Sei sulla pagina 1di 11

Arc Flash in the

National Electrical Code


DO ARTICLES 240.87 AND 240.67
ACHIEVE THEIR INTENT AND GOALS?

©IstockPhoto.Com/idealistock

By Marcelo E. Valdes, Steve Hinton, The National Electrical Code (NEC) has ­included  requirements
and Francisco Martinez for arc-flash-related labeling for several code cycles [1]. Increasingly rigorous require-
ments for specific arc-flash-related protection attempt to reduce any arc-flash
hazards to which personnel may be exposed. They may be exposed to arc-flash
hazards during planned energized work or accidentally at any time. The risk-
Digital Object Identifier 10.1109/MIAS.2018.2868354
control mechanisms added to the NEC in recent times include additional signage
Date of publication: 5 November 2018 requirements and two articles that intend to reduce arc-flash hazard by decreasing

1077-2618/19©2019IEEE j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 53


clearing time for circuits rated 1,200 A These methods can be used to
or greater whether protected by circuit reduce clearing time, but they are all
breakers or fuses. This article discusses A robust and reliable very different solutions. How does a
these recent protection requirements designer know if the specified meth-
and their intent and potential practical solution will use od provides the desired reduction of
effects as well as how to ensure that
the protection this language seeks to
a lower threshold arc-flash incident energy (Ei)? The
methods described may be divided
provide is included in the electrical due to the potential into two categories:
power distribution system. 1) those methods that expressly list
variability of the what is needed to ensure that the
Overview of Clearing
Time Methods
arcing current. protection threshold will sense the
expected available arcing current
Currently, National Fire Protection 2) those methods that imply such
Association (NFPA) 70, the 2017 needs but do not expressly state
NEC [1], has two sections addressing them.
required minimum arc-energy reduction for low-voltage This is an important distinction because adding a mech-
fuses and circuit breakers rated 1,200 A and higher. anism to reduce clearing time does not ensure its effective-
For fuses, Section 240.67 takes effect 1 January 2020. ness unless the added protection operates when needed
Section 240.87 is in effect now for circuit breakers. (i.e., at the full range of expected arcing current in the pro-
Both sections require documentation available to those tected circuit). To comply with the intent of the code, the
authorized to design, install, operate, or inspect the ability for the control measures to operate at the expected
installation as to the location of the circuit breaker or available arcing current is the key operating parameter that
fuse. Both sections offer methods to reduce clearing must be determined, regardless if it is stated in the NEC. To
time (for implied arc-flash reduction) and are shown in implement one of the stated mechanisms without knowing
Tables 1 and 2. if it will work may comply with the letter of the code but
not with its intent. In addition, a robust and reliable solu-
tion will use a lower threshold due to the potential variabil-
ity of the arcing current.
Table 1. NEC 240.87
For Circuit Breakers, One of the Following Means Shall Be How to Categorize and Evaluate Solutions
Provided: NFPA 70E-2015 [2] describes the hierarchy of risk-control
1) ZSI methods specified in American National Standards Insti-
tute (ANSI)/American Industrial Hygiene Association Z10
2) Differential relaying [3], Occupational Health and Safety Management Systems.
3) ERMS with local status indicator The hierarchy lists the following six risk-control measures:
1) elimination
4) Energy-reducing active arc-flash mitigation system
2) substitution
5) An instantaneous trip setting that is less than the available 3) engineered controls
arcing current 4) awareness
6) An instantaneous override that is less than the available 5) administrative controls
arcing current 6) personal protective equipment (PPE).
The first three methods do not require any specific
7) An approved equivalent means
action, understanding, or comprehension on the part of
the personnel benefiting from the control measure as they
are automatic or by default. However, the second three
do require active personnel participation, comprehension,
Table 2. NEC 240.67 skill, or training. That makes the second set of measures
A Fuse Shall Have a Clearing Time of 0.07 s or Lower at the fallible and subject to human error. Hence, any hazard
Available Arcing Current, or One of the Following Shall Be control measure in the upper half of the list is considered
Provided: more robust or better than those in the second half.
1) Differential relaying The first control measure, elimination, refers to any
measure that fully eliminates the hazard. The second,
2) ERMS with local status indicator substitution, refers to any measure that substitutes less
3) Energy-reducing active arc-flash mitigation system in lieu of a more hazardous situation. The third, engi-
neered controls, is any kind of automated system that,
4) An approved equivalent means
when operational, provides an automatic reduction of the

54 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019


hazard on a ­continuous basis without is important to have the correct value
any interaction from the regularly of fault current. It is best to have the
exposed personnel or anyone act- It is important to expected range of fault current avail-
ing on their behalf. It is important to able because it may vary during the
note that engineered controls tend note that engineered day due to different topologies used,
to require maintenance and possibly
adjustment to ensure they operate as
controls tend to either by the serving utility or the end
user. Higher fault current will cause
expected during the useful life of require maintenance higher incident energy for fixed clear-
the equipment. ing times proportional to available
The fourth category, awareness, and possibly fault current. Lower arcing current can
includes all methods to instruct,
advise, warn, or impart skills to oper-
adjustment to ensure result in protection operating more
slowly and higher incident energy due
ating personnel so they can reduce they operate as to the increased operating time of the
their risk. In this category are warn- protective device.
ing signs, job site meetings, training, expected during the The third parameter in arcing cur-
and so on. Administrative controls,
the fifth category, include steps or
useful life of the rent calculations is the equipment
bus/conductor gap. The arc current
actions personnel can do prior to equipment. must sustain itself across the gap. IEEE
exposure to a hazard to lower their 1584-2002 provides a table of typi-
risk. Turning a switch on or off, posi- cal gaps for various equipment types
tioning a lever, and ensuring the sta- (see Table 3).
tus of a device or apparatus prior to the task would fall Most arc-flash studies use a combination of these
under this category. The last category, PPE, entails a per- values. In equipment, however, different values could
son wearing PPE to minimize the negative effects of any be found, both larger and smaller, and this provides an
unintentional event that may occur during exposure. additional source of variation in arcing current calcula-
This article will refer to this hierarchy of risk-control tions. The 100–85% range defined in IEEE 1584-2002 for
methods to explain the measures in the NEC articles. arcing current only attempts to account for the variance in
the experimental data from the arc-flash research prior to
Arcing Current: How Low Is Low Enough? 2002. All other potential sources of variance are not con-
IEEE 1584-2002, IEEE Guide for Performing Arc Flash sidered in the current IEEE model.
Hazard Calculations [4], and IEEE 1584.1 provide formu- Sources of arcing current variance may include but are
las and methods for calculating arc-flash currents to deter- not limited to
mine arc-flash incident energy and arc-flash boundaries. ●● the chaotic nature of an electrical arcing fault

The formulas are used to calculate a value referred to as ●● variable system topology and varying short circuit current

100% arcing current and another at 85% of the first value. ●● incorrect assumptions regarding conductor impedances

The calculations are based on three factors used as vari- ●● conservative utility high-fault-current assumptions

ables within the equations: ●● conservative fault study methods by power systems

●● system voltage (nominal) engineers


●● available three-phase short circuit current ●● incorrect measurements of system conductors

●● equipment bus/conductor gap. ●● incorrect assumptions about regenerating sources

The first parameter, system voltage, is easily determined. ●● a variance in source voltage due to system loading

The second is often estimated at preliminary phases of a ●● incorrect assumptions about bus/conductor gap or

project design. And even in the later stages of a project, the arc environment (i.e., size of equipment enclosure or
short circuit current value may depend on several assump- compartment).
tions, switching or operating scenarios, and worst-case
tolerances. For the short circuit evaluation of equipment,
power system engineers performing short circuit calcula-
Table 3. A portion of IEEE 1584 Table 4, from p. 12
tions purposely drive any potential error toward higher val-
ues because that is conservative from an equipment-rating System Typical Gap Between
perspective. Ensuring properly rated equipment, per NEC Voltage (kV) Equipment Type Conductors (mm)
110.16, involves calculating maximum short circuit fault 0.208-1 Open air 10–40
current and evaluating it against the withstand and inter-
rupting ratings of the electrical distribution and protection Switchgear 32
equipment. Conservatism from the equipment ratings MCC and panels 25
perspective is not necessarily appropriate from an arc-
Cable 13
flash calculation perspective. For arc-flash calculations, it

j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 55


These sources of variance and oth- circuit, protective device coordina-
ers can yield arcing current that is tion, and arc-flash so the values for
slightly higher or lower than expect- The more sensitive arcing current can be used to deter-
ed. Slightly higher current can yield mine protective device settings.
proportionately higher arc-flash inci- protection is, the
Arcing Current Where?
dent energy, but slightly lower arcing
current can yield significantly high-
more robust it may The last question regarding arcing
er incident energy if the protection be considered. current is where is the arc? For a
reacts more slowly because it does main circuit breaker, the arcing cur-
not sense the arcing fault as expected. rent may be the bus protected by the
The more sensitive protection is, the main circuit breaker. In most cases,
more robust it may be considered, which means it is more the entire bus is considered to have the same arc-flash
likely to operate for the actual arc fault current. IEEE incident energy value. However, for a feeder in a switch-
1584.1 [4] instructs that, to calculate arc flash, consider- board, the arcing current could be at the circuit break-
ation should be made for overly conservative source fault er’s load-side terminals (location 3 in Figure 3) or at the
current and whether motors are turned on or off. It impor- far end of the feeder conductor (location 4 in Figure 3).
tant to note that IEEE 1584 is undergoing revision, and the That downstream arcing current (location 4) is probably
revised version will include additional sources of variance much lower due to the conductor impedance. It is also
both in arcing current and incident energy. When the new possible that the load-side equipment is more likely to
model becomes available, the reader is encouraged to con- be serviced while energized than the overcurrent protec-
sider it within the context of this article. tion’s secondary terminals (location 3) if it is distribution
Figures 1 and 2 show the IEEE 1584-2002 calculated equipment feeding multiple loads. Hence, the protection
85% arcing current as a percentage of short circuit cur- should consider the lower-arcing current at the far end
rent for various gap assumptions. Table 2 in IEEE 1584 of the conductors.
lists typical bus gaps for different equipment classes. Another concern is the arc-flash current at the line
For low-voltage switchgear, the commonly used value side of main devices (location 1 in Figure 3). When the
is 32 mm. For switchboard and motor control centers main device is fed from a source such as a substation
(MCCs), the typical value suggested is 25 mm, and most transformer within the owner’s system, there are ­several
engineers performing studies use this value in switch- ­measures that can be taken to provide protection for
boards and MCCs. Most moderately sized commercial the line side of the main device [5]. But when the main
and industrial power systems tend to operate with device is fed from a utility-owned transformer, options
available short circuit currents between 30 and 50 kA. are limited. Generally, it is best to isolate the main device
A conservative assumption (i.e., biasing toward a low to minimize 1) exposure when energized work is being
arcing current value) for arcing current could be approx- performed on the load side of the main device and 2) the
imately 40% for 480-V systems and 20% for 208-V sys- possibility of an arcing fault on the load side (location 2
tems. However, it is best to have a study done for short in Figure 3) propagating to the line side.

70% 50%
13 mm, 85%
60% 25 mm, 85%
40% 32 mm, 85%
40 mm, 85%
Ia as % Ibf

Ia as % Ibf

50%
30%
40%
13 mm, 85%
25 mm, 85% 20%
30%
32 mm, 85%
40 mm, 85%
20% 10%
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105

5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105

Ibf (kA) Ibf (kA)

FIGURE 1. A plot of 85% arcing current (I a) as the percentage of FIGURE 2. A plot of 85% arcing current (I a) as the percentage of
available bolted fault current (I bf) for a 480-V system, per the IEEE available bolted fault current (I bf) for a 208-V system, per the IEEE
1584-2002 model. 1584-2002 model.

56 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019


Solution Types enabling the feature allows circuit breakers at the sec-
The hazard controls listed in the NEC articles are either ond and higher tier to operate faster than if they did not
engineered or administrative controls per the hierarchy implement ZSI. However, the lowest-tier devices will not
identified in NFPA 70E [2] and ANSI Z10 [3]. The energy- operate any faster. Regardless if ZSI is implemented, it is
reducing maintenance switch is an administrative control. required that the protection thresholds be set sufficiently
The other measures are engineered controls. sensitive enough to detect the expected arcing current for
the entire protection zone.
Engineered Controls ZSI is a way to improve clearing time without sacri-
ficing system selectivity. Manufacturers may implement
Instantaneous Overcurrent Function and ZSI in different ways so the actual capabilities may vary,
Override Function Below Estimated Arcing Current but the basic principles are consistent. Figure 4 shows
In North America, circuit breakers are listed under two a simple ZSI scheme. The basic premise is that lower-
industry standards: and upper-tier devices detect the same fault current; the
●● Underwriters Laboratory (UL) 489, Molded-Case Circuit lower-tier device (fault location 2 in Figure 4) simultane-
Breakers, Molded-Case Switches, and Circuit-Breaker ously initiates its protection logic, sending a signal to the
Enclosures [6] upper-tier device indicating that it is in the process of
●● UL 1066, Standard for Low-Voltage AC and DC Power

Circuit Breakers Used in Enclosures [7]


The molded-case class may also be divided into tra-
ditional molded-case circuit breakers (MCCBs; see IEEE
3004.5 [8, p. 2]) and insulated-case circuit breakers
Source
(ICCBs; see IEEE 3004.5 [8, p. 2]). MCCBs always have
instantaneous protection. For some larger MCCBs, manu-
facturers may state instantaneous protection may be
turned off, but an instantaneous override will always be 1 Switchboard
present at a relative low multiple of the frame size, typi-
2,000 A
cally not higher than 15 times the frame size. Low-voltage
2
power circuit breakers (LVPCBs; see IEEE 3004.5 [8, p.
2]) may have a high range of adjustability in their instan- 1,200 A 1,200 A
taneous function, maybe more than 15 times the sensor 3
rating. Most LVPCBs will allow the adjustable instanta-
neous protection to be turned off. However, many will
have a fixed override that cannot be turned off. Some will 4
not have an override; hence, when the user-adjustable Load
instantaneous function is turned off, no instantaneous
protection is present. ICCBs share MCCB and LVPCB
characteristics but always implement an adjustable instan-
taneous protection or override or both.
FIGURE 3. Possible arcing fault locations relative to overcurrent
Regardless of the type of circuit breaker, it is pos- protection in equipment.
sible that the instantaneous function could be set above
the available arcing current, resulting in higher clearing
times, especially in smaller, weaker, or lower voltage
systems and when circuit breakers are larger. In terms
of device selectivity expectations for the system, if LVP- Switchboard
2,000 A Main
CBs are used within multiple coordination tiers, then it
is more likely that there will be a desire to set instanta- Restraint
Fault 1 Signal
neous protection to a high (insensitive) level or to disable
Current
it. This will be especially true if the designer is not tak-
ing advantage of modern instantaneous selective coor-
1,200-A Feeder
dination methods recently introduced by manufacturers
1,200-A Feeder
into the UL and National Electrical Manufacturers Asso-
ciation markets [9]–[11]. 2

Zone-Selective Interlocking
Zone-selective interlocking (ZSI) is commonly avail- FIGURE 4. A simple three-circuit breaker ZSI scheme with two 1,200-A
able from all circuit breaker manufacturers. In all cases, feeders providing a restrain signal to a single 2,000-A main.

j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 57


asserting a trip and protecting. The of 240.87 may be satisfied, but the
upper-tier device receives the signal intent is not. Like any other protec-
(also known as a restraint signal) and A responsible party tion, the threshold for operation must
shifts its timing from unrestrained (in- be below the available arcing current
zone protection) to restrained (backup must establish what fault expected within the target zone
protection). Depending on the device,
the restrained protection may be
the expected arcing of protection. Use of shunt trips and
lockout relays can add to the total clear-
adjustable by the user, whereas the current is and ensure ing time, negatively impacting the arc-
unrestrained protection is automatic, flash reduction.
or both may be user adjustable. When the protection is
Administrative Controls
the fault location is in position 1 in
Figure 4, the 2,000-A main should
adjusted correctly. Within the hierarchy of hazard con-
operate its protection at the faster trol measures, administrative controls
unrestrained timing point since no are second to last (with last being
restraint signal was received. The ZSI least effective). The reason for this is
scheme improves the protection provided by the main that they are very dependent on the behavior of the per-
with the assistance of the ZSI function in the 1,200-A feed- son implementing the control. For example, a person
ers. However, the ­protection provided by the 1,200-A feed- ●● could forget to implement it

ers is not improved, even though the devices are part of ●● might not be sufficiently trained to know how to

a ZSI scheme. The 1,200-A feeders may meet the letter of operate it
the code text but not its intent. ●● might not be sufficiently trained to know the need to

Modern ZSI offers significant enhancements for pro- operate it


tection [12]. ZSI implementations in advanced trip unit ●● might not know that his or her work task could have

systems may provide various ways to test the ZSI system, been incorrectly planned with the administrative con-
which has traditionally been a concern when installing trol accidentally omitted
such systems. When installing a ZSI system, it is impor- ●● could operate the incorrect control

tant to verify that it is wired correctly and signals are ●● could operate it at the wrong time

getting to the correct devices. Generally, if the wiring ●● might not know the control could be inoperative.

is damaged upstream, devices will revert to the unre- The possibility of human error will lower the value of
strained timing and, hence, protect well, but selectivity may an administrative control, relative to fully automated solu-
be compromised. tions, regardless of how effective the control is in mitigat-
ing the hazard. See ANSI Z10 [3] for further discussion.
Bus Differential Protection
Bus differential protection works on the simple concept Energy-Reducing Maintenance Switching
known as Kirchhoff’s current law. Simply stated, for this with Local Status Indicator
application, it means that all of the measured currents into
a bus must balance the measured currents leaving it. Any Sensitive to What?
imbalance in current, above the programmed threshold, Energy-reducing maintenance switches are offered by cir-
must be a fault. In a differential protection scheme, the dif- cuit breaker manufacturers and even by at least one manu-
ferential relay is connected to current sensors that measure facturer of fused UL 977 listed power switches [13]. In the
all of the power coming in, sources, and power going out code-defined requirements for this function, there are no
to loads. A fault below a feeder, such as fault 2 fed by the performance requirements, just that they must be provid-
1,200-A feeder shown in Figure 4, has power measured ed. Protection can only work as intended if it is set sensi-
going into the main bus and going through the feeder. The tive to the available arcing current magnitude. The benefit
differential relay will not sense that current as a fault. A fault of these switches is that they generally have a broad range
in location 1 on the bus in Figure 4 will cause power to flow of adjustability and should be able to be adjusted to be
into the bus and be measured at the main circuit. However, sensitive enough to achieve acceptable arc-flash reduc-
neither feeder is carrying the power out of the bus, and the tion. However, a responsible party must establish what
differential relay will sense the bus fault and signal the main the expected arcing current is and ensure the protection is
circuit breaker to open. Like the ZSI scheme described pre- adjusted correctly. Once commissioned, maintenance per-
viously, a differential scheme that includes the three circuits sonnel should only need to enable and disable the func-
shown in Figure 4 will provide additional protection for the tion as prescribed in the planned task procedures.
main bus but not for the feeder circuits. To determine the
exact zone of protection provided, the equipment draw- Indication and Control Local to What?
ings must be examined, with the exact location of current Maintenance switches should be used with indicator lights.
transformers and circuit breakers noted. Again, the letter The code states that a local indicator must be provided,

58 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019


but the text is not specific as to what should be local. Does the case for equipment fed by multiple sources involving
it need to be local to the overcurrent protection device multiple energy-reducing maintenance switches, unless
(OCPD) being affected or to the remote equipment being they are coordinated in some manner. A concern may also
protected? Good engineering practice would dictate that it be the improper use of an energy-reducing maintenance
should exist where the protected equipment is. However, switch by unqualified personnel not aware of the system’s
the switchboard manufacturer, if not given specific direc- limitations. Some of the limitations are the following.
tions to the contrary, will often include it near the OCPD ●● Neither a circuit breaker nor its load is made safe using

being controlled by the switch. Most importantly, the per- the switch. The protection provided by the circuit
son who is relying on that protection should be aware of breaker may be improved, but that does not mean the
its status and what circuit or equipment is being protected. circuit breaker or the load circuit is electrically safe.
To facility operators, it may be important to know if the ●● The arc-flash hazard at the line side of the circuit

protection is accidentally left on when not needed. breaker is not affected by an energy-reduction main-
The maintenance control switch should have test pro- tenance setting (ERMS) on that circuit breaker. Protec-
cedures for confirming that the circuit breaker or relay tion for the line side depends on an upstream device
being controlled has received the signal and processed it that may not be affected by the switch mounted in the
correctly. These should be followed up on initial start-up proximity of the circuit breaker.
and at regular intervals afterward. This could be referred ●● A bus, or equipment, may have multiple sources, and,

to as positive feedback of status. The switch should be unless the switch controls all of them, they may need
lockable so it can be properly locked in the on state by to be addressed simultaneously to make sure the haz-
maintenance personnel. ard from each source is minimized.
This function can temporarily compromise coordina- ●● When the switch is local to the circuit breaker but the

tion, until it is disabled. Users are often concerned about actual equipment to be worked on is remote, there are
forgetting to turn this off after a task, and an obvious opportunities for mistakes (e.g., setting the switch on
indication of the status is often designed into the system. the wrong OCPD or having the switch operated by
Indications, such as tower lights evident through the elec- other personnel if it’s not properly locked out in the
trical room, sound alarms, and even e-mails to supervi- enabled position).
sory personnel, have been used to ensure a maintenance ●● The switch may be used properly, but, if the setting is

switch is not left on indefinitely. Similar measures should not sensitive enough, arc-flash protection may not
be used to ensure that a maintenance switch is used be improved.
when needed. The manufacturer should be consulted for ●● Setting the normal instantaneous protection temporari-

device implementation information because wiring and ly lower, and thereby using it as an ERMS, may provide
space requirements may vary. the expected energy-reducing function. However, this
method does not provide the annunciation function
What About the Arc-Flash Label? that is described in the code, and, therefore, it is tech-
Another consideration when relying on an energy-reduc- nically not an acceptable method.
ing maintenance switch to provide lower levels of arc-
flash incident energy is whether that lower level should Approved Equivalent Means Solution
be reflected on the NFPA 70E defined arc-flash label and Energy-Reducing Active Arc-Flash Mitigation System
[2, Sec. 130.5(D), p. 28] installed on the equipment. There The code does not clearly explain what an approved
are many opinions about this subject. One argument is equivalent means or what an active energy-reducing
that arc-flash labels should not be ambiguous or complex arc-flash mitigation system is. However, there are sev-
and should be conservative in case the reader is not fully eral possibilities should the authority having jurisdiction
aware of proper procedures or inadequately trained. (AHJ) choose to accept them. Components of such sys-
tems may include
Administrative Procedures Require Qualified Personnel ●● for sensing: light-sensing relays as event detectors and

and Task Planning controllers or overcurrent relays to sense arcing current


The better protection afforded by the energy-reducing ●● for interruption: low-voltage circuit breakers, medium-

maintenance switch can be reflected in the data provided voltage circuit breakers, low-voltage fuses, medium-
by the arc-flash study and form part of the risk assess- voltage fuses, crowbars to divert energy and collapse
ment [2, Sec. 130.5, p. 25] required to plan an energized system voltage, or combinations of these.
work task [2, Sec. 130.2(A), p. 24]. The other argument Arc-flash relays are usually able to directly sense the
is that the maintenance function is embedded in the light from an arc-flash event near the sensor location
equipment and always available to be used, so the better [14]. These devices are fast and considered to be very
protection can be reflected in the arc-flash label, or a sec- good at sensing an arcing fault event. However, they have
ond label, that clearly indicates the incident energy with some drawbacks. They can unexpectedly operate from
the switch turned on or off. However, this may not be the light emanating from a circuit breaker ­interrupting

j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 59


a remote fault [15]. Furthermore, devices, which has implications on
they can sense within an equipment the ability to test them. Because an
enclosure very well but do not sense Both arcing gap and arc-flash mitigation system is a safety
a fault at the far end of a conductor mechanism, the ability to fully con-
feeding remote equipment. In some driving voltage are firm operation for maintenance pur-
cases, it may be possible to prevent
a nuisance operation due to an inter-
important factors poses is also important.

rupting circuit breaker within the affecting arcing 240.67 Fusible Switches,
enclosure using ZSI restraint from Improving Protection
the trip unit controlling the circuit current. In 2017, the NEC added Section
breaker [12, C, p. 1643] or via other 240.67, which describes requirements
interlocking methods. similar to those found in 240.87 for
Overcurrent relays, ANSI 50/51 switches with 1,200-A or higher fuses.
devices, may be able to provide additional protection and The requirements, as defined, are not necessary to be
control over and above that provided by circuit breaker enforced until 2020. The existence of the requirements
trip units in some situations. One example is sensing indicates that the code-making panel perceives a poten-
faults on the conductors between the secondary of a sub- tial hazard and consequential risk to personnel that
station transformer and the first secondary low-voltage merit consideration. The 2020 enforcement date seems
devices. Details of these implementations are beyond the to be an attempt to delay a solution having limited com-
scope of this article, and some references on secondary mercial availability.
substation protection are provided in [5]. The section allows fuse protection to be evaluated
Low-voltage circuit breakers and power switches can with the arcing current to investigate if the fuse will
be controlled from various sensing devices. When using a protect sufficiently quickly without additional protective
combination of interrupting devices and external controls, measures being applied in the system. The requirement
it is important to understand the full operation time of is for fuses to clear in 70 ms or fewer at the estimated arc-
sensing, signaling, and switching devices. In many cases, ing current. The authors believe this requirement may be
although the relay sensing may be very fast, the combina- insufficient for various reasons.
tion of the various delays provides for slower protection ●● It forces the AHJ to evaluate complex time–current-

than the integral instantaneous protection provided by curves. Not all AHJ have the skills to evaluate time–
the circuit breaker. In most cases, external relays should current curves.
only be used in special applications that warrant the com- ●● The time–current curves provided will be for a specific

plexity and cost. brand and model of fuse. When a fuse melts, it could
Medium-voltage circuit breakers may be especially be replaced by one with different characteristics. A
suitable to protect conductors and equipment fed from conservative course of action would be to use enve-
a transformer prior to the first low-voltage device. Such lope or test fuses, like fuse-to-circuit breaker series
circuit breakers may be controlled in many ways. See the rating tests do, so not just one manufacturer’s fuses
references on secondary substation protection provided in are considered.
[5] and [12]. ●● The 70-ms clearing time exceeds three cycles, and

Low- and medium-voltage fuses could, potentially, be even a three-cycle clearing time is not the best a fuse
accelerated by use of a crowbar to divert energy, collapse can do. Fuses in this size range are current limiting
voltage, and force the highest available fault current to and provide best performance when operating in
flow through the fuses to ensure they operate in their their current-limiting range. Fuses operating in their
current-limiting range. If the current is high enough, it current-limiting range may provide the best arc-flash
will flow for under half a cycle, and arc-flash protection incident energy mitigation possible for any overcur-
can be very quick with minimal consequences. Crowbars rent device.
are shunt devices that divert current and collapse system ●● Fuse curves are drawn as single-phase devices. When

voltage by causing a minimum impedance fault some- a fuse melts in one phase, the fault current in a three-
where in the system. As arc-flash protection, they should phase balanced fault changes to a single-phase fault at
work very well if the arc fault is detected. However, the 87% of the original fault current, increasing the possi-
bolted fault current may not be desirable and have seri- bility of the second or third fuse melting more slowly.
ous consequences to the distribution system. If such a The fuse curves an AHJ would review are incapable of
mitigation system is considered, the manufacturer should revealing slower melting times.
be consulted to fully understand the implications of the IEEE 1584-2002 (Sect. 5.6, p. 13) includes formulas for
application, how the sensing will operate, and how the fuses based on testing done by the research group for one
energy diversion device will operate. At the time of this brand of fuses. The tests were performed primarily at 600 V.
writing, most crowbar devices seem to be one-time-use The test data were used to derive several fuse formulas

60 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019


that could be used in lieu of time– fuse performance in 240.67, which
current curves to evaluate arc-flash allows for no additional measures to
incident energy performance. The An arc-flash study be taken to reduce clearing time for a
formulas provide for an energy calcu- fused switch. As can be seen in Figure 6,
lation based on available bolted fault is the best way to the slower 0.07 s does allow a bit more
current regardless of arcing gap and
driving voltage. Both arcing gap and
determine if the energy, although it is lower than 8 cal
up to an available 70- kA short cir-
driving voltage are important factors fuse will provide the cuit current.
affecting arcing current. Based on the IEEE 1584-2002 fuse
Furthermore, the experiments to desired protection at arc-flash incident energy formulas,
determine fuse performance also put
a thin wire (trigger wire) in series
the available arcing an attempt was made to transpose
those formulas for 480-V applications
with the fuse, which is a weak con- current expected. (see Table 4). Fuses above 1,200
ductor. The trigger wire serves as a A probably need additional means
primitive fuse. When high current is to reduce incident energy below the
passed through, both heat up and commonly desired level of 8 cal/cm2.
eventually melt. The trigger wire should melt first, caus- Likewise, at 208 V, 1,200-A fuses would benefit from the
ing an arc-flash event, which is interrupted by the fuses. additional protection described in 240.67. An arc-flash study
The current causing the wire to heat also causes the is the best way to determine if the fuse will provide the
fuse to heat before an arcing event occurs. This could desired protection at the available arcing current expected.
be interpreted as biasing the tested fuse to operate more
quickly, but no clear data are available to identify if this
is consequential.
An additional concern is that most of the test data are 14 0.025 s 0.05 s
at 600 V. This means the arcing current is a relatively high 12 0.07 s 1.2 Cal/Cm2
percentage of available short circuit fault current relative 4 Cal/Cm2 8 Cal/Cm2
to the percent at 480 or 208 V. The IEEE fuse formulas do 10
Cal/cm2

not provide any guidance on how to correct the formulas 8


when applied at lower driving voltages. Figure 5 shows 6
the identified fuses, 1,200 A and greater, and the pro-
spective fault current at which the fuse seems to reduce 4
energy to about 8 cal per the formulas provided in IEEE 2
1584-2002. 0
Figure 6 shows incident energy per the IEEE 1584- 10 20 30 40 50 60 70 80 90 100
2002 model for 480-/277- V, 32-mm gap at 18-in work- Ibf (kA)
ing distance at three clearing times: 0.025 s, typical for
a larger slow MCCB; 0.05 s, typical for a large ICCB FIGURE 6. A graph of incident energy per IEEE 1584-2002 at an
or LVPCB; and 0.07 s, the value specified as sufficient 18-in working distance for a 32-mm arcing gap. The arc-in-a-box
formulas for three different clearing times are shown for 480/277 V,
32 mm, and 18 in.

IEEE 1584-2002 Fuse Equations


32
Table 4. An approximate prospective current
Incident Energy cal/cm2

24 value where the IEEE 1584-2002 fuse formulas


predict 8-cal/cm2 incident energy at 600 V,
16 transposed for 480 and 208 V
8 Fuse Class kA for kA for kA for
and Range 8 cal 600 V 8 cal 480 V 8 cal 208 V
0
0 20 40 60 80 100 120 L, 1,601–2,000 96 120 240
Available Bolted Fault Current (kA)
L, 1,201–1,600 41 51 103
L-1601-2000 L-1201-1600 L-801-1200
L, 801–1,200 25 31 63
Determined Transposed Transposed
FIGURE 5. A fault current where the fuse limits the incident energy from graph by 5/4 ratio by 5/2 ratio
to 8 cal at 600 V, transposed to 480 and 208 V.

j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 61


Fuses can provide optimum protection if they are ●● arc-resistant equipment, which provides benefits for per-
operating within their current-limiting range. The current- sonnel working or standing near fully closed equipment;
limiting threshold is defined in the applicable standard however, it does not reduce the hazard when someone
for those fuses. The ratios and thresholds are shown is working on live equipment with doors open or covers
in Tables 5 and 6. Fuses will provide the best possible removed [17]
arc-flash protection after one fuse melts, if the expected ●● remote human–machine interface, diagnostics, dis-
arcing current is larger than the value shown in the play, and so forth, a good solution that is very easy to
current-limiting threshold table, which provides a conser- implement in modern equipment and provides many
vative interpretation of available data. Most products will benefits; however, it does not address live work hazard
perform better than standard allowed maximum thresh- control implied by the code
olds. However, different fuse manufacturers and different ●● remote circuit breaker operation, a very good risk miti-
types of fuses may be installed over time, meaning the gation method but does not address live work hazard
conservative course of action is to base design decisions concerns as the code attempts to do.
on the worst practical scenario over the life of the equip-
ment. This also adds some ­flexibility to account for other Suggested Improvements in the Code
issues that may impact fuse melting times.
Circuit Application
Arc-Flash and Electrical Safety Improvements Current code sections make no allowances for the applica-
That Do Not Address Implied Code Intent tion of the circuit being addressed. Is the circuit a service
Within the industry, many design decisions can be made entrance main, a feeder on an important distribution bus,
that have a positive impact on electrical safety and arc- or a branch device feeding a single load or machine? Is it
flash-hazard mitigation. Designers, following Prevention an additional device being used as a local disconnect pro-
Through Design principles, should consider many of viding mostly a disconnect function rather than a critical
these decisions and implement them as much as possible protective function?
in system designs. Among these considerations may be The extra protection mandated by code requirements
●● high-resistance grounding, widely believed to reduce seems to address the hazard during energized work (an
the probability of an accidental arcing fault [16] energy-reducing maintenance switch is only used during
planned exposure). But a local disconnect, such as a safety
switch, used in a circuit fed from a remote, similarly sized
Table 5. The current-limiting ratio values, circuit breaker and feeding a dedicated load is not exempt-
UL fuse standard ed from the code requirements. The extra protection is not
needed twice in the same circuit.
Fuse Class Ratio
Class RK5 65 System Voltage Considerations
Additional protection requirements are necessary at
Class RK1 30
1,200 A, regardless of system voltage. As stated previously,
Class J 30 key factors in good protection are 1) having it operate for
Class CC 30 the available arcing current and 2) the arcing current as
a percentage of the bolted fault current will vary greatly
Class L 30 (601–1,200 A)
with system voltage. If 1,200 A is the proper limit for addi-
Class L 35 (1,201–2,000 A) tional protection at 480 V, then the proper limit for 600-V
installations may be 1,600 A, and for 208-V installations, it
Class L 40 (2,001–4,000 A)
may be 600 A.

Is the Overcurrent Protection Being Improved or Not?


Table 6. The current-limiting threshold values, The code is not sufficiently specific when discussing
UL fuse standard additional protection functions, such as bus differential
or ZSI. Those enhancements only provide a benefit if
Class L Fuse Size (A) Current-Limiting Threshold (A)
they operate the overcurrent device(s) for a fault in the
1,200 36,000 zone of protection and only if the protection is as fast
1,600 56,000 as possible at expected arcing current levels. In other
words, the threshold for operation of the device must
2,000 70,000 meet the same criteria as those control methods having
3,000 120,000 a threshold identified. It is not sufficient for a device
to be installed; it must play an active protection role to
4,000 160,000
provide benefit.

62 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019


Arcing Current Location mitigation has been suitably implemented. A more practical
An additional concern, not addressed by the code when it course of action may be requiring a competent engineering
states protection will operate at the available arcing cur- professional to provide a report indicating what methods
rent expected, is that there is no definition of where the have been applied to the installation to ensure the devices
arcing current is to be determined—at the terminals of provide a reasonable limited level of incident energy. This
the overcurrent device or at the far end of the protected could be given either as a calories-per-square-centimeter
conductors? The far end of the conductors may be the target or indicating that all devices above a certain size are
equipment that may be worked on while energized. It operating as quickly as they can at or below the expected
would be reasonable to expect this is where the improved minimum arcing current level calculated.
protection is desired, but that detail is not identified in the One last note: it is important to remember that equip-
code text, and it should be. ment-based solutions will be sufficient only if mainte-
nance is properly performed and all appropriate safe
Protection with Fuses work practices are followed.
It is well understood that the faster the protection is at the
arcing current level, the better it is. Fuse performance should Author Information
be taken from the standards defining the fuse class, and for Marcelo E. Valdes (marcelo.e.valdes@ieee.org) is with
arcing current higher than those thresholds, additional protec- ABB, Cary, North Carolina. Valdes is a Fellow of the IEEE.
tion is not needed. For arcing current lower than the thresh- Steve Hinton is with Schneider Electric, Lexington, Ken-
olds, additional protection is needed. Evaluations using 0.07 s tucky. Francisco Martinez is with ABB, Tampa, Florida.
can provide higher E i levels than the code intended, espe- This article first appeared as “Arc Flash in the National Elec-
cially when fuses can perform much better. This eliminates trical Code: Articles 240.87, 240.67; Intent and Reality, Does
AHJs from having to confirm overly complex compliance for the Code Achieve Its Goals? Do You Achieve Its Goals?” at
fuse-protected circuits, and instead, a specific numerical target the 2017 IAS Annual Meeting. This article was reviewed
for arcing current versus fuse size should be provided. by the IAS Codes and Standards Committee.

Unprotected Conductors References


Some systems may have conductors not adequately pro- [1] National Electrical Code, NFPA 70-2017.
[2] Standard for Electrical Safety in the Workplace, NFPA 70E-2015.
tected in the case of an arc-flash event, particularly line-side [3] Occupational Health and Safety Management Systems, ANSI/AIHA
conductors for service entrance equipment or other large Standard Z10-2012.
equipment where the power comes from a generator or [4] IEEE Guide for Performing Arc Flash Hazard Calculations, IEEE Stan-
dard 1584-2002.
transformer. Between the power source and the first over- [5] M. D’Mello, M. Noonan, M. Valdes, and J. Benavides, “Arc flash haz-
current device, there may be no protection, or the protec- ard reduction at incoming terminals of LV equipment,” IEEE Trans. Ind.
tion operates at a different voltage and is not adequate for Appl., vol. 52, no. 1, pp. 701–711, 2016.
[6] Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-
conductors. A recommended practice within the industry Breaker Enclosures, UL Standard 489, 2016.
is to isolate such conductors so personnel working down- [7] Standard for Low-Voltage AC and DC Power Circuit Breakers Used in
stream of the local OCPD are not exposed to them. It is Enclosures, UL Standard 1066, 2012.
[8] IEEE Recommended Practice for the Application of Low-Voltage Circuit Break-
also recommended that the space with the unprotected ers in Industrial and Commercial Power Systems, IEEE Standard 3004.5-2014.
energized conductors be isolated such that the effluent [9] E. Larsen, “A new approach to low-voltage circuit breaker short-circuit
from an arc-flash event localized downstream of the local selective coordination,” in Proc. IEEE/IAS Industrial and Commercial
Power Systems Technical Conf., 2008, pp. 1–7.
OCPD cannot cause a flashover and arc-flash event at the [10] M. E. Valdes, S. Hansen, and P. Sutherland, “Optimized instantaneous
primary side of the OCPD. protection settings: Improving selectivity and arc-flash protection,” IEEE
Ind. Appl. Mag., vol. 18, no. 3, pp. 66–73, 2012.
[11] Selective Coordination of Low-Voltage Circuit Breakers, NEMA Stan-
Conclusions dard ABP 1-2016.
To ensure that the NEC is properly enforced, local AHJs [12] M. E. Valdes and J. Dougherty, “Advances in protective device inter-
must be able to reasonably verify the requirements. Ensur- locking for improved protection and selectivity,” IEEE Trans. Ind. Appl.,
vol. 50, no. 3, pp. 1639–1648, 2014.
ing that arc-flash reduction goals are achieved requires [13] Standard for Fused Power-Circuit Devices, UL Standard 977, 2012.
expert knowledge in the application of these methods [14] J. A. Kay, J. Arvola, and L. Kumpulainen, “Protecting at the speed of
described in the code. Implementing a method without light,” IEEE Ind. Appl. Mag., vol. 17, no. 3, pp. 12–18, 2011.
[15] G. Roscoe, M. E. Valdes, and R. Luna, “Methods for arc-flash detec-
understanding if or how it works can create a false sense tion in electrical equipment,” in Proc. Industry Applications Society 57th
of security. It is important that electrical inspectors examine Annu. Petroleum and Chemical Industry Conf. (PCIC), pgs. 1–8, 2010
coordination study documentation, particularly because [16] J. P. Nelson, J. D. Billman, J. E. Bowen, and D. A. Martindale, “The
effects of system grounding, bus insulation, and probability on arc flash
the art of circuit breaker selectivity requires more than just hazard reduction—Part 2: Testing,” IEEE Trans. Ind. Appl., vol. 51, no. 3,
confirming that device time–current curves do not overlap. pp. 2665–2675, 2015.
Without a high-quality short circuit coordination study and [17] R. M. Bugaris and D. T. Rollay, “Arc-resistant equipment,” IEEE Ind.
Appl. Mag., vol. 17, no. 4, pp. 62–70, 2011.
arc-flash-hazard analysis performed by a competent engi-
neer, it is difficult to confirm that arc-flash incident energy 

j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 63

Potrebbero piacerti anche