Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
net/publication/245346482
CITATIONS READS
11 2,152
5 authors, including:
Michael Kruger
41 PUBLICATIONS 232 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Michael Kruger on 19 July 2014.
Figure 7: Resonance behavior of winding and voltage source Figure 10: Delta tan δ of one phase as a function of test volt-
age: red dotted line at 50Hz, blue line at 62Hz
Tan δ was measured over the range 30 to 400 Hz. The re-
sults are shown in Figure 9. The highest gradient occurs at low
frequencies, indicating that tan δ varies rapidly near the grid
frequency and therefore the data at the test frequency must be
corrected.
An important parameter for evaluation of the condition of a
stator winding is the power factor tip-up (delta tan δ), defined
as the increase in tan δ between measuring intervals. Figure 10
shows the results for one phase of the tested generator at 50 and
62 Hz. It can be seen that the tip-up is not dependent on the test
frequency.
Figure 12: Results of PD measurement. Left: single-mode system fingerprint. Right: multi-mode system fingerprint.
SUMMARY
This paper presented a comparison of different methods of
measuring insulation resistance and tan δ (dissipation factor),
and of documenting partial discharge activity. The measurements
were made on several service-aged generators. The results for
one in-service generator, obtained between service inspections,
are discussed in detail.
Comparing classical insulation resistance measurements and
Figure 13: Three-phase amplitude relation diagram. the dielectric response behavior in the frequency domain, good
agreement is found. With the insulation time-constant, the dry-
ness can be determined relatively. In the case of resin-impreg-
nated insulation systems, additional investigations are required
recently developed PD test system [22], a synchronous measure- to determine the humidity absolutely.
ment of several quadripoles is possible [23]; thus the signal from The determination of tan δ using various test systems and
the beginning and end of the winding can be obtained in one measuring methods was carried out on-site. Because tan δ is
measurement. In the present test series, the generator was mea- frequency- and temperature-dependent, the results of series
sured using both systems, i.e., the conventional and the multi- resonance circuit measurements must be modified by correcting
sensor device. The standard frequency limit of conventional for the difference between the measurement frequency and the
broadband test systems is in the range 100 kHz to 1 MHz. power frequency.
In Figure 11, the schematic wiring diagram of each PD mea- The results obtained using various PD-test systems depend
surement circuit is shown. A coupling capacitor CKX (2 nF) is on bandwidth and the circuit configuration. The multi-synchro-
necessary for each quadripole. In the multi-synchronous system, nous system has the significant advantages that the PD activity
all coupling units are connected to the PC by a fiber optic cable, at several points can be monitored in one measurement, and the
so that fewer grounding problems arise. three-phase amplitude relation diagram makes it easy to identify
In Figure 12, the test results of phase U at the rated volt- the PD source. However, the calibration process is lengthy, so
age are shown: on the left is the fingerprint of the single-mode little time is saved overall, and a full set of quadripoles and cou-
system, and on the right that of the multi-mode system. Partial pling capacitors is needed for each channel.
discharge activity at rated voltage is expressed in pC (the QIEC
values shown in Table 1).
The fingerprints are very similar. Both show a normal distri-
REFERENCES
[1] M. Marketz, C. Rupp, and H. Egger, “Risk-based maintenance and
bution of internal discharges from delaminated insulation. The replacement strategy for generators in storage power plants,” presented at
PD patterns at the network side show low level internal and slot Hydro 2008, Ljubljana, Slovenia.
discharge activity. Some typical PD patterns are presented in [2] IEEE Recommended Practice for Testing Insulation Resistance of Rotat-
ing Machinery, IEEE Std 43-2000, 2000.
[24]–[26]. [3] IEEE Recommended Practice for Measurement of Power Factor Tip-Up
The QIEC levels on the network side are similar, but differ of Electric Machinery Stator Coil Insulation, IEEE Std 286-2000, 2000.
considerably at the neutral point (Table 1). The discrepancy is [4] IEEE Trial-Use Guide to the Measurement of Partial Discharges in Rotat-
probably caused by differences in bandwidth, equivalent circuit, ing Machinery, IEEE Std 1434-2000, 2000.
[5] High-Voltage Test Techniques—Partial Discharge Measurements, IEC
and calibration signal. 60270-2000, 2000.
One of the advantages of the synchronous test system is the [6] T. Klamt, “Corona Protection of high-voltage stator windings of hydro
three-phase amplitude relation diagram— 3PARD [26]. Using generators,” presented at Hydro 2008, Ljubljana, Slovenia.
this feature, the results of up to three PD sensors can be dis- [7] W. Zwicknagl, “Zur Frage der Bestimmung und Beurteilung des
Feuchtigkeitsgehalts der Isolierung von Generator—Hochspannungs-
played as synchronous vectors on one phase diagram. The ori- wicklungen,” Doctoral thesis, Graz University of Technology, 1965. (in
gin of PD can then be located easily by zooming into a specific German)
region of the frequency spectrum. By energizing the generator [8] Empfehlungen für die Zustandserfassung der Aktivteile Rotierender Elek-
with a single-phase source, and connecting the other phases in trischer Maschinen, 2nd ed., Vienna, Austria: Österreichischer Verband
für Elektrotechnik, 1990.
parallel with the neutral point (see Fig. 11), a phase shift caused [9] T. Leibfried and A.J. Kachler, “Insulation diagnostics on power trans-
by a distributed capacitance can also be observed using the formers using the polarisation and depolarisation current (PDC) analysis,”
3PARD diagram. presented at Int. Symp. Electrical Insulation 2002, Boston, MA.