Installation calculation report

Ngitung
Full
Page 2/50

Project: Ngitung 04/11/2019


Page 3/50

Content

1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4

1.2 Settings for wiring device calculation............................................................................................ 4

1.3 List of loads...................................................................................................................................... 4

2 Installation general design.....................................................................................................6


2.1 List of devices.................................................................................................................................. 6

3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14

3.2 Generator circuits.......................................................................................................................... 23

3.3 LV Source circuits.......................................................................................................................... 23

3.4 UPS circuits.................................................................................................................................... 23

3.5 Surge Arrester circuits................................................................................................................... 24

3.6 Capacitor bank circuits.................................................................................................................. 24

3.7 Feeder circuits................................................................................................................................ 24

3.8 LV Transformer circuits................................................................................................................. 26

3.9 Couplers circuits............................................................................................................................ 27

3.10 Generic load circuits................................................................................................................. 28

3.11 Lighting load circuits................................................................................................................ 28

3.12 Power socket load circuits....................................................................................................... 29

3.13 Motor starter combination........................................................................................................ 29

3.14 Busbar circuits.......................................................................................................................... 30

3.15 Busbar trunking system circuits............................................................................................. 30

3.16 Busbar trunking system circuits............................................................................................. 30

3.17 Lighting Busbar trunking system circuits..............................................................................30

Project: Ngitung 04/11/2019


Page 4/50

1 Project description
1.1 Project general settings
Installation standard IEC60364

Calculation standard TR50480


Circuit breaker standard IEC 60947-2
Frequency 50 Hz

1.2 Settings for wiring device calculation


Maximal CSA 300 mm²

1.3 List of loads

1.3.1 Motor loads


Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
MA 27.7 24.1 40 0.87 1 3Ph No 0
MB 194 169 280 0.87 1 3Ph No 0
MJ 27.7 24.1 40 0.87 1 3Ph No 0
MK 135 122 195 0.9 1 3Ph No 0
ME 67.2 60.5 97 0.9 1 3Ph No 0
MF 91.5 79.6 132 0.87 1 3Ph No 0
MG 111 97.5 160 0.88 1 3Ph No 0
MH 55.4 47.7 80 0.86 1 3Ph No 0
ML 15.2 13 22 0.85 1 3Ph No 0
MD 20.1 17.1 29 0.85 1 3Ph No 0
MC 15.2 13 22 0.85 1 3Ph No 0
MI 7.97 7.01 11.5 0.88 1 3Ph No 0

Project: Ngitung 04/11/2019


Page 5/50

2 Installation general design


2.1 List of devices
2.1.1 MV/LV transformer
Nbr Range Insulation Sr (kVA) ukrT (%) Connection U2 (V) SEA Rb
Name
(m)
Trafo 1 Minera Mineral oil 800 6 D 420 TN-S 10000
Distribusi

2.1.2 LV switchboards and busbar


Switchboard name Range Rating (A) IP
MCC Blokset 1350.00 IP54
SDB Blokset 750.00 IP54
SSDB Blokset 750.00 IP54

Busbar name Switchboard Ks Polarity SEA Equipotential bounding


name
Utama MCC 1 3Ph TN-S With
Utama Motor MCC 1 3Ph TN-S With
SDB All SDB 1 3Ph TN-S With
SDB motor SDB 1 3Ph TN-S With
SSDB motor SSDB 1 3Ph TN-S With

2.1.3 Circuit breaker


Name Nbr Range - Rating (A) Poles Trip unit/Curve RCD RCD class
Designation
QA 35 1 Masterpact 1250 3P3d Micrologic 5.0 X
MTZ1 -
MTZ1 12H1
MCCB 1 Compact 630 3P3d Micrologic 2.3
Outgoing NSX -
MCC 2 NSX630F
MCCB MA 1 Compact 100 3P3d MA
NSX -
NSX100F
MCCB MB 1 Compact 400 3P3d Micrologic 1.3 M
NSX -
NSX400F
MCCB MJ 1 Compact 100 3P3d MA
NSX -
NSX100F
MCCB MK 1 Compact 250 3P3d MA
NSX -
NSX250F
MCCB 1 Compact 630 3P3d Micrologic 2.3
Outgoing NSX -
MCC 1 NSX630F
MCCB 1 Compact 630 3P3d Micrologic 5.3 A
Incoming NSX -
SDB NSX630F
MCCB 1 Compact 100 3P3d Micrologic 2.2
Outgoing NSX -
SDB 2 NSX100B
MCCB 1 Acti9 iC60 - 40 3P3d C
Incoming iC60N
SSDB

Project: Ngitung 04/11/2019


Page 6/50

MCCB 1 Compact 630 3P3d Micrologic 2.3


Outgoing NSX -
SDB 1 NSX630F
MCCB ME 1 Compact 160 3P3d MA
NSX -
NSX160F
MCCB MF 1 Compact 160 3P3d MA
NSX -
NSX160F
MCCB MG 1 Compact 250 3P3d MA
NSX -
NSX250F
MCCB MH 1 Compact 100 3P3d MA
NSX -
NSX100F
MCCB ML 1 TeSys GV - 25 3P3d L25
GV4L25B
MCCB MD 1 Compact 100 3P3d MA
NSX -
NSX100F
MCCB MC 1 TeSys GV - 25 3P3d L25
GV4L25B
MCCB MI 1 Compact 100 3P3d MA
NSX -
NSX100F

2.1.4 Cable schedule


Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN
Pengh 1 MCCB MCCB Multi-core PVC 45.6 5x240 5x120
antar Outgoin Incomin Copper Copper
Caban g MCC 1 g SDB
g1
Pengh 1 MCCB MCCB Multi-core PVC 43.8 1x16 1x16
antar Outgoin Incomin Copper Copper
Caban g SDB 2 g SSDB
g2
Pengh 1 MCCB MH Multi-core PVC 22.5 1x120 1x70
antar MH Copper Copper
MH
Pengh 1 MCCB MG Multi-core PVC 22.5 2x150 2x150
antar MG Copper Copper
MG
Pengh 1 MCCB MF Multi-core PVC 21 1x240 1x120
antar MF Copper Copper
MF
Pengh 1 MCCB ME Multi-core PVC 21 1x150 1x150
antar ME Copper Copper
ME
Pengh 1 MCCB MB Multi-core PVC 21 2x300 2x300
antar MB Copper Copper
MB
Pengh 1 MCCB MI Multi-core PVC 16.5 1x2.5 1x2.5
antar MI Copper Copper
MI
Pengh 1 MCCB MC Multi-core PVC 16.5 1x10 1x10
antar MC Copper Copper
MC
Pengh 1 MCCB MJ Multi-core PVC 16.5 1x50 1x25
antar MJ Copper Copper
MJ
Pengh 1 MCCB MA Multi-core PVC 16.5 1x50 1x25
antar MA Copper Copper
Project: Ngitung 04/11/2019
Page 7/50

MA
Pengh 1 MCCB MD Multi-core PVC 15 1x50 1x25
antar MD Copper Copper
MD
Pengh 1 MCCB ML Multi-core PVC 15 1x10 1x10
antar ML Copper Copper
ML
Pengh 1 MCCB MK Multi-core PVC 15 2x150 2x150
antar MK Copper Copper
MK
WD 35 1 Trafo QA 35 Multi-core XLPE 10 3x240 3x120
Distribus Copper Copper
i

2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 240 Al 21.3 418 24
35

Project: Ngitung 04/11/2019


Page 8/50

3 Calculation notes

3.1 Source circuits


3.1.1 Circuit JTM PLN 20 kV
MV power supply W 35
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 250 MVA
MV Cable MVWD 35
Parameters
Length 10 m
Type of cable Single core
Ib 23 A
Nb of conductor per phase 1
Cross section area 1 x 240 Al mm²
Core Aluminium
Short circuit withstand 21.3 kA
Assigned voltage 20 kV
Insulation voltage 24 kV

MV/LV transformer Trafo Distribusi


Range Minera
Technology Mineral oil
Rated power 800 kVA
ukrT 6%
Type of losses AoAk
PkrT 6 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 35
Parameters
Length 10 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 1155 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Project: Ngitung 04/11/2019
Page 9/50

Standard table reference B-52-16


Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.82
Standard table reference B-52-20
User correction factor 1
Overall factor 0.82

Selected phase
Cross section area 3x240 mm²
Core Copper
Iz under real conditions 1323A
Iz’ 1614
Selected PE
Cross section area 3x120 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 22.16 19.19 0.00 13.33 0.00 15.39 0.00 17.82

Synthesis for all operating mode


(kA) 22.16 19.19 0.00 13.33 0.00 15.39 0.00 17.82

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 35
Ib 1155 A
Distance from origin NA

Sizing Information Sized by system


Range Masterpact MTZ1
Designation MTZ1 12H1
Circuit breaker rating 1250 A
Breaking capacity 42 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 5.0 X
Trip unit rating 1250 A
Long delay settings
Ir 1188 (Setting: 0.95) A
Tr 24 s
Short delay settings
Isd current 9500A
Tsd 0.4 s
Instantaneous tripping
Ii current 18750 (Setting: 15) A

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


Project: Ngitung 04/11/2019
Page 10/50

NA Discrimination can't be determinated : no


upstream Lv Breaker

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 1108.500 1108.500 1108.500 0

Synthesis for all operating mode


(A) 1108.500 1108.500 1108.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.208 0.208
UL1L2 (%) 0.241 0.241
UL2L3 (%) 0.241 0.241
UL3L1 (%) 0.241 0.241
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

3.2 Feeder circuits


3.2.1 Circuit Feeder circuit 5
Circuit breaker MCCB Outgoing MCC 2
Ib 555 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 630 A
Long delay settings
Ir 559 A
Tr 16 s
Short delay settings
Isd current 5586A
Tsd 0.02 s
Instantaneous tripping
Ii current 6900 A

Discrimination Results

Project: Ngitung 04/11/2019


Page 11/50

UpStream Discrimination Limit

Operating mode Normal


QA 35 Full Discrimination
MTZ1 12H1
Micrologic 5.0 X
1250 A / 3P3d

Project: Ngitung 04/11/2019


Page 12/50

3.2.2 Circuit Feeder circuit 20


Circuit breaker MCCB Outgoing SDB 1
Ib 520 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 630 A
Long delay settings
Ir 524 A
Tr 16 s
Short delay settings
Isd current 5244A
Tsd 0.02 s
Instantaneous tripping
Ii current 6900 A

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Incoming SDB No Discrimination
NSX630F
Micrologic 5.3 A
630 A / 3P3d

Project: Ngitung 04/11/2019


Page 13/50

3.2.3 Circuit MCC-SDB


Circuit breaker MCCB Outgoing MCC 1
Ib 554 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.3
Trip unit rating 630 A
Long delay settings
Ir 559 A
Tr 16 s
Short delay settings
Isd current 5586A
Tsd 0.02 s
Instantaneous tripping
Ii current 6900 A

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


QA 35 Full Discrimination
MTZ1 12H1
Micrologic 5.0 X
1250 A / 3P3d

Cable Penghantar Cabang 1


Parameters
Length 45.6 m
Max length NA
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 7
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 554 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Project: Ngitung 04/11/2019
Page 14/50

Temperature factor 0.77


Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.45
Standard table reference B-52-19
User correction factor 1
Overall factor 0.409

Selected phase
Cross section area 5x240 mm²
Core Copper
Iz under real conditions 572A
Iz’ 1400
Selected PE
Cross section area 5x120 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 20.66 17.89 0.00 12.58 0.00 13.53 0.00 15.67

Synthesis for all operating mode


(kA) 20.66 17.89 0.00 12.58 0.00 13.53 0.00 15.67

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker MCCB Incoming SDB


Ib 554 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX630F
Circuit breaker rating 630 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 5.3 A
Trip unit rating 630 A
Long delay settings
Ir 554 A
Tr 4s
Short delay settings
Isd current 5540A
Tsd 0.4 s
Instantaneous tripping
Ii current 6930 A

Discrimination Results
Project: Ngitung 04/11/2019
Page 15/50

UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing MCC 1 No Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 553.500 553.500 553.500 0

Synthesis for all operating mode


(A) 553.500 553.500 553.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.470 0.262
UL1L2 (%) 0.543 0.302
UL2L3 (%) 0.543 0.302
UL3L1 (%) 0.543 0.302
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Project: Ngitung 04/11/2019


Page 16/50

3.2.4 Circuit SDB-SSDB


Circuit breaker MCCB Outgoing SDB 2
Ib 33.5 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100B
Circuit breaker rating 100 A
Breaking capacity 25 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 2.2
Trip unit rating 40 A
Long delay settings
Ir 33.8 A
Tr 16 s
Short delay settings
Isd current 338A
Tsd 0.02 s
Instantaneous tripping
Ii current 600 A

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Incoming SDB Full Discrimination
NSX630F
Micrologic 5.3 A
630 A / 3P3d

Cable Penghantar Cabang 2


Parameters
Length 43.8 m
Max length NA
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 5
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 34 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Project: Ngitung 04/11/2019
Page 17/50

Standard table reference B-52-15


Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.6
Standard table reference B-52-19
User correction factor 1
Overall factor 0.545

Selected phase
Cross section area 1x16 mm²
Core Copper
Iz under real conditions 34.9A
Iz’ 64
Selected PE
Cross section area 1x16 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 4.60 3.98 0.00 2.87 0.00 1.74 0.00 2.01

Synthesis for all operating mode


(kA) 4.60 3.98 0.00 2.87 0.00 1.74 0.00 2.01

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker MCCB Incoming SSDB


Ib 33.5 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60N
Circuit breaker rating 40 A
Breaking capacity 10 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation C
Trip unit rating 40 A
Long delay settings
Ir 40 A
Tr NA
Short delay settings
Isd current 320A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit
Project: Ngitung 04/11/2019
Page 18/50

Operating mode Normal


MCCB Outgoing SDB 2 No Discrimination
NSX100B
Micrologic 2.2
40 A / 3P3d

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 33.500 33.500 33.500 0

Synthesis for all operating mode


(A) 33.500 33.500 33.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.255 0.785
UL1L2 (%) 1.449 0.906
UL2L3 (%) 1.449 0.906
UL3L1 (%) 1.449 0.906
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Project: Ngitung 04/11/2019


Page 19/50

3.3 Motor starter combination


3.3.1 Circuit Motor Load A
Circuit breaker MCCB MA
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation MA
Trip unit rating 50 A
Long delay settings
Ir 50 A
Tr NA
Short delay settings
Isd current 700A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing MCC 2 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Contactor LC1D80
Designation LC1D80
Type of coordination T2

Thermal relay LTMR100


Designation LTMR100
Ir 40

Cable Penghantar MA
Parameters
Length 16.5 m
Max length 167 m
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Project: Ngitung 04/11/2019
Page 20/50

Type of cable Multi-core


Nb of additional touching circuits 7
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 40 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.54
Standard table reference B-52-19
User correction factor 1
Overall factor 0.491

Selected phase
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 56.9A
Iz’ 116
Selected PE
Cross section area 1x25 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.13 14.83 0.00 10.53 0.00 6.84 0.00 7.92

Synthesis for all operating mode


(kA) 17.13 14.83 0.00 10.53 0.00 6.84 0.00 7.92

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MA
Startup type Star-delta
U 400 V
Mechanical power 22 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 40 A
Sr for sizing 27.7 kVA
Pr for sizing 24.1 kW
cos 0.87
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Project: Ngitung 04/11/2019
Page 21/50

Sensitivity to over voltage NA


Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 40.000 40.000 40.000 0

Synthesis for all operating mode


(A) 40.000 40.000 40.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.330 0.122
UL1L2 (%) 0.381 0.141
UL2L3 (%) 0.381 0.141
UL3L1 (%) 0.381 0.141
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.438
3.3.2 Circuit Motor Load B
Circuit breaker MCCB MB
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX400F
Circuit breaker rating 400 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation Micrologic 1.3 M
Trip unit rating 320 A
Long delay settings
Ir 320 A
Tr NA
Short delay settings
Isd current 4160A
Tsd 0.03 s
Instantaneous tripping
Ii current 4800 A

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing MCC 2 6900 A
NSX630F
Micrologic 2.3
630 A / 3P3d

Project: Ngitung 04/11/2019


Page 22/50

Contactor LC1F330
Designation LC1F330
Type of coordination T2

Thermal relay LTMR08


Designation LTMR08
Ir 280

Cable Penghantar MB
Parameters
Length 21 m
Max length 306 m
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 4
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 280 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.6
Standard table reference B-52-19
User correction factor 1
Overall factor 0.545

Selected phase
Cross section area 2x300 mm²
Core Copper
Iz under real conditions 345A
Iz’ 632
Selected PE
Cross section area 2x300 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 20.49 17.75 0.00 12.50 0.00 13.56 0.00 15.70

Synthesis for all operating mode


Project: Ngitung 04/11/2019
Page 23/50

(kA) 20.49 17.75 0.00 12.50 0.00 13.56 0.00 15.70

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MB
Startup type Star-delta
U 400 V
Mechanical power 160 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 280 A
Sr for sizing 194 kVA
Pr for sizing 169 kW
cos 0.87
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 280.000 280.000 280.000 0

Synthesis for all operating mode


(A) 280.000 280.000 280.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.341 0.132
UL1L2 (%) 0.393 0.153
UL2L3 (%) 0.393 0.153
UL3L1 (%) 0.393 0.153
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.608
3.3.3 Circuit Motor Load J
Circuit breaker MCCB MJ
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation MA
Project: Ngitung 04/11/2019
Page 24/50

Trip unit rating 50 A


Long delay settings
Ir 50 A
Tr NA
Short delay settings
Isd current 700A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing MCC 2 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Contactor LC1D80
Designation LC1D80
Type of coordination T2

Thermal relay LTMR100


Designation LTMR100
Ir 40

Cable Penghantar MJ
Parameters
Length 16.5 m
Max length 167 m
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 7
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 40 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.54
Standard table reference B-52-19
User correction factor 1
Project: Ngitung 04/11/2019
Page 25/50

Overall factor 0.491

Selected phase
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 56.9A
Iz’ 116
Selected PE
Cross section area 1x25 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.13 14.83 0.00 10.53 0.00 6.84 0.00 7.92

Synthesis for all operating mode


(kA) 17.13 14.83 0.00 10.53 0.00 6.84 0.00 7.92

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MJ
Startup type Star-delta
U 400 V
Mechanical power 22 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 40 A
Sr for sizing 27.7 kVA
Pr for sizing 24.1 kW
cos 0.87
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 40.000 40.000 40.000 0

Synthesis for all operating mode


(A) 40.000 40.000 40.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.330 0.122
UL1L2 (%) 0.381 0.141
UL2L3 (%) 0.381 0.141
UL3L1 (%) 0.381 0.141
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
Project: Ngitung 04/11/2019
Page 26/50

UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.438
3.3.4 Circuit Motor Load K
Circuit breaker MCCB MK
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250F
Circuit breaker rating 250 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation MA
Trip unit rating 220 A
Long delay settings
Ir 220 A
Tr NA
Short delay settings
Isd current 3080A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing MCC 2 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Contactor LC1F225
Designation LC1F225
Type of coordination T2

Thermal relay LTMR08


Designation LTMR08
Ir 195

Cable Penghantar MK
Parameters
Length 15 m
Max length 296 m
Installation method 70
D1
Multi-core cable in conduit or in

Project: Ngitung 04/11/2019


Page 27/50

cable ducting in the ground


Type of cable Multi-core
Nb of additional touching circuits 4
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 195 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.6
Standard table reference B-52-19
User correction factor 1
Overall factor 0.545

Selected phase
Cross section area 2x150 mm²
Core Copper
Iz under real conditions 237A
Iz’ 434
Selected PE
Cross section area 2x150 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 20.80 18.01 0.00 12.64 0.00 13.81 0.00 16.00

Synthesis for all operating mode


(kA) 20.80 18.01 0.00 12.64 0.00 13.81 0.00 16.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MK
Startup type Star-delta
U 400 V
Mechanical power 110 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 195 A
Sr for sizing 135 kVA
Pr for sizing 122 kW
cos 0.9
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
Project: Ngitung 04/11/2019
Page 28/50

THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 195.000 195.000 195.000 0

Synthesis for all operating mode


(A) 195.000 195.000 195.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.315 0.106
UL1L2 (%) 0.363 0.123
UL2L3 (%) 0.363 0.123
UL3L1 (%) 0.363 0.123
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.487
3.3.5 Circuit Motor Load E
Circuit breaker MCCB ME
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX160F
Circuit breaker rating 160 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation MA
Trip unit rating 100 A
Long delay settings
Ir 100 A
Tr NA
Short delay settings
Isd current 1400A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing SDB 1 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Project: Ngitung 04/11/2019


Page 29/50

Contactor LC1D150
Designation LC1D150
Type of coordination T2

Thermal relay LTMR08


Designation LTMR08
Ir 97

Cable Penghantar ME
Parameters
Length 21 m
Max length 360 m
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 7
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 97 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.54
Standard table reference B-52-19
User correction factor 1
Overall factor 0.491

Selected phase
Cross section area 1x150 mm²
Core Copper
Iz under real conditions 106A
Iz’ 217
Selected PE
Cross section area 1x150 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.39 15.06 0.00 10.82 0.00 10.79 0.00 12.49

Project: Ngitung 04/11/2019


Page 30/50

Synthesis for all operating mode


(kA) 17.39 15.06 0.00 10.82 0.00 10.79 0.00 12.49

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor ME
Startup type Star-delta
U 400 V
Mechanical power 55 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 97 A
Sr for sizing 67.2 kVA
Pr for sizing 60.5 kW
cos 0.9
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 97.000 97.000 97.000 0

Synthesis for all operating mode


(A) 97.000 97.000 97.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.618 0.148
UL1L2 (%) 0.714 0.171
UL2L3 (%) 0.714 0.171
UL3L1 (%) 0.714 0.171
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.880
3.3.6 Circuit Motor Load F
Circuit breaker MCCB MF
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX160F
Circuit breaker rating 160 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Project: Ngitung 04/11/2019
Page 31/50

Trip unit designation MA


Trip unit rating 150 A
Long delay settings
Ir 150 A
Tr NA
Short delay settings
Isd current 2100A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing SDB 1 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Contactor LC1D150
Designation LC1D150
Type of coordination T2

Thermal relay LTMR08


Designation LTMR08
Ir 132

Cable Penghantar MF
Parameters
Length 21 m
Max length 217 m
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 5
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 132 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.6
Standard table reference B-52-19
Project: Ngitung 04/11/2019
Page 32/50

User correction factor 1


Overall factor 0.545

Selected phase
Cross section area 1x240 mm²
Core Copper
Iz under real conditions 153A
Iz’ 280
Selected PE
Cross section area 1x120 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.75 15.38 0.00 11.05 0.00 10.67 0.00 12.35

Synthesis for all operating mode


(kA) 17.75 15.38 0.00 11.05 0.00 10.67 0.00 12.35

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MF
Startup type Star-delta
U 400 V
Mechanical power 75 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 132 A
Sr for sizing 91.5 kVA
Pr for sizing 79.6 kW
cos 0.87
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 132.000 132.000 132.000 0

Synthesis for all operating mode


(A) 132.000 132.000 132.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.614 0.144
UL1L2 (%) 0.709 0.166
UL2L3 (%) 0.709 0.166
UL3L1 (%) 0.709 0.166
UL1N (%) 0.000 0.000
Project: Ngitung 04/11/2019
Page 33/50

UL2N (%) 0.000 0.000


UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.933
3.3.7 Circuit Motor Load G
Circuit breaker MCCB MG
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250F
Circuit breaker rating 250 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation MA
Trip unit rating 220 A
Long delay settings
Ir 220 A
Tr NA
Short delay settings
Isd current 3080A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing SDB 1 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Contactor LC1F185
Designation LC1F185
Type of coordination T2

Thermal relay LTMR08


Designation LTMR08
Ir 160

Cable Penghantar MG
Parameters
Length 22.5 m
Max length 289 m
Installation method 70
D1
Multi-core cable in conduit or in
Project: Ngitung 04/11/2019
Page 34/50

cable ducting in the ground


Type of cable Multi-core
Nb of additional touching circuits 4
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 160 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.6
Standard table reference B-52-19
User correction factor 1
Overall factor 0.545

Selected phase
Cross section area 2x150 mm²
Core Copper
Iz under real conditions 237A
Iz’ 434
Selected PE
Cross section area 2x150 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 18.82 16.30 0.00 11.60 0.00 12.36 0.00 14.31

Synthesis for all operating mode


(kA) 18.82 16.30 0.00 11.60 0.00 12.36 0.00 14.31

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MG
Startup type Star-delta
U 400 V
Mechanical power 90 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 160 A
Sr for sizing 111 kVA
Pr for sizing 97.5 kW
cos 0.88
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
Project: Ngitung 04/11/2019
Page 35/50

THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 160.000 160.000 160.000 0

Synthesis for all operating mode


(A) 160.000 160.000 160.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.601 0.131
UL1L2 (%) 0.694 0.151
UL2L3 (%) 0.694 0.151
UL3L1 (%) 0.694 0.151
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.898
3.3.8 Circuit Motor Load H
Circuit breaker MCCB MH
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation MA
Trip unit rating 100 A
Long delay settings
Ir 100 A
Tr NA
Short delay settings
Isd current 1400A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing SDB 1 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Project: Ngitung 04/11/2019


Page 36/50

Contactor LC1D115
Designation LC1D115
Type of coordination T2

Thermal relay LTMR08


Designation LTMR08
Ir 80

Cable Penghantar MH
Parameters
Length 22.5 m
Max length 234 m
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 4
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 80 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.65
Standard table reference B-52-19
User correction factor 1
Overall factor 0.591

Selected phase
Cross section area 1x120 mm²
Core Copper
Iz under real conditions 113A
Iz’ 192
Selected PE
Cross section area 1x70 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 16.90 14.63 0.00 10.52 0.00 9.43 0.00 10.92

Project: Ngitung 04/11/2019


Page 37/50

Synthesis for all operating mode


(kA) 16.90 14.63 0.00 10.52 0.00 9.43 0.00 10.92

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MH
Startup type Star-delta
U 400 V
Mechanical power 45 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 80 A
Sr for sizing 55.4 kVA
Pr for sizing 47.7 kW
cos 0.86
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 80.000 80.000 80.000 0

Synthesis for all operating mode


(A) 80.000 80.000 80.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.626 0.156
UL1L2 (%) 0.723 0.180
UL2L3 (%) 0.723 0.180
UL3L1 (%) 0.723 0.180
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.866
3.3.9 Circuit Motor Load L
Circuit breaker MCCB ML
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range TeSys GV
Designation GV4L25B
Circuit breaker rating 25 A
Breaking capacity 25 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Project: Ngitung 04/11/2019
Page 38/50

Trip unit designation L25


Trip unit rating 25 A
Long delay settings
Ir 25 A
Tr NA
Short delay settings
Isd current 350A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing SDB 1 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Contactor LC1D65A
Designation LC1D65A
Type of coordination T2

Thermal relay LTMR27


Designation LTMR27
Ir 22

Cable Penghantar ML
Parameters
Length 15 m
Max length NA
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 5
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 22 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.6
Standard table reference B-52-19
Project: Ngitung 04/11/2019
Page 39/50

User correction factor 1


Overall factor 0.545

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 27.3A
Iz’ 50
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 7.73 6.69 0.00 4.80 0.00 3.06 0.00 3.55

Synthesis for all operating mode


(kA) 7.73 6.69 0.00 4.80 0.00 3.06 0.00 3.55

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor ML
Startup type Star-delta
U 400 V
Mechanical power 11 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 22 A
Sr for sizing 15.2 kVA
Pr for sizing 13 kW
cos 0.85
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 22.000 22.000 22.000 0

Synthesis for all operating mode


(A) 22.000 22.000 22.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.746 0.276
UL1L2 (%) 0.861 0.318
UL2L3 (%) 0.861 0.318
UL3L1 (%) 0.861 0.318
UL1N (%) 0.000 0.000
Project: Ngitung 04/11/2019
Page 40/50

UL2N (%) 0.000 0.000


UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.909
3.3.10 Circuit Motor Load D
Circuit breaker MCCB MD
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation MA
Trip unit rating 50 A
Long delay settings
Ir 50 A
Tr NA
Short delay settings
Isd current 700A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Outgoing SDB 1 Full Discrimination
NSX630F
Micrologic 2.3
630 A / 3P3d

Contactor LC1D80
Designation LC1D80
Type of coordination T2

Thermal relay LTMR100


Designation LTMR100
Ir 29

Cable Penghantar MD
Parameters
Length 15 m
Max length NA
Installation method 70
D1
Multi-core cable in conduit or in
Project: Ngitung 04/11/2019
Page 41/50

cable ducting in the ground


Type of cable Multi-core
Nb of additional touching circuits 7
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 29 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.54
Standard table reference B-52-19
User correction factor 1
Overall factor 0.491

Selected phase
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 56.9A
Iz’ 116
Selected PE
Cross section area 1x25 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 16.46 14.26 0.00 10.18 0.00 7.06 0.00 8.17

Synthesis for all operating mode


(kA) 16.46 14.26 0.00 10.18 0.00 7.06 0.00 8.17

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MD
Startup type Star-delta
U 400 V
Mechanical power 15 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 29 A
Sr for sizing 20.1 kVA
Pr for sizing 17.1 kW
cos 0.85
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
Project: Ngitung 04/11/2019
Page 42/50

THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 29.000 29.000 29.000 0

Synthesis for all operating mode


(A) 29.000 29.000 29.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.549 0.079
UL1L2 (%) 0.634 0.091
UL2L3 (%) 0.634 0.091
UL3L1 (%) 0.634 0.091
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 0.634
3.3.11 Circuit Motor Load C
Circuit breaker MCCB MC
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range TeSys GV
Designation GV4L25B
Circuit breaker rating 25 A
Breaking capacity 25 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Trip unit designation L25
Trip unit rating 25 A
Long delay settings
Ir 25 A
Tr NA
Short delay settings
Isd current 350A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Incoming SSDB 52 A
iC60N
C
40 A / 3P3d

Project: Ngitung 04/11/2019


Page 43/50

Contactor LC1D65A
Designation LC1D65A
Type of coordination T2

Thermal relay LTMR27


Designation LTMR27
Ir 22

Cable Penghantar MC
Parameters
Length 16.5 m
Max length NA
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 5
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 22 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.6
Standard table reference B-52-19
User correction factor 1
Overall factor 0.545

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 27.3A
Iz’ 50
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 2.98 2.58 0.00 1.86 0.00 1.58 0.00 1.83

Project: Ngitung 04/11/2019


Page 44/50

Synthesis for all operating mode


(kA) 2.98 2.58 0.00 1.86 0.00 1.58 0.00 1.83

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MC
Startup type Star-delta
U 400 V
Mechanical power 11 kW
Startup current Id/Ir 2.4
Transient current I’’d/Ir <=19
Ir for sizing 22 A
Sr for sizing 15.2 kVA
Pr for sizing 13 kW
cos 0.85
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 22.000 22.000 22.000 0

Synthesis for all operating mode


(A) 22.000 22.000 22.000 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.558 0.303
UL1L2 (%) 1.799 0.350
UL2L3 (%) 1.799 0.350
UL3L1 (%) 1.799 0.350
UL1N (%) 0.000 0.000
UL2N (%) 0.000 0.000
UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 2.019
3.3.12 Circuit Motor Load I
Circuit breaker MCCB MI
Ib NA
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX100F
Circuit breaker rating 100 A
Breaking capacity 36 kA
TNS One pole breaking capacity NA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 3P3d
Project: Ngitung 04/11/2019
Page 45/50

Trip unit designation MA


Trip unit rating 12.5 A
Long delay settings
Ir 12.5 A
Tr NA
Short delay settings
Isd current 175A
Tsd NA
Instantaneous tripping
Ii current NA

Discrimination Results
UpStream Discrimination Limit

Operating mode Normal


MCCB Incoming SSDB 67 A
iC60N
C
40 A / 3P3d

Contactor LC1D80
Designation LC1D80
Type of coordination T2

Thermal relay LTMR27


Designation LTMR27
Ir 11.5

Cable Penghantar MI
Parameters
Length 16.5 m
Max length NA
Installation method 70
D1
Multi-core cable in conduit or in
cable ducting in the ground
Type of cable Multi-core
Nb of additional touching circuits 5
Insulation PVC
Ground temperature 40 °C
Level of third harmonic THDI 0%
Ib 12 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 0.77
Standard table reference B-52-15
Soil thermal resistivity factor 1.18
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.6
Standard table reference B-52-19
Project: Ngitung 04/11/2019
Page 46/50

User correction factor 1


Overall factor 0.545

Selected phase
Cross section area 1x2.5 mm²
Core Copper
Iz under real conditions 13.1A
Iz’ 24
Selected PE
Cross section area 1x2.5 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 1.44 1.25 0.00 0.90 0.00 0.61 0.00 0.71

Synthesis for all operating mode


(kA) 1.44 1.25 0.00 0.90 0.00 0.61 0.00 0.71

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Asynchronous LV Motor MI
Startup type Star-delta
U 400 V
Mechanical power 5.5 kW
Startup current Id/Ir 2
Transient current I’’d/Ir <=19
Ir for sizing 11.5 A
Sr for sizing 7.97 kVA
Pr for sizing 7.01 kW
cos 0.88
Polarity 3Ph
Number of circuit 1
Ku (mode Normal) 1
Harmonic generator No
THDI3 0%
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 11.500 11.500 11.500 0

Synthesis for all operating mode


(A) 11.500 11.500 11.500 0
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 1.901 0.646
UL1L2 (%) 2.195 0.745
UL2L3 (%) 2.195 0.745
UL3L1 (%) 2.195 0.745
UL1N (%) 0.000 0.000
Project: Ngitung 04/11/2019
Page 47/50

UL2N (%) 0.000 0.000


UL3N (%) 0.000 0.000

Startup Voltage drop


UStartUp 2.261

3.4 Busbar circuits


3.4.1 Circuit Utama
Busbar Utama
Parameters
Switchboard Name MCC
Switchboard Range Blokset
Rating (A) 1350
IP IP54
Feeder
Circuit name Protection name Protection type

Feeder circuit 5 MCCB Outgoing MCC 2 NSX630F

MCC-SDB MCCB Outgoing MCC 1 NSX630F

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 22.16 19.19 0.00 13.34 0.00 15.40 0.00 17.83

Synthesis for all operating mode


(kA) 22.16 19.19 0.00 13.34 0.00 15.40 0.00 17.83

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.2 Circuit Utama Motor


Busbar Utama Motor
Parameters
Switchboard Name MCC
Switchboard Range Blokset
Rating (A) 1350
IP IP54
Feeder
Circuit name Protection name Protection type

Motor Load A MCCB MA NSX100F

Motor Load B MCCB MB NSX400F

Motor Load J MCCB MJ NSX100F

Motor Load K MCCB MK NSX250F

Project: Ngitung 04/11/2019


Page 48/50

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 22.16 19.19 0.00 13.34 0.00 15.40 0.00 17.83

Synthesis for all operating mode


(kA) 22.16 19.19 0.00 13.34 0.00 15.40 0.00 17.83

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.3 Circuit SDB All


Busbar SDB All
Parameters
Switchboard Name SDB
Switchboard Range Blokset
Rating (A) 750
IP IP54
Feeder
Circuit name Protection name Protection type

SDB-SSDB MCCB Outgoing SDB 2 NSX100B

Feeder circuit 20 MCCB Outgoing SDB 1 NSX630F

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 20.66 17.89 0.00 12.58 0.00 14.52 0.00 16.82

Synthesis for all operating mode


(kA) 20.66 17.89 0.00 12.58 0.00 14.52 0.00 16.82

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.4 Circuit SDB motor


Busbar SDB motor
Parameters
Switchboard Name SDB
Switchboard Range Blokset
Rating (A) 750
IP IP54
Feeder
Circuit name Protection name Protection type

Motor Load E MCCB ME NSX160F

Motor Load F MCCB MF NSX160F

Project: Ngitung 04/11/2019


Page 49/50

Motor Load G MCCB MG NSX250F

Motor Load H MCCB MH NSX100F

Motor Load L MCCB ML GV4L25B

Motor Load D MCCB MD NSX100F

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 20.66 17.89 0.00 12.58 0.00 14.52 0.00 16.82

Synthesis for all operating mode


(kA) 20.66 17.89 0.00 12.58 0.00 14.52 0.00 16.82

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.5 Circuit SSDB motor


Busbar SSDB motor
Parameters
Switchboard Name SSDB
Switchboard Range Blokset
Rating (A) 750
IP IP54
Feeder
Circuit name Protection name Protection type

Motor Load C MCCB MC GV4L25B

Motor Load I MCCB MI NSX100F

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 4.60 3.98 0.00 2.87 0.00 3.31 0.00 3.83

Synthesis for all operating mode


(kA) 4.60 3.98 0.00 2.87 0.00 3.31 0.00 3.83

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Project: Ngitung 04/11/2019


Page 50/50

NOTICE
RISK OF INACCURATE DATA RESULTS.

 Configure the software correctly to get accurate reports and/or


data results.
 Do not rely solely on software messages and reports to determine
if the system is functioning correctly.
 Make sure that you have entered the correct inputs for the required
components.
 Review the calculated results and solutions provided by the
software before submitting the report.
Failure to follow these instructions can result in incorrect bill of
material and loss of business.