWRO permeate water storage


tank
Qty : 1 no.
Capacity : Will be sized for one hour
requirement of the normal
operation of the plant.
Material of construction : Mild Steel with Epoxy paint

A common CIP system will be provided for both SWRO and BWRO units. The CIP system will be
provided with 2x100% Flushing pump, 1x100% CIP Tank, 2x100% CIP Pump and 1x100% CIP
micron cartridge filter.

Name : Flushing Pump


Qty : 2x100%
Type : Horizontal Centrifugal.
Material of construction : SS 304 or equivalent.

Name : CIP Tank


Qty : 1x100%
Type : Vertical, Cylindrical.
Material of construction : FRP or equivalent.

Name : CIP Pump


Qty : 2x100%
Type : Horizontal Centrifugal.
Material of construction : SS 316 or equivalent.

Name : CIP Micron Cartridge Filter


Qty : 2x100%
Type : Vertical, Cylindrical.
Material of construction : Casing: Carbon steel with Rubber
lining
Filter Element: PP

Rev.A 11 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134
5.3. DEMINERALISATION SYSTEM

2x100% EDI feed pump will be provided which will take suction from the BWRO permeate water
storage tank and pump to 2x100% EDI units.

Name : EDI Feed Pump


Qty : 2x100%
Type : Horizontal Centrifugal.
Material of construction : SS 304 or equivalent.

Name : EDI Unit


Qty : 2x100%
Type : Tubular / Plate
Capacity : 75 m3/h (Minimum)
Recovery : 95%
Material of construction : SS / FRP

The Demineralized water from the EDI unit will be stored in 1x100% DM Water storage tank (Not in
the scope of WTP package).

Name : DM Water Storage Tank


Qty : 1x100%
Type : Vertical, Cylindrical.
Capacity : Sized for 72 hours requirement of
full load normal operation of the
plant.
Material of construction : MS Epoxy painted.

BULK ACID AND ALKALI STORAGE REQUIREMENTS:

1x100% bulk sulphuric acid Storage tank will be provided for storing the sulphuric acid. The tank will
be of horizontal centrifugal type and the material of construction will be Carbon steel. The bulk storage
tank will be sized for 10 days requirement of the water treatment plant. Fume scrubbers will be
provided for bulk acid storage tank. 2x100% sulphuric acid unloading cum transfer pump will be
provided for unloading the acid and transferring the same to dosing tank.

1x100% sulphuric acid dosing tank will be provided for dosing the acid. The type of the tank will be
vertical, cylindrical and will be sized for one day requirement. 2x100% sulphuric acid dosing pumps
will be provided. This pump will be of reciprocating type.

Rev.A 12 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134
1x100% bulk caustic Storage tank will be provided. The tank will be of vertical centrifugal type and
the material of construction will be FRP or equivalent. The bulk storage tank will be sized for 10 days
requirement of the water treatment plant. 2x100% caustic unloading cum transfer pump will be
provided for unloading the caustic and transferring the same to dosing tank.

1x100% caustic dosing tank will be provided for dosing the caustic. The type of the tank will be
vertical, cylindrical and will be sized for one day requirement. 2x100% caustic dosing pumps will be
provided. This pump will be of reciprocating type. The pump will be of PVDF with PTFE diaphragm
material. Safety shower and eye washer will be provided at suitable locations.

1x100% Instrument Air receiver and 1x100% Service air receiver will be provided for WTP area to
store the instrument air and service air respectively. These tanks will be of vertical, cylindrical and the
material will be Carbon steel with epoxy painting or equivalent.

5.4. REMINERALISATION SYSTEM

Remineralization chemicals will be added to the outlet water from the SWRO before storing in service
water storage tank. This water will be used for plant service water and potable water requirement.

1x100% sodium bicarbonate injection tank will be provided along with 2x100% sodium bicarbonate
dosing pump for injecting the chemicals at the inlet of the service water storage tank.

1x100% Calcium chloride injection tank will be provided along with 2x100% calcium chloride dosing
pump for injecting the chemical at the inlet of the service water storage tank.

Necessary injection quills and static mixer will be provided for injection and proper mixing of
chemicals.

5.5. SEA WATER ANALYSIS

Sl.
Parameter Unit Value
No.
1. pH @ 25 ºC 8.3
2. Temperature Deg C 30.5
3. Total Dissolved Solids mg/L 33662
4. Total Suspended Solids mg/L 123
5. Total Hardness mg/L 6025
6. Carbonate Hardness mg/L <1
7. Conductivity µS/cm 60650
8. Free Carbon Dioxide mg/L <1
9. Dissolved silica mg/L <1

Rev.A 13 of 14
DESIGN CRITERIA – WATER TREATMENT PLANT
J910-DD02-P0GDF-125134
Sl.
Parameter Unit Value
No.
10. Total Alkalinity (as CaCO 3) mg/L 105
11. Methyl orange (MO) alkalinity (as CaCO 3) mg/L 128
12. Phenolphthalein alkalinity (as CaCO 3) mg/L <1
13. COD mg/L 83
14. Potassium (K) mg/L 280
15. Sodium (Na) mg/L 10132
16. Calcium (Ca) mg/L 343
17. Magnesium (Mg) mg/L 1255
18. Iron (Fe) mg/L <0.01
19. Aluminum (Al) mg/L 0.01
20. Ammonium (NH4) mg/L <0.1
21. Barium (Ba) mg/L 0.028
22. Stronsium (Sr) mg/L 5.3
23. Chloride (Cl) mg/L 18659
24. Sulfate (SO4) mg/L 2865
25. Bicarbonate (HCO 3) mg/L 128
26. Carbonate (CO3) mg/L <1
27. Hydroxide (OH) mg/L <1
28. Nitrate (NO3) mg/L <0.01
29. Nitrite (NO2) mg/L <0.005

6. PERFORMANCE GUARANTEE

The guaranteed water quality at the outlet of the EDI units will be as given below:

Conductivity : less than 0.2 micro S/cm at 25° C


Total silica : less than 0.02mg/l as SiO2
Total hardness : Less than 0.0005 mmol/l *
Sodium : Less than 0.020 mg/l *
* These parameters will be tested at Laboratory

7. Reference

Plant water balance diagram – J910-XG07-P0GHE-125001.


P&ID – Water treatment system - J910-XG02-P0GDF-125137

Rev.A 14 of 14

Potrebbero piacerti anche