Sei sulla pagina 1di 88

Operating Instructions

Smartec S CLD134
Conductivity Measuring System

Standard Number 74-03

BA401C/07/en/01.08
71066353
Software version 1.13 or later
Brief overview
This overview explains how to use these Operating Instructions to commission your measuring
system quickly and safely.

Safety instructions
→ Page 5 ff. General safety instructions
→ Page 6 ff. Explanation of the warning symbols
You can find special instructions at the appropriate position in the chapter in question. The
significance is indicated with the icons Warning #, Caution " and Note !.
Æ
Installation
→ Page 12 ff. Here, you can find information on installation conditions and the dimensions of the measuring
system.
→ Page 19 ff. These pages explain how to install the measuring system
Æ
Wiring
→ Page 22 ff. Here, you can find out how to connect your measuring system.
You also find information on how to connect the CLS54 sensor if you are using a separate
version.
Æ
Operation
→ Page 28 The display and operating elements are described here.
→ Page 31 The operating concept is described here.
→ Page 38 ff. The system configuration is explained here.
→ Page 56 ff. You can find information on how to calibrate the sensor here.
Æ
Maintenance
→ Page 59 ff. Here, you can find information on the maintenance of the measuring point.
→ Page 64 ff. Accessories which can be supplied for the measuring system are listed on the pages indicated.
→ Page 66 ff. Use the trouble-shooting information given here if your system should not work properly.
→ Page 72 ff. Spare parts that can be delivered and a system overview are listed on these pages.
Æ
Technical data
→ Page 78 Dimensions
→ Page 78 ff. Process conditions, weight, material
Æ
Index
→ Page 84 ff. The index helps you to find information and important terms easily and quickly.

Endress+Hauser
Smartec S CLD134

Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 5 6 Commissioning . . . . . . . . . . . . . . . . . . 33
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
1.2 Installation, commissioning and operation . . . . . . . . 5 6.2 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.3 Quick setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.4 Instrument configuration . . . . . . . . . . . . . . . . . . . . 38
1.5 Notes on safety conventions and symbols . . . . . . . . . 6 6.4.1 Setup 1 (conductivity, concentration) . . . . . 38
6.4.2 Setup 2 (temperature) . . . . . . . . . . . . . . . . 39
2 Identification . . . . . . . . . . . . . . . . . . . . 7 6.4.3 Current outputs . . . . . . . . . . . . . . . . . . . . . 41
6.4.4 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 7 6.4.5 Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.1.1 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . 7 6.4.6 Relay configuration . . . . . . . . . . . . . . . . . . 44
2.1.2 Product structure Smartec S CLD134 . . . . . 8 6.4.7 Temperature compensation with table . . . . 46
2.1.3 Basic version and function extensions . . . . . 9 6.4.8 Concentration measurement . . . . . . . . . . . 47
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 6.4.9 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
2.3 Certificates and approvals . . . . . . . . . . . . . . . . . . . 10 6.4.10 E+H Service . . . . . . . . . . . . . . . . . . . . . . . 52
6.4.11 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3 Installation . . . . . . . . . . . . . . . . . . . . . 11 6.4.12 Determining the temperature coefficient . . 53
3.1 Quick installation guide . . . . . . . . . . . . . . . . . . . . . 11 6.4.13 Remote parameter set switching
3.1.1 Measuring system . . . . . . . . . . . . . . . . . . . 11 (measuring range switching, MRS) . . . . . . . 53
3.2 Incoming acceptance, transport, storage . . . . . . . . . 12 6.4.14 Calibration . . . . . . . . . . . . . . . . . . . . . . . . 56
3.3 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 12 6.5 Communication interfaces . . . . . . . . . . . . . . . . . . . 58
3.3.1 Notes on installation . . . . . . . . . . . . . . . . . 12
3.3.2 CLD134 separate version . . . . . . . . . . . . . . 14 7 Maintenance . . . . . . . . . . . . . . . . . . . . 59
3.3.3 CLD 134 compact version . . . . . . . . . . . . . 17 7.1 Maintenance of Smartec S CLD134 . . . . . . . . . . . . 59
3.4 Installation instructions . . . . . . . . . . . . . . . . . . . . . 19 7.1.1 Dismantling Smartec S CLD134 . . . . . . . . . 59
3.4.1 Mounting CLD134 separate version . . . . . . 19 7.1.2 Replacement of central module . . . . . . . . . 60
3.4.2 Mounting CLD134 compact version or 7.2 Maintenance of measuring system . . . . . . . . . . . . . 61
CLS54 sensor for separate version . . . . . . . 21 7.2.1 Cleaning conductivity sensors . . . . . . . . . . 61
3.5 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 21 7.2.2 Checking inductive conductivity sensors . . 61
7.2.3 Instrument check by medium simulation . . 62
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 22 7.2.4 Checking line extension and junction box . 63
4.1 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . 22 7.3 Service equpipment "Optoscope" . . . . . . . . . . . . . . 63
4.1.1 Electrical connection of transmitter . . . . . . 22
4.2 Alarm contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 8 Accessories . . . . . . . . . . . . . . . . . . . . . 64
4.3 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 27 8.1 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
8.2 Extension cable . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5 Operation . . . . . . . . . . . . . . . . . . . . . . 28 8.3 Junction box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.1 Quick operation guide . . . . . . . . . . . . . . . . . . . . . . 28 8.4 Post mounting kit . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.2 Display and operating elements . . . . . . . . . . . . . . . 28 8.5 Software upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.2.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 8.6 Calibration solutions . . . . . . . . . . . . . . . . . . . . . . . 65
5.2.2 Operating elements . . . . . . . . . . . . . . . . . . 29 8.7 Optoscope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.2.3 Key assignment . . . . . . . . . . . . . . . . . . . . . 29
5.3 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 9 Troubleshooting . . . . . . . . . . . . . . . . . 66
5.3.1 Operating concept . . . . . . . . . . . . . . . . . . . 31 9.1 Troubleshooting instructions . . . . . . . . . . . . . . . . . 66
9.2 System error messages . . . . . . . . . . . . . . . . . . . . . . 66
9.3 Process-specific errors . . . . . . . . . . . . . . . . . . . . . . 67
9.4 Instrument-specific errors . . . . . . . . . . . . . . . . . . . 70
9.5 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
9.5.1 Exploded view . . . . . . . . . . . . . . . . . . . . . . 73
9.5.2 Spare part kits . . . . . . . . . . . . . . . . . . . . . . 74
9.6 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.7 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.8 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Endress+Hauser 3
Smartec S CLD134

10 Technical Data. . . . . . . . . . . . . . . . . . . 76
10.1 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
10.2 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
10.3 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
10.4 Performance characteristics . . . . . . . . . . . . . . . . . . 77
10.5 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
10.6 Mechanical construction . . . . . . . . . . . . . . . . . . . . 78
10.7 Measurement data of CLS54 sensor . . . . . . . . . . . . 78
10.8 Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
10.9 Chemical durability of CLS54 sensor . . . . . . . . . . . 79

11 Appendix. . . . . . . . . . . . . . . . . . . . . . . 80

Index . . . . . . . . . . . . . . . . . . . . . . . . . . 84

4 Endress+Hauser
Smartec S CLD134 Safety instructions

1 Safety instructions

1.1 Designated use


Smartec S CLD134 is a field-tested and reliable transmitter used to determine the conductivity of
liquid media.
It is particularly suitable for use in the foodstuffs industry.
Any other use than the one described here compromises the safety of persons and the entire
measuring system and is, therefore, not permitted.
The manufacturer is not liable for damage caused by improper or non-designated use.

1.2 Installation, commissioning and operation


Please note the following items:
• Installation, commissioning, operation and maintenance of the measuring system must only be
carried out by trained technical personnel.
The technical personnel must be authorized for the specified activities by the system operator.
• Electrical connection must only be carried out by a certified electrician.
• Technical personnel must have read and understood these Operating Instructions and must
adhere to them.
• Before commissioning the entire measuring point, check all the connections for
correctness. Ensure that electrical cables and hose connections are not damaged.
• Do not operate damaged products and secure them against unintentional
commissioning. Mark the damaged product as being defective.
• Measuring point faults may only be rectified by authorized and specially trained
personnel.
• If faults can not be rectified, the products must be taken out of service and secured against
unintentional commissioning.
• Repairs not described in these Operating Instructions may only be carried out at the
manufacturer’s or by the service organization.

1.3 Operational safety


The transmitter has been designed and tested according to the state of the art and left the factory in
perfect functioning order.
Relevant regulations and European standards have been met.
As the user, you are responsible for complying with the following safety conditions:
• Installation instructions
• Local prevailing standards and regulations.
Immunity to interference
This instrument has been tested for electromagnetic compatibility in industrial use according to
applicable European standards.
Protection against interference as specified above is valid only for an instrument
connected according to the instructions in these Operating Instructions.

1.4 Return
If the transmitter has to be repaired, please return it cleaned to the sales center responsible. Please
add a detailed failure description. If the failure diagnosis is not clear please send also the cable and
the sensor.
Please use the original packaging, if possible.
Please enclose the completed "Declaration of Hazardous Material and De-Contamination" (copy the
second last page of these Operating Instructions) with the packaging and also the shipping
documents.

Endress+Hauser 5
Safety instructions Smartec S CLD134

1.5 Notes on safety conventions and symbols

Safety symbols

Warning!
# This symbol alerts you to hazards. They can cause serious damage to the instrument or to persons
if ignored.
Caution!
" This symbol alerts you to possible faults which could arise from incorrect operation. They could
cause damage to the instrument if ignored.

! Note!
This symbol indicates important items of information.

Electrical symbols

%
Direct Current (DC)
A terminal at which DC is applied or through which DC flows.

&
Alternating Current (AC)
A terminal at which (sine-form) AC is applied or through which AC flows.

Ground connecting
) A terminal, which, from the user’s point of view, is already grounded using a grounding system.

Protective ground terminal


* A terminal which must be grounded before other connections may be set up.

Alarm relay
b
Input

Output

DC voltage source

Temperature sensor

6 Endress+Hauser
Smartec S CLD134 Identification

2 Identification

2.1 Device designation

2.1.1 Nameplate
Compare the order code on the nameplate (on the Smartec) with the product structure (see below)
and check that it agrees with your order.
You can identify the instrument variant by the order code on the nameplate. Under "Codes", you
can find the release code for the software upgrade "MRS".

Made in Germany, D-70839 Gerlingen


SMARTEC S conductivity
order code CLD134-PMV530AB2
serial no. 1C466C05 G00 codes - / 8833
meas. range 100 µS … 2000 mS/cm
temperature -10 … +125 °C
output 1 0/4 … 20 mA HART
output 2 0/4 … 20 mA
mains 230 VAC 50/60 Hz 7.5 VA

prot. class IP 67
ambient temp. 0 … +55°C .
131085-4D
a0005491

Fig. 1: Nameplate CLD134 (example)

Endress+Hauser 7
Identification Smartec S CLD134

2.1.2 Product structure Smartec S CLD134

Housing
E Transmitter only (without sensor)
P Compact version
W Separate transmitter, cable length 5 m / 16.41 ft
X Separate transmitter, cable length 10 m / 32.81 ft
S Separate transmitter, cable length 20 m / 65.62 ft

Process connection
000 Not selected (transmitter only)
MV5 Dairy fitting DIN 11851, DN 50a)
AA5 Aseptic fitting DIN 11864-1 form A, pipe DIN 11850, DN 50
CS1 Clamp ISO 2852, 2" (long)
SMS SMS 2"b)
VA4 Varivent® N DN 40 to 125
BC5 NEUMO BioControl® D50

Cable entry
3 Cable gland M 20 x 1.5
5 Conduit adapter NPT ½ "

Power supply
0 230 V AC
1 115 V AC
5 100 V AC
8 24 V AC / DC

Current output / communication


AA Current output conductivity, without communication
AB Current output conductivity and temperature, without communication
HA HART, current output conductivity
HB HART, current output conductivity and temperature
PE PROFIBUS-PA, no current output
PF PROFIBUS-PA, M 12 connector, no current output
PP PROFIBUS-DP, no current output

Additional features
1 Basic version
2 Remote parameter set switching
3 Biological reactivity tests according to USP <87>, <88> class VI
4 Remote parameter set switching and biological reactivity tests according to
USP <87>, <88> class VI
5 CRN approval (according to ASME B31.3)c)
6 CRN approval (according to ASME B31.3)c) + Biological reactivity tests
according to USP <87>, <88> class VI

CLD134- complete order code


a)
Dairy pipe fitting DIN 11851 is generally not considered hygienic. With the adapter SKS Siersma,
it meets the 3-A standards requirements.
b)
Process connection is not considered hygienic according to the requirements of EHEDG.
c)
CRN approval only valid for process connections MV5, CS1 and VA4.

8 Endress+Hauser
Smartec S CLD134 Identification

2.1.3 Basic version and function extensions

Functions of the basic version Options and their functions

• Measurement • Second current output for temperature (hardware


• Calibration of cell constant option)
• Calibration of residual coupling • HART communication
• Calibration of installation factor • PROFIBUS communication
• Read instrument parameters Remote parameter set switching (software option):
• Linear current output
• Remote switching of max. 4 parameter sets
• Current output simulation (measuring ranges)
• Service functions • Temperature coefficients can be determined
• Temperature compensation selectable (e.g. 1 free
• Temperature compensation selectable (e.g. 4 free
coefficient table) coefficient tables)
• Concentration measurement selectable (4 defined • Concentration measurement selectable (4 defined
curves, 1 free table)
curves, 4 free tables)
• Relay as alarm contact
• Check of measuring system by PCS alarm (live check)
• Relay can be configured as alarm or limit contact
Biological reactivity according to USP <87>, <88>
class VI

2.2 Scope of delivery


The scope of delivery of the compact version inlcudes:
• Smartec S CLD134 compact measuring system with integrated sensor
• Terminal strip set
• Operating Instructions BA401C/07/en
• Versions with HART communication only:
Operating Instructions Field communication with HART, BA212C/07/en
• Versions with PROFIBUS interface only:
– Operating Instructions Field communication with PROFIBUS, BA213C/07/en
– M12 connector (-******PF* versions only)
The scope of delivery of the separate version includes:
• Smartec S CLD134 transmitter
• CLS54 inductive sensor with fixed cable
• Terminal strip set
• Operating Instructions BA401C/07/en
• Versions with HART communication only:
Operating Instructions Field communication with HART, BA212C/07/en
• Versions with PROFIBUS interface only:
– Operating Instructions Field communication with PROFIBUS, BA213C/07/en
– M12 connector (-******PF* versions only)
The scope of delivery of version "transmitter without sensor" includes:
• Smartec S CLD134 transmitter
• Terminal strip set
• Operating Instructions BA401C/07/en
• Versions with HART communication only:
Operating Instructions Field communication with HART, BA212C/07/en
• Versions with PROFIBUS interface only:
– Operating Instructions Field communication with PROFIBUS, BA213C/07/en
– M12 connector (-******PF* versions only)

Endress+Hauser 9
Identification Smartec S CLD134

2.3 Certificates and approvals


Declaration of conformity
The product meets the legal requirements of the harmonized European standards. It thus complies
with the legal requirements of the EC directives.
The manufacturer confirms successful testing of the product by affixing the 4 symbol.
FDA
All materials in contact with medium are listet at FDA.

EHEDG
The sensor CLS54 has been certified for in-place cleanability according to EHEDG document 2.

! Note!
The cleanability of a sensor also depends on the way of installation. To install the sensor in a pipe
system use the appropriate and EHEDG certified flow assembly for the respective process
connection.

3-A
Certified according to 3-A Standard 74-03 ("3-A Sanitary Standards for Sensor and Sensor Fittings
and Connections Used on Milk and Milk Products Equipment").

Biological reactivity (USP class VI) (optional)


Certificate on biological reactivity tests according to USP (United States Pharmacopeia) part <87>
und part <88> class VI with traceability of the materials in contact with medium.

Pressure approval
Canadian pressure approval for pipes according to ASME B31.3

10 Endress+Hauser
Smartec S CLD134 Installation

3 Installation

3.1 Quick installation guide


The following procedure should be followed for a complete measuring point installation:
Compact version:
• Perform an air set. Install the compact version at the measuring point (see chapter "Mounting
CLD134 compact version").
• Connect the compact version as described in the chapter "Electrical connection".
• Start up the compact version as described in the chapter "Commissioning".
Separate version:
• Mount the transmitter (see chapter "Mounting CLD134 separate version").
• If you have not yet installed the sensor at the measuring point, perform an Airset and install the
sensor (see the Technical Information of the sensor).
• Connect the sensor to the Smartec S CLD134 as described in the chapter "Electrical connection".
• Connect the transmitter as described in the chapter "Electrical connection".
• Start up the Smartec S CLD134 as described in the chapter "Commissioning".

3.1.1 Measuring system


A complete measuring system comprises:
• the Smartec S CLD134 transmitter (separate version)
• the CLS54 conductivity sensor with integrated temperature sensor and fixed cable
or
• the CLD134 compact version with integrated CLS54 conductivity sensor
Optional for the separate version: CLK5 extension cable, VBM junction box, mounting kit for pipe
mounting

B
ENDRESS+HAUSER
SMARTEC S

ALARM
CAL +
E –

a0005438

Fig. 2: Complete measuring systems Smartec S CLD134 as separate transmitter and compact version
A CLS54 conductivity sensor
B Smartec S CLD134 transmitter
C Smartec S CLD134 compact version with integrated CLS54

Endress+Hauser 11
Installation Smartec S CLD134

3.2 Incoming acceptance, transport, storage


• Make sure the packaging is undamaged!
Inform the supplier about damage to the packaging. Keep the damaged packaging until the matter
has been settled.
• Make sure the contents are undamaged!
Inform the supplier about damage to the delivery contents. Keep the damaged products until the
matter has been settled.
• Check that the scope of delivery is complete and agrees with your order and the shipping
documents.
• The packaging material used to store or to transport the product must provide shock protection
and humidity protection. The original packaging offers the best protection. Also, keep to the
approved ambient conditions (see "Technical data").
• If you have any questions, please contact your supplier or your sales center responsible.

3.3 Installation conditions

3.3.1 Notes on installation


Installation positions
The sensor has to be immersed completely into the media. Avoid bubbles in the area of the sensor.

! Note!
For use in hygienic applications only use materials that comply with 3-A standards 74-03 and the
FDA requirements. The cleanability of a sensor also depends on the way of installation. To install
the sensor in a pipe system use the appropriate and EHEDG certified flow assembly for the
respective process connection.

a0005442

Fig. 3: Installation positions of conductivity sensors


A Not for hygienic applications

Air set
Perform an air set before sensor installation (see chapter "Calibration"). Make sure that the
instrument is ready for operation, i.e. mains and sensor are connected.

12 Endress+Hauser
Smartec S CLD134 Installation

Wall distance
The sensor’s distance from the pipe wall affects the measuring accuracy (see Fig. 5).

In narrow installation conditions, the ion flow


in the medium is affected by the pipe walls.
This effect is compensated by the so-called
installation factor.
When the distance from the wall is sufficient,
i.e. a > 15 mm / 0.59", the installation factor
can be ignored (f = 1.00). When the wall
distance is lower, the installation factor
increases in the case of electrically insulating
pipes (f > 1) while it decreases for electrically
conductive pipes (f < 1); see Fig. 5.

a
The determination of the installation factor is a0005440

described in the chapter "Calibration". Fig. 4: Installation of CLD134


a Wall distance

1.40
2

1.20

1.00

1
0.80
0 5 10 15 20 25 a [mm]

0.20 0.39 0.59 0.79 0.98 a [inch]


a0005441

Fig. 5: Relationship between installation factor and distance from wall a


1 Electrically conductive pipe wall
2 Insulating pipe wall

Endress+Hauser 13
Installation Smartec S CLD134

3.3.2 CLD134 separate version

142 / 5.59

160 / 6.30
225 / 8.86 Ø 7 / 0.28

225 / 8.86

175 / 6.89

95 / 3.74

mm /inch
a0005632

Fig. 6: CLD134 wall mounting with mounting plate

109 / 4.29

Ø max. 60 /
Ø max. 2.36
95 / 3.74

170 / 6.69

mm / inch
a0005633

Fig. 7: CLD134 mounting on pipes Ø 60 mm (2.36")

14 Endress+Hauser
Smartec S CLD134 Installation

133.7/5.26
54.5/2.15
Ø 64/2.52

58/2.28
78.5/3.09
9/
Ø 5
0.3
28.5/1.12 33/1.30

Ø 6/0.24 10.2/0.40 mm/inch


11.5/0.45
a0005429

Fig. 8: Dimensions CLS54 (long version)

Conductivity sensors for the separate transmitter


CLS54 conductivity sensors with various process connections covering all common installation
conditions are available for the separate version.

A B

133.7/5.26 133.7/5.26

Ø 89.5/
Ø 84/
3.52
17.7/0.70 3.31 12.5/0.49
0 0
16/0.63 16/0.63
36.5/1.44 36.5/1.44
Ø 6/0.24 mm/inch Ø 6/0.24
a0004949

Fig. 9: Process connections CLS54 (short version)

A NEUMO BioControl D50


for pipe connection: DN 40 (DIN 11866 series A, DIN 11850)
DN 42,4 (DIN 11866 series B, DIN EN ISO 1127)
2" (DIN 11866 series C, ASME-BPE)
B Varivent N DN 40 to 125

Endress+Hauser 15
Installation Smartec S CLD134

A B
133.7/5.26 133.7/5.26

11/0.43 4/0.16 Ø 51/2.01


0 0 Ø 65/2.56
62.6/2.46

58/2.28 58/2.28
78.5/3.09 78.5/3.09

C D
133.7/5.26 133.7/5.26

54.5/2.15
2.85/0.11 64/2.52
0 0 66.85/2.63

58/2.28 58/2.28
78.5/3.09 mm/inch 78.5/3.09
a0005436

Fig. 10: Process connections CLS54 (long version)


A Dairy pipe fitting DIN 11851, DN 50 (union nut is included)
B SMS 2" (union nut is included)
C Clamp ISO 2852, 2"
D Aseptic- fitting DIN 11864-1 form A, for pipe according to DIN 11850, DN 50

16 Endress+Hauser
Smartec S CLD134 Installation

3.3.3 CLD 134 compact version


225/8.86

176.6/6.95
207/8.15
9/
Ø 35
0.

***
33/1.30
142/5.59
10.2/0.40

95/3.74
mm/inch

28.5/1.12

a0005500
Fig. 11: Dimensions of CLD134 compact version
*** depending on ordered process connection

Process connections
Various process connections covering all common installation conditions are available for the
compact version.
The compact version is installed at the measuring point with the required process connection.

A B

Ø 89.5/
Ø 84/
3.52
17.7/0.70 3.31 12.5/0.49
0 0
16/0.63 16/0.63
9/ 36.5/1.44 9/
Ø 35 Ø 35 36.5/1.44
0. Ø 6/0.24 mm/inch 0.
Ø 6/0.24
a0005501
Fig. 12: Process connections compact version (short)
A NEUMO BioControl D50
for pipe connection: DN 40 (DIN 11866 series A, DIN 11850)
DN 42,4 (DIN 11866 series B, DIN EN ISO 1127)
2" (DIN 11866 series C, ASME-BPE)
B Varivent N DN 40 to 125

Endress+Hauser 17
Installation Smartec S CLD134

A B

11/0.43 4/0.16 Ø 51/2.01


0 0 Ø 65/2.56
62.6/2.46
9/ 9/
Ø 35 Ø 35
0. 0.
58/2.28 58/2.28
78.5/3.09 78.5/3.09
10.2/0.40 10.2/0.40

C D

54.5/2.15
2.85/0.11 64/2.52
0 0 66.85/2.63

9/ 9/
Ø 35 Ø .35
0. 0
58/2.28 58/2.28
78.5/3.09 78.5/3.09
10.2/0.40 10.2/0.40

mm/inch
a0005502

Fig. 13: Process connections compact version (long)


A Dairy pipe fitting DIN 11851 DN 50 (union nut is included)
B SMS 2" (union nut is included)
C Clamp ISO 2852, 2"
D Aseptic fitting DIN 11864-1 form A, for pipe according to DIN 11850, DN 50

18 Endress+Hauser
Smartec S CLD134 Installation

3.4 Installation instructions

3.4.1 Mounting CLD134 separate version


Wall mounting
For wall mounting, attach the mounting plate to the wall by drilling holes as required. Anchors and
screws are to be provided by the operator.

142 / 5.59

160 / 6.30
Ø 7 / 0.28
225 / 8.86

225 / 8.86

175 / 6.89 95 / 3.74

mm /inch
a0005632

Fig. 14: Wall mounting of CLD134 separate version

! Note!
Wall mounting is not recommended for hygienic sensitive areas.

Endress+Hauser 19
Installation Smartec S CLD134

Post mounting
A mounting kit for installing the housing on horizontal or vertical posts or pipes (max. Ø 60 mm /
Ø 2.36")

a0004902

Fig. 15: Mounting kit for installing the CLD134 separate version on posts

! Note!
For use in hygienic sensitive areas, shorten the threads as much as possible.
1. Remove the mounting plate.
2. Insert the holding bars through the pre-drilled holes of the mounting plate and screw the
mounting plate onto the transmitter.
3. Use the brackets to install the Smartec S on the post or pipe (Fig. 16).

 max. 60 / 2.36

mm / inch
a0005634

Fig. 16: Post mounting of CLD134 separate version

20 Endress+Hauser
Smartec S CLD134 Installation

3.4.2 Mounting CLD134 compact version or CLS54 sensor for


separate version

! Note!
Perform an Airset and calibrate the sensor before installing the compact version or the sensor.
Install the compact version or the CLS54 sensor directly on the pipe or vessel socket via the process
connection (depending on ordered version).
1. When installing the Smartec S CLD134 or the sensor, make sure that the flow opening of the
sensor is oriented in the flow direction of the medium. An orientation arrow on the sensor
facilitates orientation.
2. Tighten the flange.

! Note!
• Choose the immersion depth of the sensor in the medium such that the coil body is completely
immersed.
• Please observe the notes on the wall distance in the chapter "Installation conditions".
• Please observe the limits for the medium and ambient temperature when using the compact
version (see chapter "Technical data").

Sensor positioning: compact version


The sensor in the compact housing must be oriented in the flow direction.
If you need to reorient the sensor in relation to the housing, proceed as follows:
1. Remove the cover.
2. Loosen the screws of the electronics box and carefully remove the box from the housing.
3. Loosen the three sensor fastening screws until the sensor can be turned.
4. Align the sensor and tighten the screws. Do not exceed the maximum torque of 1.5 Nm!
5. Reassemble the transmitter housing in reverse sequence of operations.

! Note!
For exact positions of the electronics box and the sensor screws, see the exploded view in the
chapter "Spare parts".

A B

a0005635

Fig. 17: Sensor orientation in the transmitter housing


A Standard orientation
B Sensor turned by 90°

3.5 Post-installation check


• After installation, check the measuring system for damages.
• Check the sensor orientation to the flow direction of the medium.
• Check that the coil body of the sensor is completely immersed in the medium.

Endress+Hauser 21
Wiring Smartec S CLD134

4 Wiring

4.1 Electrical connection


# Warning!
• The electrical connection must only be carried out by a certified electrician.
• Technical personnel must have read and understood the instructions in this manual and must
adhere to them.
• Ensure that there is no voltage at the power cable before beginning the connection work.

4.1.1 Electrical connection of transmitter


Proceed as follows to connect the Smartec S CLD134:

1. Loosen the 4 Phillips screws on the housing


cover and remove the cover.
2. # Warning!
Do not remove the cover frame while the
instrument is energized!
1
Remove the cover frame from the terminal
blocks. To do this, introduce a screwdriver in
the recess (A) according to Fig. 18 and push
the tab inward (B).
3. Thread the cables through the open cable
glands into the housing according to the A
terminal assignments in Fig. 19.
4. Connect the power wires according to the B
terminal assignments in Fig. 20.
5. Connect the alarm contact according to the
terminal assignments in Fig. 20.
6. Connect the housing ground. 2
7. Separate version: Connect the sensor
according to the terminal assignments in 3
Fig. 20.
In the case of the separate version, the 4
conductivity sensor CLS54 is connected using
5
the shielded multi-core special cable CLK5.
Preparation instructions are supplied with the a0005636

cable. Use junction box VBM (see chapter Fig. 18: View of housing with cover removed
"Accessories") to extend the measuring cable. 1 Cover frame
The maximum cable length if extended using 2 Fuse
a junction box is 55 m (180 ft.). 3 Removeable electronics box
4 Terminals
8. Tighten the cable glands firmly. 5 Housing ground

22 Endress+Hauser
Smartec S CLD134 Wiring

A B
1 2 3

1 2 3

5 4

6 5 4

a0005439

Fig. 19: Terminal assignments of cable glands on Smartec S CLD134


A Separate version B Compact version
1 Cable gland for analog output, binary input 1 Cable gland for analog output, digital input
2 Cable gland for alarm contact 2 Cable gland for alarm contact
3 Cable gland for power supply 3 Cable gland for power supply
4 Housing ground 4 Housing ground
5 Pressure comp. element PCE (Goretex®- filter) 5 Pressure comp. element PCE (Goretex®- filter)
6 Cable gland for sensor connection, M 16x1.5
Wiring diagram

Alarm
(contact position: no current)

Screen
15 84 12 13 11 16 83 S 42 43 41 ( (
Screen

31 32 33 34 85 86 93 94 81 82
YE GN Coax BN
Coax
WH RD GN/YE

BN
(unused) BU
WH outer
screen
PE

CLK 5
Pg 13.5 Pg 13.5

CLK5
with CLS54 sensor Power supply
a0005637-en

Fig. 20: Electrical connection of Smartec S CLD134

Endress+Hauser 23
Wiring Smartec S CLD134

Connection diagram

84
31
mA 15
A 32 16 F
Lf
83

33 optional S
mA
B 34
11
12
G
13

85
C 15 V
86

93 41
42
D 10-50 V H
94 43

81
~

~
– I
E 10-50 V
82

PE

a0004895

Fig. 21: Electrical connection of Smartec S CLD134


A Signal output 1 conductivity F Conductivity sensor
B Signal output 2 temperature G Temperature sensor
C Auxiliary power output H Alarm (contact position: no current)
D Binary input 2 (MRS1+2) I Power supply
E Binary input 1 (hold / MRS 3+4) MRS Remote parameter set switching (measuring range
switching)

Connection of binary inputs

A B
D1 D2

15 V

85 86 81 82 93 94

S1 S2

a0005639

Fig. 22: Connection of binary inputs when using external contacts


A Auxiliary power output
B Contact inputs D1 and D2
S1 External contacts, not energized
S2 External contacts, not energized

24 Endress+Hauser
Smartec S CLD134 Wiring

Connection compartment sticker

131082-4A

Sensor
31 + 15
Lf
32 - 84

33 + 12 WH
Temp.
34 - (opt.) 13 YE

NC 11 GN

85 + 16
+15V
86 - 10mA 83

93 + S
Bin 2
94 - 42

81 + 43
Bin 1
82 - 41

NC ~
– Mains
NC ~
– Hilfsenergie

a0005644

Fig. 23: Connection compartment sticker of Smartec S

! Note!
The protection class of this instrument is I. The metal housing must be connected to PE.

" Caution!
• Terminals designated as NC may not be switched.
• Undesignated terminals may not be switched.

Endress+Hauser 25
Wiring Smartec S CLD134

Structure and termination of measuring cable

Semiconductor (84) (83)


screen

Screen Screen
S 11 12 13 83 16 15 84
(15) (16)
GN WH YE BU RD RD BU
WH
RD RD WH
GN (11)
WH (12) BN CLK5
(unused)
YE (13)

CLK5

a0005640-en a0004906

Fig. 24: Structure of CLK5 measuring cable Fig. 25: Electrical connection of the CLS54 sensor for
the separate version

Install the ready-made special measuring cable


as shown in the figure:
• Insert the cable through a cable gland into the
wiring compartment.
• Strip approx. 3 cm (1.2 ") of the braided
screen and fold it back over the cable
GY
insulation.
• Push the crimping ring attached to the
supplied screen connection over the prepared
S/ braided screen and pull the ring tight with a
pair of pliers.
• Connect the litz wire to the screen
connection.
a0005043
• Connect the remaining wires according to the
Fig. 26: Screen connection CLK5 connection diagram.
• Tighten the cable gland.

4.2 Alarm contact


A B

41 41

42 42

43 43
C07-CLD132xx-04-06-00-xx-005.eps

Fig. 27: Recommended fail-safe circuit for an alarm contact


A Normal operating state B Alarm state

Normal operating state Alarm state


• Instrument in operation • Error message available (Alarm LED red)
• No error message available (Alarm LED off) or
È Relay picked up • Instrument defective or voltage-free (Alarm LED
È Contact 42/43 closed off)
È Relay dropped out
È Contact 41/42 closed

26 Endress+Hauser
Smartec S CLD134 Wiring

4.3 Post-connection check


After wiring up the electrical connection, carry out the following checks:

Device status and specifications Remarks

Are the transmitter or the cable externally damaged? Visual inspection

Electrical connection Remarks

Are the installed cables strain-relieved?

No loops and cross-overs in the cable run?

Are the signal cables correctly connected acc. to the wiring diagram?

Are all screw terminals tightened?

Are all cable entries installed, tightened and sealed?

Are the PE distributor rails grounded (if present)? Grounding at place of installation

Endress+Hauser 27
Operation Smartec S CLD134

5 Operation

5.1 Quick operation guide


You have the following options of operating Smartec S:
• Local operation via operating keys
• Via HART® interface (optional, for corresponding order version) via:
– HART® hand-held terminal or
– PC with HART® modem and Commuwin II software
• Via PROFIBUS PA/DP (optional, for corresponding order version)
PC with a corresponding interface and the Commuwin II software (see "Accessories") or via
programmable logic controller (PLC).

! Note!
For operation via HART or PROFIBUS PA/DP, read the corresponding chapters in the additional
operating instructions:
• PROFIBUS PA/DP, field communication with Smartec S CLD134, BA213C/07/en
• HART®, field communication with Smartec S CLD134, BA212C/07/en
The following chapters describe local operation via operating keys.

5.2 Display and operating elements

5.2.1 Display
LED indicators

Alarm indication for continuous limit violation, temperature sensor failure


or system errors (see error list in chapter "Troubleshooting").

Liquid crystal display

1 2 3 4 5

7
14
mS/cm
2000 O213
8

20 mA
13 9

12 11 10
a0005645

Fig. 28: LCD of Smartec S CLD134


1 Measuring mode indicator (normal operation) 8 In measuring mode: variable measured
2 Calibration mode indicator In setup mode: parameter adjusted
3 Calibration complete indicator 9 Function coding display
4 Setup mode indicator (configuration) 10 In measuring mode: secondary measured value
5 "Hold" mode indicator (outputs reflect last current In setup / calibr. mode: e.g. parameter
status) 11 Manual / automatic temperature compensation
6 Signal reception indicator for units with display
communication 12 Error indicator
7 Indication of relay state: d inactive, c active 13 Sensor symbol, flashes during calibration
14 In measuring mode: Main measured valued
In setup / calibr. mode: e.g. parameter

28 Endress+Hauser
Smartec S CLD134 Operation

5.2.2 Operating elements


The operating keys are located underneath the housing cover. The display and the alarm LED are
visible through the viewing window. For operation, open the housing cover by removing the 4
screws.

mS/cm
2000 O213

20 mA
ENDRESS+HAUSER
SMARTEC S

ALARM
CAL + 4

E – 3
2
a0004899

Fig. 29: Operating elements of Smartec S CLD134


1 Liquid crystal display showing measured values and configuration data
2 4 operating keys for calibration and instrument configuration
3 Field for user labeling
4 LED indicator for alarm function

5.2.3 Key assignment

CAL key
When the CAL key is pressed, the instrument prompts for the calibration
access code:
• Code 22 for calibration
• Code 0 or any other number to view the calibration data
Use the CAL key to acknowledge calibration data and to continue through
the calibration process.
ENTER key
When the ENTER key is pressed, the instrument prompts for the setup
access code:
• Code 22 for setup and configuration
• Code 0 or any other number to view the configuration data.
The ENTER key has several functions:
• It calls up the setup menus from the measuring mode
• It is used to store (acknowledge) data entered in setup mode
• It is used to move on within function groups

Endress+Hauser 29
Operation Smartec S CLD134

PLUS key and MINUS key


In setup mode, the PLUS and MINUS keys have the following functions:
• Selection of function groups
! Note!
To select function groups in the order given in the chapter "Instrument
configuration", use the MINUS key.
• Setting of parameters and numeric values
In measuring mode, repeatedly pressing the PLUS key displays the
following settings in sequence:
1. Temperature display in °F
2. Hide temperature display
3. Display of uncompensated conductivity value
4. Back to basic setting
In measuring mode, repeatedly pressing the MINUS key displays the
following settings in sequence:
1. Display of current measuring range
2. Display of current errors in sequence (max. 10)
3. After all errors are displayed, the standard display is shown again. In
function group F, you can define an alarm for each error code.
Escape function
Press the PLUS and MINUS keys simultaneously to return to the main
menu. During calibration, this key combination goes directly to the end of
calibration. When the PLUS and MINUS keys are pressed once more, the
instrument returns to the measuring mode.

Locking the keypad


Pressing the PLUS and ENTER keys simultaneously for minimum 3s locks
the keypad against unintentional entries. However, all settings can still be
read.
The code prompt displays the code 9999.

Unlocking the keypad


Pressing the CAL and MINUS keys simultaneously for minimum 3s unlocks
the keypad.
The code prompt displays the code 0.

30 Endress+Hauser
Smartec S CLD134 Operation

5.3 Local operation

5.3.1 Operating concept

Operating modes

Measuring mode:
standard mode of
operation, displaying
current measured values

Calibration mode: Setup mode


execution of access to all
calibration routine configuration
settings

Code

The function groups


are selected with the
PLUS or MINUS key.
C07-CLD132xx-19-06-00-en-002.eps

Fig. 30: Description of operating modes

! Note!
If no key is pressed for 15 min. in setup mode, the instrument automatically switches back to the
measuring mode. An active Hold function (Hold at Setup) is then reset.

Access codes
All instrument access codes are fixed, i.e. they cannot be modified. When the instrument requests
the access codes, it recognizes the difference between codes.
• CAL key + Code 22: access to calibration and offset menus.
• ENTER key + Code 22: access to the configuration menus, allowing configuration and
user-specific settings.
• PLUS + ENTER keys: locks the keypad.
• CAL + MINUS keys: unlocks the keypad.
• CAL or ENTER key + any code: access to Read mode, i.e. all settings can be read but not
changed.

Endress+Hauser 31
Operation Smartec S CLD134

Menu structure
The configuration and calibration functions are arranged in a menu structure by function groups.
The function groups are selected in the setup mode with the PLUS and MINUS keys. The ENTER
key is used to move from one function to the next within a function group.
The PLUS and MINUS keys are used for option selection and editing. Selections must be confirmed
by pressing the ENTER key. This also moves the cursor to the next function.
Pressing the PLUS and MINUS keys at the same time terminates programming (return to main
menu).
When the PLUS and MINUS keys are pressed once more, the instrument returns to the measuring
mode.

! Note!
• If a change is made but not confirmed by pressing the ENTER key, the previous setting is retained.
• See the appendix of these operating instructions for an overview of the Smartec menu structure.

1
-

E E E
E E

C07-CLD132xx-19-06-00-xx-010.eps

Fig. 31: Schematic of the Smartec menu structure

Hold function: "Freezing" the outputs


The current output can be “frozen” in the setup mode and during calibration, i.e. the last current
value is constantly output. The display shows the “HOLD” message.

! Note!
• Hold settings can be found in the chapters "Service" and "Remote parameter set switching
(measuring range switching, (MRS)".
• During “HOLD” in the measuring mode the contact will go to the normal position if it is
configured as a limit contact.
• An active hold has priority over all other automatic functions.
• A possibly accumulated alarm delay is reset to “0”.
• The hold function can also be activated externally via the hold input (see wiring diagram; binary
input 1).
• The manual hold (field S5) remains active even after a power failure.

32 Endress+Hauser
Smartec S CLD134 Commissioning

6 Commissioning

6.1 Function check


# Warning!
• Check all connections for correctness.
• Make sure that the supply voltage is identical to the voltage indicated on the nameplate!

6.2 Start-up

Before first start-up, make sure you understand Setup mode


how to operate the transmitter. You should • SETUP 1 (A)
make particular reference to chapters 1 (Safety • SETUP 2 (B)
instructions) and 5 (Operation). • OUTPUT (O)
After power-up (connection to power), the • ALARM (F)
instrument performs a self-test and then enters • CHECK (P)
the measuring mode. • RELAY (R)
Calibrate the sensor as described in the chapter • ALPHA TABLE (T)
"Calibration". • CONCENTRATION (K)
• SERVICE (S)
! Note!
• E+H SERVICE (E)
During first start-up, calibration of the sensor is
absolutely required to enable the measuring • INTERFACE (I)
system to perform accurate measurement. • TEMPERATURE COEFFICIENT (D)
• MRS (M)
Configure the transmitter as described in the
chapter "Quick setup". The values set by the Calibration mode
user are kept even in the event of a power • CALIBRATION (C)
failure.
The following function groups are available on
the Smartec S CLD134 (the function groups that
are only available on the version equipped with
the function extension are marked accordingly
in the function descriptions):

Function display:
The displayed code indicates
s the function position in the
2 F3 function group.

Err.delay Additional information

C07-CLD132xx-07-06-00-en-003.eps

Fig. 32: Example for display in setup mode

Selecting and locating functions is facilitated by


a code displayed for each function in a special
C131 C132 C133 display field Fig. 32.
The structure of this coding is given in Fig. 33.
C121 The first column indicates the function group as
a letter (see group designations). The functions
C C1 C111 in the individual groups are counted from the
top to the bottom and from the left to the right.
C07-CLD132xx-13-06-00-xx-005.eps

Fig. 33: Function coding

For a detailed description of the function groups available on the Smartec S CLD134 see the chapter
"Instrument configuration".

Endress+Hauser 33
Commissioning Smartec S CLD134

Factory settings
When the instrument is switched on for the first time, the factory settings are in effect. The
following table provides an overview of all major settings.
Please refer to the description of the individual functions in the chapter "Instrument configuration"
for all other factory settings (the factory settings are printed in bold letters).

Function Factory setting

Type of measurement Inductive conductivity measurement,


temperature measurement in °C

Temperature compensation type Linear with reference temperature 25 °C (77 °F)

Temperature compensation Automatic (ATC on)

Relay function Alarm

Hold Active during configuration and calibration

Measuring range 10 μS/cm to 2000 mS/cm (measuring range set automatically)

Current outputs 1* and 2* 4 to 20 mA

Current output 1: measured value for 4 mA 0 μS/cm


signal current*

Current output 1: measured value for 20 mA 2000 mS/cm


signal current*

Current output 2: measured value for 4 mA 0.0 °C (32 °F)


signal current*

Current output 2: measured value for 20 mA 150.0 °C (302 °F)


signal current*

* if equipped accordingly

34 Endress+Hauser
Smartec S CLD134 Commissioning

6.3 Quick setup


After switching the transmitter on, configure the major functions required for accurate
measurement. The following section gives you an example for a basic configuration.

Input Selection or range Display


(factory setting bold)

1. Press the ENTER key.


2. Enter the code 22 to be able to edit the setup. Press
the ENTER key.

3. Press the MINUS key several times until the "Service"


function group is displayed. S

4. Press the ENTER key to edit this function group.


SERVICE
ENG = English
GER = German
5. Select your language, e.g. "ENG" for English.
Confirm your entry be pressing the ENTER key.
FRA = French
ITA = Italian
ENG S1

NEL = Dutch
ESP = Spanish Language
6. Press the PLUS and MINUS keys simultaneously to
quit the "Service" function group.

7. Press the MINUS key several times until the "Setup 1"
function group is displayed. A

8. Press the ENTER key to edit "Setup 1".


SETUP 1

9. In A1, select the operating mode, e.g.


"cond" = conductivity.
cond = conductivity
conc = concentration
cond A1
Confirm your selection by pressing the ENTER key.
Oper.Mode
%
ppm
10. In A2, press the ENTER key to confirm the factory
setting.
mg/l
TDS = Total Dissolved
ppm A2
Solids
none
Conc.Unit

XX.xx
11. In A3, press the ENTER key to confirm the factory
setting.
X.xxx
XXX.x
XX.xx A3
XXXX
Format

auto, μS/cm, mS/cm,


12. In A4, press the ENTER key to confirm the factory
settting.
S/cm, μS/m, mS/m, auto A4
S/m
Unit

13. In A5, enter the cell constant for the connected 1/cm
sensor. Refer to the sensor’s or the compact version’s 0.10 ... 6.3 ... 99.99 6.300 A5
quality certificate for the exact value.
Cellconst

Endress+Hauser 35
Commissioning Smartec S CLD134

Input Selection or range Display


(factory setting bold)

14. In A6, press the ENTER key to confirm the factory


setting.
If your wall distance is smaller than 15 mm / 0.59", 0.10 ... 1 ... 5.00 1.000 A6
refer to the chapters 3.3.1 and 6.4.14 for information
on determining the installation factor. InstFac

15. If you are working in applications that fluctuate a


great deal and you need to stabilize the display, enter
the required damping factor in A7.
1
1 ... 60
1 A7
Confirm your entry by pressing ENTER.
The display returns to the inital display of "Setup 1". Damping

16. Press the MINUS key to go to the "Setup 2" function


group. B

17. Press the ENTER key to edit "Setup 2".


SETUP 2

18. In B1, select the temperature sensor of your


Pt100
conductivity sensor. By default, your measuring
system is supplied with the CLS54 sensor with
Pt1k = Pt 1000
NTC30
Pt1k B1
Pt 1000 temperature sensor.
Confirm your entry by pressing ENTER.
fixed
ProcTemp.

19. In B2, select the appropriate temperature none


compensation for your process, e.g. "lin" = linear. lin = linear
Confirm your selection by pressing ENTER. NaCl = common salt lin B2
For detailed information on temperature (IEC 60746)
compensation, see chapter 6.4.2. Tab 1 ... 4 TempComp.

20. In B3, enter the temperature coefficient α.


%/K
Confirm your entry by pressing ENTER.
For detailed information on determining the
2.1 %/K
0.0 ... 20.0 %/K
2.10 B3
temperature coefficient, see chapters 6.4.2 or 6.4.12.
Alpha val

21. The real temperature is displayed in B5. If necessary,


Display and entry of real °C
calibrate the temperature sensor to an external
measurement.
temperature 0.0 B5
-35.0 ... 250.0 °C
Confirm your entry by pressing ENTER.
RealTemp.

22. The difference between the measured and the entered


temperatures is displayed. °C
Press the ENTER key.
0.0 °C
-5.0 ... 5.0 °C
0.0 B6
The display returns to the initial display of the
"Setup 2" function group. TempOffs.

23. Press the MINUS key to go to the "Output" function


group. O

24. Press the ENTER key to edit the output settings.


OUTPUT

25. In O1, select your output, e.g. "out1" = output 1.


Confirm your selection by pressing ENTER.
out 1
out 2
out1 O1
Sel. Out

36 Endress+Hauser
Smartec S CLD134 Commissioning

Input Selection or range Display


(factory setting bold)

26. In O2, select the linear characteristic.


Confirm your selection by pressing ENTER.
lin = linear (1)
sim = simulation (2)
lin O2
Sel.Type

27. In O211, select the current range for your output,


e.g. 4 ... 20 mA.
4 ... 20 mA
0 ... 20 mA
4-20 O211
Confirm your selection by pressing ENTER.
Sel.Range

28. In O212, enter the conductivity corresponding to the


0.00 μS/cm µS/cm
minium current value at the transmitter output, e.g.
0 μS/cm.
0.00 μS/cm ... 0 O212
2000 mS/cm
Confirm your entry by pressing ENTER.
0/4 mA
29. In O213, enter the conductivity corresponding to the
maximum current value at the transmitter output,
2000 mS/cm mS/cm
e.g. 930 mS/cm.
Confirm your entry by pressing ENTER.
0.0 μS/cm ... 930 O213
2000 mS/cm
The display returns to the initial display of the
"Output" function group.
20 mA
30. Press the PLUS and MINUS keys simultaneously to
return to measuring mode.

! Note!
You must perform an air set before installing the sensor. To do so, refer to the chapter "Calibration".

Endress+Hauser 37
Commissioning Smartec S CLD134

6.4 Instrument configuration


The following sections give a detailed description of all Smartec S CLD134 functions.

6.4.1 Setup 1 (conductivity, concentration)


In the SETUP 1 function group, you can change the operating mode and the sensor settings.
You have already made all settings of this menu during the quick setup but you can modify the
settings at any time.

Coding Field Selection or range Display Info


(factory settings bold)

Function group
A A Basic settings.
SETUP 1
SETUP 1
Display varies depending on instrument
version:
– cond
A1 Select operating mode
cond = conductivity
conc = concentration
cond A1 – conc

Oper.Mode "Any change


Caution!
in operating mode causes an
automatic reset of user settings.

%
ppm
A2
Select concentration
unit to be displayed
mg/l ppm A2
TDS = Total Dissolved Solids
none Conc.Unit

XX.xx
A3
Select display format
for concentration unit
X.xxx
XXX.x
XX.xx A3
XXXX
Format

Select unit to be
A4 displayed for
auto, μS/cm, mS/cm, S/cm,
μS/m, mS/m, S/m
auto A4 When “auto” is selected, the maximum
resolution possible is automatically selected.
conductivity
Unit

1/cm For the exact value of the cell constant, refer


A5
Enter cell constant for
connected sensor
0.10 ... 6.3 ... 99.99 6.300 A5 to the sensor’s or the compact version’s
quality certificate.
Cellconst

This is where the installation factor is edited.


A6 Installation factor 0.10 ... 1 ... 5.00 1.000 A6 The correct factor is determined in C1(3), see
chapter "Calibration" or referring to the
InstFac installation factor diagram.

Measured value damping causes averaging


over the specified number of individual
A7
Enter measured value
damping
1
1 ... 60
1 A7 measured values. It is used, for example, to
stabilize the display with applications that

Damping fluctuate a great deal.


There is no damping if “1” is entered.

38 Endress+Hauser
Smartec S CLD134 Commissioning

6.4.2 Setup 2 (temperature)


The temperature compensation only needs to be performed in the conductivity mode (selection in
field A1).
The temperature coefficient specifies the change in conductivity per degree of temperature change.
It depends on the chemical composition of the medium and the temperature itself.
In order to compensate for this dependence, three different compensation types can be selected in
the Smartec S:

Linear temperature compensation


k*
The change between two temperature points is
considered to be constant, i.e. α = const. The
α value can be edited for the linear
compensation type. The reference temperature is
25 °C (77 °F). a

T
C07-CLD132xx-05-06-00-xx-009.eps

Fig. 34: Linear temperature compensation


* uncompensated conductivity

NaCl compensation
2,7
a [%/K]
The NaCl compensation (according to IEC
60746) is based on a fixed nonlinear curve that
defines the relationship between the temperature
coefficient and the temperature. This curve is 2,5
used for lower concentrations of up to approx.
5 % NaCl.

2,3

2,1
0 48 96 144

T [°C]
C07-CLD132xx-05-06-00-xx-010.eps

Fig. 35: NaCl compensation

Temperature compensation with table


When using the alpha table function for temperature compensation, the following conductivity data
of the process medium to be measured are required:
Value pairs of temperature T and conductivity κ with:
• κ(T0) for the reference temperature T0
• κ(T) for temperatures which occur in the process

Endress+Hauser 39
Commissioning Smartec S CLD134

A B
 a
k1

a2
k(T0)
a1
k2

T1 T0 T2 T T1 T2 T
C07-CLD132xx-05-06-00-xx-011.eps

Fig. 36: Determination of temperature coefficient


A Required data
B Calculated α values

Use the following formula to calculate the α values for the temperatures occurring in your process:

a = 100% . k(T) - k(T0) ; T ¹ T0


k(T0) T - T0
Enter the α−T value pairs calculated with this formula in the fields T5 and T6 of the function group
ALPHA TABLE.
In the SETUP 2 function group, you can change the settings for temperature measurement.
You have already made the settings of this function group during quick setup but you can modify
the settings at any time.

Coding Field Selection or range Display Info


(factory settings bold)

Function group
B B Settings for temperature measurement.
SETUP 2

SETUP 2

Pt100
If set to "fixed":
B1
Select temperature
sensor
Pt1k = Pt 1000
NTC30
Pt1k B1 no temperature measurement, a fixed
temperature value is entered instead.
fixed
ProcTemp.

This option is not displayed for concentration


none
measurement.
B2
Select temperature
compensation type
lin = linear
NaCl = common salt (IEC 60746)
lin B2 The options Tab 2 ... 4 are only available for
transmitters with the "Remote measuring
Tab 1 ... 4
TempComp. range switching" upgrade.

%/K
B3
Enter temperature
coefficient α
2.1 %/K
0.0 ... 20.0 %/K
2.10 B3 Only if B2 = lin.
Tables defined in B2 are not active in this case.
Alpha val

40 Endress+Hauser
Smartec S CLD134 Commissioning

Coding Field Selection or range Display Info


(factory settings bold)

°C
B4
Enter process
temperature
25 °C
-10.0 ... 150.0 °C
25.0 B4 Only if B1 = fixed.
This value can only be specified in °C.
ProcTemp.

Display temperature Display and entry of real °C This entry is used to calibrate the temperature
B5 and calibrate temperature 0.0 B5 sensor to an external measurement.
temperature sensor -35.0 ... 250.0 °C Omitted if B1 = fixed.
RealTemp.

The difference between the entered actual


°C
B6
Temperature
difference is displayed
0.0 °C
-5.0 ... 5.0 °C
0.0 B6
value and the measured temperature is
displayed.
TempOffs. Omitted if B1 = fixed.

6.4.3 Current outputs


The OUTPUT function group is used to configure the individual outputs.
Furthermore, a current output value can be simulated to check the current outputs (O2 (2)).

Coding Field Selection or range Display Info


(factory settings bold)

Function group Configuration of the current output (not


O O
OUTPUT available for PROFIBUS versions).
OUTPUT

O1 Select current output


out1
out2
out1 O1 A different characteristic can be selected for
each output.
Sel. Out

O2 O2 (1)
Enter linear
characteristic
lin = linear (1)
sim = simulation (2)
lin O2 The slope of the characteristic may be
positive or negative.

Sel.Type

O211 Select current range


4 ... 20 mA
0 ... 20 mA
4-20 O211
Sel.Range

Enter the measured value corresponding to


Cond: 0.00 μS/cm
0/4 mA value: µS/cm the minimum current value (0/4 mA) at the
O212 enter corresponding
Conc: 0.00 %
Temp.: -10.0 °C
0 O212 transmitter output.
measured value Display format from A3.
entire measuring range
0/4 mA (Spreading: see Technical data.)

Endress+Hauser 41
Commissioning Smartec S CLD134

Coding Field Selection or range Display Info


(factory settings bold)

Enter the measured value corresponding to


Cond: 2000 mS/cm
20 mA value: mS/cm the maximum current value (20 mA) at the
O213 enter corresponding
Conc: 99.99 %
Temp.: 60.0 °C
2000 O213 transmitter output.
measured value Display format from A3.
entire measuring range
20 mA (Spreading: see Technical data.)

O2 (2)
Current output
simulation
lin = linear (1)
sim = simulation (2)
sim O2 The simulation is terminated by selecting (1).

Sel.Type

mA
O221 Enter simulation value
current value
0.00 ... 22.00 mA
4.00 O221 The current value entered here is output
through the current output.

Simulat.

6.4.4 Alarm
The ALARM function group is used to define various alarms and to set output contacts.
Each individual error can be defined to be effective or not (at the contact or as an error current).

Coding Field Selection or range Display Info


(factory settings bold)

Function group
F F Alarm function settings.
ALARM

ALARM

F1 Select contact type


Stead = steady contact
Fleet = fleeting contact
Stead F1 The contact type selected here only applies to
the alarm contact.

Cont.Type

F2 Select time unit


s
min
s F2
Time unit

Depending on the unit selected in F2, the


s
F3 Enter alarm delay
0 s (min)
0 ... 2000 s (min)
0 F3 alarm delay is entered in s or min.
The alarm delay does not affect the LED; it
Err.Delay indicates the alarm immediately

This selection must be made even if all error


messages are suppressed in F5.
F4 Select error current
22 mA
2.4 mA
22mA F4
"If you selected
Caution!
the "0-20 mA" range in O211,
Err.Curr you may not select the "2.4 mA" option here.

42 Endress+Hauser
Smartec S CLD134 Commissioning

Coding Field Selection or range Display Info


(factory settings bold)

Select the errors that are to trigger an alarm


signal.
The errors are selected via the error number.
F5 Select error
1
1 ... 255
1 F5 Please refer to the table in chapter 9.2 "System
error messages" for the error numbers. The
Sel.Error factory settings remain in effect for all errors
not edited.

If set to “no”, all the other alarm settings (e.g.


alarm delay) are also deactivated. The settings
Set alarm contact to be
F6 effective for selected
yes
no
yes F6 themselves are retained.
This setting only applies to the error selected
error
Rel.Assg in F5.
Factory setting is no starting with E080!

The error current selected in F4 becomes


Set error current to be effective or is suppressed when an error
F7 effective for selected
no
yes
no F7 occurs.
error This setting only applies to the error selected
Curr.Assg in F5.

F8
Return to menu or
select next error
next = next erorr
←R
R F8 If next is selected, the software returns to F5.
If ←R is selected, it returns to F.
Select

6.4.5 Check
PCS alarm (Process Check System)
The PCS alarm is only available for transmitters with remote parameter set switching.
This function is used to examine the measuring signal for deviations. If the measuring signal is
constant for a specific period of time (several measured values), an alarm is issued. This type of
sensor behaviour may be caused by soiling, etc.

t
C07-CLD132xx-05-06-00-xx-007.eps

Fig. 37: PCS alarm (live check)


A Constant measuring signal = alarm is triggered after the configured PCS period

! Note!
An active PCS alarm is automatically cleared when the measuring signal changes.

Endress+Hauser 43
Commissioning Smartec S CLD134

Coding Field Selection or range Display Info


(factory settings bold)

Function group
P P Settings for sensor and process monitoring.
CHECK

CHECK
This function is used to monitor the measuring
signal.
off An alarm is triggered if it does not change for
P1
Set PCS alarm
(live check)
1h
2h
off P1 the period selected here.
Monitoring limit:

PCS alarm
4h 0.3 % of mean value over selected period of
time.
(Error no.: E152)

6.4.6 Relay configuration


For Smartec S CLD134 equipped with remote parameter set switching (measuring range switching),
there are three options for configuring the relay (selection in field R1):
• Alarm
The relay closes the contact 41/42 (voltage-free, safe state) if an alarm condition according to
chapter 9.2 occurs and if the setting in the “Alarm contact” column is “yes”. You can change
these settings as required (field F5 ff).
• Limit
The relay only closes the contact 42/43 if one of the defined limits is violated (value above or
below limit, see Fig. 38) but not when an alarm condition is detected.
• Alarm + Limit
The relay closes the contact 41/42 if an alarm condition occurs. Limit violations only cause the
relay to switch if error E067 is set to “yes” during relay assignment (field F6).
Please refer to Fig. 38 for a graphic representation of the contact states of the alarm contact.
• When the measured value increases (max function), the relay goes into alarm state (limit
exceeded) at time t2 when the switch-on point has been exceeded (t1) and the pickup delay
(t2 – t1) has expired.
• When the measured value decreases, the relay returns to normal operating state when the
measured value drops below the switch-off point and after the dropout delay (t4 - t3).
• When the pickup and dropout delays are set to 0 s, the switch-on and switch-off points are
identical to the contact switching points.
Settings for a minimum function can be made in the same way as for a maximum function.

44 Endress+Hauser
Smartec S CLD134 Commissioning

1
2 4

t1 t2 t3 t4 t

B 4

3
1

t1 t2 t3 t4 t
C07-CLD132xx-05-06-00-xx-008.eps

Fig. 38: Relation of switch-on and switch-off points and pickup and dropout delays
A Switch-on point > switch-off point: Max. function 1 Switch-on point
B Switch-on point < switch-off point: Min. function 2 Switch-off point
3 Contact ON
4 Contact OFF

Coding Field Selection or range Display Info


(factory settings bold)

Function group
R R Settings for relay contacts.
RELAY

RELAY

alarm
R1 Select function limit alarm R1 When “alarm” is selected, the fields R2 ... R5
are irrelevant.
al+li = alarm + limit
Function
Only the operating mode selected in A1
Cond: 2000 mS/cm mS/cm appears.
R2
Enter contact
switch-on point
Conc: 99.99 % 2000 R2
! Note!
entire measuring range Never set the switch-on point and the
On Value switch-off point to the same value.

The switch-off point entry selects a max


Cond: 2000 mS/cm mS/cm contact (switch-off point < switch-on point) or
R3
Enter contact
switch-off point
Conc: 99.99 % 2000 R3 a min contact (switch-off point > switch-on
entire measuring range point), thereby implementing a hysteresis
Off Value function (see Fig. 32).

s
R4 Enter pickup delay
0s
0 ... 2000 s
0 R4
On Delay

Endress+Hauser 45
Commissioning Smartec S CLD134

Coding Field Selection or range Display Info


(factory settings bold)

s
R5 Enter dropout delay
0s
0 ... 2000 s
0 R5
Off Delay

R6 Select simulation
auto
manual
auto R6
This selection can only be made if "limit" has
been selected in R1.
Simulat.

This selection can only be made if "manual"


R7 Switch relay on or off
on
off
off R7 has been selected in R6. The relay can be
switched on and off.
Relay

6.4.7 Temperature compensation with table


This function group is used to perform a temperature compensation with table (field B2 in SETUP 2
function group).
Enter the α−T value pairs in the fields T5 and T6.

Coding Field Selection or range Display Info


(factory settings bold)

Function group
T T Settings for temperature compensation.
ALPHA TABLE

ALPHA TAB

Selection of table to be edited.


T1 Select table
1
1 ... 4
1 T1 Options 1 ... 4 are only available if the
instrument is equipped with the remote
editCurve measuring range switching.

T2 Select table option


read
edit
read T2
Sel.Table

Up to 10 value pairs can be entered in the α


T3
Enter number of table
value pairs
1
1 ... 10
1 T3 table. These are numbered from 1 ... 10 and
can be edited individually or in sequence.
No. Elem.

1
T4 Select table value pair 1 ... number of table value pairs 1 T4 If "assign", go to T8.
assign
Sel.Elem.

46 Endress+Hauser
Smartec S CLD134 Commissioning

Coding Field Selection or range Display Info


(factory settings bold)

The temperature values must have a


°C minimum distance of 1 K.
T5
Enter temperature
value
0.0 °C
-10.0 ... 150.0 °C
0.0 T5 Factory setting for temperature value of value
pairs in table:
Temp.val. 0.0 °C; 10.0 °C; 20.0 °C; 30.0 °C ...

%/K
T6
Enter temperature
coefficient α
2.10 %/K
0.00 ... 20.00 %/K
2.10 T6
alpha val

T8
Enter whether or not
the table status is ok
yes
no
yes T8 If “yes”, return to T.
If “no”, return to T3.

Status ok

6.4.8 Concentration measurement


The transmitter can convert conductivity values to concentration values. For this, set the operating
mode to Concentration measurement (see field A1).

You must enter the basic data to which the concentration calculation should refer. For the most
common substances, the required data is already saved in your device. You can select one of these
substances in field K1.
If you want to specify the concentration of a sample, which is not saved in the device, you require
the conductivity characteristics of the medium. To get the characteristics, you can either refer to the
data sheets of the medium or determine the characteristics yourself.
1. To do so, create samples of the medium with the concentrations occurring in your process.
2. Measure the uncompensated conductivity of these samples at temperatures which likewise
occur in your process. To get the uncompensated conductivity, press the PLUS key several
times in measuring mode (see chapter "Key functions") or deactivate the temperature
compensation (Setup 2, field B 2).

– For variable process temperature:


If the variable process temperature should be taken into account for concentration
measurement, you must measure the conductivity of each created sample at two different
temperatures at least (ideally at the lowest and highest process temperature). The
temperature values for the various samples must be identical. However, the difference
between the temperatures must be at least 0.5 °C (0.9 °F).
At least two differently concentrated samples measured at two different temperatures are
required because the transmitter needs a minimum of four references.

– For constant process temperature:


Measure the differently concentrated samples at this constant process temperature.
A minimum of two samples is necessary.
Finally, you should have measuring data which are similar to those shown in the following figures:

Endress+Hauser 47
Commissioning Smartec S CLD134

κ 2 κ
T3 2
1 T3 1
T2
T2
T1
T1

Cmin Cmax C Cmin Cmax C


C07-CLD132xx-05-06-00-xx-012.eps

Fig. 39: Measured data for variable process temperatures (example)


κ Conductivity 1 Measuring point
C Concentration 2 Measuring range
T Temperature

k k

1 T 1 T

Cmin Cmax C Cmin Cmax C


C07-CLD132xx-05-06-00-xx-015.epsB

Fig. 40: Measured data for a constant process temperature (example)


κ Conductivity T Constant temperature
C Concentration 1 Measuring range

The characteristics received from the measuring


κ κ
points must be strictly monotonously increasing
or strictly monotonously decreasing in the range
of the process conditions. Therefore, neither
maxima / minima nor ranges with a constant
behaviour can occur. Curve profiles such as
C C
those in Fig. 41 are not permitted. C07-CLD132xx-05-06-00-xx-016.eps

Fig. 41: Impermissible curve profiles


κ Conductivity
C Concentration
Value entry
Enter the three characteristic values for each measured sample in the fields K6 to K8 (value triplets
of conductivity, temperature and concentration).
• Variable process temperature:
Enter at least four value triplets.
• Constant process temperature:
Enter at least two value triplets.

! Note!
• Please make sure that the concentrations and temperatures measured for your samples
correspond to the measuring range of the process. If the measured values of the process are
outside the range of your sample values, this considerably reduces the level of accuracy and the
error messages E078 or E079 will be displayed.
If you enter an additional value triplet of 0 μS/cm and 0 % for each temperature used, you can
work from the start of measuring range with sufficient accuracy and without an error message.
• In case of concentration measurement, temperature compensation is automatically performed
using the entered table values. Therefore, the temperature coefficient set in the SETUP 2 function
group is not active.

48 Endress+Hauser
Smartec S CLD134 Commissioning

• Enter the values in the order of increasing concentration (see the following example).

mS/cm % °C (°F)

240 96 60 (140)

380 96 90 (194)

220 97 60 (140)

340 97 90 (194)

120 99 60 (140)

200 99 90 (194)

Coding Field Selection or range Display Info


(factory settings bold)

Settings for concentration measurement. Four


Function group
K K fixed and four editable concentration fields are
CONCENTRATION
stored in this function group.
CONCENTRA

NaOH 0... 15 %
Select concentration
H2SO4 0 ... 30 % The user tables 2 ... 4 can only be selected if
K1
curve to be used to
calculate the display
H3PO4 0 ... 15 % NaOH K1 the instrument is equipped with the remote
HNO3 0 ... 25 % measuring range switching.
value
Tab 1 ... 4 act.curve

K2
Select correction
factor
1
0.5 ... 1.5
1 K2 If required, select a correction factor (only
available for the user tables).

Conc.Fact

When editing a curve, another curve should


be used to calculate the current display values
K3
Select table to be
edited
1
1 ... 4
1 K3 (see K1).
Selections 2 ... 4 are only available with the
editCurve remote measuring range switching.

K4 Select table option


read
edit
read K4 This selection applies to all concentration
curves.

Table

K5
Enter number of
reference triplets
4
1 ... 16
4 K5 Each triplet consists of three numeric values.

No. Elem.

1
K6 Select triplet 1 ... number of triplets in K4 1 K6 Any triplet can be edited.
If "assign", go to K10.
assign
Sel.Elem.

Endress+Hauser 49
Commissioning Smartec S CLD134

Coding Field Selection or range Display Info


(factory settings bold)

mS/cm
K7
Enter uncompensated
conductivity
0.0 mS/cm
0.0 ... 9999 mS/cm
0.0 K7
conduct.

%
K8
Enter concentration
value for K6
0.00 %
0.00 ... 99.99 %
0.0 K8
concentr.

°C
K9
Enter temperature
value for K6
0.0 °C
-35.0 ... 250.0 °C
0.0 K9
Temp.val.

K10
Enter whether or not
the table status is ok
yes
no
yes K10 Back to K.

Status ok

6.4.9 Service

Coding Field Selection or range Display Info


(factory settings bold)

Function group
S Settings for service functions.
S SERVICE
SERVICE
ENG = English
GER = German
S1 Select language
FRA = French
ITA = Italian
ENG S1
This field must be configured once during
start-up. Then you can exit S1 and continue.
NEL = Dutch
ESP = Spanish Language

froz.: Display of last value before activation of


S2 HOLD effect
froz. = last value
fix = fixed value
froz. S2
hold.
fix: When hold is active, the fixed value

Holdeffec
entered in S3 is displayed.

0
0
%
S3 Enter fixed value 0 ... 100 % S3 Only available if S2 = fixed value.
(of current output value)
Fixed Val

S+C = setup and calibration


S4 Hold configuration
CAL = calibration
Setup = setup
S+C S4
S = setup
C = calibration

Auto HOLD
none = no hold

50 Endress+Hauser
Smartec S CLD134 Commissioning

Coding Field Selection or range Display Info


(factory settings bold)

S5 Manual hold
On
Off
off S5

Man.HOLD

s
S6
Enter hold dwell
period
10 s
0 ... 999 s
10 S6

Cont.Time

Enter SW upgrade Entering an incorrect code returns you to the


S7
release code of
function extension
0
0 ... 9999
0 S7
measurement menu. The number is edited
with the PLUS or MINUS key and confirmed
MRS with the ENTER key.
MRSCode

S8
Order number is
displayed
order S8
The order code is not automatically changed
to reflect an upgrade.

CLD134-xx

S9
Serial number is
displayed
SerNo S9

xxxxxxxx
Facty= All data are cleared and reset to the
factory settings!
Reset of instrument Sens = Sensor data are cleared (temp. offset,
(restore default values) no
no
air set value, cell constant, installation factor)
S10 Sens = sensor data S10
Facty = factory settings ! Note!

S.Default After a reset plesase change the cell constant


in field A5 to 6.3 and the temperature sensor
in field B1 to Pt1k.

S11
Perform instrument
test
no
Displ = display test
no S11

Test

Endress+Hauser 51
Commissioning Smartec S CLD134

6.4.10 E+H Service


Coding Field Selection or range Display Info
(factory settings bold)

Function group E+H


E E E+H service settings.
SERVICE

E+H SERV

Contr = controller (1)


E1 Select module
Trans = transmitter (2)
MainB = mainboard (3)
Contr E1
Select
Sens = sensor (4)

E111
E111: Version of transmitter software
E121
E131
Software version is
displayed
xx.xx E111 E121-141: Version of module firmware (if
available)
SW-Vers.
E141

E112
E122
E132
Hardware version is
displayed
xx.xx E112 Cannot be edited.

HW-Vers.
E142

E113
E123
E133
Serial number is
displayed
SerNo E113 Cannot be edited.
E143
xxxxxxxx

E145
E146
E147
Enter and confirm
serial number
SerNo E145

E148
xxxxxxxx

6.4.11 Interfaces
Coding Field Selection or range Display Info
(factory settings bold)

Function group Communication settings (HART or


I I
INTERFACE PROFIBUS transmitter versions only).

INTERFACE

Address
I1 Enter address
HART: 0 ... 15
or
126 I1

Address
PROFIBUS: 0 ... 126

I2 Tag description Tag I2


@@@@@@@@

52 Endress+Hauser
Smartec S CLD134 Commissioning

6.4.12 Determining the temperature coefficient


Determining the temperature coefficient by the following method is only possible for instruments
equipped with remote parameter set switching (see "Product structure"). Standard instruments
(basic versions) can be retrofitted with remote parameter set switching (see chapter "Accessories").

Coding Field Selection or range Display Info


(factory settings bold)

Settings for temperature coefficient. Calculator


Function group
function: calculates the α value from the
D TEMPERATURE D
compensated conductivity + uncompensated
COEFFICIENT
DET.ALPHA conductivity + temperature value.

Displays the current compensated


µS/cm
D1
Enter compensated
conductivity
current value
0 ... 9999
2000 D1
conductivity. If necessary, change this value to
the desired value (determined by a
Cond.comp comparison measurement for example).

Display of µS/cm
D2 uncompensated
current value
0 ... 9999
2077 D2 Current value of uncompensated conductivity,
cannot be edited.
conductivity
Cond.unc.

°C
D3
Enter current
temperature
current value
-35.0 ... 250.0 °C
60.0 D3
Meas.temp

%/K
D4
Display of determined
α value
2.20 D4 Used in B3 for example. You must enter the
value manually.
alpha val

6.4.13 Remote parameter set switching (measuring range switching,


MRS)
You can order the remote parameter set switching via binary inputs directly as an option of your
transmitter (see "Product structure") or you can retrofit a standard transmitter with the MRS
function extension (see the chapter "Accessories").
The remote parameter set switching function permits complete parameter sets to be entered for up
to 4 substances.
Individual settings for each parameter set:
• Operating mode (conductivity or concentration)
• Temperature compensation
• Current output (main parameter and temperature)
• Concentration table
• Limit relay

Endress+Hauser 53
Commissioning Smartec S CLD134

Assignment of binary inputs


The transmitter has 2 binary inputs. They can be defined in field M1 as follows:

Assignment of field M1 Assignment of binary inputs

M1 = 0 MRS not active. The binary input 1 can be used for external hold.

The binary input 2 can be used to switch between 2 measuring ranges (parameter
M1 = 1
sets). The binary input 1 can be used for external hold.

The binary inputs 1 and 2 can be used to switch between 4 measuring ranges
M1 = 2
(parameter sets). This is the setting used in the following example.

Settings of the 4 parameter sets


Example: CIP cleaning
Binary input 1 0 0 1 1

Binary input 2 0 1 0 1

Parameter set 1 2 3 4

Coding / Alkaline
Medium Beer Water Acid
software field solution

M4 Operating mode Conductivity Conductivity Concentration Concentration

M8, M9 Current output 1 to 3 mS/cm 0.1 to 0.8 mS/cm 0.5 to 5% 0.5 to 1.5 %

M6 Temp. comp. User Tab. 1 linear - -

M5 Conc. tab. - - NaOH User Tab.

M10, M11 Limits on: 2.3 mS/cm on: 0.7 μS/cm on: 2 % on: 1.3 %
off: 2.5 mS/cm off: 0.8 μS/cm off: 2.1 % off: 1.4 %

Coding Field Selection or range Display Info


(factory settings bold)

Settings of remote parameter set switching


(measuring range switching).
M Function group MRS M M1 + M2: apply to measuring mode.
M3 ... M11: apply to configuration of
MRS parameter sets.

0 = no MRS
1 = 2 parameter sets selectable via binary
M1 Select binary inputs
1
0, 1, 2
2 M1 input 2. Binary input 1 for hold.
2 = 4 parameter sets selectable via binary
Bin.Input inputs 1+2.

Displays active
If M1 = 0, selectable.
M2
parameter set or, if
M1 = 0, select active
1
1 ... 4 if M1 = 0
1 M2 If M1 = 1 or 2, display depending on binary
inputs.
parameter set
Act.MR

1
Select parameter set to Selection of parameter set to be configured
M3 be configured in
1 ... 4 if M1=0
1 ... 2 if M1=1
1 M3 (the active parameter set is selected in M2 or
M4 ... M8 with the binary inputs).
1 ... 4 if M1=2
Edit MR

54 Endress+Hauser
Smartec S CLD134 Commissioning

Coding Field Selection or range Display Info


(factory settings bold)

M4 Select operating mode


cond = conductivity
conc = concentration
cond. M4 The operating mode can be individually
defined for each parameter set.

Oper.Mode

M5 Select medium
NaOH, H2SO4, H3PO4, HNO3
Tab 1 ... 4
NaOH M5 Only available if M4 = conc.

Conc.Tab.

M6
Select temperature
compensation
none, lin, NaCl,
Tab 1 ... 4 if M4 = cond
lin M6 Only available if M4 = cond.

TempComp

2.10 M7
2.10 %/K %/K
M7 Enter α value Can only be entered if M6 = lin.
0 ... 20 %/K

alpha val

0 M8
µS/cm
Enter measured value Cond.: 0 ... 2000 mS/cm
M8
for 0/4 mA value Conc.: Unit: A2, format: A3
0/4 mA

2000 M9
mS/cm
Enter measured value Cond.: 0 ... 2000 mS/cm
M9
for 20 mA value Conc.: Unit: A2, format: A3

20 mA

2000 M10
Enter switch-on point Cond.: 0 ... 2000 mS/cm mS/cm
M10
for limit Conc.: Unit: A2, format: A3

PV on
The switch-off point entry selects a max
contact (switch-off point < switch-on point) or
a min contact (switch-off point > switch-on
2000 M11
Enter switch-off point Cond.: 0 ... 2000 mS/cm mS/cm
M11 point), thereby implementing an always
for limit Conc.: Unit: A2, format: A3
required hysteresis function. Never set the
PV off switch-off point and the switch-on point to
the same value.

! Note!
If remote parameter set switching is selected, the parameter sets that have been entered are
processed internally but the fields A1, B1, B3, R2, K1, O212, O213 show the values of the first
measuring range.

Endress+Hauser 55
Commissioning Smartec S CLD134

6.4.14 Calibration
To access the "Calibration" function group, press the CAL key.
This function group is used to calibrate the transmitter. Two different types of calibration are
possible:
• Calibration by measurement in a calibration solution of a known conductivity.
• Calibration by entering the exact cell constant of the conductivity sensor.

! Note!
• At first start-up of inductive sensors, an airset is absolutely required in order for the measuring
system to be able to generate accurate measuring values.
• If the calibration procedure is aborted by pressing the PLUS and MINUS keys at the same time
(return to C114, C126 or C136) or if the calibration is faulty, then the previous calibration data
are reinstated. A calibration error is indicated by the “ERR” message and flashing of the sensor
symbol on the display.
Repeat calibration!
• The instrument is automatically switched to hold during calibration (factory setting).

Coding Field Selection or range Display Info


(factory settings bold)

Function group
C C Calibration settings.
CALIBRATION
CALIBRAT

Airs = Airset (1)


C1 (1)
Compensation of
residual coupling
Cellc = cell constant (2) AirS C1
InstF = installation factor (3)
Calibrat
When commissioning inductive sensors, an
airset is mandatory.
The calibration of the sensor is to be
performed in air. The sensor must be dry.

Remove sensor from the medium and dry completely.

~~~
~ ~
~ ~~

µS/cm
C111
Residual coupling start
calibration (airset)
current measured value 0.0 C111 Start calibration with CAL.

AirSet

µS/cm
C112
Residual coupling is
displayed (airset)
-80.0 ... 80.0 μS 5.3 C112 Residual coupling of measuring system
(sensor and transmitter).

AirSetVal

If the calibration status is not o.k., the second


C113
Calibration status is
displayed
o.k.
E xxx
o.k. C113 display line shows an explanation of the
error.
Status

56 Endress+Hauser
Smartec S CLD134 Commissioning

Coding Field Selection or range Display Info


(factory settings bold)

yes If C113 = E xxx, then only no or new.


C114
Store calibration
results?
no yes C114 If new, return to C.
new If yes/no, return to “Measurement”.
Store

Airs = Airset (1)


C1 (2)
Calibration of cell
constant
Cellc = cell constant (2) Cellc C1
InstF = installation factor (3)
Calibrat

Immerse sensor in calibration solution.


The sensor should be immersed at a
! Note!
This section decribes the calibration for temperature compensated conductivity.
sufficient distance from the vessel wall

For calibration with uncompensated conductivity, set the temperature ~~~ (installation factor has no influence if

coefficient α to 0. ~ ~ a > 15 mm / 0.59").


~ ~~

°C
C121
Enter process
temperature (MTC)
25 °C
-35.0 ... 250.0 °C
25.0 C121 Only exists if B1 = fixed.

ProcTemp.
This value is specified in the Technical
Information of all E+H calibration solutions.
2.10 C122
Enter α value of 2.10 %/K %/K You can also use the printed-on table to
C122
calibration solution 0.00 ... 20.00 %/K calculate the value.
Set α to 0 for calibration with
alpha val uncompensated values.

Enter correct mS/cm


C123 conductivity value of
current measured value
0.0 ... 9999 mS/cm
10.30 C123 The display is always in mS/cm.
calibration solution
Real. val

1/cm
C124
Calculated cell
constant is displayed
0.1 ... 6.3 ... 99.99 cm-1 6.300 C124 The calculated cell constant is displayed and
entered in A5.

Cellconst

If the calibration status is not o.k., the second


C125
Calibration status is
displayed
o.k.
E xxx
o.k. C125 display line shows an explanation of the
error.
Status

yes If C125 = E xxx, then only no or new.


C126
Store calibration
results?
no yes C126 If new, return to C.
new If yes/no, return to “Measurement”.
Store

Endress+Hauser 57
Commissioning Smartec S CLD134

Coding Field Selection or range Display Info


(factory settings bold)

Airs = Airset (1)


Calibration with
C1 (3) sensor adaptation for
Cellc = cell constant (2)
InstF = installation
InstF C1 Sensor calibration with compensation of wall
inductive sensors
factor (3)
Calibrat influence.
The distance from the sensor to the pipe wall
and the pipe material (conductive or
non-conductive) influence the measured
value. The installation factor compensates
this influence. See chapter "Installation
The sensor is installed in the process. conditions".

°C
C131
Enter process
temperature (MTC)
25 °C
-35.0 ... 250.0 °C
25.0 C131 Only exists if B1 = fixed.

MTC temp.
This value is specified in the Technical
Information of all E+H calibration solutions.
2.10 C132
Enter α value of the 2.10 %/K %/K You can also use the printed-on table to
C132
calibration solution 0.00 ... 20.00 %/K calculate the value.
Set α to 0 for calibration with
alpha val uncompensated values.

Enter correct mS/cm


C133 conductivity value of
current measured value
0.0 ... 9999 mS/cm
10.30 C133 Determine the correct conductivity value by
a reference measurement.
the medium
Real val.
The distance of the sensor to the pipe wall
and the pipe material (conductive or
C134
Calculated installation
factor is displayed
1
0.10 ... 5.00
1 C134 nonconductive) influence the measured
value. The installation factor compensates

InstFact this influence. See chapter "Installation


conditions".

If the calibration status is not o.k., the second


C135
Calibration status is
displayed
o.k.
E xxx
o.k. C135 display line shows an explanation of the
error.
Status

yes If C135 = E xxx, then only no or new.


C136
Store calibration
results?
no yes C136 If new, return to C.
new If yes/no, return to “Measurement”.
Store

6.5 Communication interfaces


Please refer to separate operating instructions BA212C/07/en (HART) or BA213C/07/en
(PROFIBUS) for transmitters equipped with a communication interface.

58 Endress+Hauser
Smartec S CLD134 Maintenance

7 Maintenance
Take all necessary measures in due time to guarantee the safety of operation and reliability of the
entire measuring system.
Maintenance on the Smartec S CLD134 includes:
• Calibration (see chapter "Calibration")
• Cleaning of assembly and sensor
• Checking of cables and connections.

# Warning!
• Please be aware of effects work performed on the instrument might have on the process control
system or the process itself.
• When removing the sensor during maintenance or calibration, please consider potential hazards
due to pressure, high temperatures and contamination.
• Disconnect the instrument from the power source before opening it up.
Work with live lines may only be performed by trained electricians!
• Switched contacts may be supplied from separate circuits. These circuits must also be
de-energized before work on the terminals is performed.
Caution ESD!
• Electronic components are sensitive to electrostatic discharges. Personal protective measures,
such as discharge via PE or permanent grounding using a wrist strap, are to be taken.
• For your own safety, use only original spare parts. Original parts will guarantee functionality,
accuracy and reliability after repairs.

! Note!
Please contact your Endress+Hauser representative if you have any questions. You can also send
your queries to the Endress+Hauser Service Organisation via the Internet: www.endress.com

7.1 Maintenance of Smartec S CLD134

7.1.1 Dismantling Smartec S CLD134

" Caution!
Consider potential effects on process when removing the instrument from service!

! Note!
For item numbers see the exploded view drawing in chapter 9.5.
1. Remove the cover (item 40).
2. Remove the internal protecting cover (item 140). Release the lateral latches with a
screwdriver.
3. Pull off the five-pole terminal block first to de-energize the instrument.
4. Then pull off the remaining terminal blocks. Now you can dismantle the instrument.
5. Loosen 4 screws to remove the complete electronics box from the steel housing.
6. The power supply module is snapped in and can be loosened and removed by slightly bending
the electronics box walls. Start with the rear catches!
7. Pull off the ribbon cable connected (item 110); now the power supply can be removed.
8. The central module is also snapped in and easy to remove. Note! The central module may be
fastened with an additional center screw. Remove this screw if present.

Endress+Hauser 59
Maintenance Smartec S CLD134

7.1.2 Replacement of central module

! Note!
A replacement central module LSCx-x is supplied from the factory with the instrument serial
number of the new module. Since the serial and release numbers are linked to enable the extended
functions and parameter set switching, an existing extension / MRS cannot be active. All the
editable data are reset to the factory settings following central module replacement.
Proceed as described below when replacing the central module:
1. If possible, record the user settings of the instrument, e.g.:
– Calibration data
– Conductivity and temperature current assignment
– Relay function selections
– Limit settings
– Alarm settings, alarm current assignment
– Monitoring functions
– Interface parameters
2. Dismantle the instrument as described in the chapter "Dismantling Smartec S CLD134".
3. Refer to the part number of the central module to determine whether the new module has the
same part number as the old one.
4. Assemble the instrument with the new module.
5. Start up the instrument and test its basic functions (e.g. measured value and temperature
display, operation via keyboard).
6. Enter the instrument serial number:
– Read the instrument serial number (“ser-no.”) on the nameplate.
– Enter this number in the fields E115 (year, one-digit), E116 (month, one-digit), E117
(sequence number, four-digit).
– Field E118 displays the complete number for verification;
" Caution!
The serial number can only be entered – and only once – in the case of a new module from
the factory with a new module number! Make sure that your entry is correct before
confirming with ENTER!
Entry of an incorrect code will prevent the extended functions from being enabled. An
incorrect serial number can only be corrected at the factory.
– confirm with ENTER or abort and re-enter.
7. Enter the release code in field Feld S7 (see nameplate "/Codes:").
8. Verify that the functions have been enabled:
Extension functions e.g. by accessing function group CHECK / code P, PCS function must be
available; Measuring range switching e.g. by calling up alpha tables (function group T / 1 to 4
must be selectable in T1).
9. Enter the default values of the cell constant (6.3 cm-1) in field A5 and of the temperature sensor
(Pt1k) in field B1.
10. Restore the user settings of the instrument.

60 Endress+Hauser
Smartec S CLD134 Maintenance

7.2 Maintenance of measuring system

7.2.1 Cleaning conductivity sensors


Inductive sensors are less sensitive to soiling than conventional conductive sensors since there is no
galvanic contact with the medium.
However, dirt may collect in the flow opening (making it narrower), which changes the cell
constant. In this case, an inductive sensor also requires cleaning.
Recommended cleaning procedure:
• Oily and greasy coatings:
Clean with detergent (fat solvent, e.g. alcohol, acetone, poss. detergent).

# Warning!
Protect your hands, eyes and clothes when using the cleaning agents described below!
• Limestone deposits or metal hydroxide coatings:
Loosen coatings with diluted hydrochloric acid (3 %), brush off carefully if necessary and rinse
thoroughly with plenty of clear water.
• Coatings containing sulphide (from FGD or sewage treatment plants):
Use mixture of hydrochloric acid (3 %) and thiourea (commercially available), brush off carefully
if necessary and rinse thoroughly with plenty of clear water.
• Coatings containing protein (food industry):
Use mixture of hydrochloric acid (0.5 %) and pepsin (commercially available), brush off carefully
if necessary and rinse thoroughly with plenty of clear water.

7.2.2 Checking inductive conductivity sensors


The following specifications apply to the CLS54 sensor.
The sensor lines on the instrument or junction box are to be disconnected for all tests described
here!
• Testing transmitting and receiving coils
– Ohmic resistance approx. 1 ... 3 Ω.
– Inductivity approx. 180 ... 550 mH (at 2 kHz; serial connection as equivalent circuit diagram)
Separate version: measure the white and red coaxial cables.
Compact version: measure the white and brown coaxial cables.
(Between the inner conductor and screen in both cases.)
• Testing the coil shunt
– A shunt between the two sensor coils is not allowed. The resistance measured should be
>20 MΩ.
Test with ohmmeter between brown or red coaxial cable and white coaxial cable.
• Testing the temperature sensor
Use the table in chapter "Instrument check by medium simulation" to check the Pt1000 in the
sensor.
Measure between the green and white wires in the case of the separate version and between
green and yellow. The resistance values should be identical.
Compact version: measure between the two red wires.
• Testing the temperature sensor shunt
– Shunts between the temperature sensor and the coils are not allowed. Check with ohmmeter
for >20 MΩ.
Measure between the temperature sensor wires (green + white + yellow or red + red) and the
coils (red and white coaxial cables or brown and white coaxial cables).

Endress+Hauser 61
Maintenance Smartec S CLD134

7.2.3 Instrument check by medium simulation


The inductive sensor cannot be simulated.
However, the overall system comprising the CLD134 and inductive sensor can be checked using
equivalent resistances. Note the cell constant ( knominal = 6.3 cm-1 for CLS54).
For an accurate simulation, the actual cell constant (can be read in field C124) is to be used to
calculate the display value:
Conductivity[mS/cm] = k ⋅1/(R[kΩ] ⋅ 1.21). Values for simulation with CLS54 at 25 °C / 77 °F:
Simulation resistance R Default cell constant k Conductivity display

10 Ω 6.3 cm-1 520 mS/cm

26 Ω 6.3 cm-1 200 mS/cm

100 Ω 6.3 cm-1 52 mS/cm

260 Ω 6.3 cm-1 20 mS/cm

2.6 kΩ 6.3 cm-1 2 mS/cm

26 kΩ 6.3 cm-1 200 μS/cm

52 kΩ 6.3 cm-1 100 μS/cm

Conductivity simulation:
Pull a cable through the sensor opening and then connect, e.g. to a decade resistor.
Temperature sensor simulation:
The temperature sensor of the inductive sensor is connected to terminals 11, 12 and 13 on the
instrument (compact version and separate version).
For simulation, the temperature sensor is disconnected, and an equivalent resistance is connected
instead. This resistance must also be connected using a three-wire arrangement, i.e. connection to
terminals 11 and 12, with a bridge from 12 to 13.
The table shows some resistance values for temperature simulation:
Temperature Resistance

- 20 °C (-4 °F) 921.3 Ω

-10 °C (14 °F) 960.7 Ω

0 °C (32 °F) 1000.0 Ω

10 °C (50 °F) 1039.0 Ω

20 °C (68 °F) 1077.9 Ω

25 °C (77 °F) 1097.3 Ω

50 °C (122 °F) 1194.0 Ω

80 °C (176 °F) 1308.9 Ω

100 °C (212 °F) 1385.0 Ω

150 °C (302 °F) 1573.2 Ω

200 °C (392 °F) 1758.4 Ω

62 Endress+Hauser
Smartec S CLD134 Maintenance

7.2.4 Checking line extension and junction box


• Use the methods described in chapters "Checking inductive conductivity sensors" and
"Instrument check by medium simulation" to perform a quick functional check from the
conductivity sensor to the measuring instrument via an extension.
• Checking the extension cable type:
– The inductive sensor only works reliably with the original CLK5 cable!
• Check junction boxes for moisture (possible influence in low conductivity range):
– Dry junction box
– Replace cover gasket
– Inspect cable glands for tightness
– Use desiccant bag
• Check junction boxes for correct line connections:
– When the prescribed original CLK5 cable is used, the cable wires (colors) are connected 1:1.
• Check junction boxes for correct outer screen connections:
– Immunity to interference is only guaranteed if the screens are connected!
• Check junction boxes for tightness of clamping screws and examine for corrosion:
– Tighten screws some time after start-up
– Replace terminals if corroded; make sure that the junction box is tight.

7.3 Service equpipment "Optoscope"


The Optoscope together with the “Scopeware” software offers the following possibilities, without
having to remove or open the transmitter and without galvanic connection to the instrument:
• Documentation of the instrument settings in conjunction with Commuwin II
• Software update by the service technician
• Upload/download a hex dump to duplicate configurations.
The Optoscope serves as an interface between the transmitter and PC / laptop. The information
exchange takes place via the optical interface on the transmitter and via an RS 232 interface on the
PC / laptop (see "Accessories").

Endress+Hauser 63
Accessories Smartec S CLD134

8 Accessories

8.1 Sensors
• Indumax H CLS54
Inductive conductivity sensor with fast response time and hygienic design;
with integrated temperature sensor.
Order according to product structure, see Technical Information TI400C/07/en.

8.2 Extension cable


Extension cable CLK5
• For inductive conductivity sensors, for extension via the VBM junction box, sold by the meter
• Order no.: 50085473

8.3 Junction box


• Junction box VBM
for extension of measuring cable connection between sensor and instrument, material cast
aluminium, ingress protection 65;
order no.: 50003987
! Note!
The desiccant bag must be checked and replaced at regular intervals which depend on ambient
conditions in order to prevent inaccurate measurement due to moisture bridges in the measuring
line.
62.5 / 2.46

125 / 4.92
113 / 4.45

approx. 136 /
5.35
0.39
10 /

52 / 2.05
80 / 3.15
55 / 2.17
26.8 /
1.06

mm / inch
a0004901-en

• Desiccant bag with color indicator for VBM junction box;


order no. 50000671

64 Endress+Hauser
Smartec S CLD134 Accessories

8.4 Post mounting kit


• Mounting kit for installation of Smartec S CLD132/CLD134 on horizontal or vertical pipes and
posts (max. Ø 60 mm (2.36")), material stainless steel 1.4301;
order no.: 50062121

a0004902

Fig. 42: Mounting kit for installing CLD132/CLD134 separate version on posts or pipes (base plate belongs to the
scope of delivery of the transmitter)

8.5 Software upgrade


• Software upgrade
Remote parameter set switching (measuring range switching, MRS) and determination of
temperature coefficient;
order no.: 51501643
Serial number of instrument must be specified with order.

8.6 Calibration solutions


Precision solutions, traceable to SRM (standard reference material) by NIST, for qualified calibration
of conductivity measurement systems according to ISO 9000, with temperature table
• CLY11-B
149.6 μS/cm (reference temperature 25 °C / 77 °F), 500 ml / 16.9 fl.oz
Order no. 50081903
• CLY11-C
1.406 mS/cm (reference temperature 25 °C / 77 °F), 500 ml / 16.9 fl.oz
Order no. 50081904
• CLY11-D
12.64 mS/cm (reference temperature 25 °C/ 77 °F), 500 ml / 16.9 fl.oz
Order no. 50081905
• CLY11-E
107.0 mS/cm (reference temperature 25 °C / 77 °F), 500 ml / 16.9 fl.oz
Order no. 50081906

8.7 Optoscope
• Optoscope
Interface between transmitter and PC / laptop for service purposes.
The Windows software "Scopeware" required for the PC or laptop is supplied with the Optoscope.
The Optoscope is supplied in a sturdy plastic case with all the accessories required.
Order no. 51500650

Endress+Hauser 65
Troubleshooting Smartec S CLD134

9 Troubleshooting

9.1 Troubleshooting instructions


The transmitter continually monitors its own functions. If the instrument detects a defect, the error
number appears on the display. This error number is displayed underneath the main value unit
display. If several errors are detected, these can be called up with the MINUS key.
Refer to the table "System error messages" for error numbers and the appropriate corrective
measures.
In case of malfunctions or errors without error messages, use the tables "Process-specific errors" and
"Instrument-specific errors" to locate and eliminate the error. The "Instrument-specific errors" table
also specifies required spare parts.

9.2 System error messages


The system error messages can be called up and selected with the MINUS key.

Error no. Display Tests and / or measures Alarm contact Error current

Factory User Factory User

E001 EEPROM memory error 1. Switch instrument off and back on. yes no

Instrument not calibrated, calibration 2. Set to factory settings (S11). yes no


data invalid, no user data or user data 3. Load hardware-compatible software (with
invalid (EEPROM error), software does Optoscope, see chapter "Service equipment
E002 not match hardware (central module) Optoscope").
4. If problem persists, return instrument to your
local Endress+Hauser sales agency for repair or
replace instrument.

Download error Download must not access locked functions (e.g. yes no
E003
temperature table in basic version).

Transmitter malfunction, software yes no


E007
does not match transmitter version

Sensor or sensor connection faulty Check sensor and sensor connection (see chapter yes no
E008 "Instrument check by medium simulation" or call
the E+H Service).

No temperature sensor connected or Check temperature sensor and connections; if yes no


E010 temperature sensor short-circuited necessary, check instrument with temperature
(temperature sensor faulty) simulator.

E025 Limit for air set offset exceeded Repeat air set (in air) or replace sensor. Clean and yes no
dry sensor before air set.

E036 Sensor calibration range exceeded Clean and recalibrate sensor; if necessary, check yes no
sensor and connections.
E037 Below calibration range of sensor yes no

E045 Calibration aborted Recalibrate. yes no

Calibration range of installation factor Check pipe diameter, clean sensor and repeat yes no
E049
exceeded calibration.

Below calibration range of installation yes no


E050
factor

Below measuring range of main Immerse sensor in conductive medium or perform yes no
E055
parameter air set.

Measuring range of main parameter Check measurement, control and connections yes no
E057
exceeded (simulation see chapter "Instrument check by
medium simulation").
E059 Below temperature measuring range yes no

Temperature measuring range yes no


E061
exceeded

66 Endress+Hauser
Smartec S CLD134 Troubleshooting

Error no. Display Tests and / or measures Alarm contact Error current

Factory User Factory User

E063 Below current output range 1 Check measured value and current output yes no
assignment (function group O).
E064 Current output range 1 exceeded yes no

E065 Below current output range 2 Check measured value and current output yes no
assignment.
E066 Current output range 2 exceeded yes no

Limit contactor set value exceeded Check measured value, limit setting and metering yes no
devices.
E067
Only available with R1 = alarm + limit value or limit
value.

Temperature outside α value table Check measurement and tables. yes no


E077
range

Temperature outside concentration yes no


E078
table

Conductivity outside concentration yes no


E079
table

Current output 1 parameter range too Spread current output. no no


E080
small

Current output 2 parameter range too Spread current output. no no


E081
small

E100 Current simulation active no no

Service function yes Switch service function off or switch instrument off no no
E101
and back on.

E102 Manual mode active no no

E106 Download yes Wait for download to end. no no

E116 Download error Repeat download. no no

Distance between temperature values Enter correct values in α value table (minimum no no
E150 in α value table too small distance of 1 K required between temperature
values).

E152 Live Check alarm Check sensor and connection. no no

9.3 Process-specific errors


Use the following table to locate and correct errors.

Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel

Calibration faulty Calibrate instrument according to chapter Calibration solution or sensor certificate
"Calibration".

Sensor soiled Clean sensor. See chapter "Cleaning conductivity sensors".

Incorrect temperature measurement Check temperature value on instrument Temperature measuring instrument,
and reference unit. precision thermometer
Display deviates from Incorrect temperature compensation Check compensation method (none / ATC Please note: transmitter has separate
reference measurement / MTC) and compensation type calibration and operating temperature
(linear/substance/user table). coefficients.

Reference instrument calibration faulty Calibrate reference instrument or use Calibration solution, operating instructions
calibrated instrument. of reference instrument

Incorrect ATC setting on reference Compensation method and compensation Operating instructions of reference
instrument type must be identical on both instruments. instrument

Endress+Hauser 67
Troubleshooting Smartec S CLD134

Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel

Short circuit / moisture in sensor Check sensor. See chapter "Checking inductive
conductivity sensors".

Short circuit in cable or junction box Check cable and junction box. See chapter "Checking extension cable and
junction box".

Interruption in sensor Check sensor. See chapter "Checking inductive


conductivity sensors".

Interruption in cable or junction box Check cable and junction box. See chapter "Checking extension cable and
Implausible measured junction box".
values in general:
Incorrect cell constant setting Check cell constant. Sensor nameplate or certificate
– continuous measured
value overflow Incorrect output assignment Check assignments of measured value to
– measured value always current signal.
000
Incorrect output function Check 0-20 / 4 -20 mA selection and curve
– measured value too low
shape (linear / table).
– measured value too high
– measured value frozen Air cushion in assembly Check assembly and installation.
– incorrect current output
Incorrect temperature measurement / Check instrument with equivalent Pt1000 simulation: s. chapter "Instrument
value
temperature sensor defective resistance/ check Pt1000 in sensor. check by medium simulation".
Pt1000 test: s. chapter "Checking inductive
conductivity sensors".

Transmitter module defective Test with new module. See chapters "Instrument-specific errors" and
"Spare parts".

Impermissible instrument operating Switch instrument off and back on. EMC problem: check grounding and line
state (no response to key actuation) routing if problem persists or call
Endress+Hauser Service to test.

Incorrect sensor connection Verify connections using connection Connection diagramm in chapter "Electrical
diagram; three-wire connection mandatory. connection"

Measuring cable defective Check cable for interruption/short circuit/ Ohmmeter; also see chapter "Instrument
Incorrect temperature value
shunt. check by medium simulation".

Incorrect temperature sensor type Select temperature sensor type on


instrument (field B1).

No / incorrect temperature ATC: select compensation type; linear: set


compensation correct coefficient.
MTC: set process temperature.

Incorrect temperature measurement Check temperature value. Reference instrument, thermometer

Bubbles in medium Suppress bubble formation:


– gas bubble trap
– counterpressure (cover)
– bypass measurement
Incorrect conductivity
measured value in process Incorrect sensor orientation Flow opening of sensor must point in Compact version: Remove electronics box to
medium flow direction. turn sensor (s. chapter "Sensor positioning").
Separate version: turn sensor in flange.

Flow rate too high (may cause bubbles) Reduce flow or choose low turbulence
mounting position.

Interference current in medium Ground medium close to sensor; Most frequent cause of currents in medium:
remove/repair interference source. defective submerged motors

Sensor soiled or coated Clean sensor (see chapter "Cleaning Heavily soiled media: use spray cleaning.
conductivity sensors").

Measuring cable interferences Connect cable screen according to See chapter "Electrical connection".
connection diagram.

Signal output line interferences Check line routing, try separate line routing. Separate routing of signal output and
Measured value fluctuates
measuring input lines

Interference currents in medium Eliminate source of interference or ground


medium close to sensor.

68 Endress+Hauser
Smartec S CLD134 Troubleshooting

Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel

Relay configured for alarm Activate limit contactor. See field R1.

Pickup delay setting too long Shorten pickup delay. See field R4.
Limit contact does not work
"Hold" function active “Automatic Hold” during calibration, See fields S2 to S5.
“Hold” input activated;
“Hold” via keyboard active.

Dropout delay setting too long Shorten dropout delay. See field R5.
Limit contact works
continuously Control loop interruption Check measured value, current output,
actuators, chemical supply.

Line open or short-circuited Disconnect line and measure directly on mA meter 0–20 mA
No conductivity current instrument.
output signal
Output defective See chapter "Instrument-specific errors".

Current simulation active Switch off simulation. See field O22.


Fixed conductivity current Impermissible operating state of Switch instrument off and back on. EMC problem: check installation, screen,
output signal processor system grounding if problem persists/ call
Endress+Hauser Service to test.

Incorrect current assignment Check current assignment: 0–20 mA or Field O211


4–20 mA?

Incorrect current output Total load in current loop excessive Disconnect output and measure directly on mA meter for 0–20 mA DC
signal (> 500 Ω.) instrument.

EMC (interference coupling) Disconnect both output lines and measure Use screened lines, ground screens on both
directly on instrument. sides, route line in other duct if necessary.

Instrument does not have 2nd current Refer to nameplate for variant; change Module LSCH-x2,
No temperature output output LSCH-x1 module if necessary. see chapter "Spare parts".
signal
Instrument with PROFIBUS PA PA instrument has no current output!

Extension package Extension package not enabled (enable – When upgrading instrument with For a detailed description, see chapter
functions not available with code that depends on serial extension package: code received from "Replacement of central module".
(Live Check, current curve number and is received from Endress+Hauser ⇒ enter.
2 ... 4, alpha value curve Endress+Hauser with order of – After replacing defective LSCH/LSCP
2 ... 4, user conc. curve extension package) module: first enter instrument serial
1 ... 4) number (s. nameplate) manually, then
enter code.

No central HART module Verify by looking at nameplate: Upgrade to LSCH-H1 / -H2.


HART = -xxxxxxHAx and -xxxxxxHBx

Current output < 4 mA

No or wrong DD (device description)

HART interface missing

Instrument not registered with HART


server

Load too low (load > 230 Ω required) For further information see
No HART communication BA212C/07/en, “Field communication
HART receiver (e.g. FXA 191) not
with HART”.
connected via load but via power supply

Incorrect device address (addr. = 0 for


single operation, addr. > 0 for
multi-drop operation)

Line capacitance too high

Line interferences

Several devices set to same address Set addresses correctly. Communication not possible with several
devices set to same address.

Endress+Hauser 69
Troubleshooting Smartec S CLD134

Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel

No central PA/DP module Verify by looking at nameplate: Upgrade to LSCP module,


PA = -xxxxxxPEx and = -xxxxxxPFx see chapter "Spare parts".
DP = -xxxxxxPPx

Incorrect instrument software version


(without PROFIBUS)

Commuwin (CW) II:


Incompatible CW II and instrument
software versions

No or incorrect DD/DLL

Incorrect baud rate setting for segment


coupler in DPV-1 server For further information, see
No PROFIBUS®
BA213C/07/en "Field communication
communication Incorrect station (master) addressed or with PROFIBUS PA/DP".
duplicate address

Incorrect station (slaves) address

Bus line not terminated

Line problems
(too long, cross section too small; not
screened, screen not grounded, wires
not twisted)

Bus voltage too low Voltage at instrument’s PA/DP connector


(bus supply voltage typ. 24 V DC for must be at least 9 V.
non-Ex)

9.4 Instrument-specific errors


The table below will help you diagnose problems and specifies the spare parts required.
A diagnosis depending on difficulty and measuring equipment at hand is to be performed by:
• trained operator personnel
• operator’s electricians
• company responsible for system installation / operation
• E+H Service
Please refer to the chapter "Spare parts" for information on the exact designations of the spare parts
and their installation.

Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel

No mains voltage Check if mains voltage is available. Electrician / e.g. multimeter

Wrong supply voltage / voltage too low Compare mains voltage and rating on Operator (utility company specification or
nameplate. multimeter)

Connection fault Terminal not tightened;; Electrician


insulation clamped in terminal;
wrong terminals used.

Fuse blown Compare mains voltage and rating on Electrician / correct fuse;
Display dark, no LEDs
nameplate and replace fuse. see drawing in chapter "Spare parts".
active
Power supply unit defective Replace power supply unit using correct On-site diagnosis by E+H Service (test
variant. module required)

Central module LSCH / LSCP defective Replace central module using correct On-site diagnosis by E+H Service (test
variant. module required)

Ribbon cable between central module Check ribbon cable, replace if necessary. See chapter "Spare parts".
and power supply unit loose or
defective

Central module defective Replace central module. On-site diagnosis by E+H Service (test
Display dark, LED active
(module: LSCH/LSCP) module required)

70 Endress+Hauser
Smartec S CLD134 Troubleshooting

Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel

Display shows measured Ribbon cable or transmitter module not Reinsert transmitter module, use additional Refer to exploded view in chapter "Spare
value but properly installed fastening screw M3 if necessary. Check if parts".
ribbon cable is inserted correctly.
– value does not change
and / or Impermissible operating system state Switch instrument off and back on. Possible EMC problem: if problem persists,
– instrument cannot be check the installation or call E+H Service to
operated have it checked.

Incorrect display, missing Moisture or dirt in display frame, rubber Replace central module LSC.... See chapter "Spare parts".
dots, segments, characters not pressed on correctly or PCB Emergency: Remove display frame, clean
or lines contacts soiled glass and PCB, dry well and reinstall. Do
not touch conducting rubber with hands!

Incorrect voltage / too high Compare mains voltage and rating on Operator, electrician
nameplate.

Instrument gets hot Heating from process or solar radiation Improve positioning or use separate version.
Use sun protection outdoors.

Power supply unit defective Replace power supply unit. Can only be diagnosed by E+H Service.

Incorrect measured Transmitter module defective (module: Test measuring inputs: Test negative: replace module (using correct
conductivity and / or MKIC), please perform tests and take variant).
– Simulation with resistance, see table in
temperature value measures according to chapter "Process Refer to exploded view in chapter "Spare
chpt. "Instrument check by medium
errors without messages" parts".
simulation".
– Connect 1000 Ω resistor to terminals
11 / 12 + 13 = display 0 °C.

Not calibrated correctly Test with built-in current simulation (field If simulation value is incorrect: recalibration
O221), connecting mA meter directly to at factory or new LSCxx module are
Load excessive
current output. required.
Incorrect current output Shunt / short-circuit to frame in If simulation value is correct: check current
signal current loop loop for load and shunts.

Incorrect mode of operation Check whether 0–20 mA or 4–20 mA has


been selected.

No current output signal Current output stage defective Test with built-in current simulation, If test fails:
(LSCH/LSCP module) connecting mA meter directly to current Replace central module LSCH/LSCP (using
output. correct variant).

No or wrong release codes used If upgraded: Check whether correct serial To be handled by E+H Sales.
Additional functions number was used when ordering extension
(extended functions or functions or MRS.
measuring range switching) Incorrect instrument serial number Check whether serial number on nameplate Instrument serial no. in LSCH/LSCP
missing stored in LSCH/LSCP module matches SNR in LSCH/ LSCP (field S 10). module is required for the function
extensions.

Additional (extended LSCH or LSCP replacement modules For LSCH / LSCP with serial no. 0000, an For a detailed description, see chapter
functions or measuring are supplied with the instrument serial instrument serial no. can be entered once "Replacement of central module".
range switching) not no. 0000. Extensions are not released in fields E115 to E118.
available after replacement ex-factory. Then enter release code for extension
of LSCH/LSCP module package.

Wrong central module HART: LSCH-H1 or -H2 module, Replace central module;
PROFIBUS PA: LSCP-PA module, operator or E+H-Service.
PROFIBUS DP: LSCP-DP module,
No HART or PROFIBUS see fields E111 ... 113.
PA/DP interface function
Wrong instrument software SW version, see field E111. SW can be changed with Optoscope.

Incorrect configuration See troubleshooting table in chapter


"System errors without messages".

Endress+Hauser 71
Troubleshooting Smartec S CLD134

9.5 Spare parts


Spare parts are to be ordered from your sales center responsible. Specify the order numbers listed in
the chapter "Spare parts kits".
To be on the safe side, you should always specify the following data with your spare part orders:
• Instrument order code (order code)
• Serial number (serial no.)
• Software version where available
Refer to the nameplate for the order code and serial number.
The software version is displayed in the instrument sofware (see chapter "Instrument configuration")
if the instrument processor system is functional.

72 Endress+Hauser
Smartec S CLD134 Troubleshooting

9.5.1 Exploded view

unlock protective cover


Slot for screwdriver to
Pos. 140

Pos. 30
Betrieb nur
mit dieser
und Schutzle Abdecku
iteransch ng
luß
Operation
only with
and protectiv this
e earth con cover
nection

Pos. 10
Install electronics box first,
then connect instrument
and snap on protective cover

Pos. 20

Pos. 40

Pos. 50 ... 55

Pos. 120 ... 122

Pos. 130

Ribbon cable on
right plug connector
(module viewed from Pos. 110
front)

Pos. 60/61 CAL


+
Alarm

E -
Fuse
M3, 15A /5*20
Corner into all variants
which power
supply assembly
is inserted Pos. 90 / 91

Pos. 80

Pos. 70 ... 75

First corner to be
inserted into electronics Pos. 100 /101
box during assembly
a0005652-en

The exploded view drawing shows all components and spare parts of Smartec S CLD134. Use the
position numbers to find the spare parts designation and their order number in the following section.

Endress+Hauser 73
Troubleshooting Smartec S CLD134

9.5.2 Spare part kits

Item Kit designation Name Function/content Order number

10 Housing bottom, separate Bottom assembly 51501574

20 Housing bottom, compact Bottom assembly 51501576

30 Post mounting kit 1 pair of post mounting parts 50062121

40 Housing cover Cover with accessories 51501577

50 Sensor assembly MV5, Spare sensor 71020487


dairy fitting

51 Sensor assembly AA5, Spare sensor 71020488


aseptic fitting

52 Sensor assembly CS1, Spare sensor 71020489


clamp ISO 2852 2"

53 Sensor assembly SMS, Spare sensor 71020490


SMS 2"

54 Sensor assembly VA4, Spare sensor 71020491


Varivent® N DN 40 to 125

55 Sensor assembly BC5, Spare sensor 71020492


Neumo BioControl® D50

60 Elektronics box Box w. membrane, key tappets 51501584

61 Electronics box PA/DP Box with front foil, key tappets, 51502280
protection cover

70 Central module (controller) LSCH-S1 1 current output 51502376

71 Central module (controller) LSCH-S2 2 current outputs 51502377

72 Central module (controller) LSCH-H1 1 current output + HART 51502378

73 Central module (controller) LSCH-H2 2 current outputs + HART 51502379

74 Central module (controller) LSCP-PA PROFIBUS PA / no current output! 51502380

75 Central module (controller) LSCP-DP PROFIBUS DP / no current 51502381


output!

80 Conductivity transmitter MKIC Conductivity + temperature input 51501206

90 Power supply unit (main LTGA 100/115/230 V AC 51501585


module)

91 Power supply unit (main LTGD 24 V AC + DC 51501586


module)

100 Terminal strip kit Terminal strips 5/8/13 poles 51501587

101 Terminal strip kit PA/DP Terminal strips 5/8/13 poles 51502281

110 Ribbon cable 20-wire line with connector 51501588

121 Cable entry kit M20 Cable glands, plugs, Goretex filter 51502282

122 Cable entry kit Conduit Cable glands, plugs, Goretex filter 51502283

130 Screw and gasket kit All screws and gaskets 51501596

140 Protection cover kit Protection cover for connection 51502382


compartment

74 Endress+Hauser
Smartec S CLD134 Troubleshooting

9.6 Return
If the transmitter has to be repaired, please return it cleaned to the sales center responsible. Please
add a detailed failure description. If the failure diagnosis is not clear please send also the cable and
the sensor.
Please use the original packaging, if possible.
Please enclose the completed "Declaration of Hazardous Material and De-Ccontamination" (copy
the second last page of these Operating Instructions) with the packaging and also the shipping
documents.

9.7 Disposal
The device contains electronic components and must therefore be disposed of in accordance with
regulations on the disposal of electronic waste.
Please observe local regulations.

9.8 Software history

Date Version Changes to Software Documentation: Edition

03/2006 1.12 Original software BA401C/07/en/03.06

07/2007 1.13 Change of cell constant BA401C/07/en/07.07

Endress+Hauser 75
Technical Data Smartec S CLD134

10 Technical Data
10.1 Input
Measured variables Conductivity
Concentration
Temperature

Measuring range Conductivity: recommended range:


100 μS/cm to 2000 mS/cm
(uncompensated)

Concentration
– NaOH: 0 to 15 %
– HNO3: 0 to 25 %
– H2SO4: 0 to 30 %
– H3PO4: 0 to 15 %

Temperature: –35 to +250 °C (-31 to +482 °F)

Cable specification max. cable length 55 m (180.46 ft) with CLK5 cable (separate version)

Binary inputs 1 and 2 Voltage: 10 to 50 V DC

Current consumption: max. 10 mA at 50 V

10.2 Output
Output signal Conductivity, concentration: 0 / 4 to 20 mA, galvanically isolated
Temperature (optional second current
output)

Minimum distance for Conductivity measurement:


0 / 4 to 20 mA output signal – Measured value 0 to 19.99 μS/cm: 2 μS/cm
– Measured value 20 to 199.9 μS/cm: 20 μS/cm
– Measured value 200 to 1999 μS/cm: 200 μS/cm
– Measured value 0 to 19.99 mS/cm: 2 mS/cm
– Measured value 20 to 200 mS/cm: 20 mS/cm
– Measured value 200 to 2000 mS/cm: 200 mS/cm

Concentration measurement: no minimum distance

Signal on alarm 2.4 mA or 22 mA error current

Load max. 500 Ω

Output range Conductivity: adjustable


Temperature: adjustable

Signal resolution max. 700 digits/mA

Separation voltage max. 350 VRMS / 500 V DC

Overvoltage protection acc. to EN 61000-4-5:1995

Auxiliary voltage output Output voltage: 15 V ± 0.6 V

Output current: max. 10 mA

Contact outputs Switching current with ohmic load max. 2 A


(cos ϕ = 1):

Switching current with inductive load max. 2 A


(cos ϕ = 0.4):

Switching voltage: max. 250 V AC, 30 V DC

Switching power with ohmic load max. 500 VA AC, 60 W DC


(cos ϕ = 1):

Switching power with inductive load max. 500 VA AC


(cos ϕ = 0.4):

Limit contactor Pickup / dropout delay: 0 to 2000 s

Alarm Function (switchable): steady / fleeting contact

Alarm delay: 0 to 2000 s (min)

76 Endress+Hauser
Smartec S CLD134 Technical Data

10.3 Power supply

Supply voltage Depending on ordered version:


100 / 115 / 230 V AC +10 / -15 %, 48 to 62 Hz
24 V AC/DC +20 / -15 %

Power consumption max. 7.5 VA

Mains fuse Fine-wire fuse, medium time lag, 250 V / 3.15 A

10.4 Performance characteristics

Measured value resolution Temperature: 0.1 °C (0.18 °F)

Measured value deviation1) Conductivity:


– Display: max. 0.5 % of measured value ± 4 digits
– Conductivity signal output: max. 0.75 % of current output range

Temperature
– Display: max. 0.6 % of measuring range
– Temperature signal output: max. 0.75 % of current output range

Repeatability1 Conductivity: max. 0.2 % of measured value ± 2 digits

Measuring frequency 2 kHz


(oscillator)

Temperature compensation Range: –10 to +150 °C (14 to 302 °F)

Compensation types: – none


– linear with freely selectable temperature
coefficient α
– one freely programmable coefficient table
(four tables available in versions with remote
parameter set switching)
– NaCl acc. to IEC 746-3

Minimum distance for table: 1K

Reference temperature 25 °C (77 °F)

Temperature offset adjustable, ± 5 °C / 9 °F, for temperature display adjustment

1) acc. to IEC 746 part 1, nominal operating conditions

10.5 Environment

Ambient temperature 0 to +55 °C (32 to 131 °F)

Ambient temperature limits –10 to +70 °C (14 to 158 °F) (separate version and separate transmitter)
–10 to +55 °C (14 to 131 °F) (compact version)
(see Fig. 41 "Permissible temperature ranges of Smartec S CLD134")

Storage temperature –25 to +70 °C (-13 to 158 °F)

Electromagnetic compatibility Interference emission and interference resistance acc. to EN 61326: 1997 / A1: 1998

Ingress protection IP 67

Relative humidity 10 to 95%, non-condensing

Vibration resistance acc. to Oscillation frequency: 10 to 500 Hz


IEC 60770-1 and IEC 61298-3
Deflection (peak value): 0.15 mm / 0.01"

Acceleration (peak value): 19.6 m/s2 (64.3 ft/s2)

Impact resistance Display window: 9J

Endress+Hauser 77
Technical Data Smartec S CLD134

10.6 Mechanical construction

Design, dimensions Separate transmitter with mounting L x W x D: 225 x 142 x 109 mm (8.86 x 5.59
plate x 4.29 ")

Compact transmitter MV5, CS1, L x W x D: 225 x 142 x 109 mm (8.86 x 5.59


AA5, SMS: x 10.04 ")

Compact transmitter VA4, BC5: L x W x D: 225 x 142 x 109 mm (8.86 x 5.59


x 8.39 ")

Weight Separate version

Transmitter: approx. 2.5 kg (5.5 lb.)

Sensor CLS54: depending on version 0.3 to 0.5 kg


(0.66 to 1.1 lb.)

Compact version with CLS54 approx. 3 kg (6.6 lb.)


sensor:

Transmitter materials Housing: stainless steel 1.4301, polished

Front window: polycarbonate

10.7 Specification of CLS54 sensor

Conductivity measuring range recommended range: 100 μS/cm to 2000 mS/cm (uncompensated)

Measured value deviation ± (0.5 % of measured value + 10 μS/cm) after calibration


(plus inaccuracy of the conductivity of the calibration solution)

Cell constant k = 6.3 cm-1

Temperature sensor Pt 1000 (class A acc. to IEC 60751)

Temperature measuring range -10 to +150 °C (+14 to +302 °F)

Temperature response time t90 ≤ 26 s

Materials in contact with medium Virgin PEEK

Materials not in contact with medium PPS-GF40, stainless steel 1.4404 (AISI 316L), screws: 1.4301 (AISI 304),
FKM, EPDM (seal), PVDF (cable gland - separate version only),
TPE (cable - separate version only)

Surface roughness Ra ≤ 0.8 μm (smooth, injection-molded PEEK surface) for the surfaces in
contact with medium

10.8 Process

Process temperature CLS54 sensor with separate version: -10 to 125 °C (14 to 257 °F)
at 70 °C (158 °F) ambient temperature

Compact version: -10 to 55 °C (14 to 131 °F)


at 55 °C (131 °F) ambient temperature
-10 to 125 °C (14 to 257 °F)
at 35 °C (95 °F) ambient temperature

Sterilisation CLS54 sensor with separate version: max. 150 °C (302 °F) at 70 °C (158 °F)
ambient temperature, 5 bar (72.5 psi),
max. 60 min

Compact version: max. 150 °C (302 °F) at 35 °C (95 °F) ambient


temperature, 5 bar (72.5 psi), max. 60 min

Process pressure max. 12 bar (174 psi) up to 90 °C (194 °F)


8 bar (116 psi) at 125 °C (257 °F)
0 to 5 bar ( 0 to 72.5 psi) when in CRN-applicable areas (tested with 50 bar (725 psi))
underpressure down to 0.1 bar (1.45 psi) absolute

Ingress protection CLS54 IP 68 / NEMA 6P ( 1m water column, 50 °C, 168 h)


sensor

78 Endress+Hauser
Smartec S CLD134 Technical Data

Permissible temperature ranges of Smartec S CLD134

[°F] [° C]
A
158 70
C
140 60
131 55

Ambient temperature
122 50 B

104 40
95 35
86 30

68 20

50 10

32 0

–10
55
–10 0 20 40 60 80 100 120 140 [° C]

32 68 104 131140 176 212 248 257 284


[°F]
Medium temperature
a0005499-en

Fig. 43: Permissible temperature ranges of Smartec S CLD134


A CLS54 sensor with separate version
B Compact version
C Short term for sterilization (<60 min)

Pressure-temperature load curve of CLS54 sensor

[psi] [bar]

174 12

B
116 8

72.5 5
58 4
A

–10 0 10 30 50 70 90 110 125 150 [° C]

32 50 86 122 158 194 230 257 302 [°F]


a0008379

Fig. 44: Pressure / temperature load curve


A short-time sterilization (max. 60 min)
B MAWP (maximum allowable working pressure) according to ASME-BPVC Sec. VIII, Div 1, UG101 for CRN
registration

10.9 Chemical durability of CLS54 sensor

Medium Concentration PEEK

Caustic soda NaOH 0 to 15 % 20 to 90 °C (68 to 194 °F)

Nitric acid HNO3 0 to 25 % 20 to 90 °C (68 to 194 °F)

Phosphoric acid H3PO4 0 to 15 % 20 to 80 °C (68 to 176 °F)

Sulphuric acid H2SO4 0 to 30 % 20 °C (68 °F)

Peracetic acid H3C-CO-OOH 0.2 % 20 °C (68 °F)

No responsibility is taken for the correctness of this information.

Endress+Hauser 79
Appendix Smartec S CLD134

11 Appendix
Operating matrix
Calibration Entry of Entry of a value of Entry of correct Display of calculated
calibration temperature calibration solution conductivity value of installation factor
(if B1 = fixed) calibration solution
InstF 2.10 %/K 1.0
= installation factor C1 (3) 25.0 °C 0.00 ... 20.00 %/K current meas. value C133 0.10 ... 5.0
–35.0 ... +250.0 °C C131 C132 0.0 µS/cm ... 9999 mS/cm C134

Entry of Entry of a value of Entry of correct Display of calculated


Cellc calibration temperature calibration solution conductivity value of cell constant
= cell constant (if B1 = fixed) . calibration solution
C1 (2) . . -1
2.10 %/K current meas. value C123 0.1 ... 9.99 cm
25.0 °C 0.00 ... 20.00 %/K
–10.0 ... +150.0 °C C121 C122 0.0 mS/cm ... 9999 mS/cm C124

Function group
Residual coupling Display of Display of Store
CALIBRATION Airs = Airset
Start calibration residual coupling value calibration status calibration results
C1 (1) .
current meas. value -80.0 ... 80.0 µS o.k.; yes; no; new
C C112
C111 E--- C113 C114
any code
Read mode:
Code 22
Edit mode:

Display of Display of Display of


conductivity and conductivity conductivity (uncompensated)
MEAS. VALUE DISPLAY temperature (°F) concentration

Conductivity
and
Display of current Error display
temperature (°C)
parameter set (up to 10 errors)
(Remote parameter set Err ---
switching only)
any code
Read mode:
Code 22
Edit mode:

Function group Selection of operating mode Selection of display Selection of display format Selection of display Entry of cell constant
unit (if A1 = conc) unit
SETUP 1
cond = conductivity ppm; mg/l; %; TDS; none X.xxx; XX.xx; XXX.x; XXXX auto; µS/cm; mS/cm; S/cm; 0.1 ... 6.3 ... 99.99 cm-1
conc = concentration µS/m; mS/m; S/m

A A1 A2 A3 A4 A5

Function group Selection of Selection of temperature Entry of a value Entry of correct Temperature sensor
temperature measurement compensation type (if B2 = linear) process temperature offset
SETUP 2 .none
(if B1 = fixed) (not if B1 = fixed)
Pt100 lin = linear 2.10 %/K
Pt1k (= Pt 1000) NaCI = common salt 0.00 ... 20.00 %/K 25.0 °C Entry of actual temp.
NTC30 (= NTC 30 kW) Tab = table 1 ... 4 –35.0 °C ... +250.0 °C –35.0 ... +250.0 °C
fixed (>1 with software option
B only)
B1 B2 B3 B4 B5

Selection of characteristic Entry of


simulation value

sim = simulation current value


O2 (2) 0 ... 22.00 mA
O221

Function group Selection of Selection of Entry of Entry of


OUTPUT current output current range 0/4 mA value 20 mA value

Out 1; Out 2 lin = linear 4-20 mA; 0-20 mA 0 µS/cm; 0 %; 0 °C 2000 mS/cm; 99.99 %;
O2 (1) entire meas. range 150.0 °C
entire meas. range
O O1 O211 O212 O213

Function group Selection of Selection of Entry of Determination of Selection of


ALARM contact type unit for alarm delay error current error number
alarm delay
Stead = steady contact 0s ... 2000 s (min) 22 mA 1
F (depending on F2) 2.4 mA F4 1 ... 255
Fleet = fleeting contact F1 s; min F2 F3 F5

Function group PCS alarm setting


CHECK (live check)
(with software option Monitoring limit
only) off / 1h / 2h / 4h 0.3 % of mean value
P over time entered P1

a0005699-en

80 Endress+Hauser
Smartec S CLD134 Appendix

Display of Store
calibration status calibration results

o.k.; yes; no; new


E---
C135 C136

Display of Store
calibration status calibration results

o.k.; yes; no; new


E---
C125 C126

Entry of installation factor Entry of


measured value damping

01 ... 1.00 ... 5.00 1 (no damping)


1 ... 60

A6 A7

Display of
temperature difference
(not if B1 = fixed)

0.0 °C
–5.0 ... 5.0 °C
B6

Field for entry of


user setting

Set alarm contact to be Set error current Select "next error"


effective to be effective or return to menu

yes; no no; yes next = next error


F6 F7 ¬R F8

a0005700-en

Endress+Hauser 81
Appendix Smartec S CLD134

Function group Selection of Selection of contact Selection of contact Pickup delay Dropout delay
RELAY function switch-on point switch-off point setting setting
(with software option only)
Alarm; 2000 mS/cm; 99.99 % 2000 mS/cm; 99.99 % 0s 0s
Limit; entire meas. range entire meas. range 0 ... 2000 s 0 ... 2000 s
Alarm+limit
R R1 R2 R3 R4 R5

Function group Selection of Selection of Entry of number Selection of Entry of


ALPHA TABLE tables table option of value pairs in table table value pair temperature value
1 (x value)
1 ... 4 read 1 1
(>1 with software option edit 1 ... 10 1 ... number of T3 0.0 °C
T only) T1 T2 T3 assign T4 –35.0 ... 250.0 °C T5

Function group Selection of active Multiplication factor Selection of Selection of Entry of number of
concentration table for concentration value tables table option value pairs in table
CONCENTRATION of a user table 1
NaOH; H2SO4; (with user tables only) 1 ... 4 read 4
H3PO4; HNO3 1 (>1 with software edit 1 ... 16
K User 1 ... 4 K1 0.5 ... 1.5 K2 option only) K3 K4 K5

Function group Selection of Selection of Entry of HOLD configuration Manual HOLD


SERVICE language HOLD effect fixed value none = no HOLD
(only if S2 = fixed) S+C = during setup
ENG; GER froz = last value 0 and calibration off
ITA; FRA fixed = fixed value 0 ... 100 % Setup = during setup on
S ESP; NEL S1 S2 of 20 or 16 mA S3 CAL = dur. calibration S4 S5

Module selection Software Hardware Display of Entry of


version version serial number serial number

SW version HW version yes


Sens = sensor E1(4) no
E141 E142 E143 E144

Software Hardware Display of


version version serial number
MainB = E1(3) SW version HW version
Mainboard
E131 E132 E133

Software Hardware Display of


version version serial number
Trans =
Transmitter E1(2) SW version HW version

E121 E122 E123

Function group Software Hardware Display of


E+H SERVICE version version serial number

Contr = Controller SW version HW version


E1(1)
E E111 E112 E113

Function group Entry of address Tag description


INTERFACE HART: 0 ... 15
PROFIBUS: 1 ... 126
I I1 @@@@@@@@ I2

Function group Entry of Display of Entry of Display of


DETERMIN. OF compensated uncompensated current temperature determined Alpha value
conductivity conductivity
TEMPERATURE 2.10 %/K
COEFFICIENT(with current value current value current value
software option only) D 0 ... 9999 0 ... 9999 –35 ... +250 °C
D1 D2 D3 D4

Function group Selection of binary Display of current Selection of Selection of oper. mode Selection of medium
REMOTE inputs for MRS parameter set parameter set
NaOH; H2SO4;
PARAMETER SET 2 cond = conductivity
1 1 H3PO4; HNO3;
SWITCHING 0 ... 2 1 ... 4 if M1=0 1 ... 4 if M1=0 conc = concentration User 1 ... 4
(MRS) M M1 M2 1 ... 2 if M1=1 M3 M4 (if M4=conc) M5

a0005701-en

82 Endress+Hauser
Smartec S CLD134 Appendix

Selection of Switch simulation


simulation on or off
(only if R1 = limit) (only if R6 = manual)

auto off
manual on
R6 R7

Entry of Output
temperature coefficient a table status o.k.
(y value)
yes; no
2.10 %/K
0.00 ... 20.00 %/K T6 T7

Selection of Entry of Entry of associated Entry of associated Output


table value pair uncompensated concentration value temperature value table status o.k.
conductivity value
1 0.00 % 0.0 °C yes; no
1 ... number from K5 0.0 µS/cm 0 ... 99.99 % –35.0 ... +250.0 °C
K6 0.0 ... 9999 mS/cm K7 K8 K9 K10

Entry of Entry of Display of Display of Instrument reset Start


HOLD dwell period release code for order number serial number instrument test
SW upgrade MRS no;
10 Sens = sensor data; no;
0 ... 999 s 0000 Facty = factory settings Display
S6 0000 ... 9999 S7 S8 S9 S11
S10

Entry of Entry of Entry of Confirm


serial number serial number serial number serial number
1st digit 2nd digit 3rd - 6th digit
yes
0 1 1 no
0 ... 9 E145 1 ... 9, A, B, C E146 1 ... FFF E147 E148

Selection of Entry of Entry of measured value Entry of measured value Entry of limit Entry of limit
temperature compensation alpha value for 0/4 mA value for 20 mA value switch-on point switch-off point
cond.: 0 ... 2000 mS/cm cond.: 0 ... 2000 mS/cm cond.: 0 ... 2000 mS/cm cond.: 0 ... 2000 mS/cm
none; lin; NaCl; 2.1 conc.: 0 ... 99.99 % conc.: 0 ... 99.99 % conc.: 0 ... 99.99 % conc.: 0 ... 99.99 %
Tab 1 ... 4 0 ... 20 %/K Unit: A2 Unit: A2 Unit: A2 Unit: A2
if M4=cond M6 if M6=lin M7 Format: A3 M8 Format: A3 M9 Format: A3 M10 Format: A3 M11

a0005702-en

Endress+Hauser 83
Smartec S CLD134

Index
A I
Access codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Icons
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Immunity to interference . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Alarm contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Anschlussraumaufkleber . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Installation . . . . . . . . . . . . . . . . . . . . . . . . . 5, 11–12, 19, 21
C Compact version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Separate version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Installation conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Calibration solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Compact version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Check Separate version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Conductivity sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 27 Instrument-specific errors . . . . . . . . . . . . . . . . . . . . . . . . . 70
Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Instrument . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 J
Line extension and junction box . . . . . . . . . . . . . . . . . 63 Junction box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
CLS54 sensor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 K
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . 5, 33–34, 58 Key assignment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Communication interfaces . . . . . . . . . . . . . . . . . . . . . 52, 58
Concentration measurement. . . . . . . . . . . . . . . . . . . . . . . 47 L
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
M
D Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . 10 Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Dismantling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Smartec S CLD134 . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Mechanical construction. . . . . . . . . . . . . . . . . . . . . . . . . . 78
Menu structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
E Monitoring functions
E+H Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 MRS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Binary inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Electrical icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 N
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Errors
Instrument specific . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
O
Process specific . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
System error messages . . . . . . . . . . . . . . . . . . . . . . . . 66 Operating matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Exploded view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Extension cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 28–29, 31
Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
F Optoscope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63, 65
Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41, 76
H
Hold function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32, 50

84 Endress+Hauser
Smartec S CLD134

P
PCS alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Performance characteristics . . . . . . . . . . . . . . . . . . . . . . . . 77
Post mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Post mounting kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . 15, 17
Process-specific errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Product structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Q
Quick setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

R
Relay configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Remote measuring range switching . . . . . . . . . . . . . . . . . . 53
Replacement of central module . . . . . . . . . . . . . . . . . . . . . 60
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 75

S
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Setup 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Setup 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Software upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Symbols
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
System error messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

T
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76–78
Temperature coefficient. . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Temperature compensation . . . . . . . . . . . . . . . . . . . . . . . . 46
Linear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
NaCl . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
With table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

U
Use
Designated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

W
Wall distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Endress+Hauser 85
Smartec S CLD134

86 Endress+Hauser
Declaration of Hazardous Material and De-Contamination
Erklärung zur Kontamination und Reinigung
Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA#
clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
RA No. Bitte geben Sie die von E+H mitgeteilte Rücklieferungsnummer (RA#) auf allen Lieferpapieren an und vermerken Sie diese
auch außen auf der Verpackung. Nichtbeachtung dieser Anweisung führt zur Ablehnung ihrer Lieferung.

Because of legal regulations and for the safety of our employees and operating equipment, we need the "Declaration of Hazardous Material
and De-Contamination", with your signature, before your order can be handled. Please make absolutely sure to attach it to the outside of the
packaging.
Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, benötigen wir die unterschriebene
"Erklärung zur Kontamination und Reinigung", bevor Ihr Auftrag bearbeitet werden kann. Bringen Sie diese unbedingt außen an der
Verpackung an.

Type of instrument / sensor Serial number


Geräte-/Sensortyp ____________________________________________ Seriennummer ________________________

Used as SIL device in a Safety Instrumented System / Einsatz als SIL Gerät in Schutzeinrichtungen

Process data/Prozessdaten Temperature / Temperatur_____ [°F] _____ [°C] Pressure / Druck _____ [psi] _____ [ Pa ]
Conductivity / Leitfähigkeit ________ [µS/cm] Viscosity /Viskosität _____ [cp] _____ [mm2/s]

Medium and warnings


Warnhinweise zum Medium

harmful/
Medium /concentration Identification flammable toxic corrosive irritant other * harmless
Medium /Konzentration CAS No. entzündlich giftig ätzend gesundheits- sonstiges* unbedenklich
schädlich/
reizend
Process
medium
Medium im
Prozess
Medium for
process cleaning
Medium zur
Prozessreinigung
Returned part
cleaned with
Medium zur
Endreinigung
* explosive; oxidising; dangerous for the environment; biological risk; radioactive
* explosiv; brandfördernd; umweltgefährlich; biogefährlich; radioaktiv
Please tick should one of the above be applicable, include safety data sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen.

Description of failure / Fehlerbeschreibung __________________________________________________________________________


______________________________________________________________________________________________________________
______________________________________________________________________________________________________________

Company data /Angaben zum Absender

Company /Firma ___________________________________ Phone number of contact person /Telefon-Nr. Ansprechpartner:


_________________________________________________ ____________________________________________
Address / Adresse Fax / E-Mail ____________________________________________
_________________________________________________
_________________________________________________ Your order No. / Ihre Auftragsnr. ____________________________

“We hereby certify that this declaration is filled out truthfully and completely to the best of our knowledge.We further certify that the returned
parts have been carefully cleaned. To the best of our knowledge they are free of any residues in dangerous quantities.”
“Wir bestätigen, die vorliegende Erklärung nach unserem besten Wissen wahrheitsgetreu und vollständig ausgefüllt zu haben. Wir bestätigen
weiter, dass die zurückgesandten Teile sorgfältig gereinigt wurden und nach unserem besten Wissen frei von Rückständen in gefahrbringen-
der Menge sind.”
P/SF/Konta XIV

(place, date / Ort, Datum) Name, dept./Abt. (please print /bitte Druckschrift) Signature / Unterschrift
www.endress.com/worldwide

BA401C/07/en/01.08
Printed in Germany / FM+SGML 6.0 / DT
71066353

Potrebbero piacerti anche