Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
(GEN. CIVIL) 0318-000-16-47-DB-01 Rev. A
Page 2 of 8
CONTENTS
1.0 SCOPE
4.0 FENCING
8.0 PITCHING
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
(GEN. CIVIL) 0318-000-16-47-DB-01 Rev. A
Page 3 of 8
1.0 SCOPE
1.1 This document covers engineering design basis for General Civil works such as site
grading, fencing, roads, pavements, storm water drainage, water supply, waste
collection & disposal system for Despatch terminal (DT), Sectionalising Valve (SV)
stations, Intermediate Pigging stations (IP), Tap-off Points (TOP) etc.
2.1 Civil works & Roads: Indian Standards (IS) and Indian Road Congress (IRC)
Codes
2.2 Water services: Manual on water supply and treatment (Published by Ministry
of works and housing, Delhi)
2.4 OISD-STD-117 (Fire Protection Facilities for Petroleum Depots and Terminals and
Pipeline installations).
OISD-STD-118 (Layout for Oil and Gas Installation)
OISD - 163 (Process Control Room Safety) For Blast resistant Control room
3.1 The Overall Plot Plan shall be developed based on good engineering practice &
meeting requirement of statutory bodies.
3.2 Additionally the Overall Plot Plan shall also meet the requirement of OISD norms.
3.3 The various statutory approvals shall be obtained with the Owner’s assistance as
and when required.
4.0 FENCING
4.1.1 Intermediate Pipeline installation coming on route i.e. SV, IP, and TOP etc.
- 1.5m high chain link fencing with additional 0.5m high barbed wire fencing
over 0.5m high Brick masonry wall.
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
(GEN. CIVIL) 0318-000-16-47-DB-01 Rev. A
Page 4 of 8
5.1 All the tree roots and vegetation shall be grubbed up minimum 150 mm and
removed from site.
5.2 The grading of the area shall be done by cutting and filling with the following:
b. Filling area
5.3.1 New Site: To be kept 150 to 300mm above the nearby metalled road level
and may vary as per site requirement for new stations/locations.
6.1 ROADS
a) All SV(s), IP(s) and TOP: 4.0 M wide bituminous road consisting of
3.0m wide carriage way and 0.5m wide
shoulders on either side.
ii) Road inside Battery limit
a) All SV(s), IP(s) and TOP: 4.0m wide concrete road consisting of
3.0m wide carriage way and 0.5m
wide shoulders on either side.
b) Receipt Terminal : 6.0 M wide concrete road consisting of
4.0m wide carriage way and 1.0m
wide shoulders on either side.
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
(GEN. CIVIL) 0318-000-16-47-DB-01 Rev. A
Page 5 of 8
6.2.0 PAVEMENTS
8.0 PITCHING
In filled up areas where level difference is more than 1.0m and upto 2.0mRR
masonry pitching shall be provided on slopes for protection of earth against
erosion and sliding all around station and approach road. The limit of
pitching shall be within fenced area.
9.1.3 System- Under ground main ring with Galvanized Iron (G.I.) pipes and
fittings conforming to IS:1239 (Heavy).
9.1.4 Storage- Overhead HDPE water storage tank of Capacity 1.0 cu.m kept
on individual building as per IS:12701
9.2.0 Water System (un-manned stations, i.e. SV and IP and isolated installation)
No Toilet facility and water supply system is considered for these stations.
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
(GEN. CIVIL) 0318-000-16-47-DB-01 Rev. A
Page 7 of 8
10.1.0 General
10.1.1 Oily water sewer is not envisaged for any of the pipeline installation.
10.1.2 Acidic waste collected from battery room of control building shall be
neutralized by providing Neutralization Pit and neutralised water to be
disposed in the nearest open storm water drains.
10.1.3 For dry batteries no neutralisation pit is required because there is no acid
leakage.
10.2.1 Acidic and Alkali seer : Neutralization Pit (and neutralized water
discharge to nearby open drain).
10.3.2 If cushion over sewer pipe is less than 1200mm under roads, sewer shall be
encased in cement concrete.
10.4.0 Manholes
10.5.1 Acidic and Alkali sewer: High Density Polyethylene (HDPE) as per IS:
4984
10.5.2 Manhole for acid / alkali sewer shall be provided with Acid/Alkali proof
lining.
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
DOCUMENT No.
ENGINEERING DESIGN BASIS
(GEN. CIVIL) 0318-000-16-47-DB-01 Rev. A
Page 8 of 8
12.1 The Fire Protection facilities shall be provided meeting the minimum the
requirements of TAC for insurance purposes.
12.3 Adequate number of capacity 4.5kg CO2 type and capacity 10kg dry
chemical powder portable extinguisher of capacity shall be provided at all
Despatch Station, Receipt Station, SV(s) and IP(s) stations as per IS:2190.
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved